Professional Documents
Culture Documents
ETS Series AC Servo User's Manual: Version V1.06
ETS Series AC Servo User's Manual: Version V1.06
ETS Series AC Servo User's Manual: Version V1.06
(Version:V1.06)
Revision History
Addition:EMJ-A5APA、EMJ-01APA、
EMJ-02APC、EMJ-04APC、EMG-10APB、
EML-10APB
Appendix B Addition:A25、A26、A27
Appendix A Revision:Pn511、Pn700
4.7.1 Revision:diagram
Addition: A43、A45~A48、A50~A56、A58、
Appendix B
A59
ETS Series AC Servo User's Manual
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form,
or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
ESTUN. No patent liability is assumed with respect to the use of the information contained herein.
-1-
ETS Series AC Servo User's Manual
This manual describes the following information required for designing and maintaining ETS series servo drives.
•Communication protocols.
Intended Audience:
-2-
ETS Series AC Servo User's Manual
Safety Precautions
Failure to observe this may result in damage to servo drive and servomotor.
■Please note that even after power is removed, residual voltage still remains in the capacitor inside the servo drive. If
inspection is to be performed after power is removed, please wait 5 minutes to avoid risk of electrical shock.
The servo drive generates heat. Install the servo drive so that it can radiate heat freely. When installing servo drives
with other devices in a control panel, provide at least 10mm space between them and 50mm space above and below
them.Please install servo drives in an environment free from condensation, vibration and shock.
Please comply with the following instructions to avoid noise generated by signal lines.
3. Single point grounding is required for the servomotor and servo drive (grounding resistance 100Ω or below).
4. Never use a line filter for the power supply in the circuit.
For a ground-fault interrupter, always use a fast-response type or one designed for PWM inverters. Do not use a
time-delay type.
Failure to observe this caution may result in injury or damage to the product due to unstable operation.
Frequently turning the power ON and OFF causes the internal circuit elements to deteriorate, resulting in unexpected
-3-
ETS Series AC Servo User's Manual
—Contents—
Chapter 1 ........................................................................................................................................................................ - 7 -
Chapter 2 ...................................................................................................................................................................... - 13 -
Installation ..................................................................................................................................................................... - 13 -
2.1 Servomotor ..................................................................................................................................................... - 13 -
2.1.1 Storage ................................................................................................................................................ - 13 -
2.1.2 Installation Sites .................................................................................................................................. - 13 -
2.1.3 Installation Alignment ........................................................................................................................... - 14 -
2.1.4 Installation Orientation ......................................................................................................................... - 14 -
2.1.5 Handling Oil and Water ........................................................................................................................ - 14 -
2.1.6 Cable Tension ...................................................................................................................................... - 15 -
2.1.7Install to the Client ................................................................................................................................ - 15 -
2.2 Servo Drive ..................................................................................................................................................... - 15 -
2.2.1 Storage ................................................................................................................................................ - 15 -
2.2.2 Installation Sites .................................................................................................................................. - 15 -
2.2.3 Installation Orientation ......................................................................................................................... - 16 -
2.2.4 Installation Method .............................................................................................................................. - 16 -
Chapter 3 ...................................................................................................................................................................... - 18 -
Wiring ............................................................................................................................................................................ - 18 -
3.1 Main Circuit Wiring .......................................................................................................................................... - 18 -
3.1.1 Typical Main Circuit Wiring Examples .................................................................................................. - 19 -
3.1.2 Names and Functions of Main Circuit Terminals .................................................................................. - 21 -
3.2 I/O Signals ...................................................................................................................................................... - 22 -
3.2.1 Examples of I/O Signal Connections ................................................................................................... - 22 -
3.2.2 I/O Signal Connector (CN1_A/CN1_B/CN1_C) Terminal Layout......................................................... - 23 -
3.2.3 I/O Signal Names and Functions ......................................................................................................... - 25 -
3.2.4 Interface Circuit ................................................................................................................................... - 26 -
3.3 Wiring Encoders.............................................................................................................................................. - 27 -
3.3.1 Connecting an Encoder(CN2_A/ CN2_B/ CN2_C) .............................................................................. - 27 -
3.3.2 Encoder Connector(CN2_A/ CN2_B/ CN2_C) Terminal Layout .......................................................... - 28 -
3.4 Communication Connection(CN3/CN4) ..................................................................................................... - 28 -
3.5 Standard Wiring Example ............................................................................................................................... - 29 -
3.6 Wiring for Noise Control .................................................................................................................................. - 33 -
3.6.1 Noise Control ....................................................................................................................................... - 33 -
3.6.2 Precautions on Connecting Noise Filter .............................................................................................. - 34 -
-4-
ETS Series AC Servo User's Manual
Chapter 4 ...................................................................................................................................................................... - 37 -
Operation ...................................................................................................................................................................... - 37 -
4.1 Trial Operation ................................................................................................................................................ - 37 -
4.1.1 Trial Operation for Servomotor Without Load ...................................................................................... - 39 -
4.1.2 Trial Operation for Servomotor without Load from Host Reference ..................................................... - 41 -
4.1.3 I/O JOG control .................................................................................................................................... - 43 -
4.1.4 Trial Operation with the Servomotor Connected to the Machine.......................................................... - 43 -
4.1.5 Trial Operation for Servomotor with Brakes ......................................................................................... - 45 -
4.2 Control Mode Selection................................................................................................................................... - 45 -
4.3 Setting Common Basic Functions ................................................................................................................... - 46 -
4.3.1 Setting the Servo ON Signal ................................................................................................................ - 46 -
4.3.2 Switching the Servomotor Rotation Direction ...................................................................................... - 47 -
4.3.3 Setting the Overtravel Limit Function ................................................................................................... - 48 -
4.3.4 Setting for Holding Brakes ................................................................................................................... - 51 -
4.4 Absolute Encoders .......................................................................................................................................... - 54 -
4.4.1 Selecting an Absolute Encoder ............................................................................................................ - 55 -
4.4.2 Handling Battery .................................................................................................................................. - 56 -
4.4.3 Replacing Battery ................................................................................................................................ - 57 -
4.4.4 Absolute Encoder Setup(Fn010、Fn011) ............................................................................................ - 57 -
4.5 Operating Using Speed Control with Internally Set Speed .............................................................................. - 57 -
4.5.1 Setting Parameters .............................................................................................................................. - 57 -
4.5.2 Soft Start.............................................................................................................................................. - 58 -
4.5.3 Speed Reference Filter Time Constant ................................................................................................ - 58 -
4.5.4 S-curve Risetime ................................................................................................................................. - 59 -
4.5.5 Encoder Signal Output ........................................................................................................................ - 59 -
4.5.6 Speed coincidence output ................................................................................................................... - 61 -
4.5.7 Speed control(contact reference) ........................................................................................................ - 62 -
4.6 Operating Using Position Control .................................................................................................................... - 64 -
4.6.1 Basic Setting in Position Control.......................................................................................................... - 64 -
4.6.2 Setting the Clear Signal ....................................................................................................................... - 66 -
4.6.3 Setting the Electronic Gear .................................................................................................................. - 66 -
4.6.4 Smoothing ........................................................................................................................................... - 70 -
4.6.5 Low Frequency Vibration Suppression ................................................................................................ - 71 -
4.6.6 Positioning Completion Output Signal ................................................................................................. - 73 -
4.6.7 Reference Pulse Inhibit Function(INHIBIT) .......................................................................................... - 74 -
4.6.8 Position Control (contact reference) .................................................................................................... - 75 -
4.7 Limiting Torque................................................................................................................................................ - 78 -
4.7.1 Internal Torque Limit ............................................................................................................................ - 78 -
4.7.2 External Torque Limit ........................................................................................................................... - 79 -
4.8 Other Output Signals ...................................................................................................................................... - 80 -
4.8.1 Servo alarm output .............................................................................................................................. - 80 -
4.8.2 Others .................................................................................................................................................. - 80 -
4.9 Online Autotuning............................................................................................................................................ - 82 -
4.9.1 Online Autotuning ................................................................................................................................ - 82 -
4.9.2 Online Autotuning Procedure ............................................................................................................... - 82 -
4.9.3 Setting Online Autotuning .................................................................................................................... - 83 -
-5-
ETS Series AC Servo User's Manual
Chapter 5 ...................................................................................................................................................................... - 88 -
-6-
ETS Series AC Servo User's Manual
Chapter 1
1.1.1 Servomotor
EMJ– 08 A P B 1 1 -WR
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】 【8+9】
EMJ Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
Incremental Wire-saving Type:
A5 0.05kW P 1 None
2500P/R
01 0.1kW F Incremental encoder:1048576P/R 2 With oil seal
02 0.2kW S Absolute encoder:131072P/R 3 With brake (DC24V)
04 0.4kW 【5】Designing Sequence 4 With oil seal and brake(DC24V)
08 0.75kW Code Spec. 带制动器(DC24V)
【8+9】Connector
10 1.0kW A Designing sequence A Code Spec.
B Designing sequence B Standard connector
-7-
ETS Series AC Servo User's Manual
EMG– 10 A F A 1 1
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】
EMG Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
EML– 10 A F A 1 1
ESTUN Servomotor
【1+2】 【3】 【4】 【5】 【6】 【7】
EML Model
【1+2】
【4】Encoder 【7】Option
Rated Output
Code Spec. Code Spec. Code Spec.
-8-
ETS Series AC Servo User's Manual
-9-
ETS Series AC Servo User's Manual
Voltage Version
A:200VAC P:Position control
ETS–101010AP C– CAN
Communication
ETS model servo drive
CAN:CAN model
None:Pulse model
C axis Rated Output Encoder Interface
C: Wire-saving incremental
encoder (2500P/R)
G: 17/20 bit serial encoder
B axis Rated Output (Automatic identification)
Version
P:Position control
- 10 -
ETS Series AC Servo User's Manual
1.2.1 Servomotor
Encoder
Mounting hole
Shell
Output shaft
Flange
Charge indicator
Lights when the main circuit power supply is
ON and stays lit as long as the main circuit
power supply capacitor remains charged.
Main circuit power supply terminals Connector for communication
Used for main circuit power supply input. Used to communicate with other devices.
Control power supply terminals
Used for control power supply input Encoder connector
Regenerative resistor connecting terminals Connects to the encoder in the
Used to connect external regenerative servomotor.
resistors.
Ground terminal
Be sure to connect to protect electric shock.
- 11 -
ETS Series AC Servo User's Manual
Charge indicator
Lights when the main circuit power supply is
ON and stays lit as long as the main circuit
power supply capacitor remains charged.
Main circuit power supply terminals Connector for communication
Used for main circuit power supply input. Used to communicate with other devices.
Control power supply terminals
Used for control power supply input Encoder connector
Regenerative resistor connecting terminals Connects to the encoder in the
Used to connect external regenerative servomotor.
resistors.
Ground terminal
Be sure to connect to protect electric shock.
- 12 -
ETS Series AC Servo User's Manual
Chapter 2
Installation
2.1 Servomotor
Servomotor can be installed either horizontally or vertically. However, if the servomotor is installed incorrectly, the
service life of the servomotor will be shortened or unexpected problems may occur.
Please observe the installation instructions described below to install the servomotor correctly.
Before installation:
Anticorrosive paint is coated on the edge of the servomotor shaft. Clean off the anticorrosive paint thoroughly using
a cloth moistened with thinner.
Avoid getting thinner on other parts of the servomotor when cleaning the shaft.
Anticorrosive paint
2.1.1 Storage
When the servomotor is not being used, store it in an area with a temperature between -20℃ and 60℃ with thepower
cable disconnected.
The servomotor is designed for indoor use.Install the servomotor in an environment which meets the following
conditions.
Free from corrosive and explosive gases.
Well-ventilated and free from dust and moisture.
Ambient temperature from0 to 40℃.
Relative humidity from 26% to 80%( non-condensing).
Facilitates inspection and cleaning.
