Professional Documents
Culture Documents
Service Manual Ecmo Livanova s5 Cp5
Service Manual Ecmo Livanova s5 Cp5
This document is property of SORIN GROUP. No part of this document may be reproduced or transmitted in any form or by any means without the prior permission of SORIN GROUP.
Document title :
Unless explicitly stated on the copy itself, printed and/or electronic copy opened outside MasterControl system are uncontrolled documents.
Service Manual S5 System
Notes :
(1) Document approval: see approval on original on paper; approval on MC is only related to
document loading. (2) Valid approval date is stated on paper copy.
Change number :
Doc Type : (321-F) SEM - Servicing M Release date : 20 May 2014 3:50 PM
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
Signature Manifest
Document Number: CP_SEM_5811-0000 Revision: 000
Title: Service Manual S5 System
All dates and times are in Central European Time.
Quick Approval
Approve Now
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System
Service Instructions
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Service Instructions
All rights reserved, especially the right to reproduction and distribution as well as translation. No part
of this document may be reproduced – by photocopy, microfilm or any other process – nor may any
part of it be stored, edited, duplicated or distributed by electronic means without the written
permission of SORIN GROUP DEUTSCHLAND GMBH.
Service Instructions
Version 07/2013 - SM-5811-0000.04 ENG
SM-5811-0000.04 ENG
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Table of Contents
Table of Contents
1 Introduction
1.1 About the Service Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1
1.1.1 Symbols used in these Service Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1
1.1.2 Chapters in these Service Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2
2 Safety
2.1 Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1
3 System description
3.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1
SM-5811-0000.04 ENG 1
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Table of Contents
6 Replacing components
Instructions for technical safety inspection (TSI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1
2 SM-5811-0000.04 ENG
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Table of Contents
SM-5811-0000.04 ENG 3
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Table of Contents
7 Appendix
7.1 S5 system specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1
7.1.1 Dimensions, weights, operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1
Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1
Masts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2
Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3
System panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4
7.1.2 Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5
Electronics and power pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5
UPS and batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5
System panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6
Modules and sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.7
AC outlet strip with isolation transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.9
7.1.3 Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.10
4 SM-5811-0000.04 ENG
Source: MASTERCONTROL ** Document No., Status: CP_SEM_5811-0000 /000, RELEASE ** Printed by:
S5 System • Introduction
1 Introduction
1.1 About the Service Instructions
These Service Instructions (along with the training given by SORIN GROUP DEUTSCHLAND GMBH)
provide basic information on the maintenance and repair of your S5 System. This manual has been
designed solely for use by suitably qualified service technicians. In the interest of the safety of
patients and all users:
!
Only service technicians who have been trained and duly authorised by
SORIN GROUP DEUTSCHLAND GMBH may perform service on the S5 System.
All information on the operation of the S5 System can be found in the Operating Instructions. These
Service Instructions will refer to the appropriate chapter of the Operating Instructions as required.
The symbols are intended to help the user find particular text passages. The meaning of the symbols is
as follows:
! Danger! Failure to pay attention may put the health and safety of the patient
and/or the operator at risk.
! Warning! Failure to pay attention may cause damage to the machine or other
equipment.
✓ A check list for a quick and safe follow-up on whether operational steps have
been carried out completely.
4 Brief overview system panel – Brief overview of all key icons and displays
5 Fault messages and troubleshooting – List of all fault messages and fault isolation tips
◗ S5 mast retaining flange, left Side components for supporting the sliding T-bar handles
◗ S5 mast retaining flange, right and telescopic masts
◗ S5 mast system (complete) Comprises:
– Two vertical telescope masts
– One movable telescope mast
– Push bars (left and right)
– Horizontal mast
– Crossbar for movable mast
◗ S5 telescope mast with infusion rack Fixed telescope mast
(abbreviation: telescope mast) with 4-arm bottle holder
◗ S5 telescope mast, movable with Movable telescope mast with 4-arm bottle holder
infusion rack
(abbreviation: movable mast)
◗ S5 crossbar for movable mast 4 position Permanently mounted on the back of the console for
(abbreviation: crossbar for movable supporting the movable telescope mast
mast)
◗ S5 horizontal mast 4 position With 2 mast retainers (left and right) for attachment to the
(abbreviation: horizontal mast) vertical masts
◗ S5 system panel 4 position The modular control unit mounted on the mast comprises
(abbreviation: system panel) 4 module slots to take a maximum of 4 display and control
modules with touch screens.
Blank modules are plugged into slots which are not being
used.
◗ S5 display and control module Central interface between the user and the S5 System
comprising:
– Touch screen
– Housing
◗ Start page After switching on, if the self-test has run without any
faults (the S5 System and the system panel), the start
page will appear on the system panel.
The Start page is dependent on the total configuration of
the system and the parameters last saved in the
– System menu
– UPS menu
– Menus for the control and monitoring functions
– Menus for the monitoring functions
– Display menu
– Equipment menu (optional)
◗ Main menu (Main page) Overall display of all menus during operation on the
system panel.
◗ System menu This is where:
– date and time are displayed
– alarms, warnings and error messages are displayed
– pending alarms are deleted, cleared and silenced
◗ Functional group The displet on the display and control module on the
system panel, the sensor module in the E/P pack and the
corresponding sensor (or sensors) represent a
“functional group” (e.g. “Temperature monitor” displet
and sensor module and the temperature probes).
Although all entry and display displets are combined on
the system panel, each functional group operates
independently.
◗ HLM Heart-Lung-Machine
◗ EMC ElectroMagnetic Compatibility
◗ UPS Uninterruptible Power Supply
◗ OT Operating Theatre
◗ DMS Data Management System
◗ CAN Controller Area Network (CAN bus)
◗ BPM (bpm) Pulse frequency per minute (beats per minute)
◗ RPM (rpm) Revolutions Per Minute
◗ LPM (l/min) Litres Per Minute
◗ LCD Liquid Crystal Display
◗ PMC (PM) Pulse Mode Control (Pulse Mode)
◗ ECG ElectroCardioGram
◗ BSA BSA display (Body Surface Area display):
Display for calculating the body surface area
(abbreviation: BSA display)
◗ ECC-Timer ECC (Extracorporeal circuit):
Facilitates an independent measuring of time during an
extracorporeal circuit (abbreviation: ECC-Timer).
◗ APC Air Purge Control :
An optional S5 System component that facilitates the
controlled removal of bubbles from bubble traps.
◗ B-Care5 Optional system component of the S5 System for
determining the oxygen saturation, haematocrit value
and blood temperature in the venous blood circuit. For
further information, please refer to the separate B-Care5
operating instructions.
◗ ESD Electro Static Discharge
2 Safety
2.1 Approvals
Like development and manufacturing, service must also be conducted in conformance with the
following standards and statutes:
– Declaration of Conformity
The S5 System is a medical device, class IIb (MDD 93/42/EEC). A Declaration of Conformity has been
issued for the S5 System.
!
◗ In accordance with the applicable regulations, the Stöckert S5 System is used to perform, control
and monitor extracorporeal circulation during an operation. Any use outside this specification is
not in accordance with the regulations and SORIN GROUP DEUTSCHLAND GMBH will not assume
any liability for damage in such a case. Use in accordance with regulations also includes
compliance with the operating instructions, as well as repair and maintenance according to the
maintenance instructions.
◗ Relevant accident prevention measures according to existing local regulations and employees’
health and safety regulations must be complied with. SORIN GROUP DEUTSCHLAND GMBH will not
accept any liability for damage due to non-compliance with these regulations.
