Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HTB Series

GFM-600HT 2V600Ah
Sacred Sun HTB VRLA battery uses latest AGM technology designed for high temperature resistant performance
with good cycle life and fast charging acceptance ability. Its average temperature can be 35-40℃.. HTB's reduced
needs for cooling saves energy and reduces cost. It is suitable for high temperature environments both in floating
and cyclic applications. Sacred Sun has two ranges: 12V front terminal and 2V top terminal.

Benefits
● Long life according to EUROBAT Classification
● Specifically designed for semi-stable mains
● High discharge performance
● 99%+ gas recombination efficiency
● Maximum charge efficiency
● Low self-discharge rate
● Easy installation and handling

Applications Drawing
● High temperature BTS
● Unstable grid BTS
● Remote area BTS
● Solar (Wind) energy storage system

Standards
337

345

347

● JIS C8704-1
● JIS C8704-2
● IEC 60896-21/22
● IEC 61427
● EUROBAT guide
● Installation compliant with EN50272-2
GFM-21

Specifications

Battery Model GFM-600HT


Design Life ( Years, 35℃) 10

10HR (60A, 1.80V) 5HR (109A, 1.80V) 3HR (159A, 1.80V) 1HR (348A, 1.75V)
Capacity (Ah, 25℃)
600 545 477 348

Length Width Height Total Height


Dimensions (mm)
296 178 337 347

Approx. Weight (kg) 43.0


Reference Internal Resistance (mΩ) 0.35 (fully charged @ 25℃)
Maximum Discharge Current (A/5 Sec.) 3800
Self-Discharge (25℃) ≤1% per month

Cycle use Float use


Charge Voltage (V/cell, 25℃)
2.35 (-3.0mV/℃/cell), max charge current: 120A 2.25 (-3.0mV/℃/cell)

Short Circuit Current (A) 6600


www.sacredsun.com

Discharge Data

Constant Current Discharge Data (25℃, A)


End min h
Voltage
(V/cell) 5 10 15 20 30 1 2 3 5 6 8 10 24

1.60 1428 1094 896 757 595 373 229 169 114 100.0 79.7 68.3 29.2

1.65 1274 992 821 699 556 363 225 166 113 99.2 78.9 67.2 29.0

1.70 1164 902 752 669 519 350 221 164 111 98.2 78.2 66.0 28.8

1.75 1000 826 701 627 499 348 217 161 110 97.0 77.4 64.3 28.6

1.80 886 754 656 584 476 336 212 159 109 95.8 76.6 60.0 28.4

Constant Power Discharge Data (25℃, W/cell)


End min h
Voltage
(V/cell) 5 10 15 20 30 1 2 3 5 6 8 10 24

1.60 2250 1880 1571 1364 1106 723 458 334 226 199 163 136 67.2

1.65 2020 1691 1425 1246 1035 692 443 325 222 195 161 133 66.0

1.70 1898 1535 1313 1150 968 668 431 318 219 192 159 132 64.9

1.75 1688 1412 1212 1071 906 637 420 311 215 190 157 130 63.9

1.80 1564 1290 1114 986 851 616 408 305 211 187 154 129 63.2

Rack Layout Performance Curve

0.12C 2.4 1.4C


Charge Voltage
2.10
1.2C

Charge Voltage(V)
Charge current(A)

0.10C
2.3

Charge Capacity(Ah)
2.00 Charge Capacity
1.0C
0.08C
1.90
2.2
0.8C
1.80 0.06C
Voltage(V/cell)

0.17C10

0.10C10
0.25C10

0.6C
2.1
0.55C 10

1.70 0.04C
0.4C
0.82C10

1.60 2.0
0.02C
1.42C10
1.74C10

Charge Current 0.2C

1.50
0 1.9 0
0.01 0.05 0.1 0.2 0.5 1 2 5 10 20 50 0.0 5.0 10.0 15.0 20.0 25.0
Time(h) Charge time(h)

Discharge Performance Charge Performance

120% 20
20
100%
18
16
80%
Discharge capacity

Design life(years)

14

60% 12
10
40% 8
6
20% 4
48V Standard Rack (Anti-seismic rack is optional) 0%
2
0
Rack material: powder-coated steel -15 -5 5 15 25 35 45 20 25 30 35 40 45 50 55
Temperature (℃) Temperature (℃)

Height*width: 6*4/4*6 (optional)


Ref. GFM-600HT Rack (approx. weight: 1125kg) Temperature vs. capacity Design life vs. temperature

Sacred Sun Power Sources Co., ltd. Sacred Sun Asia Pacific Sacred Sun Europe SPRL Sacred Sun MEA FZE

No.1 Shengyang Road Qufu City, PRC No. 15, Yishun Industrial Street 1, Schoenstraat 96-9140 Temse, Belgium S10122A1O19 Jebel Ali, Dubai,
sales@sacredsun.cn #01-17, WIN5, Singapore 768091 sales.eu@sacredsun.cn United Arab Emirates
sales.asia@sacredsun.cn sales.mea@sacredsun.cn