- 13 -
ETS Series AC Servo User's Manual
Align the shaft of the servomotor with that of the machinery shaft to be controlled. Then connect the two shafts with
an elastic coupling.
Install the servomotor so that alignment accurancy falls within the range shown below.
Measure this distance at four different positions in the circumference. The difference between the maximum and
minimum measurements must be 0.03mm or less.(Turn together with couplings.)
Note:
·If the alignment accurancy is incorrect , vibration will occur, resulting in damage to the bearings.
·Mechanical shock to the shaft end is forbidden, otherwise it may result in damage to the encoder of the servomotor.
If the servomotor is used in a location that is subject to water or oil drops, make sure of the servomotor protective
specification. If the servomotor is required to meet the protective specification to the through shaft section by default,
use a servomotor with an oil seal.
- 14 -
ETS Series AC Servo User's Manual
When connecting the cables, the bending radius should not be too small, do not bend or apply tension to cables.
Since the conductor of a signal cable is very thin (0.2 mm or 0.3 mm), handle it with adequate care.
When the servo motor is mounted to the client,please firmly secure the servo motor by the screws with backing ring
as shown in the figure.
In
or stall
ien at
tat ion
io
n
ETS series servo drive is a base-mounted type. Incorrect installation will cause problems. Always observe the
installation instructions described below.
2.2.1 Storage
When the servomotor is not being used, store it in an area with a temperature between -20℃ and 85℃ with the
power cable disconnected.
- 15 -
ETS Series AC Servo User's Manual
Install the servo drive perpendicular to the wall as shown in the figure. The servo drive must be oriented this way
because it is designed to be cooled by natural convection or a cooling fan if required. Firmly secure the servo drive
through two mounting holes.
Wall
Ventilation
When installing multiple servo drives side by side in a control panel, observe the following installation method.
■Installation Orientation
Install servo drive perpendicular to the wall so that the front panel (containing connectors) faces outward.
■Cooling
Provide sufficient space around each servo drive to allow cooling by natural convection or fans.
When installing servo drives side by side, provide at least 30mm space from the cabinet,at least 10mm space
- 16 -
ETS Series AC Servo User's Manual
between each individual servo drive and at least 50mm space above and below each one as well as shown in the figure
above. Ensure the temperature inside the control panel is evenly distributed, and prevent the temperature around each
servo drive from increasing excessively. Install cooling fans above the servo drives if necessary.
■Working conditions
1.Temperature:0~ 55℃
3.Vibration:4.9m/s2 or less
- 17 -
ETS Series AC Servo User's Manual
Chapter 3
Wiring
Please observe the following instructions while wiring the main circuit.
!CAUTION
·Do not bundle or run power and signal lines together in the same duct. Keep power andsignallines
separated by at least 300 mm.
·Use twisted-pair shielded wires or multi-core twisted-pair shielded wires for signal and encoder feedback
lines.
·The maximum length is 3 m for reference input lines and 20 m for encoder feedback lines.
·Do not touch the power terminals for 5 minutes after turning power OFF because high voltage may still
remain in the servo drive.
- 18 -
ETS Series AC Servo User's Manual
ETS-101010APC-CAN/ETS-1010APC-CAN
Three-phase +10%
AC200~230 -15%
50/60Hz
Molded-case
Circuit Breaker
Surge
Protector
Noise Filter
1RY PL
ON 1MC
OFF 1MC 1RY
Note :The wiring of ETS two-axis servo drive does not include the gray part of graph.
- 19 -
ETS Series AC Servo User's Manual
ETS-101010APG-CAN/ETS-1010APG-CAN
Three-phase +10%
AC200~230 -15%
50/60Hz
Molded-case
Circuit Breaker
Surge
Protector
Noise Filter
1RY PL
ON 1MC
OFF 1MC 1RY
Serial Encoder
7 S+
8 S- Encoder
CN2_C
17 BAT+
18 BAT- PGA
5 PG5V
9 PG0V
19 Shield
Note :The wiring of ETS two-axis servo drive does not include the gray part of graph.
- 20 -
ETS Series AC Servo User's Manual
Terminal
Name Functions
Symbol
Main circuit
L1,L2,L3 power supply Three-phase 200~230VAC +10%~-15% (50/60Hz)
input terminal
Axis A servomotor
U_A,V_A,
connection Connect to the axis A servomotor.
W_A
terminals
Axis B servomotor
U_B,V_B,
connection Connect to the axis B servomotor.
W_B
terminals
Axis C servomotor
U_C,V_C,
connection Connect to the axis C servomotor.
W_C
terminals
Control circuit
L1C,L2C power supply Single-phase 200~230VAC +10%~-15% (50/60Hz)
input terminal
Ground terminals Connects to the power supply ground terminals and servomotor ground terminal.
External If using an internal regenerative resistor, please short B2 and B3. Remove the wire
regenerative between B2 and B3 and connect an external regenerative resistor(provided by
B1,B2,B3
resistor connection customer) between B1 and B2, if the capacity of the internal regenerative resistor is
terminal insufficient.
- 21 -
ETS Series AC Servo User's Manual
CN1_A
34
PAO
P represent multi-twisted 35
pair wire /PAO
Power supply for open collector 23 2KΩ
reference PL1
25 150Ω 32
PULS PULS PBO
P /PULS 24 33 PG dividing
/PBO ratio output
Position reference
Power supply for open collector 28 2KΩ
reference PL2
150Ω 30 PCO
SIGN 27
SIGN
P /SIGN 26 31
/PCO
Servo ON 36
SG
(When ON Servo function DICOM 3.3KΩ 18
+ 9
enabled) +24V - /S-ON ~
P Control 10
(When ON, P control
enabled) /P-CON
Forward rotation 11 ~
8
prohibited /COIN+
(When OFF, forward rotation ~ 7
P-OT ~ /COIN- /COIN Positioning complete
prohibited) 12
(/V-CMP Speed coincident )
Reverse rotation
/TGON Rotation Detection
prohibited
N-OT 13 ~ /S-RDY Servo Ready
(When OFF, reverse rotation
2 /CLT Torque limit Detection
prohibited) /TGON+ /BR Brake interlock
Alarm reset ~ 1 *
/ALM-RST ~ /TGON- * PGC Encoder C pulse output
(When ON, alarm reset) 14
OT Over travel
Clear signal input
/RD Servo enabled motor
(When ON, displacement
/CLR ~ excitation
clears) 15 6
Forward external torque /S-RDY+ /HOME Home completion
~ 5
limit /PCL /S-RDY- /TCR Torque Detection
(When ON, limit enabled) 16 ~
Reverse external torque
limit /NCL
~
+24V
17
(When ON, limit enable) 4 Alarm output
ALM+
0V (When Alarm triggered,OFF)
~ 3 ALM-
Photocoupler output
Max.applicable Voltage:DC30V
Max.applicable Current:DC50mA
Connector frame
FG * Specific pins output can be defined
Sheild wires connect to the connector frame
- 22 -
ETS Series AC Servo User's Manual
- 23 -
ETS Series AC Servo User's Manual
Notes:
1.The list of CN1_A、CN1_B、CN1_C about I/O Signal Names and Functions are the same.
2.(*)The signals of CN1_A/B/C-1、2,CN1_A/B/C-5、6,CN1_A/B/C-7、8 can be modified by Pn511;
(*)The signals of CN1_A/B/C-10、11、12、13 can be modified by Pn509;
(*)The signals of CN1_A/B/C-14、15、16、17 can be modified by Pn510;
Please refer to A.3 Parameters in details for detailed information.
Notes :
1. Spare terminals can not be used for relay purpose.
2. Connect shielded cable wires of I/O signals to connector shell(frame grounding).
- 24 -
ETS Series AC Servo User's Manual
Terminal
Name Function
No.
DICOM 9 Control power supply input for I/O signals: Provide the +24V DC power supply
/COIN-
7 Positioning completion(Speed coincidence):
(/V-CMP-)
Turns ON when the number of positional error
/COIN+ pulses reaches the value set.
8
(/V-CMP+)
The function of I/O are default,it can be
Motor rotation detection: when the servomotor
/TGON- 1
is rotating at a speed higher than the motor changed by setting parameters.
/TGON+ 2 speed setting.
Servo ready:
/S-RDY- 5
ON if there is no servo alarm when the
/S-RDY+ 6 control/main circuit power supply is turned ON.
ALM- 3 Servo alarm:
ALM+ 4 Turns off when an error is detected.
PAO+ 34
Phase-A signal
PAO- 35 Converted two-phase pulse(phases A
PBO+ 32 and B) encoder output.
Phase-B signal
PBO- 33
PCO+ 30
Phase-C signal Zero-point pulse(Phase-C) signal
PCO- 31
GND 18,36 GND
FG Shell Connect frame to ground if the shield wire of the I/O signal cable is connected to the
- 25 -
ETS Series AC Servo User's Manual
connector shell.
This section shows examples of servo drive I/O signal connection to the host controller.
The input circuit interface connects through a relay or open-collector transistor circuit.Select a low-current relay otherwise
Servodrive Servodrive
DC24V DC24V
+24VIN 50mA min. 3.3KΩ
50mA min. 3.3KΩ +24VIN
/S-ON,etc. /S-ON,etc.
The amount of two-phase (phase A and phase B) pulse output signals (PAO,/PAO,PBO,/PBO) and zero-point pulse
signals(PCO,/PCO) are output via line-driver output circuits.Normally, the servo drive uses this output circuit in speed
control to comprise the position control system at the host controller. Connect the line-driver output circuit through a line
DC5V~24V
Relay
0V
Note:
Maximum voltage should be no more than 30VDC, and maximum current should be no more than 50mA.
- 26 -
ETS Series AC Servo User's Manual
ETS-101010APC-CAN/ETS-1010APC-CAN
Wire-saving Incremental
Encoder Servodrive Host controller
*
CN2_A/B/C CN1_A/B/C
*
1(A) PA 2-1
Phase-A 1-34 PAO
2(B) P /PA 2-2
1-35 /PAO P
3(C) PB 2-3
4(D) P /PB 2-4 Phase-B 1-32 PBO
5(E) PC 2-5
1-33 /PBO P
6(F) P /PC 2-6
Phase-C 1-30 PCO
1-31 /PCO P
PG
Applicable line-
receiver SN75175
manufactured by TI
or the equivalent.
7(H) 2-7、2-8、2-9
PG5V
8(G) 2-17、2-18、2-19
PG0V
1-18 SG
0V 0V
1-36
FG Connector shell
9(J)
Connector shell
(Shell)
shielded wires
ETS-101010APG-CAN/ETS-1010APG-CAN
Incremental/Absolute Encoders Servodrive Host controller
*
CN2 CN1
*
K(1) PS 7
Phase-A 20 PAO
L(2) P /PS 8
21 /PAO P
T(3) BAT+ 17
S(4) P BAT- 18 Phase-B 22 PBO
23 /PBO P
Phase-C 24 PCO
25 /PCO P
PG
Output line driver
AM26LS31 manufactured
by TI or the equivalent. Applicable line-
receiver SN75175
manufactured by TI
or the equivalent.
H(5) PG5V 9
G(6) PG0V 19
50 DGND
0V 0V
* P
Represents multi-core twisted pair shielded wires.
Note: (1)BAT+ and BAT- signals are not used when using an incremental encoder .
(2)The pin numbers for the connector wiring differ depending on the servomotors .
- 27 -
ETS Series AC Servo User's Manual
ETS-101010APC-CAN/ETS-1010APC-CAN
Terminal
Name Function
No.