◗ SORIN GROUP DEUTSCHLAND GMBH will not assume any liability for injuries and/or damage
caused by failure to observe the safety instructions or operating instructions or by the operator not
taking due care. This also applies if the operator’s duty to take due care has not been specifically
expressed to the user.
◗ The S5 System has been designed according to current state-of-the art technology and accepted
safety standards. However, danger may arise to the patient, the user or other equipment during
operation.
◗ The operating instructions must be available close to the S5 System at all times. Incomplete or
illegible operating instructions must be replaced immediately.
◗ According to the European Directive 93/42 EEC and the national standards based on this directive,
the S5 System must be subjected to a regular maintenance check by an authorised service
technician. The S5 System must be subjected to this maintenance check every 1000 operating
hours or at least every 12 months, whichever comes first.
◗ In addition to the operating instructions, the relevant legal, general and binding regulations
concerning the prevention of accidents must be followed.
◗ In order to take into account situations which are clinic-specific and outside of normal routines,
e. g. certain working procedures, the operating instructions must be supplemented with relevant
instructions (supervision and registration requirements, etc).
◗ Persons operating the S5 System must familiarise themselves thoroughly with the operating
instructions before working on the machine!
◗ The firmware installed in the device must correspond to the version numbers listed in the Firmware informa-
Operating Instructions. tion:See
Operating
Instructions
◗ Always switch off the S5 System using the main switch. Otherwise, the batteries may totally
discharge.
◗ If modifications affecting safety or performance are noticed when the S5 System is not in use, shut
down the machine immediately and have it checked by an authorised service technician.
◗ Do not execute any modifications or extensions to the machine unless they have been tested and
approved by SORIN GROUP DEUTSCHLAND GMBH, otherwise SORIN GROUP DEUTSCHLAND GMBH
cannot assume any liability or responsibility.
◗ Keep the S5 System clean! This will prevent incorrect contact and faults due to dirt etc. Routine Mainte-
nance: See
Operating
Instructions
◗ The S5 System must only be operated and maintained by trained and qualified personnel.
!
◗ When in operation, the S5 System must be monitored at all times. Non-compliance with this duty
may result in danger to the patient's health! The safety features of the S5 System (alarm signals
etc.) are intended to assist the user and do not free him from his responsibility to monitor the
equipment continuously and conscientiously.
!
◗ A cardiopulmonary bypass requires comprehensive monitoring of both the patient and the
perfusion status. For this reason, all relevant values which are not recorded directly on the
S5 System must be monitored externally.
!
◗ Medical conclusions must not be drawn from and interventions in the perfusion must not be carried
out on the basis of the displays which have been obtained from serial data.
◗ All values from the entire system which have been determined or displayed must be checked for
plausibility. Pay attention to the pump parameters which are being used and the material and
diameter of the tubing.
◗ Before operating the S5 System, the user must read the operating instructions thoroughly and
become familiar with the machine functions.
!
◗ Before using the machine, check all cables, tubes, connectors and other accessories to make sure
that they are connected correctly, are not leaking and are in perfect working order. Replace all
damaged components immediately.
◗ Ensure that the tubes are laid out as straight as possible and do not kink or twist the cables.
Kinked or twisted cables could pose a hazard to any persons present (causing them to stumble or
get caught up in them).
◗ Make sure that the air circulation at the ventilation openings is unimpeded. Insufficient ventilation
may cause overheating.
◗ Modifications or extensions to the machine or the use of spare parts which have not been tested
and approved by SORIN GROUP DEUTSCHLAND GMBH may have a detrimental effect on the safety
and operation of the machine. If this happens, SORIN GROUP DEUTSCHLAND GMBH cannot accept
any liability or responsibility.
!
◗ Do not use any more connectors or tubing than is necessary for operating the machine in
accordance with the regulations. Additional connectors etc. increase the risk of faults.
◗ Accessories and supplementary devices which have not been tested and approved by
SORIN GROUP DEUTSCHLAND GMBH must have evidence to show that their use does not represent
a safety hazard.
◗ Electrical installations must be in accordance with the national standards and regulations. Please
refer to the specifications.
◗ The S5 System complies with the requirements for Protection Class 1 (IEC 60601-1). It must be
connected to a properly fused and grounded AC power supply.
◗ For safety reasons, a potential equalisation cable must be connected to a point intended for such
purpose in the operating theatre (OT).
◗ Regularly check the operational safety of all electrical connections, cables and sockets. Safety checks: See
Operating
◗ For office equipment, the minimum distance of 1.50 m to the patient must be observed. Instructions
◗ Devices that are connected to the system connection panel or the side system slots must be
approved by the SORIN GROUP DEUTSCHLAND GMBH.
◗ Equipment connected to the AC outlet strip with isolation transformer must comply with the
relevant office equipment standard (IEC 60950-1) or IEC 60601-1 for medical equipment.
!
◗ Before carrying out maintenance and cleaning work on the machine, disconnect it completely from
the power supply. Make sure that the system is switched off (as the UPS permits operation even
without the mains power supply).
◗ Do not fail to follow the regulations concerning routine maintenance, as well as the prescribed
maintenance intervals stated in the operating instructions.
◗ Ensure that no liquids or cleaning agents enter the machine housing through the vents or other
openings.
◗ Repair work on the machine must only be carried out by authorised service technicians. To
guarantee safe and reliable operation of the machine, only genuine spare parts from
SORIN GROUP DEUTSCHLAND GMBH must be used.
◗ Please note that the S5 System features a UPS supplied by two batteries. When you are working
with the housing open or on the E/P pack itself, the danger of short circuits remains as long as the
batteries are connected and charged, even though the mains power cable may be disconnected.
◗ Always use suitable removal and insertion tools in order to avoid bending electrical contacts (e.g.
of connectors) or damaging plugs or socket housings.
◗ Please take care not to damage cables or their insulation on the sharp edges of panels and printed
circuit boards during assembly. Route the cables in a way that prevents them from being pinched
by fasteners or by the edges of panels.
◗ Observe the local (country-specific) configuration of the individual components of the mains power
supply and the associated connection procedures as specified in the wiring diagram in the
appendix.
◗ Please read the information on the correct handling of (heavy) objects in Chapter 6. Two people are
required to disassemble E/N pack due to its dead weight.
◗ Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components
susceptible to ESD, ensure that you use ESD mats, wrist straps, or similar.
!
2.3 Safety feature on the S5 System
◗ The S5 System contains an emergency power supply (Uninterruptible Power Supply or UPS) which Duration of UPS
guarantees uninterrupted operation in the event of a power failure or other disruption. operation:
See Operating
Instructions
◗ Both visual and acoustic alarms are triggered if there is a system fault when the machine is
switched on.
◗ If there is a system fault during operation, a fault message is output. Faults during oper-
ation in the OT:
◗ In the event of an emergency, the S5 System can be started via the UPS. See Operating
Instructions
◗ When switching on, all pumps and devices which are integrated in the S5 System carry out an
automatic self-test.
◗ Any faults which occur during operation are displayed on the system panel.
3 System description
3.1 General description
The Stöckert S5 System (abbreviation: S5 System) is a modular perfusion system which can be
assembled and configured for different applications at any time. The S5 System controls and monitors
extracorporeal blood circulation during a cardiopulmonary perfusion.
8 10
7
14
16
11
12
17
15
13
2
5
4
18
19
22
25 23
24
27
26
27
20
21
28
29
30
32
31
14
33
35
36 37
34
39
38
Because most of the components are identical in function and construction, the following overview
lists only the obvious differences.
41
42
44
40
43
43
45
59 46 58
47 48 49 50 51 52 60
61 62 63 64 65 66 67 68 69 57 56 55 53
54
64 Cardioplegia sensor module Connection for bubble sensor and pressure transducer for
cardioplegia control
65 Temperature sensor module Connecting the temperature probes to the temperature
monitor
66 Interface module Connecting for data transfer of external devices
(e.g. Data Management System, abbreviation: DMS)
67 APC sensor module (optional) Connects the bubble sensor of the Air Purge Control
68 B-Care5 sensor module Connection of the venous sensor for blood gas monitor
78
72 74
80
82
76
81
83
84
86
75 70 73 16
71
79
85
86
77
70 17
78
29 90
80
82
88
81
89
87 83
93 84
86
92
95 79
91
85
94
96
100 98 86
30
99
97
105
32
104
102
101
103
G S5 MRP 85/1 and ◗ Circuit board Motor power amplifier HME 0402
S5 MRP 85/2 ◗ Circuit board Motor controller HMR 0403
◗ (for more details see S5 DPR 85)
H S5 control panels for mast ◗ S5 control panel for mast roller pump 150/85 and S5 control panel
roller pumps for two mast roller pumps 85
◗ Circuit board Fan control HDM 0503
As you can see from the previous list of components, certain assemblies of the S5 System cannot be
repaired separately by a service technician on site. Therefore please take note of the following
conditions before you begin to perform service:
E/P pack
Due to its weight, removal of the E/P pack is best done by two persons. Also note that the S5 System
features a UPS supplied by two batteries. When you are working on the E/P pack, the danger of short
circuits remains as long as the batteries are connected and charged, even though the mains power
cable may be disconnected.
On-site repairs can be performed by replacement of circuit boards or individual assemblies (e.g. shaft
encoder, connecting cable). The circuit boards themselves should not be repaired on site.
Sensor modules
On-site repairs can be performed by replacement of circuit boards. The circuit boards themselves
should not be repaired on site.
A4
A 10
A9
A 14
A 13
A 15
A3
A8 A2
A7
A1
A6
A5 A 11
A 3 AC outlet connection
A 11 Carrying handle
A 13 Speaker
A 14 Bus bar
A 16
A 17
A 18
A 19
A 20
A 23
A 22
A 21
A 22 Switching power supply (for details see Page 3.22) HLM-NT-S5 96-403-551
A 23
A8
A7
A6
A 23 S5 System boards
A 24
S5/C5 A 29
S3
A 25
A 26
A 22 A 29
A 27
A 28
B 11 B4 B1 B1 B3
B6
B 12
B2
B9
B5
B8
B 14
B 13 B7 B 10
B 6 Speaker 97-103-669
C
C 11 C9 C 12
C1
C2
C3
C4
C 13
C 14
C 11
C6
C5
C 6 Speaker 97-103-669
D1
D1
D5
D4
D3
D7
D9
D 10
D6
D5
D 7 Speaker 97-103-669
D 11 D 12 D3
D8
D4
D7
D9
D 10
D6
D5
Note:
The S5 system panel (6 pos.) is made up of two S5 system panels (3 pos.). As the functions performed
by these S5 system panels are identical, we are using the S5 system panel (3 pos.) for the overview.
There are differences in the holder. For more information about this holder, refer to the section entitled
„Assembly System panel“ on page 7.33.
D7 Speaker 97-103-669
D 13
D 14
D8
D3
D4
D7
D9
D 10
D2
D6
D5
D7 Speaker 97-103-669
E1
E2
E3
E4
E5
E6
E7
E9
E8
F
F3
F2
F4
F5
F6
F1
F9
F8
F7
G G4 G2
G3
G5
G9
G6
G7
H H8
H9
H6
H 11 H 10
H4
H 12
H3
H5
H 13 H 14
H 15
H1
Fig. 22: Assembly overview Control panels for mast roller pumps
H 4 Computer board (for details see Page 3.42) HKR 0325 90-305-620
H 10 Line filter
H 11 Switch
H 12 Speaker 97-103-669
H 15 Fan
A 32
A 33
A 34
A 39
A 36
A 40
A 21
A 35
A 31
A 37 A 30
A 38
A 41
A 38 Connection system boards (HEK 0411 and HEX 0412) CON 19 96-215-252
A9
A 43
A 42
A 45
A 50 A 44
A 51
A 48 A 52
A 49 A 54
A 46 A 53
A 55
A 47
A 56
A 46 Fuse 20 A T F1 93-511-530
A 47 Fuse 20 A T F2 93-511-530
B 14
B 20 B 22
B 21
B 17
B 18
B 19
B 15
B 16
B 23
Fig. 25: Circuit board motor controller
B 21 DIP switch S1
B 13
B 24 B 27
B 26 B 25
B4
B 40 B 39
B 32 B 38
B 31
B 37
B 36
B 35
B 30
B 34
B 33
B 29 B 28
B 41
B 42
B 43
B 44
B 45
B 48
B 46 B 47
B 47
B 48
B 44 Circuit board keys and LEDs for RP 150 and MRP 85/1 HKD 0327 90-305-640
(for registration of the shaft encoder with cable har-
ness; not shown here)
B 46 Circuit board keys and LEDs for DRP 85 und MRP 85/2 HKD 0327 90-505-640
(for registration of the shaft encoder with cable har-
ness; not shown here)
B 47 LED light guide, 7-element (in this case for DRP 85)
D 18
D 17
D2
D 16
D 21
D 19
D 15
D 20
D 22
D 14
D 23
Fig. 30: Circuit board backplane system panel (4 pos. and 5 pos.)
D 12 D 18
D 16
D 15
D 19
D 17
D 20
D 24
D 10
D 25
D 28
D 26
D 27
D 29
D 31
D 30
H6 H 17
H 16
Circuit board mast roller pumps 85 (motor controller and motor power
amplifier)
G5
G 11
G 10
G 12
G 13
G 16
G 15
G 14
G6
G 18
G 20
G 19
G 17
Fig. 36: Circuit board motor power amplifier MRP85
I4
I3
I2
I5
I1
I6
J2
J1
J6
J5
J3
J4
Fig. 38: AC outlet strip with isolation transformer
J 2 Insulation 72-102-050
J 5 Transformer 96-403-070
!
All SCP Systems must only be connected to the S5 System by an appropriate (fixed) cable:
For information on service-relevant SCP System components, please refer to the separate SCP System
service manual.
For information on
◗ connecting to the S5 System and
◗ its operation
please refer to the separate operating instructions for the S5 System.
Further details concerning service component Part Numbers can be found in Chapter 7.6 „Service
component part numbers“ on page 7.26.
Detailed information on the operation of the S5 System can be found in the associated Operating
Instructions. For ease of navigation, the following pages give you a brief overview of the system menu:
Key icon Scroll (scroll text) Advances to the next text message in the system menu
Scroll
Key icon Space (Space key) Enters a space (e.g. when entering text)
Space
Key icon Cancel (abort) Closes the current window and returns to the previous
window without saving the data which has been entered
or changed
The key icons and displays listed above always have the same function and meaning. The following
sections explain the special, non-general key icons and displays of the individual menus.
Only those key icons which can be pressed in the menu shown are displayed (e.g. the key icon Scroll in
the System menu).