ETS-101010APG-CAN/ETS-1010APG-CAN
Terminal No. Name Function Terminal No. Name Function
Battery(+)
7 PS PG serial signal input 17 BAT+
(For an absolute encoder)
Battery(-)
8 /PS PG serial signal input 18 BAT-
(For an absolute encoder)
9 PG5V PG power supply +5V 19 GND PG power supply 0V
- 28 -
ETS Series AC Servo User's Manual
ETS-101010APC-CAN/ETS-1010APC-CAN
+10%
Three-phase AC200~230 50/60Hz -15%
Surge
Protector
Noise Filter
1RY PL
ON 1MC
OFF 1MC 1RY
Magnetic Contactor
A(1) Servo motor
U_A B(2)
1MC
L1 V_A C(3) MA
1MC W_A D(4)
L2 FG
1MC CN2_AWire-saving Encoder
L3
1 A+
2 A- Encoder
FG 3 B+
4 B-
L1C 5 C+
PGA
6 C-
L2C
7,8,9 PG5V
17,18,19 PG0V
CN3
CN4
Shell
FG
Connect Shield to Connector Shell
Note :The wiring of ETS two-axis servo drive does not include the gray part of graph.
- 29 -
ETS Series AC Servo User's Manual
CN1_A、CN1_B、CN1_C:
CN1_A/B/C
34
PAO
P represent multi-twisted 35
pair wire /PAO
Power supply for open collector 23 2KΩ
reference PL1
25 150Ω 32
PULS PULS PBO
P /PULS 24 33 PG dividing
/PBO ratio output
Position reference
Power supply for open collector 28 2KΩ
reference PL2
150Ω 30 PCO
SIGN 27
SIGN
P /SIGN 26 31
/PCO
Servo ON 36
SG
(When ON Servo function DICOM 3.3KΩ 18
+ 9
enabled) +24V - /S-ON ~
P Control 10
(When ON, P control
enabled) /P-CON
Forward rotation 11 ~
8
prohibited /COIN+
(When OFF, forward rotation ~ 7
P-OT ~ /COIN- /COIN Positioning complete
prohibited) 12
Reverse rotation (/V-CMP Speed coincident )
prohibited /TGON Rotation Detection
(When OFF, reverse rotation N-OT 13 ~ /S-RDY Servo Ready
2 /CLT Torque limit Detection
prohibited) /TGON+
Alarm reset /BR Brake interlock
/ALM-RST ~ 1 /TGON- *
(When ON, alarm reset) 14 ~ * PGC Encoder C pulse output
Clear signal input OT Over travel
(When ON, displacement /RD Servo enabled motor
/CLR ~ excitation
clears) 15 6
Forward external torque /S-RDY+ /HOME Home completion
~ 5
limit /PCL /S-RDY- /TCR Torque Detection
(When ON, limit enabled) 16 ~
Reverse external torque
limit /NCL
~
+24V
17
(When ON, limit enable) 4 Alarm output
ALM+
0V (When Alarm triggered,OFF)
~ 3 ALM-
Photocoupler output
Max.applicable Voltage:DC30V
Max.applicable Current:DC50mA
Connector frame
FG * Specific pins output can be defined
Sheild wires connect to the connector frame
CN3\CN4:
1 -
2 -
3 485+
4 ISO_GND
5 ISO_GND
6 485-
7 CANH
8 CANL
- 30 -
ETS Series AC Servo User's Manual
ETS-101010APG-CAN/ETS-1010APG-CAN
+10%
Three-phase AC200~230 50/60Hz -15%
Surge
Protector
Noise Filter
1RY PL
ON 1MC
OFF 1MC 1RY
Magnetic Contactor
A(1) Servo motor
U_A B(2)
1MC
L1 V_A C(3) MA
1MC W_A D(4)
L2 FG
1MC
L3 CN2_A Serial Encoder
7 S+
FG 8 S- Encoder
17 BAT+
L1C BAT-
18 PGA
5 PG5V
L2C
9 PG0V
19 Shield
7 S+
8 S- Encoder
17 BAT+
CN1_A 18 BAT- PGA
5 PG5V
9 PG0V
19 Shield
7 S+
CN1_C 8 S- Encoder
17 BAT+
18 BAT- PGA
5 PG5V
9 PG0V
19 Shield
CN3
CN4
Shell
FG
Connect Shield to Connector Shell
Note :The wiring of ETS two-axis servo drive does not include the gray part of graph.
- 31 -
ETS Series AC Servo User's Manual
CN1_A、CN1_B、CN1_C:
CN1_A/B/C
34
PAO
P represent multi-twisted 35
pair wire /PAO
Power supply for open collector 23 2KΩ
reference PL1
25 150Ω 32
PULS PULS PBO
P /PULS 24 33 PG dividing
/PBO ratio output
Position reference
Power supply for open collector 28 2KΩ
reference PL2
150Ω 30 PCO
SIGN 27
SIGN
P /SIGN 26 31
/PCO
Servo ON 36
SG
(When ON Servo function DICOM 3.3KΩ 18
+ 9
enabled) +24V - /S-ON ~
P Control 10
(When ON, P control
enabled) /P-CON
Forward rotation 11 ~
8
prohibited /COIN+
(When OFF, forward rotation ~ 7
P-OT ~ /COIN- /COIN Positioning complete
prohibited) 12
Reverse rotation (/V-CMP Speed coincident )
prohibited /TGON Rotation Detection
(When OFF, reverse rotation N-OT 13 ~ /S-RDY Servo Ready
2 /CLT Torque limit Detection
prohibited) /TGON+
Alarm reset /BR Brake interlock
/ALM-RST ~ 1 /TGON- *
(When ON, alarm reset) 14 ~ * PGC Encoder C pulse output
Clear signal input OT Over travel
(When ON, displacement /RD Servo enabled motor
/CLR ~ excitation
clears) 15 6
Forward external torque /S-RDY+ /HOME Home completion
~ 5
limit /PCL /S-RDY- /TCR Torque Detection
(When ON, limit enabled) 16 ~
Reverse external torque
limit /NCL
~
+24V
17
(When ON, limit enable) 4 Alarm output
ALM+
0V (When Alarm triggered,OFF)
~ 3 ALM-
Photocoupler output
Max.applicable Voltage:DC30V
Max.applicable Current:DC50mA
Connector frame
FG * Specific pins output can be defined
Sheild wires connect to the connector frame
CN3\CN4:
1 -
2 -
3 485+
4 ISO_GND
5 ISO_GND
6 485-
7 CANH
8 CANL
- 32 -
ETS Series AC Servo User's Manual
The servodrive uses high-speed switching elements in the main circuit. It may receive "switching noise"from these
• Position the input reference device and noise filter as close to the servo drive as possible.
• Always install a surge absorber in the relay, solenoid and electromagnetic contactor coils.
• The distance between a power line (servomotor main circuit cable) and a signal line must be at least 30 cm.Do not put
the power and signal lines in the same duct or bundle them together.
• Do not share the power supply with an electric welder or electrical discharge machine. When the servo drive is placed
near a high-frequency generator, install a noise filter on the input side of the power supplyline. As for the wiring of noise
2
2mm min.
*3 *2
Noise DC
filter power
3.5mm2 min.
plate)
*1
Wires of
3.5mm2 min. (ground plate)
(ground plate)
•For ground wires connected to the ground plate, use a thick wire with a thickness of at least 3.5 mm2 (preferably, plain
stitch cooper wire)
- 33 -
ETS Series AC Servo User's Manual
•When using a noise filter, follow the precautions in 3.6.2 Precautions on Connecting Noise Filter.
(2) Correct Grounding
Take the following grounding measures to prevent the servo drive from malfunctioning due to noise.
If the servomotor is grounded via the machine, a switching noise current will flow from the servo drive main circuit through
the servomotor stray capacitance.
Always connect servomotor frame terminal FG to the servodrive ground terminal. Also be sure to ground the ground
terminal .
If the I/O signal line receives noise, ground the 0 V line (SG) of the reference input line. If the main circuit wiring for the
motor is accommodated in a metal conduit, ground the conduit and its junction box. For all grounding, ground at one point
only.
■When the servo drive is installed on the control panel, a piece of metal plate should be fixed. It is used for fixing the servo
drive and other peripheral devices. The noise filter should be installed on the metal plate, and closed to the hole drill
through power lines on control panel. Use screws to fix the noise filter to the metal plate. The grounding terminals of noise
filter connects to the grounding terminals of control panel.
■Servo drive should be fixed on a piece of metal plate. Make sure the heat sink towards ground. The grounding terminals
of servo drive connect to the grounding terminals of control panel.
Note:
1. A single-phase servomotor should apply a two-phase filter. A three-phase servo drive should apply a
three-phase filter.
2. Choose the right filter according the specifications of operating voltage, current, and manufacturer.
(2) Precautions on Using Noise Filters
Do not put the input and output lines in the same duct or bundle them together.
- 34 -
ETS Series AC Servo User's Manual
Noise Noise
Filter Filter
Noise Noise
Filter Filter
Separate the noise filter ground wire from the output lines.
Do not accommodate the noise filter ground wire, output lines and other signal lines in the same duct or bundle them
together.
Noise Noise
Filter Filter
Connect the noise filter ground wire directly to the ground plate. Do not connect the noise filter ground wire to other
ground wires.
Noise Noise
Filter Filter
servodrive servodrive servodrive servodrive
stub
Shielded
ground wire
If a noise filter is located inside a control panel, connect the noise filter ground wire and the ground wires from other
devices inside the control panel to the ground plate for the control panel first, then ground these wires.
- 35 -
ETS Series AC Servo User's Manual
Control Panel
Servodrive
Noise
Filter
Servodrive
Ground
Ground plate
- 36 -
ETS Series AC Servo User's Manual
Chapter 4
Operation
Make sure that all wiring has been completed prior to trial operation.
Perform the following three types of trial operation in order. Instructions are given for speed control mode (standard setting)
and position control mode. Unless otherwise specified, the standard parameters for speed control mode (factory settings)
are used.
(1)Trial Operation for Servomotor Without Load (Refer to 4.1.1)
■Purpose
The servomotor is operated without connecting the shaft to the
Power Supply
machine in order to confirm the following wiring is correct.
·Power supply circuit wiring
·Servomotor wiring
·Encoder wiring
·Rotation direction and speed of servomotor.
(3) Trial operation for servomotor and machine combined. (Refer to 4.1.3)
■Purpose
Perform the trial operation with the servomotor
Power Supply
connected to the machine. The servo drive is adjusted to match the
machine characteristics.
·Servomotor speed and machine travel distance.
·Set the necessary parameters.
(Please refer to step 9-11)
- 37 -
ETS Series AC Servo User's Manual
Connect the power supply circuit (L1, L2 and L3), servomotor wiring (U, V,
W), I/O signal wiring (CN1_A/B/C), and encoder wiring (CN2_A/B/C). But
2 Wiring -
during (1) Trial Operation for Servomotor Without Load, disconnect the
CN1_A/B/C connector.
Turn the power ON. Using the panel operator to make sure that the servo
Turn the power
3 drive is running normally. If using a servomotor equipped with an absolute -
ON
encoder, please perform the setup for the absolute encoder.
Execute JOG Execute JOG operation with the servomotor alone under the no-load JOG
4
operation condition. Operation
Connect input Connect the input signals (CN1_A/B/C) necessary for trial operation to the
5 -
signals servo drive.
Input the
Host
7 Servo-ON Input the Servo-ON signal, and turn ON the servomotor.
Reference
signal
Input the reference necessary for control mode, and check the servomotor Host
8 Input reference
for correct operation. Reference
Turn the power OFF, and connect the servomotor to the machine.
Protective If using a servomotor equipped with an absolute encoder, set up the absolute
9 -
operation encoder and make the initial settings for the host controller to match the
machine’s zero position.
Using the same procedure as you did to input a reference in step 8,operate
Set necessary the servomotor via the host controller and set the parameter to make sure
10 Host
parameters. the machine’s travel direction, travel distance, and travel speed
Reference
allcorrespond to the reference.
Host
11 Operation The servomotor can now be operated. Adjust the servo gain if necessary.
Reference
- 38 -
ETS Series AC Servo User's Manual
!CAUTION
·Release the coupling between the servomotor and the machine, and secure only the servomotor without a load.
·To prevent accidents, initially perform the trial operation for servomotor under no-load conditions (with all couplings
and belts disconnected).