When a key icon is pressed, it briefly appears yellow. Activated functions are indicated by a vertical bar
in the key icon (on the left side).
To terminate the override, press the key icon Override again until it is displayed in yellow. When the
pressure is removed, the override function is deactivated.
a b
e f g
20.05.2009 14:15:01
d
100 %
Level c
Arterial Pump (1) stopped
Scroll
20.05.2009 1 a Icon System menu Display of the selected menu name, date and time.
Opens the menu entry displet for configuring the basic
settings for:
– Changing the language
– Selecting the pressure unit
– Changing the system direction of rotation
– Entering the default volume
– Entering the date and time
– Entering the menu name
– BSA settings
– Display of alarm and error messages
– clearing, overriding and muting triggered alarms
– monitor and control of the UPS functions
– current operating state of the UPS
– Displet of the interface module
– Displet of the menu for the SCP System
b Icon System
5.1 Faults
Note:
!
If no defect can be found, please forward a summary of investigation actions performed to the
Complaints Coordinator to determine if additional actions are required.
!
Note:
Even if
– all pumps are switched off,
– the system panel is switched off,
– the mains power cable is unplugged,
– and the E/P pack is switched on,
it is still possible that the batteries are totally discharged. In this case, take the appropriate steps
described in chapter 5.1.2.
System does not start Mains power cable missing – Connect/check mains power cable
with discharged or or defective
missing batteries Transformer/terminal block – Check wiring/terminal block
wired wrongly
Defective switch – Check/replace switch
Defective line filter – Check/replace line filter
Defective rectifier – Check/replace rectifier
System starts (can be Circuit breaker for system – Check / reset / replace safety cut-out
heard), but touch screen panel socket has triggered/
remains dark is defective
Comment:
Only Field Service technicians who have been trained and duly authorized by SORIN GROUP
DEUTSCHLAND GMBH may perform service on this level of investigation.
For persistent fault messages, please refer to the following section for information on further steps to
take:
Fault on pump
Turn-off path faulty A fault has been detected during the self-test.
Pump 1 The pump fails to switch itself off (e. g. ramp-up) (in this case:
pump 1).
➜ Cable break
➜ Fault in circuit board Computer board (HKR 0325)
◗ Replace cable
◗ Replace circuit board HKR 0325
◗ where necessary send pump to manufacturer for checking
Direction of rotation fault The pump ran in the wrong direction (without having been
Pump 1 instructed to do so).
◗ Send pump to manufacturer for checking.
Runaway fault The pump ran too fast (without being instructed to do so).
Pump 1
◗ Send pump to manufacturer for checking.
Runaway fault software
Pump 1
Shaft angle encoder fault The pump speed can no longer be adjusted correctly.
Pump 1
➜ Shaft encoder defective
Fault in motor controller ➜ Fault in circuit board Computer board (HKR 0325)
Pump 1
◗ Replace shaft encoder
◗ Replace circuit board HKR 0325
Motor controller failed The pump no longer allows the system to monitor it properly.
Pump 1
➜ Faulty electrical connection
Fault in motor controller ➜ Fault in circuit board Motor controller (HMS 0409)
Pump 1
◗ Check the connections between the circuit board
Motor controller (HMS 0409) and the circuit board
Computer board (HKR 0325) (i.e. check that all
connector pins are in place). If required, replace the
connectors/cables.
◗ Ensure that the connectors/cables are all firmly
connected.
◗ Replace circuit board HMS 0409.
Graphic display failure The display of current flow rate and the current pump speed
Pump 1 may be missing or incorrect.
➜ Touch screen defective
➜ Fault in circuit board Computer board (HKR 0325)
◗ Replace touch screen
◗ Replace circuit board HKR 0325
Internal temperature too high The temperature of the pump head rises above the specified
Pump 1 set temperature. The pump head might transmit heat to the
blood in the tubing.
➜ Fan defective
➜ Wrong switch setting for DIP switch Computer board
(HKR 0325)
➜ Fault in circuit board Computer board (HKR 0325)
➜ Fault in motor
◗ Check fan function (where necessary replace fan)
◗ Adjust DIP switch on the HKR 0325 to the correct
setting for fan control:
– if mast roller pumps are connected:
Switch setting ON for DIP switch 1
– if roller pumps are connected:
Switch setting OFF for DIP switch 1
◗ Replace circuit board HKR 0325
◗ Replace motor
Pump communication failed The displayed dose volume of the delivered cardioplegia
Pump 1 dose is incorrect.
➜ Hardware/software fault on pump or cardioplegia
sensor module
◗ Start at least two further administration processes.
◗ Replace cardioplegia sensor module
◗ Replace pump
◗ Replace touch screen of relevant pump
Speed knob LED failure LED display on pump control panel remains dark.
Pump 1
➜ Connections to circuit board keys and LEDs
(HKD 0327) interrupted
➜ Fault in circuit board HKD 0327
➜ (possible) fault in circuit board HKR 0325
◗ Check connections to HKD 0327
◗ Replace circuit board HKR 0327
◗ where necessary replace circuit board HKR 0325
Wrong pump head connected During maintenance work or when replacing the circuit board,
Pump 1 the DIP switch setting no longer accords with the pump
connections after pump assembly.
➜ The displet of the double roller pump is displayed on
the touch screen of the roller pump (or vice-versa).
➜ Fault in circuit board HMS 0409
◗ Adjust DIP switch on the HMS 0409 to the correct
setting:
Switch setting ON: if an RP 150 is connected
Switch setting OFF: if a DRP 85 is connected
◗ Replace circuit board HMS 0409
Battery fault
Other messages:
The charge process was interrupted:
The current offset = 23.5 A ➜ Current sensor of the battery switch board (HUS 0318)
is too large is defective
◗ Replace circuit board HUS 0318
➜ Current sensor of the HUS 0318 charger is defective
Current sensor deviation = 0.5 A!
◗ Replace current sensor
◗ Replace circuit board HUS 0318
Note:
!
When correcting a battery fault or replacing a battery, a battery test must be carried out before initial
operation of the system.
to the S5 System.
For information about the relevant alarm messages, see the S5 System operating instructions.
If an alarm is not cleared or other errors and faults are displayed, please refer to the separate
operating instructions or service manual for additional measures.
When the S5 System is used with a gas blender system, the following fault messages can also occur:
E11
RAM fault
➜ A RAM or RAM monitoring fault has occurred.
E12
EPROM CRC fault
➜ An EPROM or EPROM monitoring fault has occurred.
E14
EEPROM module: defective or not responding.
➜ An EEPROM or EEPROM monitoring fault has occurred.
E15
Fault in AD transformer
➜ An AD transformer fault has occurred.
E16
Processor fault
➜ A fault has occurred in the processor timer switch.
E17
Defective power supply
➜ A power supply fault has occurred.
E18
Fan fault
➜ A fan or fan monitoring fault has occurred.
E19
Calibration fault
➜ A fault has occurred in the actual value/actual value
comparison.
E-1
Regulator fault
➜ A fault has occurred in the set value/actual value
comparison.
E-2
Regulator fault
➜ The actual value of the voltage at a gas flow of 0 l/min
is > 50 mV.
Calibration fault
➜ A fault has occurred in the actual value /actual value
E-3 comparison:
– for the gas blender 2 l/min (25-28-69)
– for the gas blender 5 l/min (25-28-68)
!
Opening or disassembly of the individual gas blender systems on site is not permitted.
Gas blender systems must always be recalibrated after maintenance and repair.
Recalibration may only be carried out by the manufacturer using a gas test station.
Other displays
General messages are also output on the System panel as well as the specific messages for the
individual devices:
6 Replacing components
!
Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components susceptible to
ESD, ensure that you use ESD mats, wrist straps, or similar.
!
A technical safety inspection must be carried out each time a component is replaced.
Chapter 7.7 „Technical safety inspection (TSI)“ starting from page 7.44 contains the templates for the
TSI.
◗ Make sure that all E/P pack connectors (system connection panel and sensor modules in front and
the system slots beside) have been removed first.
◗ Loosen the two screws on the console.
◗ Pull the E/P pack out of the console far enough to allow you to straighten out the two handles on
the side of the pack.
◗ Now pull the E/P pack out of the console completely. Warning: Due to its weight, removal of the
E/P pack is best done by two persons.
Note:
Correct handling of objects (e.g. the E/N pack) reduces mechanical stress to the spinal column and
back muscles.
◗ Take a position as close as possible to the E/N pack and squat down.
◗ Clasp the E/N pack in both hands while keeping the back straight.
◗ Push up with the legs and lift the E/N pack without bending or twisting the spine.
◗ Carry the E/N pack as close to the body as possible.
◗ When setting down, revert to the squat position, making sure to keep the back straight.
!
Note that the S5 System features a UPS supplied by two batteries. When you are working on the E/P
pack, the danger of short circuits remains as long as the batteries are connected and charged, even
though the mains power cable may be disconnected.
◗ Loosen the six allen screws shown above (DIN 912 M4x8 / allen key size 3 mm).
◗ Remove the cover.
The rear panel of the E/P pack must also be removed in order to access other components easily:
◗ Loosen the six allen screws shown (DIN 912 M4x8 / allen key size 3 mm).
◗ Remove the rear panel.
The system boards (HEK 0411 and HEX 0412) can only be replaced as a complete unit.
Installation is carried out by reversing this sequence. Ensure the boards are not tilted.
A 57
A 51
A 54
A 29
A 58
A 59
!
◗ Loosen the allen fasteners (DIN 912 M4x10 / allen key size 4 mm) of the A 51 (red) and A 54 (black)
connections on the battery switch circuit board A 9.
Caution: Connectors are energized even when the system is switched off. Isolate loosened
connectors immediately (e.g. with shrinkdown plastic tubing or insulating tape).
◗ Loosen the connectors:
A 29 Jumper
!
Caution needs to be exercised when installing a new switching power supply: Ensure that the jumper
position A 29 is correct (pin allocation for S5/C5 System)!
A9 A 54 A 51
A 29
a S5/C5
S3
!
Tighten the allen fasteners a of the A 51 and A 54 connections to a maximum torque of 2.5 Nm per
fastener.
Otherwise, the circuit board Battery switch A 9 is damaged and proper functioning cannot be
guaranteed any longer!
The switching power supply (96-403-551) can be replaced only as a complete unit.
The installation and connection of the new switching power supply is carried out in the reverse order.
The S5 System has an integrated test routine for the batteries (see the Operating Instructions). When
the batteries no longer deliver the required power values or are defect, they must be replaced
immediately (in order to ensure that the UPS functions properly).
A 10
!
Note that the risk of short circuits remains as long as the batteries are connected and charged, even
though the mains power cable may be disconnected.
A 42
A 45
A 44
A9
A 43
In the interest of clarity, the cables have been omitted from the diagram. Always mark the plugs and
cables to avoid mistakes in subsequent assembly.
◗ Loosen the allen screws (DIN 912 M5x8 / allen key size 4 mm) of the cable connections (A 51 to A
56) including the spring washers from the circuit board A 9 (Battery switch circuit board).
When installing the circuit board, take care to avoid wedging it askew in its slot.
A9
A 50
A 48
A 49
A 46
A 47
!
Replace fuses only with fuses of the same type and specification! Otherwise the S5 System may be
damaged.
6.2 Pumps
As the pumps of the S5 System are of identical construction to some degree, we have illustrated the
following descriptions with only one figure in some cases. Unless otherwise specified, the procedure
for the installation of the pumps is identical. In the interest of clarity, cables and connectors have been
omitted in some of the figures. Always mark the plugs and cables to avoid mistakes in subsequent
assembly.
!
Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components susceptible to
ESD, ensure that you use ESD mats, wrist straps, or similar.
6.2.1 Opening the pump housing and removing the pump head
Steel retaining rings were built into the first roller pumps RP150 and RP85 delivered. The steel
retaining rings (10-86-42 maxi or mini) can be replaced with plastic retaining rings (75-521-851 or 75-
521-852 respectively).
B 52
B 51
B 50
B 54
B 53
B 49
B4
B 14
B 13
Fig. 55: Disconnecting the retaining ring (2) and dismantling the pump head
◗ Disconnect the connector B 49 and the following connectors from the circuit board B 13 (Motor
power amplifier circuit board):
B 13
B 14
◗ Pull the bracket with the two circuit boards B 13 and B 14 out of the pump housing.
B 13
B 22
B 14
◗ Disconnect the connector B 22 from the circuit board Motor power amplifier B 13.
◗ Loosen the four self-locking nuts a and carefully lift up the circuit board B 13.
◗ In order to separate the Motor controller B 14 circuit board from the retaining bracket, loosen the
four distance bolts b from the circuit board.
◗ Carefully lift up the circuit board B 14 from the retaining bracket.
No further dismantling of the double roller pump is planned. Each of the three units
– Motor controller circuit board,
– Motor power amplifier circuit board and
– Pump head (10-86-00)
is to be replaced as a complete unit.
!
When reassembling (in reverse order) thereafter take extreme care in positioning the individual
components. Screw the fasteners on the circuit boards in cross pattern and in several iterations in
order to ensure a level seat.
Take care to avoid bending the pins of the connectors.
Assembly material
a Self-locking nuts DIN 985 M3 (width across flats 5.5 mm; abbreviation: WAF)
d c
B 13
B 22
B 14
B 49
◗ Disconnect the connector B 22 from the circuit board Motor power amplifier B 13.
◗ Loosen the indicated screw (allen key size 2.5 mm) including the washer, in order to separate
the bracket with the cable B 49 from the circuit board.
◗ Loosen the indicated screws (allen key size 2.5 mm) including the spring washers and the
distance bolts.
◗ Carefully lift up the circuit board B 13.
◗ In order to separate the Motor controller B 14 circuit board from the pump head, loosen the four
distance bolts from the circuit board.
No further dismantling of the roller pump is planned. Each of the three units
– Motor controller circuit board,
– Motor power amplifier circuit board and
– Pump head (10-81-00)
is to be replaced as a complete unit.
!
When reassembling (in reverse order) thereafter be extremely careful in positioning the individual
components. Screw the fasteners on the circuit boards in cross pattern and in several iterations in
order to ensure a level seat.
Take care to avoid bending the pins of the connectors.
Assembly material
c Cable clip CC S 31
Fig. 59: Removing the pump control panel and touch screen (1)
Always mark the plugs and cables to avoid mistakes in subsequent assembly. If necessary, make a
note of the cable connection positions.
Fig. 60: Removing the pump control panel and touch screen (2)
◗ Loosen the six allen screws (DIN 912 M3x10 / allen key size 2.5 mm) including the washers (DIN
9021 3.2), spring washers (DIN 127 B3) and insulation sleeves.