In this section, confirm the cable connections of the main circuit power supply, servomotor and encoder. Incorrect wiring is
generally the reason why servomotors fail to operate properly during the trial operation.
Confirm the wiring, and then conduct the trial operation for servomotor without load according to the following steps.
Check the power supply circuit, servomotor, and encoder With the I/O signal connector
wiring. (CN1_A/B/C)disconnected, check the power supply
2
circuit and servomotor wiring.
Refer to 3.1 Main Circuit Wiring.
Turn ON the control power supply and main circuit power If the power is correctly supplied, the panel operator
display on the front panel of the servo drive will appear
supply.
as shown on the left. The display on the left indicates
Normal Display that forward run prohibited (P-OT) and reverse run
prohibited (N-OT).
3 If an alarm display appears, the power supply circuit,
servomotor wiring, or encoder wiring is incorrect. If an
Alternate Display
alarm is displayed, turn OFF the power, find the
Example of Alarm Display problem, and correct it.
When using a servomotor with a brake, release the brake Please refer to 4.3.4 Setting for Holding Brakes
4 Please refer to 4.4 Operating Using Speed Control
first before driving the servomotor.
with Internally Set Speed
- 39 -
ETS Series AC Servo User's Manual
Press the MODE key. This will turn OFF the power to
6 MODE key
the servomotor.
Press the ENTER key to return to the Fn002 display
7 ENTER key of the utility function mode. Now, the servo drive is
OFF.
Note:
The servomotor’s rotation direction depends on the setting of parameter Pn001.0(Direction Selection).
The example above describes operation with Pn001.0 in the factory setting.
- 40 -
ETS Series AC Servo User's Manual
JOG Speed
Speed Position
Pn305
Setting Range Setting Unit Factory Setting Setting Validation
0~6000 rpm 500 Immediately
Set the utility function Fn002 (JOG Mode Operation) to the reference value of servomotor speed.
The servomotor can be operated using only the panel operator without reference from the host controller.
Please note that the Forward Run Prohibited (P-OT) and Reverse Run Prohibited (N-OT) signals are invalid during JOG
mode operation.
4.1.2 Trial Operation for Servomotor without Load from Host Reference
Check that the servomotor move reference or I/O signals are correctly set from the host controller to the servo drive.
Also check the wiring and polarity between the host controller and servo drive, and the servo drive operation settings are
correct. This is the final check before connecting the servomotor to the machine.
Servodrive
CN1_A
+24V 9
/S-ON
10
CLR 15
PULS+
25
Pulse reference
PULS- 24
Reference pulse according to
parameter Pn004.2 setting. SIGN+ 27
SIGN-
26
CN1_B
/S-ON
10
CLR 15
PULS+
25
Pulse reference
PULS- 24
Reference pulse according to
parameter Pn004.2 setting. SIGN+ 27
SIGN-
26
CN1_C
/S-ON
10
CLR 15
PULS+
25
Pulse reference
- 41 -
ETS Series AC Servo User's Manual
- 42 -
ETS Series AC Servo User's Manual
This function is available under all control mode, JOG speed is according to the value that set in the
parameter Pn305; The operation is different from Fn002 and Modbus communication which have
independent S-ON operation (Mode selection、S-ON for JOG operation). I/O JOG mode don’t have
independent S-ON signal, It depends on the actual status of the control mode that used. When the
function is enable, allocation of the Input signal can be defined by Pn711 and Pn712. The combinations
of the I/O port are shown as below:
!WARNING
To power supply
To host controller
- 43 -
ETS Series AC Servo User's Manual
- 44 -
ETS Series AC Servo User's Manual
Holding brake operation of the servomotor can be controlled with the brake interlock output (/BK) signal of the servo drive.
When checking the brake operation,take advance measures to prevent vibration due to gravity acting on the machine or
external forces. Check the servomotor operation and holding brake operation with the servomotor separated from the
machine.If both operations are correct, connect the servomotor to the machine and perform trial operation.
The control modes supported by the ETS series servo drives are described below.
Parameter Control Mode
Speed Control (parameter reference)
Controls servomotor speed using parameter reference. Use in the
following instances.
H.□□0□
·To control speed
·For position control using the encoder feedback divisionoutput from
the servo drive to form a position loop in the host controller.
Position Control(Pulse train reference)
Controls the position of the servomotor using pulse train position
reference.
H.□□1□
Controls the position with the number of input pulses, and controls the
speed with the input pulse frequency.
Use when positioning is required.
Pn005
Speed Control(contact reference) Speed Control
(zero reference)
Use the three input signals /P-CON,/P-CL and /N-CL to control the
H.□□2□
speed as set in advance in the servo drive.
Three operating speeds can be set in the servo drive. (In this case, an
analog reference is not necessary.)
H.□□3□
· These are swiching modes for using the four control methods
· described above in combination. Select the control method switching
· mode that best suits the application.
H.□□5□
H.□□6□ Reserved
- 45 -
ETS Series AC Servo User's Manual
This sets the servo ON signal (/S-ON) that determines whether the servomotor power is ON or OFF.
(1)Servo ON signal(/S-ON)
Connector Pin
Type Name Setting Meaning
Number
ON(low level) Servomotor power ON. Servomotor can beoperated.
CN1_A/B/C_10
Input /S-ON Servomotor power OFF. Servomotor cannot be
(Factory setting) OFF(high level)
operated.
■Important
Always input the servo ON signal before inputting the input reference to start or stop the servomotor.
Do not input the input reference first and then use the /S-ON signal to start or stop. Doing so will degrade internal
elements and may cause the servo drive to malfunction.
A parameter can be used to re-allocate the input connector number for the /S-ON signal. Refer to 3.2.2 I/O Signal Names
and Functions.
- 46 -
ETS Series AC Servo User's Manual
The rotation direction of the servomotor can be switched without changing the reference pulse to the servo drive or the
reference voltage polarity.
This causes the rotation the servo motor shaft is rotating to change. The output signal polarity, such as the encoder pulse
output and the analog monitor signal from the servo drive do not change.
The standard setting for “forward rotation” is counterclockwise as viewed from the servomotor load end.
Reference
Parameter Name
Forward reference Reverse reference
b.□□□0 Standard setting
(CCW=forward)
CCW
(factory setting) CW
PAO
PAO
PBO PBO
Pn001
b.□□□1 Reverse rotation
mode
CCW
(CW=forward) CW
PAO PAO
PBO PBO
The direction of P-OT and N-OT change. For Pn001=b.□□□0(standard setting), counterclockwise is P-OT. For
Pn001=b.□□□1(reverse rotation mode), clockwise is P-OT.
- 47 -
ETS Series AC Servo User's Manual
The overtravel limit function forces movable machine parts to stop if they exceed the allowable range of motion and turn
ON a limit switch.
(1)Connecting the overtravel signal
To use the overtravel function, connect the following overtravel limit switch to the corresponding pin number of servo drive
CN1_A/B/C connector correctly.
overtravel. Servomotor
CN1
For example, reverse rotation is possible during forward Limit switch Limit switch
P-OT
12
overtravel. N-OT 13
■Important
When using overtravel to stop the servomotor during position control, the position error pulses are present. A clear
signal(CLR)input is required to clear the error pulses.
! CAUTION
When using the servomotor on a vertical axis, the workpiece may fall in the overtravel condition.
To prevent this, always set the zero clamp after stopping with Pn004.0=5.
- 48 -
ETS Series AC Servo User's Manual
signal.
Parameter Meaning
b.□□0□ Inputs the forward rotation prohibited(P-OT) signal
fromCN1_A/B/C_12(factory setting).
b.□□1□ Disables the forward rotation prohibited (P-OT) signal. (Allows constant
forward rotation.)
Pn000
b.□0□□ Inputs the reverse rotation prohibited(N-OT) signal
fromCN1_A/B/C_13.(factory setting)
b.□1□□ Disables the reverse rotation prohibited(N-OT) signal. (Allows constant
reverse rotation.)
·Applicable control modes: Speed control, position control, and torque control.
·After changing these parameters, turn OFF the main circuit and control power supplies, and then turn them ON again to
enable the new settings.
·A parameter can be used to re-allocate input connector number for the P-OT and N-OT signals. Refer to 3.2.2 I/O Signal
Names and Functions.
- 49 -
ETS Series AC Servo User's Manual
·After changing these parameters, turn OFF the main circuit and control power
supplies, and then turn them ON again to enable the new settings. Servodrive Servomotor
·Stop by dynamic brake: Stops by using the dynamic brake (short circuiting its
electrical circuit).
·Coast to a stop: Stops naturally, with no brake, by using the friction resistance
of the servomotor in operation.
·Plug braking: Stops by using plug braking limit torque.
·Zero Clamp Mode: A mode forms a position loop by using theposition
reference zero.
·Dynamic brake is an emergency stop function, and one of the general methods to cause a servomotor sudden stop.
·Dynamic brake suddenly stops a servomotor by shorting its electrical circuit.
·If the servomotor is frequently started and stopped by turning the power ON/OFF or using the servo ON signal(/S-ON),
the DB circuit will also be repeatedly operated, degrading the servo drive’s internal elements.
·Use the speed input reference and position reference to control the starting and the stopping of the servomotor.
- 50 -
ETS Series AC Servo User's Manual
The holding brake is used when the servo drive controls a vertical axis.
A servomotor with the brake option helps prevent movable parts from shifting due to gravity when power is removed from
the servo drive.(Refer to 4.1.4 Trial Operation for Servomotor with Brakes.)
Servomotor
Holding brake External force
1. The servomotor with the built in brake, is a de-energization brake. It is used to hold the servomotor and cannot be used
as a braking purposes. Use the holding brake only to hold a stopped servomotor.
2. When operating using only a speed loop, turn OFF the servo and set the input reference to 0V when the brake is
applied.
3. When forming a position loop, do not use a mechanical brake while the servomotor is stopped because the servomotor
enters servolock status.
(1)Wiring Example
Use the servo drive sequence output signal /BK and the brake power supply to form a brake ON/OFF circuit.
The following diagram shows a standard wiring example.
S L2 V
M
T L3 W
L1C
L2C
CN2_A/B/C PG
CN1_A/B/C
BK-RY (/BK+) *1
+24V
(/BK-) *2
BK
- 51 -
ETS Series AC Servo User's Manual
Brake interlock output (/BK) is not used with the factory setting.The output signal must be allocated.
Connector Pin Number
Parameter Meaning
+ Terminal - Terminal
The /BK signal is output from output
Pn511 H.□□□4 CN1_A/B/C-11 CN1_A/B/C-12
terminal CN1_A/B/C-11,12.
The /BK signal is output from output
Pn511 H.□□4□ CN1_A/B/C-5 CN1_A/B/C-6
terminal CN1_A/B/C -5,6.
The /BK signal is output from output
Pn511 H.□4□□ CN1_A/B/C-9 CN1_A/B/C-10
terminal CN1_A/B/C -9,10.
■Important
When set to the factory setting, the brake signal is invalid.
For the allocation of servo drive output signals other than /BK signal, refer to 3.2.2 I/O Signal Names and Functions.
0 /COIN(/V-CMP)output
Related parameter:
Parameter Setting
Name Unit Default
No. Range
Pn505 Servo ON waiting time ms -2000~2000 0
Pn506 Basic waiting flow 10ms 0~500 0
Pn507 Brake waiting speed rpm 10~100 100
Pn508 Brake waiting time 10ms 10~100 50
- 52 -
ETS Series AC Servo User's Manual
Pn505
Setting Range Setting Unit Factory Setting Setting Validation
-2000~2000 ms 0 Immediately
Pn506
Setting Range Setting Unit Factory Setting Setting Validation
Pn506 Pn505
■Important
·The servomotor will turn OFF immediately when an alarm occurs, regardless of the setting of this parameter.
·The machine movable part may shift due to gravity or external force during the time until the brake operates.
- 53 -
ETS Series AC Servo User's Manual
The following parameters can be used to change the /BK signal output conditions when a stop reference is output during
The /BK signal goes to high level(brake ON) when either of the following conditions is satisfied:
·When the servomotor speed falls below the level set in Pn507 after servo OFF.