◗ Pull the touch screen assembly out of the pump housing.
B 29
B4
B 44 B 38
B 37
B 34
◗ Carefully lay the touch screen down with the display surface facing downwards on a soft, flat work
surface. Take care not to scratch the screen.
B4
B 48
◗ Loosen the four distance bolts (internal/external thread M3 x 15) from the circuit board B 4.
◗ Take care to lift the circuit board straight upwards to avoid bending the contact pins B 48.
B 43
c a
B 40
Fig. 63: Removing the display and control module (3)
When reinserting the inverter make sure that the distance bolts a (96-530-016) including nylon
washers b (93-920-029) and c (93-920-026 under the circuit board Inverter) are installed.
B 43
B 44
To remove the display carrier and the Keys and LEDs B 44 circuit board:
◗ Loosen the PT screws (PT Z30x8 WN 5411 and allen screw DIN 912 M3x6) from the Display carrier.
◗ Carefully lift the Display carrier up. Take care to avoid damaging the cable of the LCD connection B
43 or pulling out the plug.
B 55
B 57
B 56
B 60
B 58
B 59
B 56
B 55
Fig. 65: Removal of the circuit board with the shaft encoder
◗ Always replace the shaft encoder assembly as a complete unit (with cable harness). Install the
shaft encoder in the reverse order.
When removing the line filter, the housing base plate must be removed first (see Page 6.13).
◗ Loosen the two nuts (DIN 934 M3 WAF 5.5 mm) on the line filter including the spring washers
(DIN 127, B 3).
◗ Pull the four connectors from the line filter.
F3
F4
F5
F 12
F 10
F 11
F9
◗ Disconnect the following connectors from the circuit boards F 5 (Circuit board Motor power
amplifier) and F 4 (Circuit board Motor controller):
a
b
F1
Assembly material
d Connector
◗ Rotate the holder a and housing b so you can loosen the indicated head socket screws through
opening c.
◗ Gradually loosen the four head socket screws (DIN 912 M4x8 / allen key size xx mm).
◗ Carefully remove the housing b.
For further disassembly of the MRP 150, proceed as described in section „Removal of roller pump 150“
on page 6.21.
!
When reassembling (in reverse order) thereafter be extremely careful in positioning the individual
components. Screw the fasteners on the circuit boards in cross pattern and in several iterations in
order to ensure a level seat.
Be careful not to bend the contacts of the plug connector.
G1
G5
G6
G 19
◗ Remove the three head socket screws shown above (DIN 912 M3x6 / allen key size 2.5 mm),
including washers (DIN 125 A 3.2).
Warning: The circuit board cannot be removed completely, because the connections between pump
head and circuit boards must be disconnected first!
◗ Disconnect the connector G 19 from the circuit board Motor power amplifier MRP85 G 6.
G 14
G 15
G 13
G 14
G5
G 12
G6
◗ Remove both cap nuts a (DIN 1587 M4) on heat sink b to replace the circuit board Motor power
amplifier MRP85 G 6.
G6
5
Warning: The circuit board cannot be removed completely, because the connections on the circuit
board must be disconnected first!
G6
5
G 20
G 18
G 17
◗ Lift up the circuit board motor power amplifier MRP85 G 6 circuit board.
◗ Disconnect the following connectors from the circuit board G 6:
Steel retaining rings were built into the first mast roller pumps MRP85 delivered. The steel retaining
rings (10-86-42) can be replaced with plastic retaining rings (75-521-852).
Fig. 77: Disconnecting the retaining ring (in this case: a steel retaining ring)
Fig. 78: Disconnecting the retaining ring (in this case: plastic retaining ring)
No further dismantling of the pump head RP85 is planned. The pump head (10-86-00)
is replaced as a complete unit.
!
When reassembling (in reverse order) thereafter be extremely careful in positioning the individual
components. Screw the fasteners on the circuit boards in cross pattern and in several iterations in
order to ensure a level seat.
Be careful not to bend the contacts of the plug connector.
As most of the S5 system panels are of identical construction, we have illustrated the following
descriptions with only one figure in some cases. Unless otherwise specified, the procedure for the
installation of the system panels is identical. In the interest of clarity, cables and connectors have
been omitted in some of the figures. Always mark the plugs and cables to avoid mistakes in
subsequent assembly.
!
Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components susceptible to
ESD, ensure that you use ESD mats, wrist straps, or similar.
◗ Pull the four display and control modules out vertically of the system panel housing.
◗ Loosen the eight allen screws (DIN 912 M3x10 / allen key size 2.5 mm) including the washers (DIN
125 A 3.2).
D 18 D 19
D 17 D 16
D 15
D2
◗ Loosen the eight allen screws (DIN 912 M3x6 / allen key size 2.5 mm).
◗ Remove the circuit board Backplane system panel D 2.
◗ Replace the circuit board.
◗ Install the new circuit board in the reverse order.
◗ Reconnect the connectors.
◗ Warning during assembly: Sharp edges of the housing can damage cables or their insulation.
Make sure that the cables are not being pinched.
◗ Loosen the four PT screws (KB 30x10 WN 1411) and carefully lift the rear of the housing up.
D 25
D 26
D 27
D 10
Abb. 88: Replacing the circuit board display and control module
◗ In order to separate the circuit board display and control module D 10 of the frame, loosen the four
allen screws (DIN 912 M3x6 / allen key size 2.5 mm).
◗ Carefully lift up the circuit board D 10.
D 31
D 29
D 31
◗ Note when assembling: It is essential that both seals a (72-102-018) for the LCD touchscreen are
refitted. Ensure that the ribbon cable is located in the depression in the seal.
As the control panels are of identical construction to some degree, we have illustrated the following
descriptions with only one figure in some cases. Unless otherwise specified, the procedure for the
installation of the control panels is identical. In the interest of clarity, cables and connectors have
been omitted in some of the figures. Always mark the plugs and cables to avoid mistakes in
subsequent assembly.
!
Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components susceptible to
ESD, ensure that you use ESD mats, wrist straps, or similar.
◗ Remove the six allen screws (DIN 912 M3x10 / allen key size 2.5 mm).
H8
H 18
H 19
H 12
H 20
◗ Disconnect the following connectors from the circuit board computer board H 4:
H 21
H 15
H 18
H6
◗ Disconnect the following connectors from the circuit board fan control H 6:
◗ Remove the two allen screws shown above (DIN 912 M3x6 / allen key size 2.5 mm), including
washers (DIN 125 A 3.2).
Removal of the circuit board computer board H 4 is necessary in the following cases:
– To replace this circuit board
– In order to gain access to the inverter H 7 circuit board and keys and LEDs H 5 located underneath it
– To access the inverter and the keys and LEDs circuit boards located underneath it
– To replace the shaft encoder H 13
H4
H 25
H 13
H 24
H5
H 23
H 22
◗ Disconnect the following connectors from the circuit board computer board H 4:
H4
◗ Remove the four distance bolts (internal/external thread M3x12 (AF 5.5 mm)
from the circuit board H 4.
◗ Take care to lift the circuit board straight upwards to avoid bending the contact pins a.
H7
H 24
H3
H5
To remove the display carrier and the keys and LEDs H 5 circuit board:
◗ Remove the PT screws (PT Z30x8 WN5411) and head socket screws (DIN 912 M3x6) from the display
carrier.
◗ Carefully lift off the display carrier.Take care to avoid damaging the cable of the LCD connection H 3
or pulling out the plug.