Servo OFF
/S-ON input Servo ON
or alarm or
power OFF
Servomotor stopped
by applying DB or
Servomotor Speed Pn507 coasting.
(Pn004.0)
Pn508
- 54 -
ETS Series AC Servo User's Manual
Parameter Meaning
Pn002 b.□0□□ Use the absolute encoder as an absolute encoder. (Factory setting)
·The back-up battery is not required when using the absolute encoder as an incremental encoder.
·After changing these parameters, turn OFF the main circuit and control power supplies and then turn them ON
- 55 -
ETS Series AC Servo User's Manual
In order for the absolute encoder to retain position data when the power is turned OFF, the data must be backed up by a
battery.
Please purchase the special cable and battery case mabe by Estun if an absolute encoder is used.
Encoder cable
- 56 -
ETS Series AC Servo User's Manual
The servo drive will generate an absolute encoder battery alarm (A.48) when the battery voltage drops below about 3.1V.
1. Replace the battery with only the servo drive control power supply turned ON.
2. After replacing the battery, using the panel operator with utility function Fn011 to cancel the absolute encoder battery
alarm (A.48).
3. Turn ON the servo drive power back again. If it operates without any problems, the battery replacement has been
completed.
Note:
·The servo drive will generate an absolute encoder battery alarm (A.48) when the battery voltage drops below about 3.1V.
·If an absolute encoder battery alarm (A.47) occurred, it means the battery voltage drops below about 2.5V, and the
multiturn data is lost. Please reset the absolute encoder after changing the battery.
Note:
1. Encoder setup operation is only possible when the servo is OFF.
2. If the absolute encoder alarms(A.45~A.48,A.51 ) are displayed, cancel the alarm by using the same method as the
setup. They cannot be cancelled with the servo drive alarm reset input signal(/ALM-RST).
3. Any other alarms that monitor the inside of the encoder should be cancelled by turning OFF the power.
Parameter Meaning
Pn005 H.□□0□ Control mode selection:Speed control(Internally set speed)(factory setting)
- 57 -
ETS Series AC Servo User's Manual
The soft start function converts the stepwise speed reference inside the servo drive to a consistent rate of acceleration
and deceleration.
Pn310 can be used to select the soft start form:
0: Slope; 1: S curve; 2: 1st-order filter; 3: 2nd-order filter
Soft Start Acceleration Time
Speed
Pn306
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
Soft Start Deceleration Time
Speed
Pn307
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
The soft start function enables smooth speed control when inputting a stepwise speed reference or when selecting
internally set speeds. Set both Pn306 and Pn307 to “0” for normal speed control.
Set these parameters as follows:
·Pn306:The time interval from the time the servomotor starts until the servomotor is 1000rpm.
·Pn307:The time interval from the time the servomotor is 1000rpm until it stops.
Pn306 Pn307
- 58 -
ETS Series AC Servo User's Manual
S-curve Risetime
Speed
Pn309
Setting Range Setting Unit Factory Setting Setting Validation
0~10000 1ms 0 Immediately
Encoder feedback pulses processed inside the servo drive can be output externally.
Type Signal Name Connector Pin Number Name
PAO+ 34 Encoder output phase A
Output
PAO- 35 Encoder output phase /A
PBO+ 32 Encoder output phase B
Output
PBO- 33 Encoder output phase /B
PCO+ 30 Encoder output phase C(zero-point pulse)
Output
PCO- 31 Encoder output phase /C(zero-point pulse)
Encoder CN1
*
CN2 Phase A(PAO)
Serial Data Frequency Phase B(PBO)
PG
dividing
Phase C(PCO)
circuit
*The dividing output phase form is the same as the standard setting(Pn001.0=0) even if inreverse rotation
mode(Pn001.0=1).
■Output phase form
Pn001.0=0:
- 59 -
ETS Series AC Servo User's Manual
90°
Forward(CCW) 90° Reverse(CW)
Phase A Phase A
Phase B Phase B
t t
Pn001.0=1:
90°
Forward(CCW) 90° Reverse(CW)
Phase A Phase A
Phase B Phase B
t t
If the servomotor is not equipped with an absolute encoder, the servomotor needs two full rotations before using the servo
drive's Phase-C pulse output as the zero point reference.
Dividing:Dividing means that the divider converts data into the pulse density(Pn200) based on the pulse data of the
encoder installed on the servomotor, and outputs it. The setting unit isnumber of pulses/revolution.
- 60 -
ETS Series AC Servo User's Manual
PAO
PBO
1 revolution
The speed coincidence (/V-CMP) output signal is output when the actual servomotor speed during speed control is the
same as the speed reference input. The host controller uses the signal as an interlock.
Type Signal Name Connector Pin Number Setting Meaning
CN1_A/B/C-7,8 ON(low level) Speed coincides.
Output /V-CMP(/COIN)
(factory setting) OFF(high level) Speed does not coincide.
Coincidence Difference
Speed
Pn501
Setting Range Setting Unit Factory Setting Setting Validation
0~100 rpm 10 Immediately
The /V-CMP signal is output when the difference between the speed reference and actual servomotor speed is less than
Pn501.
■Example
The /V-CMP signal turns ON at 1900 to 2100rpm ifthe Pn501 parameter is set to 100 and the reference speed is 2000rpm.
Servomotor speed Pn501
Reference speed
■Note
This pin outputs the /COIN signal in position control mode, and the /V-CMP signal in speed control mode.
- 61 -
ETS Series AC Servo User's Manual
The function of internally set speed selection allows speed control operation by externally selecting an input signal from
among seven servomotor speed setting made in advance with parameters in the servo drive. The speed control
operations within the three settings are valid. There is no need for an external speed or pulse generator.
Servodrive
SPEED5 Pn320
SPEED6 Pn321
/N-CL
SPEED7 Pn322
■Parameters setting
Parameter Meaning
Pn005 H.□□2□ Control mode selection:Speed control(contact reference)
Pn316
Setting Range Setting Unit Factory Setting Setting Validation
Pn317
Setting Range Setting Unit Factory Setting Setting Validation
Pn318
Setting Range Setting Unit Factory Setting Setting Validation
Pn319
Setting Range Setting Unit Factory Setting Setting Validation
Pn320
Setting Range Setting Unit Factory Setting Setting Validation
Pn321
Setting Range Setting Unit Factory Setting Setting Validation
- 62 -
ETS Series AC Servo User's Manual
Pn322
Setting Range Setting Unit Factory Setting Setting Validation
Input Signal
Speed
/P-CON /P-CL /N-CL
Input Signal
Speed
/P-CON /PCL /NCL
OFF(H) OFF(H) Positioncontrol(pulse train reference)
OFF(H) ON(L) SPEED1
OFF(H)
ON(L) OFF(H) SPEED2
ON(L) ON(L) SPEED3
OFF(H) OFF(H) SPEED4
OFF(H) ON(L) SPEED5
ON(L)
ON(L) OFF(H) SPEED6
ON(L) ON(L) SPEED7
- 63 -
ETS Series AC Servo User's Manual
Set the following parameters for position control using pulse trains.
Parameter Meaning
Pn005 H.□□1□ Control mode selection:position control(pulse train reference)
Set the input form for the servo drive using parameter Pn004.2 according to the host controllerspecifications.
Reference Input Pulse Forward Rotation Reverse Rotation
Parameter
Pulse Form Multiplier Reference Reverse
PULS PULS
Sign+pulse train (CN1_A/B/C-25 ) (CN1_A/B/C-25)
(factory setting)
PULS
(CN1_A/B/C-25) PULS
L
(CN1_A/B/C-25)
CW+CCW SIGN
H.□1□□ — (CN1_A/B/C-27
SIGN
(CN1_A/B/C-27) L
Pn004 (positive logic)
■Note:
The input pulse multiplier can be set for the two-phase pulse train with 90°phase differential reference pulse form.
- 64 -
ETS Series AC Servo User's Manual
PULS
(CN1_A/B/C-25)
SIGN
(CN1_A/B/C-27)
×1
×4
- 65 -
ETS Series AC Servo User's Manual
□□2□ Clearthe error pulse when S-OFF orovertravel (excep for zero clamp)
(1)Electronic Gear
The electronic gear enables the workpiece travel distance per input reference pulse from the host controller to be set to
any value.
One reference pulse from the host controller, i.e., the minimum position data unit, is called a reference unit.
When the Electronic Gear is Not Used When the Electronic Gear is Used
workpiece workpiece
Reference unit:1µm
(2)Related Parameters
Pn201
Setting Range Setting Unit Factory Setting Setting Validation
1~65535 — 1 After restart
- 66 -
ETS Series AC Servo User's Manual
Pn202
Setting Range Setting Unit Factory Setting Setting Validation
1~65535 — 1 After restart
32 Bit Electronic Gear Ratio (Numerator,H)
Pn705 Setting Range Setting Unit Factory Setting Setting Validation
1~9999 10000 0 After restart
32 Bit Electronic Gear Ratio (Numerator,L)
Pn706 Setting Range Setting Unit Factory Setting Setting Validation
1~9999 1 1 After restart
32 Bit Electronic Gear Ratio (Denominator,H)
Pn707 Setting Range Setting Unit Factory Setting Setting Validation
1~9999 10000 0 After restart
32 Bit Electronic Gear Ratio (Denominator,L)
Pn708 Setting Range Setting Unit Factory Setting Setting Validation
1~9999 1 1 After restart
The deceleration ratio of the servomotor and the load shaft is given as n/m where m is the rotation of the servomotor and n
is the rotation of the load shaft.
B Pn 201
Electronic gear ratio:
A Pn 202
No. of encoder pulses 4 m
Travel dis tan ce per load n
shaft revolution (reference units )
- 67 -
ETS Series AC Servo User's Manual
5 Calculate the electronic gear ratio. Use the electronic gear ratio equation to calculate the ratio (B/A).
6 Set parameters. Set parameters using the calculated values.
The following examples show electronic gear ratio settings for different load configurations.
Load Configuration
Ball Screw Disc Table Belt and Pulley
- 68 -
ETS Series AC Servo User's Manual
Servomotor n
Pitch=P(mm/rev)
Reference pulse B +
Position Speed
A — loop loop
(mm / P) m
- 69 -
ETS Series AC Servo User's Manual
4.6.4 Smoothing
Parameter Description
0:1st-order filter
Pn205
1:2nd-order filter
* After changing the parameter, turn OFF the power once and turn it ON again to enable the new setting.
(2)Filter-related Parameters
Position Reference Acceleration/Deceleration Time Constant
Position
Pn204
Setting Range Setting Unit Factory Setting Setting Validation
0~32767 0.25ms 0 Immediately
■Important
When the position reference acceleration/deceleration time constant (Pn204) is changed, a value with no reference
pulse input and a position error of 0 will be enabled. To ensure that the setting value is correctly reflected, stop the
reference pulse from the host controller and input the clear signal (CLR), or turn OFF to clear the error.
This function provides smooth servomotor operation in the following cases.
·When the host controller that outputs a reference that cannot perform acceleration/deceleration processing.
·When the reference pulse frequency is too low.
·When the reference electronic gear ratio is too high (i.e., 10× or more)
- 70 -
ETS Series AC Servo User's Manual
(1)Note:
For the low rigidity load, low frequency vibration will occur continually at the front end of the load during fast acceleration
or fast deceleration. The vibration may delay positioning time and affect the productive efficiency.
The function of low frequency vibration suppression is embedded in ETS series servo drives by calculating the load
Workbench
Servomotor
(2)Application:
Low frequency vibration suppression function is enabled in both speed control mode and position control mode.
Low frequency vibration suppression function is disabled or can not reach the expected effect in the following conditions.
Write the frequency data measured(unit:0.1Hz) directly to Parameter Pn411, if the vibration frequency can be
- 71 -
ETS Series AC Servo User's Manual
ΔT
0
t
f = 1 / ΔT
Related Parameters
Parameter Meaning
- 72 -
ETS Series AC Servo User's Manual
This signal indicates that servomotor movement has been completed during position control. Use the signal as an
interlock to confirm that positioning has been completedat the host controller.
Type Signal Name Connector Pin Number Setting Meaning
CN1_A/B/C-7, ON(low level) Positioning has been
CN1_A/B/C-8 completed.
Output /COIN
(Factory setting) OFF(high level) Positioning is not
completed.
·This output signal can be allocated to an output terminal with parameter Pn511. Refer to 3.2.2 I/O Signal Names and
Functions.
Positioning Error
Position
Pn500 Setting Range Setting Unit Factory Setting Setting Validation
0~5000 1Puls 10 Immediately
Reference
Speed Servomotor speed
Pn500
Error pulse
(Un011,Un012)
/COIN
(CN1_A/B/C-11,12)
■Note
·/COIN is a position control signal.
·This signal is used for the speed coincidence output /V-CMP for speed control, and it always OFF(high level) for torque
control.
- 73 -
ETS Series AC Servo User's Manual
(1)Description
This function inhibits the servo drive from counting input pulses during position control.
Servodrive
Pn005.1
Pn005=H.□□1□
OFF +
Reference pulse
Pn005=H.□□4□ Error Counter
ON -
/P-CON
/P-CON
Feedback pulse
(2)Setting Parameters
Parameter Meaning
Pn005 H.□□4□ Control mode selection:position control(pulse train reference)⇔INHIBIT
■Inhibit(INHIBIT) switching condition
·/P-CON signal ON (low level)
ON OFF ON
/P-CON
Reference pulse
t1 t2
t1,t2≤ 0.5ms
Input reference pulses are not
counted during this period.
- 74 -
ETS Series AC Servo User's Manual
Position control under contact reference (parameter Pn005.1=5). In this mode, servo drive can position with a single axes
without a host controller.
There are 16 position control points with each being able to set move distance, running speed, constants for position
reference filter time, and the stop time when positioning completed. Two speeds (1. speed moving toward distance switch
“speed of looking for reference point”. 2. Speed moving away from distance switch “moving speed.”) of reference points
could be set as:
Two position modes: 1. Absolute position mode 2. Relative position mode
Two running modes: 1. Circling mode 2. Non-circling mode
Two step switching method: 1. Delay step switching 2. /P-CON signal switching
Method of looking for reference points: 1. Forward direction 2. Reverse direction
■Adjusting offset
Offset of each points has two correspondent parameters: one unit of the parameter is 【x 10000 reference pulse】and the
other is 【x 1 reference pulse】. Setting range of both parameters is: (-9999----+9999), while offset value equals sum of
those two values.
For example:
No.0 offset correspond to parameter Pn600【x 10000 reference pulse】 and Pn601【x 1 reference pulse】. Set Pn600
= 100, Pn601=-100.
No.0 offset value = Pn600x10000 reference pulse + Pn601x1 reference pulse
= 100x10000 reference pulse + (-100)x1 reference pulse
= 999900 reference pulse
With the same principle, we can conclude: in order to get the same results, we also can set Pn600 = 99 and Pn601 =
9900.
Thus, we can see when the two parameters are not zero; we can get same result by two ways: one is to set the two
parameters both negative or both positive, or one negative the other positive.
■Speed
Speed mentioned here refers to the steady speed during which the motor is running, which is similar to the pulse
frequency given from the external pulse reference in position control.However, this speed has nothing to do with the
electronic gear; it is the actual speed of the motor.
- 75 -
ETS Series AC Servo User's Manual
Setting
Para. No. Name and description Default
range
[0] Clear error pulse when S-0FF, not clear error pulse
when overtravel.
Pn004.1 0~2 0
[1] Not clear error pulse
[2] Clear error pulse When S-OFF or over travel
Usually, the set speed of the reference point (Pn685) is high, and the moving speed (Pn686) is low. Note: if moving speed
is too high, precision of finding a reference point would be affected.
When looking for a reference point, /PCL and /NCL are no longer programmed to limit external current.
■Related parameter
Para. No. Description Observation
Choose between cycle run and single run. Changing steps will be performed till
0: Cycle run, /PCL as start signal, /NCL reverse to the end point is completed comma
look for reference point. and the next change will start from
1: Single run, /PCL as start signal, /NCL reverse to the start point during multi-points
Pn681.0 look for reference point. cycle run.
2. Cycle run, /NCL as start signal, /PCL reverse to Point control program will not
look for reference point. change steps after the end point is
3. Single run, /NCL as start signal, /PCL reverse to completed during multi- points single
look for reference point. run.
- 76 -
ETS Series AC Servo User's Manual
- 77 -
ETS Series AC Servo User's Manual
The servo drive provides internal torque limit/external torque limitfor limiting output torque to protect the machine.
Pn402
t
t
Pn401
Speed Speed
Limiting torque
Maximum torque
■Note:
Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.
- 78 -
ETS Series AC Servo User's Manual
This function allows the torque to be limited at specific times during machine operation, for example, during press stops
An input signal is used to enable the torque limits previously set in parameters.
(1)Related Parameters
Forward External Torque Limit
Speed Position
Pn403 Setting Range Setting Unit Factory Setting Setting Validation
0~300 % 100 Immediately
Reverse External Torque Limit
Speed Position
Pn404 Setting Range Setting Unit Factory Setting Setting Validation
0~300 % 100 Immediately
Note: The setting unit is a percentage of rated torque (i.e., the rated torque is 100%).
(2)Input Signals
Signal Connector Pin
Type Setting Meaning Limit Value
Name Number
ON(low level) Forward external torque limit Pn403
Input /P-CL Pn509.0=6
OFF(high level) Forward internal torque limit Pn401
ON(low level) Reverse external torque limit Pn404
Input /N-CL Pn509.0=7
OFF(high level) Reverse internal torque limit Pn402
When using this function, make sure that there are no other signals allocated to the same terminals as /P-CL and /N-CL.
High 0 0
level
Speed Pn403
Pn401 Speed
/N-CL
(Reverse
External
Torque Pn404 Pn404
Torque Torque
Limit Input)
Low
0 0
level
Pn403
Speed Speed
Pn401
Note: Select the servomotor rotation direction by setting Pn001=b.□□□0 (standard setting, CCW=Forward direction).
- 79 -
ETS Series AC Servo User's Manual
The following diagram shows the right way to connect the Alarm Output.
Servo drive
CN1
I/O Power supply
+24V 0V
Optocoupler output 4 ALM+
(Each output node)
50mA max
Max.output voltage: 30V ALM-
Max.output current: 50mA 3
An external +24V I/O power supply is required since there is no +24V power source available inside the servo drive.
Output → ALM+CN1_A/B/C-4 Servo alarm output
Output → ALM- CN1_A/B/C-3 Servo alarm output uses grounding signal
ALM outputs a signal when the servo drive is detected in an abnormal state.
Servo drive
Be detected
abnormal ALM Output
Normally, the external circuit consists of /ALM should be able to switch off the power of servo drive.
When “servo alarm(ALM)” happens, always remove alarm reasons first , and then turn the input signal "/ALM-RST" to ON
position to reset alarm status.
4.8.2 Others
- 80 -
ETS Series AC Servo User's Manual
CN1_A/B/C-7/8
ON=L Homing is enabled
8 /HOME CN1_A/B/C-1/2
CN1_A/B/C-5/6 OFF=H Homing is disabled
Not including this setting in the Motor output torque is higher than
ON=L
default setting,please choose Pn529 setting value.
9 /TCR
terminal output by setting parameter Motor output torque is lower than
OFF=H
Pn511 Pn529 setting value.
- 81 -
ETS Series AC Servo User's Manual
Online autotuning calculates the load moment of inertia during operation of the servo drive and sets parametersso that the
servo gains are consistent with the machine rigidity.
Online autotuning may not be effective in the following cases:
• The motor high speed is lower than 100 rpm.
• The motor acceleration or deceleration is lower than 5000rpm/s.
• Load rigidity is low and mechanical vibration occurs easily or friction is high.
•The speed load moment is changed greatly.
• Mechanical gas is very large.
If the condition meets one of the above cases or the desired operation cannot be achieved by the online autotuning,
set the value in Pn106 (Load inertia percentage) and performthe adjustment manually.
!WARNING
■Do not perform extreme adjustment or setting changes causing unstable servo operation.Failure to observe
this warning may result in injury and damages to the machine.
■ Adjust the gains slowly while confirming motor operation.
- 82 -
ETS Series AC Servo User's Manual
Start
No
Yes
No
No
End
Related parameters:
Parameter Setting Factory Setting
Name Unit
No. Range Setting Invalidation
Online autotuning setting
Pn100 0:Manual gain adjustment — 0~6 0 After restart
1,2,3=Normal mode;4,5,6=Vertical load
- 83 -
ETS Series AC Servo User's Manual
There are 16 machine rigidity settings for online autotuning, When the machine rigidity setting is selected, the servo
gains (speed loop gain, speed loop integral time constant, position loop gain) are determined automatically. The
factory setting for the machine rigidity setting is 5.
Machine Position Loop Gain【s-1】 Speed Loop Gain【Hz】 Speed Loop Integral Time
Rigidity Setting Pn104 Pn102=Pn104*( Pn128+1) Constant【0.1ms】
Pn103
0 10 40 800
1 15 60 600
2 20 80 450
3 25 100 400
4 30 120 300
5 40 160 200
6 65 260 140
7 80 320 110
8 100 400 90
9 120 480 80
10 140 560 70
11 160 640 60
12 180 720 55
13 210 840 50
14 250 1000 40
15 300 1200 30
- 84 -
ETS Series AC Servo User's Manual
The servomotor always needs to operate at a fixed position. This position is normally regarded as the zero position. When
the host controller is turned on, the zero position adjustment is required before processing. This zero position will be
regarded as the reference point. ESTUN servo drives can perform this function by the homing function.
(2)Related parameter:
- 85 -
ETS Series AC Servo User's Manual
Please set Pn689 according to the actual operation in position control mode. When starting the homing function, the
servomotor will run at the speed of Pn685 when detecting the rising edge of SHOM signal; the servomotor will run at the
speed of Pn686 according to the setting of Pn689.1 when detecting the valid ORG signal.
When input ORG and the encoder C-Pulse is detected, the servo drive will begin to calculate the number of homing offset
pulses. When offset pulses is completed, the servomotor stops and outputs homing completion signal /HOME, then
Pn685 (Hitting the origin signal (ORG)) is usually set at high speed, Pn686 (Leaving the origin signal ORG) is usually set
at low speed.
Please be attention that if Pn686 is setting too high, the precision of mechanical zero position will be affected.
After hitting the origin signal ORG, the motor will return to find C-pulse; the figure is shown as below:
Speed Pn 685
(rpm)
Pn 686
ORG
Encoder C-pulse
- 86 -
ETS Series AC Servo User's Manual
Mechanical shaft
Encoder C-pulse
ORG
Rising edge
SHOM
After hitting the origin signal ORG, the motor will find C-pulse directly; the figure is shown as below:
Speed Pn 685
rpm
Pn 686
Find C-pulse without
0rpm returning
ORG
Encoder C-pulse
Corresponding position:
Mechanical shaft
Encoder C-pulse
ORG
Rising edge
SHOM
- 87 -
ETS Series AC Servo User's Manual
Chapter 5
Panel Operator
The panel operator is a built-in operator that consists of display section and keys located on the front panel of the servo
drive.
Parameter setting, status display ,and execution of utility function are enabled using the panel operator.
The names and functions of the keys on the panel operator are shown as follows:
A
B
C
Panel Corresponding
Function
Symbol Key Name
AXIS AXIS key To switch the number of axis
·To display the parameter settings and setting values.
▲ INC key
·To increase the setting value.
▼ DEC key
·To decrease the setting value.
·To select a basic mode, such as the display mode, parameter setting
M MODE key mode, monitor mode, or utility function mode.