H 13
H 27
H 26
H 30
H 28
H 29
H 26
H 13
Fig. 98: Removing of the circuit board with the shaft encoder
◗ Replace the shaft encoder as a complete unit only (with cable harness). Fit the shaft encoder in the
reverse order.
◗ Note when assembling: Sharp edges on the housing can damage cables or their insulation. Take
care to ensure that cables are not pinched.
Ensure that you do not position the shaft encoder cable harness close to the fan!
As the exterior design of the sensor modules is virtually identical, we have only used one figure of the
interface module in following description. In the interest of clarity, cables and connectors have been
omitted. Always mark the plugs and cables to avoid mistakes in subsequent assembly.
!
Please note that it is essential that ESD protective safety measures are taken when working with
components susceptible to ESD. When removing or fitting circuit boards or components susceptible to
ESD, ensure that you use ESD mats, wrist straps, or similar.
b
c
a
d
For further information about assembly material and the part numbers of the relevant sensor modules,
refer to the section entitled „Assembly Sensor modules“ on page 7.35.
6.8.1 Console
!
Be extremely careful when reassembling. When installing the TSG console, the console plate and the
console must be decoupled. Ensure that 4 PA washers each were inserted under both plate connector
blocks. The plate connector blocks are screwed to the console by means of PT screws.
Check that the potential equalisation cables within the console are connected correctly.
Material
Note:
Do not try to force screws. Screws that are secured with Loctite must be carefully heated before you
start to loosen them. All screws must be secured with Loctite during assembly. Make absolutely sure
that no Loctite gets onto other components.
I4
I9
I 11
I8
I7
I 10
I 7 Spanner Ø 25 mm 48-30-70
I 8 Spanner Ø 33 mm 48-30-71
Reassembly is carried out in the reverse order. Make sure that the spanners I 7 and I 8 are not tilted.
I 13
I 14
I 12 I5
I5 Foot 48-30-54
I 12 Spanner Ø 25 mm 48-30-70
Reassembly is carried out in the reverse order. Make sure that the spanner I 12 is not tilted. Ensure that
the O ring I 14 is seated correctly.
I3
I 20 I 19
I 21
I 15
I 18
I 17 I 16
Fig. 103: Mast system accessories (3)
I 18 Spanner Ø 33 mm 48-30-71
When reassembling (in reverse order) thereafter take extreme care in positioning the wedge I 16.
Tighten the allen screw I 19 and I 20 and the hex nut I 17 carefully to ensure they are seated correctly.
I2
I 22
I 23
I 24
To replace:
Reassembly is carried out in the reverse order. Make sure that the clamp piece I 23 is not tilted.
Note:
Please note that the allen screw I 22 must be secured with Loctite 638 during assembly. Make
absolutely sure that no Loctite 638 gets onto other components.
In the interest of clarity, cables and plug connectors have been omitted in some of the illustrations.
Always mark the plugs and cables to avoid mistakes in subsequent assembly. If necessary, make a
note of the cable connection positions. In addition, observe the wiring diagram in the appendix.
◗ Hold the AC outlet strip with isolation transformer firmly before you start to loosen the cap nuts.
◗ Loosen the four cap nuts a shown above (DIN 1587 M4) including the respective washers.
◗ Place the AC outlet strip with isolation transformer facing downwards on a flat work surface.
◗ Loosen the nine allen screws shown above (DIN 912 M4x8 / allen key size 3 mm).
◗ Remove the cover.
Always mark the plugs and cables to avoid mistakes in subsequent assembly. If necessary, make a
note of the cable connection positions. In addition, observe the wiring diagram in the appendix.
The installation and connection of the new power socket is carried out in the reverse order. Check that
the cable connections and screws are all properly secured.
Fig. 111: Overview of cable connections (socket for mains power connection)
The installation and connection of the new socket is carried out in the reverse order. Check that the
cable connections and screws are all properly secured.
The installation and connection of the new circuit breaker is carried out in the reverse order. Check
that the cable connections are all properly secured.
When reassembling (in reverse order) thereafter be extremely careful in positioning the individual
components.
6.10 Connectors
When inserting the new cable ensure that the connections are correctly assigned. For overview the
most important connectors with pin assignment. Further information to the part numbers is provided
in the chapter 7.6 „Service component part numbers“ on page 7.28.
ODU plug
1
2 8
1 8
2
Fig. 115: ODU plug (e.g. connecting pumps and devices to system slots )
Amphenol plug
2
1
Fig. 116: Amphenol plug (connecting AC outlet connection to the E/P pack)
1 2 1 7
Fig. 117: Phoenix plug (e.g. connecting power supply of the pumps (internal))
1 2 3
B
A
Fig. 118: FCI plug (e.g. CAN (internal) or diverse pump connections (internal))
21 432 1
Fig. 119: Molex plug (e.g. connecting Hall sensors, fans etc.)
2
1
Fig. 120: AMP plug (e.g. connecting speaker system panel and pumps)
7 Appendix
7.1 S5 system specifications
Console
Operating conditions
Operating Temperature + 10 °C ... + 40 °C
Storage Temperature 0 °C ... + 40 °C
Relative Humidity (Operating and Storing) 30% ... 75%
Masts
Telescope masts
Height (from the floor)
in the lowest configuration 1230 mm min.
1840 mm max.
in the highest configuration 1520 mm min.
2120 mm max.
Diameter (fixed part) Ø 33 mm
Movable mast
Height (from the floor) 1520 mm min.
2120 mm max.
Diameter (fixed part) Ø 33 mm
Horizontal mast
Length
3 position 806 mm
4 position 896 mm
5 position 1081 mm
Diameter Ø 25 mm
Pumps
System panel
Drip-proof IPX1
Output voltage
Nominal voltage 24 V
Minimum voltage 19 V
Maximum voltage 32 V
Output power
Nominal output power 400 W
Capacity of new batteries 17 Ah
Fuse protection of batteries 40 A
Discharger
Input voltage 24 V DC
Current 8A
Fuse protection of the discharger 10 A slow (DIN 41662)
System panel
Level
Alarm limit (level sensor) for oxygenators/reservoirs made of Level display of the sensor holder ±10 mm
rigid polycarbonate, wall thickness at sensor position 3 mm
max.
Pressure
Measurement range -200 mm Hg to +800 mm Hg
Resolution 1 mm Hg
Cardioplegia
Pressure measurement range -200 mm Hg to +800 mm Hg
Resolution 1 mm Hg
Temperature monitor
Display range 0 °C to +50 °C
Timer
Counting range 0 - 999 min 59 sec
Timer (optional)
Counting range 0 - 10 h (up and down)
APC
Accuracy of volume measurement (air and blood are suctioned)
when delivering pure liquid ±10% min.