◄ ENTER key To display the parameter settings and setting values, and release ararm.
Note: In this manual, the Panel Symbol is represented by Corresponding Key Name for easy understanding.
Servo axisescan be switched by pressing the AXIS key when the panel operator in display mode.
- 88 -
ETS Series AC Servo User's Manual
A
B
C
The basic modes include status display mode, parameter setting mode, monitor mode, and utility function mode. Each
time the MODE key is pressed, the next mode in the sequence is selected.
Select a basic mode to display the operation status, set parameters and operation references.
The basic mode is selected in the following order.
Power ON
Monitor mode
The status display mode displays the servo drive status as bit data and codes.
Selecting Status Display Mode
The status display mode is selected when the power supply is turned ON. If it is not displayed, select this mode by
pressing MODE key.
Note that the display differs between the speed/torque controland position control types.
- 89 -
ETS Series AC Servo User's Manual
{
{
Bit Data Code
①
③
④ ⑦
⑤ ⑥
2
○ Base lock Lit for base block. Not lit at servo ON. Base block Lit for base block. Not lit at servo ON.
- 90 -
ETS Series AC Servo User's Manual
Codes Display
Code Meaning
Baseblock
Servo OFF(servomotor power OFF)
Run
Servo ON(servomotor power ON)
Forward Run Prohibited
CN1_A/B/C_12(P-OT)is OFF.
Reverse Run Prohibited
CN1_A/B/C_13(N-OT)is OFF.
Alarm Status
Displays the alarm number.
Press ENTER key to clear the present servo alarm.
The servo drive offers a large number of functions, which can be selected or adjusted by the parameter settings. Refer
toA.1 Parameter List for details.
■Parameter Setting Procedures
The parameter settings can be used for changing parameter data. Before changing the data, check the permitted range of
the parameter.
The example below shows how to change parameter Pn102 from “100” to “85”.
1. Press MODE key to select the parameter setting mode.
4. Press the INC or DEC key to change the data to the desired number 00085. Hold the key to accelerate the changing
of value. When the maximum value or minimum value is reached, pressing INC or DEC key respectively, will have no
effect.
5. Press the ENTER or MODE key once to return to the display of Pn102.
- 91 -
ETS Series AC Servo User's Manual
The monitor mode allows the reference values input into the servo drive, I/O signal status, and servo drive internal status
to be monitored.
The example below shows how to display the value (1500) stored in Un001.
1.Press MODE key to select the monitor mode.
2.Press the INC or DEC key to select the monitor number to display.
3.Press the ENTER key to display the data for the monitor number selected at step 2.
4.Press the ENTER key once more to return to the monitor number display.
- 92 -
ETS Series AC Servo User's Manual
- 93 -
ETS Series AC Servo User's Manual
- 94 -
ETS Series AC Servo User's Manual
In utility function mode, the panel operator can be used to run and adjust the servo drive and servomotor.
The following table shows the parameters in the utility function mode.
Parameter No. Function
Fn000 Alarm traceback data display
Fn001 Parameter setting initialization
Fn002 JOG mode operation
Fn003 Reserved
Fn004 Reserved
Fn005 Automatic adjustment of servomotor current detection
Fn006 Manual adjustment of servomotor current detection
Fn007 Software version display
Fn008 Position teaching
Fn009 Static inertia detection
Fn010 Reserved
Fn011 Reserved
Fn012 Reserved
Fn013 Parameters copy
Fn014 Reserved
The alarm traceback display can display up to 10 previously occurred alarms.The alarm is displayed on Fn000, which is
stored in the alarm traceback data.
Follow the procedures below to confirm alarms which have been generated.
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the function number of alarm traceback data display.
3. Press the ENTER key once, the latest alarm data is displayed.
Alarm Sequence NumberAlarm Code
4.Press the INC or DEC key to display other recent alarms that have occurred.
Note: Hold the ENTER key for one second with alarm code displaying, all the alarm traceback datas will be cleared.
- 95 -
ETS Series AC Servo User's Manual
(axis A)
(axis B)
(axis C)
4.Hold the ENTER key for one second, the parameters will be initialized.
5. Release the ENTER key to ruturn to the utility function mode display Fn001.
Note:
Press the ENTER key during servo ON does not initialize the parameter settings.
Initialize the parameter settings with the servo OFF.
- 96 -
ETS Series AC Servo User's Manual
4. Press the MODE key to enter into servo ON(servomotor power ON) status.
5. Press the MODE key to switch between the servo ON and servo OFF status.The servo drive must be in servo ON
status when the servomotor is running.
6. Press the INC or DEC key to rotate the servomotor.
7. Press the ENTER key to return to utility function mode display Fn002.Now the servo is OFF(servomotor power OFF).
- 97 -
ETS Series AC Servo User's Manual
Automatic servomotor current detection offset adjustment is performed at ESTUN before shipping. Basically, the user
does not need to perform this adjustment.
Perform this adjustment only if highly accurate adjustment is required for reducing torque ripple caused by current offset.
This section describes the automatic and manual servomotor current detection offset adjustment.
Note:
·Offset-adjustment of the servomotor current detection signal is possible only while power is supplied to the main
circuit power supply and with the servo is the OFF state.
·Execute the automatic offset adjustment if the torque ripple is too big when compared with that of other servo
drives.
·If this function, particularly manual adjustment, is executed carelessly, it may worsen the characteristics.
3. Press the ENTER key to enter into the automatic adjustment of the servomotor current detection signal mode.
4.Press the MODE key,the display will blinks for one second. The offset will be automatically adjusted.
5. Press the ENTER key to return to the utility function mode display Fn005.
Thus, the automatic offset-adjustment of the servomotor current detection signal is complete.
3. Press the ENTER key to enter into the manual adjustment of the servomotor current detection signal.
- 98 -
ETS Series AC Servo User's Manual
4. Press the MODE key to switch between the phase U(o _ CuA) and phase V(1_ Cub) servomotor current detection
offset adjustment.
5. Hold the ENTER key for one second to display the phase V offset amount.
7. Press the ENTER key for one second to return to the display in step 3 or 4.
8. Press the ENTER key to return to the utility function mode display Fn006.
Thus, the manual offset-adjustment of the servomotor current detection signal is completed.
Note:
The adjusting range of the servomotor current detection offset is -100 to +100.
- 99 -
ETS Series AC Servo User's Manual
Select Fn007 in utility function mode to check the current software version of the drive.
1. Press the MODE key to select the utility function mode.
2. Press the INC or DEC key to select the utility function number Fn007.
3. Press the ENTER key to display the DSP software version (the highest bit displays d or E or F or 0).
4.Press the MODE key to display the FGPA/CPLD software version (the highest bit displays P).
4. Press the MODE key to rotate the servomotor, and the servomotor dynamic speed will be displayed.
5. The unit of the servomotor and load total inertia displayed when servomotor stops is kg.cm²
- 100 -
ETS Series AC Servo User's Manual
Note:Make sure that the servomotor completes at least 6 full revolutions in the CCW direction before detection.
- 101 -
ETS Series AC Servo User's Manual
Chapter 6
MODBUS Communication
ETS series servo drives provide the MODBUS communication function with RS-485 interface,
which can be used to easily set parameters or to perform monitoring operations and so on.
The definitions of the servo drive communication connector terminals(CN3、CN4) are as follows.
Note:
1. The length of the cable should be less than 100 meters and in a environment with minimal electrical
disturbance/interference. However, if the transmission speed is above 9600bps, please use the communication cable
within 15 meters to ensure transmission accuracy..
2. A maximum of 31 servo drives can be connected when RS485 is used. Terminating resistances are used at both ends
of the 485 network. If more devices are wanted to connect, use the repeaters to expand.
3. CN3 of servo drive is always used as communication cable input terminal,and CN4 is always used as communication
cable output terminal(If still need to connect slave stations,the communication cable is connected from CN4 terminal to
the next slave station; if need not, add balance resistor in CN4 terminal.).It is prohibited to connect CN3 of any two servo
drives directly when multiple ETS series servo drives are connected.
Example:
When a RS-485 network is composed of a PLC and three servo drives (A, B, and C), the cable wiring is shown as follows:
PLC→CN3 of A, CN4 of A→CN3 of B, CN4 of B→CN3 of C, CN4 of C→120Ω terminating resistance.
- 102 -
ETS Series AC Servo User's Manual
Setting
Parameter No. Description Control Mode Meaning
Validation
Pn700.0 MODBUS baud rate
[0] 4800bps
[1] 9600bps
[2] 19200bps
[3] 38400bps
[4] 57600bps
[5] 115200bps
Pn700.1 Communication protocol
selection
[0] 7,N,2(MODBUS,ASCII)
[1] 7,E,1(MODBUS,ASCII)
[2] 7,O,1(MODBUS,ASCII)
Pn700 Hex After restart ALL
[3] 8,N,2(MODBUS,ASCII)
[4] 8,E,1(MODBUS,ASCII)
[5] 8,O,1(MODBUS,ASCII)
[6] 8,N,2(MODBUS,RTU)
[7] 8,E,1(MODBUS,RTU)
[8] 8,O,1(MODBUS,RTU)
Pn700.2 Communication protocol
selection
[0] SCI communication with no
protocol
[1] MODBUS SCI communication
Pn700.3 Reserved
Axis address of MODBUS protocol
Pn701 Axis address After restart ALL
communication
- 103 -
ETS Series AC Servo User's Manual
There are two modes for MODBUS communication: ASCII (American Standard Code for information interchange) mode
and RTU (Remote Terminal Unit) mode.
The next section describes the two communication modes.
ASCII Mode:
Every 8-bit data is consisted by two ASCII characters. For example: One 1-byte data 64 H(Hexadecimal expression)is
expressed as ASCII code ‘64’, which contains ‘6’ as ASCII code 36H and ‘4’as ASCII code 34H.
RTU Mode:
Every 8-bit data is consisted by two 4-bit hexadecimal data, that is to say, a normal hexadecimal data. For example:
decimal data 100 can be expressed as 64H by 1-byte RTU data.
Data Structure:
10-bit character form(7-bit data)
Pn700.1=0:7,N,2(Modbus,ASCII)
7-data bits
10- bits character frame
Pn700.1=1:7,E,1(Modbus,ASCII)
7-data bits
10- bits character frame
Pn700.1=2:7,O,1(Modbus,ASCII)
7-data bits
10- bits character frame
- 104 -
ETS Series AC Servo User's Manual
8,N,2(Modbus,ASCII / RTU)
8-data bits
11- bits character frame
8,E,1(Modbus,ASCII / RTU)
8-data bits
11- bits character frame
8,O,1(Modbus,ASCII / RTU)
8-data bits
11- bits character frame
RTU Mode:
STX Sleep interval of at least 4 bytes transmission time.
ADR Communication address=>1-byte
CMD Reference code=>1-byte
DATA(n-1) Data content=>n-word=2n-byte,n≦12
……
DATA(0)
CRC CRC checking code=>1-byte
End 1 Sleep interval of at least 4 bytes transmission time.
- 105 -
ETS Series AC Servo User's Manual
communication speed).
ADR(communication address)
Valid communication address:1 to 254
For example: communicate with the servo drive which address is 32(20 in hex):
ASCII mode:ADR=‘2’,‘0’=>‘2’=32H,‘0’=30H
RTU mode:ADR=20H
CMD(command reference)and DATA(data)
Data structure is determined by command code. Regular command code is shown as follows:
Command code: 03H,read N words(word),N ≦ 20.
For example: read 2 words starting from 0070 H from the servo drive which address is 01 H.