± 20 ml
Accuracy of time measurement ± 1s sec
Pressure monitor
See sensor module 2 channel pressure
monitor
Bubble detector
See alarm limit of the bubble sensor
Interface module
Serial interface
Baud rate (fixed) 9600
Word length (fixed) 7 bit
Parity (fixed) none
Stop bits (fixed) 1
Time grid (fixed) 10 seconds
(interval of the data sent by the S5 System)
7.1.3 Pumps
Concentricity
Pump raceway 0.03 mm 0.03 mm
Occlusion symmetry 0.03 mm 0.03 mm
Occlusion rollers 0.015 mm 0.015 mm
Displays
rpm display range 0 to 250 rpm 0 to 250 rpm
Resolution 1 rpm 1 rpm
l/min display range (flow)
1/8" 0 to 0.83 l/min 0 to 0.44 l/min
3/16" 0 to 1.79 l/min 0 to 0.93 l/min
1/4" 0 to 3.12 l/min 0 to 1.57 l/min
5/16" 0 to 4.70 l/min 0 to 2.33 l/min
3/8" 0 to 6.50 l/min o
1/2" 0 to 11.2 l/min o
Deviation between follower pump and max. 1 percentage point of the flow ratio setting
master pump
Power supply
Operating voltage 24 V DC 24 V DC
Power consumption 160 W 160 W
Power consumption for mast roller pump MRP 150: 160 W MRP 85: 80 W
Touch screen
Pixel Failure Class Conformity with Pixel Failure Class III
7.2 Labelling
Declaration of Conformity
Protection class I
SN Serial number
Date of manufacture
Manufacturer
V Voltage
V ~ (Alternating current)
V = (Direct current)
I Current
f Frequency
Additional icons:
When mounting devices and accessories, the maximum
kg permitted load on the infusion rack is 5 kg.
When mounting devices and accessories, the maximum
permitted load on the telescope mast is 20 kg.
When mounting devices and accessories, the maximum
permitted load on the overall system is 45 kg.
When mounting devices and accessories, the maximum
permitted load on the telescope mast of the extension
system is 40 kg.
When mounting devices and accessories, the maximum
permitted load on the vertical mast of the extension
system is 11.5 kg.
The maximum permitted load on the shelf is 8 kg.
Warning: Rotating parts! Risk of crushing!
Close cover before use
Icons on the console, pump housing, system panel and control panels:
– on the console: Switch S5 System on/off
– on the pump housing: Switch the pump on/off
– on the system-panel: Switch the system panel on/off
– on the control panels: Switching the control panels
and connected mast roller pumps on/off
– others: Switching the corresponding device or
accessory on/off
Additional designations and icons on the nameplates of the holders for the level sensor:
Quantity
100 (in this case: package contains 100 sensor holders)
Contents
Use by
Expiry date
Non steriIe
NON
STERILE
7.3.1 S5 System
E/P pack
consisting of:
Electronics and power pack including 28-98-00
S5 DC/DC module 28-98-20
S5 UPS module 28-98-80
S5 battery discharger 28-98-90
Mast systems
Telescope mast with infusion rack 48-30-50
Telescope mast, movable with infusion rack 48-30-51
S5 System components
S5 System panel 4 position for 4 display and control modules 28-95-00
S5 System panel 3 position for 3 display and control modules (optional) 28-95-03
S5 System panel 5 position for 5 display and control modules (optional) 28-95-01
S5 System panel 6 position for 6 display and control modules (optional) 28-95-04
Display and control module 28-95-10
Blank module 28-95-30
Pump accessories
Pump cover for roller pump RP 150 10-81-75
Pump cover for roller pump DRP 85 10-86-45
2 direction rotation arrows 76-012-001
Bubble sensor
1/4" (6.35 mm) 23-07-40
1/2" (12.7 mm) 23-07-45
3/8" (9.56 mm) 23-07-50
3/16" (4.76 mm) 23-07-55
Pump spacer
for console table 3 position 48-31-20
for console table 4 position 48-41-20
for console table 5 position 48-51-20
Tubing clamps
Electrical remote-controlled tubing clamp (for installation on mast) 60-05-00
consists of:
Tubing clamp
Swivel arm with fast clamp connector 500 mm
Cable for connection to the S5 System (including blocking ferrite) 45-12-00
Note:
To read out data via the blood gas analysers and patient monitors listed here, at least one
interface module must be connected in the E/P pack. Use the system menu to select and
assign the relevant devices. For more information, refer to the C5 System operating
instructions.
The connection of these devices depends on the current firmware release of the interface
module. The devices listed here are only examples.
The compatibility of disposables and accessories (as stated in the European Directive 93/42 EEC,
Appendix 9.1/Basic Requirements) with the S5 System must be verified and guaranteed by the
manufacturer concerned. All safety checks and operational checks must be carried out in accordance
with the operating instructions supplied with the equipment concerned.
The compatibility of disposables manufactured by the Sorin Group for extracorporeal circulation with
the S5 System is guaranteed.
7.5 Warranty
These part numbers concern assemblies and components that are intended solely for use by service
technicians. The position number references relate to the illustration of the components in Chapter 3.
USA 97-103-692
China 97-103-693
A 23 S5 System boards
Assembly RP 150
Housing-mounted components:
Assembly DRP 85
Housing-mounted components:
Connector 28-95-24
D3 Mast joint holder (complete for 3 pos., 4 pos. and 5 pos.) 55-90-56
Console accessories
Keys and LEDs circuit board (MRP 150 and MRP 85/1) HKD 0327 90-305-640
Keys and LEDs circuit board (MRP 85/2) HKD 0327 90-505-640
Motor power amplifier MRP 85/x (L-shaped circuit HME 0402 90-305-700
board)
Motor output stage (all except MRP 85/x) HMF 0408 90-305-760
Circuit board for fan control panel (complete) HDM 0503 90-105-850
Cap 10-88-71
RP 150 97-101-914
Cable set HKR 0325 <– –> Filter and
filter <– –> switch
MRP 150
Cable harness Panduit UL PLT. 7M 96-510-101
DRP 85 97-101-915
Cable set HKR 0325 <– –> Filter and
filter <– –> switch
Cable harness HUS 0318 <– –> circuit breaker for HBP 97-101-922
0321
Cable harness HUS 0321 <– –> line circuit breaker HK 97-101-926
Mast accessories
Spanner Ø 25 mm 48-30-70
Spanner Ø 33 mm 48-30-71
Spanner Ø 25 mm 48-30-70
Spanner Ø 33 mm 48-30-71
PT screws 71-119-828
Screw M4
Screw M4
Nut M4
J2 Insulation 72-102-050
Screw M4
Washer B4
A technical safety inspection must be carried out each time a component is replaced.
PERMISSIBLE DEVI-
TYPE OF CHECK ATION
RESULT
I. VISUAL INSPECTIONS
1) Safety-relevant label
2) Visible damage to supply line
3) Condition of safety-relevant mechanical parts
4) Contamination detrimental to safety
in accordance
(including mains
(including mains
PA
with UL 2601
IENC =
power cable)
power cable)
Threshold
Threshold
U.S.A.)
IESFC = PA
IBNC = PA
Rprotective earth [ȍ]
IENC [ȝA]
IESFC [ȝA] IBSCF = PA
IBNC [ȝA]
IBSFC [ȝA]
Risolation [Mȍ] Riso = M:
Shelf with Additional Power Socket / Additional Power Socket S5/C5 4X-XX-XX
Definition of outline: The outline numbering system of this document is identical to the outline system for the corre-
sponding TSC protocol STK-43-70-XX-00. Each outline item contained in STK-43-70-XX-00 is described in more detail
in the section with the corresponding number in this document.
Required testing equipment:
x Voltage tester
x Safety tester
IDENTIFICATION
x Enter serial number and date of manufacture (month/year) for the additional power socket
Enter the actual values determined during testing of the respective test specimen. If the expected values are
met, the release field should be clearly marked "ok".
I. VISUAL INSPECTIONS
DESCRIPTION EXPECTED RESULTS
1) Safety-relevant label
Check labeling for completeness. All name and information plates are present.
6)
Check proper voltage supply to each power socket using the Each power socket is supplied with proper
measuring device. voltage.