ASCII mode:
Reference information: Response information:
STX “:” STX “:”
‘0’ ‘0’
ADR ADR
‘1’ ‘1’
‘0’ ‘0’
CMD CMD
‘3’ ‘3’
‘0’ Data number ‘0’
‘0’ (count as byte) ‘4’
Data start address
‘7’ ‘0’
‘0’ Content of data start ‘0’
‘0’ address 0200H ‘0’
Data number ‘0’ ‘0’
(count as word) ‘0’ ‘0’
‘2’ Content of second data ‘0’
‘8’ address 0201 H ‘0’
LRC checking
‘A’ ‘0’
End 1 (0D H)(CR) ‘F’
LRC checking
End 0 (0A H)(LF) ‘8’
End 1 (0D H )(CR)
End 0 (0A H )(LF)
RTU mode:
Reference information: Response information:
ADR 01 H ADR 01 H
CMD 03 H CMD 03 H
00 H (high-bit) Data number
Data start address 04 H
70 H (low-bit) (count as byte)
Data number 00 H Content of data start 00 H (high-bit)
(count as word) 02 H address 0200H 00 H (low-bit)
CRC checking C5 H (low-bit) Content of second data 00 H (high-bit)
CRC checking D0 H (high-bit) address 0201 H 00 H (low-bit)
CRC checking FA H (low-bit)
CRC checking 33 H (high-bit)
- 106 -
ETS Series AC Servo User's Manual
ASCII mode:
Reference information: Response information:
STX “:”
STX “:”
‘0’
ADR ‘0’
‘1’ ADR
‘1’
‘0’
CMD ‘0’
‘6’ CMD
‘6’
‘0’
‘0’
‘0’
Data start address ‘0’
‘7’ Data start address
‘7’
‘0’
‘0’
‘0’
‘0’
‘0’
Data content Content of data start ‘0’
‘0’
address 0200H ‘0’
‘1’
‘1’
‘8’
LRC checking ‘8’
‘8’ LRC checking
‘8’
End 1 (0D H)(CR)
End 1 (0D H )(CR)
End 0 (0A H)(LF)
End 0 (0A H )(LF)
RTU mode:
Reference information: Response information:
ADR 01 H
CMD 06 H ADR 01 H
00 H (high-bit) CMD 06 H
Data start address 00 H (high-bit)
70 H (low-bit) Data start address
00 H (high-bit) 70 H (low-bit)
Data content 00 H (high-bit)
01 H (low-bit) Data content
CRC checking 49 H (low-bit) 01 H (low-bit)
- 107 -
ETS Series AC Servo User's Manual
- 108 -
ETS Series AC Servo User's Manual
ASCII mode:
Communication is ended with (0DH) - [carriage return] and (0AH) - [new line].
RTU mode:
When the time exceeds the sleep interval by at least 4 bytes transmission time while in the current communication speed,
it means the communication is finished.
Example:
The following example uses C language to generate CRC value. The function needs two parameters.
unsigned char * data;
unsigned char length;
The function will return unsigned integer type CRC value.
- 109 -
ETS Series AC Servo User's Manual
When the first and second communication faults occur, the servo drive is running normally, and will feed back an error
frame.
When the third communication fault occurs, transmission data will be recognized as invalid to give up, and no error frame
is returned.
For example: Servo drive axis number is 03H,write data 06Hinto parameter Pn100 is not allowed , because the range of
parameter Pn100is0~6. The servo drive will feedback an error frame, the error code is 03H (Beyond the parameter’s
maximum value or minimum value).
Host controller data frame:
start Slave station address Command Data address,content Checking
03H 06H 0002H 0006H
Besides, if the data frame sent from host controller slave station address is 00H, it determines the data to be broadcast
data. The servo drives will not feed back any frames.
- 110 -
ETS Series AC Servo User's Manual
- 111 -
ETS Series AC Servo User's Manual
01:Enable
1023 3023 5023 JOG servo enabled Write only
00:Disable
01:Forward rotation
1024 3024 5024 JOG forward rotation Write only
00:Stop
01:Reverse rotation
1025 3025 5025 JOG reverse rotation Write only
00:Stop
Note:
1. Parameter area(axis A 0000~0348H、axis B 2000~2348H 、axis C 4000~4348H)
Parameter address is relevant to the parameters in the parameter list.
For example, axis A parameter Pn000 is relevant to communication address 0000H; parameter Pn102 is relevant to
communication address 0066H.
2. Alarm information storage area(axis A 07F1~07FAH、axis B 27F1~27FAH、axis C 47F1~47FAH)
Historical alarm number Description Communication address
Historical alarm 1 07F1H、27F1H、47F1H
0
(the latest alarm)
07F2H ~ 07F9H 、 27F2H ~
1~8 Historical alarm 1 ~ 9
27F9H、47F2H ~ 47F9H
9 Historical alarm 10(the furthest alarm) 07FAH、27FAH、47FAH
5. Software version(090FH)
Use digit to represent servo drive software version. For example, if the read out data is 0100H,it means the software
version is t-1.00.
- 112 -
ETS Series AC Servo User's Manual
Chapter 7
ETS-1010APC-CAN/ETS-101010APC-CAN
Servo Drive Model
ETS-1010APG-CAN/ETS-101010APG-CAN
EMJ-A5A EMJ-01A EMJ-02A EMG-10A
Applicable Servomotor Model
EMJ-04A EMJ-08A EMJ-10A EML-10A
Input Main Circuit Three-phase 200~230VAC +10% -15% (50/60Hz)
Power
Control Circuit Single-phase 200~230VAC +10%~-15% (50/60Hz)
Supply
Control Method SVPWM
Incremental Wire-saving type:2500 P/R
Feedback
Serial Encoder 131072P/R/1048576P/R
Ambient/Storage
0~55℃/-20~85℃
Temperature
Ambient/Storage
Operating Conditions 90% RH (with no condensation)
Humidity
Vibration/Shock
Vibration Resistance:4.9m/s2,Impact Resistance:19.6m/s2
Resistance
Configuration Base-mounted
Rotation
Speed Direction With /P-CON signal
Selection Selection
Speed
Speed Speed 1 to 7
Control
Soft
Function Start 0~10s(Can be set individually for acceleration and deceleration.)
Setting
Sign + pulse train; CCW + CW pulse train;
Type
90°phase difference 2-phase (phase A + phase B)
Form Non-insulated linde driver (about + 5V), open collector
Pulse ×1 multiplier:4Mpps
Reference ×2 multiplier:2Mpps
Position
Control Frequency ×4 multiplier:1Mpps
Open collector:200Kpps
Frequency will begin to decline when the duty ratio error occurs..
Position
Reference Position Setting 16 position nodes can be set.
Setting
Encoder Dividing Pulses Phase-A, phase-B, phase-C, line driver output
I/O Output Number of dividing pulses:(1~16384)/16384
Signals Sequence Number of
3×8channels
Input channels
- 113 -
ETS Series AC Servo User's Manual
- 114 -
ETS Series AC Servo User's Manual
- 115 -
ETS Series AC Servo User's Manual
Appendix A
Parameter
- 116 -
ETS Series AC Servo User's Manual
- 117 -
ETS Series AC Servo User's Manual
- 118 -
ETS Series AC Servo User's Manual
- 119 -
ETS Series AC Servo User's Manual
- 120 -
ETS Series AC Servo User's Manual
- 121 -
ETS Series AC Servo User's Manual
capacity.
Funtion selection switches Pn000~Pn009 Control mode, stop mode, and some functions selection
Parameters of servo gain Pn102~Pn134 Position gain, speed gain,rigidity,etc.
Position control related parameters Pn200~Pn206 PG divided ratio, electronic gear, etc.
Speed control related parameters Pn304~Pn322 Speed reference input, soft start, etc.
Torque control related parameters Pn401~Pn410 Torque limit, etc.
Parameters to control I/O port Pn500~Pn528 Allocation of I/O port function
Point-to-point control and homing control Pn600~Pn688 Internal point-to-point control and homing control related
related parameters parameters
Communication parameters Pn700~Pn704 Setting of communication parameters
- 122 -
ETS Series AC Servo User's Manual
t1,t2>1ms
- 123 -
ETS Series AC Servo User's Manual
Reference pulse
t1 t2
t1,t2>1ms
Reference pulse
t1 t2 t3 t4
t1,t2,t3,t4>1ms
Pn203
Pn201 Electronic gear numerator 2 Pn201
Electronic gear numerator 1 PCON enabled Electronic gear numerator 1
PCON disabled PCON disabled
Reference pulse
t1 t2
t1,t2>1ms
Pn002.1Reserved
Pn002.2 Reserved
Pn002.3 Reserved
Pn003.0 Reserved
Pn003.1Reserved
Pn003.2 Low speed compensation
[0] Without low speed correction
[1]With low speed correction to avoid servomotor
creeping, but the degree of correction is
Pn003 Binary After restart ALL determined by the setting in Pn219.
Pn003.3 Overload enhancement
[0] Without overload enhancement function
[1]With overload enhancement function, which can
enhance the overload capacity when servomotor
exceeds the 2 times rated overload. It is used in
frequent power ON/OFF occasions.
Pn004.0 Stop Mode
Pn004.0
[0]Stops the servomotor by applying DB and then
ALL
releases DB.
Pn004.1
[1]Coast to a stop.
P
Pn004 Hex After restart [2]Stops the servomotor by DB when servo OFF,
Pn004.2
stops the servomotor by plug braking when overtravel,
P
then places it into coast (power OFF) mode.
Pn004.3
[3]Makes the servomotor coast to a stop state when
P
servo OFF, stops the servomotor by plug braking
- 124 -
ETS Series AC Servo User's Manual
- 125 -
ETS Series AC Servo User's Manual
- 126 -
ETS Series AC Servo User's Manual
- 127 -
ETS Series AC Servo User's Manual
Speed reference
Error counter
Pn111
Pn500
- 128 -
ETS Series AC Servo User's Manual
- 129 -
ETS Series AC Servo User's Manual
- 130 -
ETS Series AC Servo User's Manual
- 131 -
ETS Series AC Servo User's Manual
- 132 -
ETS Series AC Servo User's Manual
- 133 -
ETS Series AC Servo User's Manual
- 134 -
ETS Series AC Servo User's Manual
Pn526 Reserved — — —
Pn527 Reserved — — —
- 135 -
ETS Series AC Servo User's Manual
- 136 -
ETS Series AC Servo User's Manual
- 137 -
ETS Series AC Servo User's Manual
- 138 -
ETS Series AC Servo User's Manual
- 139 -
ETS Series AC Servo User's Manual
Appendix B
Alarm Display
Alarm Alarm
Alarm Name Meaning
Display Output
A.06 ╳ Position error pulse overflow Position error pulse exceededparameter (Pn504)
A.20 ╳ Power line phase shortage One phase does not bring into main circuit power supply.
- 140 -
ETS Series AC Servo User's Manual
Alarm Alarm
Alarm Name Meaning
Display Output
The parameter setting of servo drive does not match the
A.43 ╳ Servo drive type error
servomotor.
Absolute encoder multiturn
A.45 ╳ Absolute encoder multiturn information is faulty.
information error
Absolute encoder multiturn
A.46 ╳ Absolute encoder multiturn information overflow.
information overflow
A.47 ╳ Battery voltage below 2.5V Absolute encoder multiturn information is lost.
A.53 ╳ Serial encoder calcaution error Encoder or the encoder decoding circuit is faulty.
Parity bit or end bit in serial encoder Encoder signal is disturbed or the encoder decoding circuit
A.54 ╳
control domain error is faulty.
Serial encoder communication data Encoder signal is disturbed or the encoder decoding circuit
A.55 ╳
checking error is faulty.
End bit in serial encoder control Encoder signal is disturbed or the encoder decoding circuit
A.56 ╳
domain error is faulty.
A.58 ╳ Serial encoder data empty The EEPROM data of serial encoder is empty.
A.59 ╳ Serial encoder data format error The EEPROM data format of serial encoder is incorrect.
A.67 ╳ Receiving heartbeat timeout The master station sends heartbeat time timeout.
CAN Synchronization frame interval The filling time and the cycle of the synchronous frame
A.68 ╳
is too short does not matchor communication is faulty.
CAN Synchronization frame interval The filling time and the cycle of the synchronous frame
A.69 ╳
is too long does not match or communication is faulty.
- 141 -