AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

Installation Manual

AREA54-1
16 Bit multiprocessor modular analogue Control Panel
Page 2 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

ELKRON S.p.A. reserves the right to make changes to this manual and to the product described without further notification.
ELKRON S.p.A. accepts no responsibility for the misuse of the product.

3 20-10-06 Revision table added; manufacter info changed; RS232 color added. N.M.

Rev. Date Description ID


Page 3 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

Table of Contents
1 Dimensions ....................................................................................................................................... 5

2 Internal module arrangement .......................................................................................................... 7

3 Optional modules placing................................................................................................................ 8

4 Jumper – Selection jumpers............................................................................................................ 9


4.1 Selection jumpers – Functions ....................................................................................................................9
4.2 Selection jumpers - Relays........................................................................................................................10
4.3 Selection jumpers - Lines ..........................................................................................................................10
5 CPU54-1 Card.................................................................................................................................. 11

6 ALIM54 Module ............................................................................................................................... 13

7 Detection line configuration .......................................................................................................... 14

8 Detection lines ................................................................................................................................ 15


8.1 Connection to loop line - class A ...............................................................................................................15
8.1.1 Loop connection operation - class A.....................................................................................................16
8.1.2 Loop line electrical characteristics ........................................................................................................16
8.2 Connection to open line - class B..............................................................................................................17
8.2.1 Open line connection operation – class B ............................................................................................18
8.2.2 Open line electrical characteristics .......................................................................................................18
8.3 Test procedure for the Detection Lines .....................................................................................................19
8.3.1 Measurement for loop line connections - class A .................................................................................19
8.3.2 Measurement for open line connections - class B ................................................................................19
9 Addressing ...................................................................................................................................... 20
Page 4 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

Symbol Legend

) Important information concerning the described function


HELP
Help
Sample configuration

Possibly hazardous condition for the user or possible damaging of the control panel

Warnings

Do not use the keyboard if it is visibly damaged.


Do not use drills or metal objects to press the keys.
Page 5 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

1 Dimensions

350.0mm 160.5mm
[13.78in] [6.32in]

450.0mm
[17.72in]

000132

Fig. 1 External dimensions


Page 6 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

Ø23.0mm
Ø17.0mm [Ø0.91in]
[Ø0.67in]

120.0mm 120.0mm
[4.72in] [4.72in]

300.0mm
[11.81in]

000133

Fig. 2 Holes for cables to pass through and drilling template for wall fixing.
Page 7 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

2 Internal module placement

Display 4x40

CPU54-1
A
CARTER

Piastra Led 000137


Led Board ALIM54

Fig. 3 Internal module placement

To access the battery compartment and the power supplier terminal boxes or to install
additional modules, proceed as described:
- switch off the control panel disconnecting main power and removing the electrical connection with
the batteries.
- disconnect the cables connected to the JP4 and M2 connectors located on the CPU54-1 board.
- remove the locking screws “A” and rotate the support carrying the CPU54-1 board.
To access the ALIM54 power supplier, remove the covering above (carter).
Page 8 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

3 Optional modules placing


The following optional modules can be mounted in AREA54-1:
• MCS54 (RS232 – Remote panel – Printer)
• MMS54 (Modem – Mimic Panel – Master & slave)

Place modules as show in figure below.


For further information see modules user’s manual.

MCS54 MMS54

000163

Fig. 4 Optional modules placement


Page 9 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

4 Jumper – Selection jumpers


Some jumpers located on the CPU54-1 allows the selection of particular functions and / or
detection lines and output relays controls.
Before changing any jumper setting make sure that power is turned off.

) Do not operate on jumpers not listed in the table here below.


JP22 JP21 JP4 M2
COM1 MODULE COM2 MODULE

JP7
2 3

2 3

JP7
JP23

JP24

JP8

JP8
JP5
1

1
2 3

2 3
JP23

JP24
1

1
LED MODULE

2 1
JP16

1 2 3
3

JP3

1 2 3
JP1 F1 JP26

JP26
1

JP17
2

1 2 3
1
JP16 3

JP1
JP17

1 2 3
JP3

1 2 3 1
JP2 1 2 3

JP2
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 20 2122 23 24

000136

Fig. 5 View of the selection jumpers

4.1 Selection jumpers – Functions

Jumper Position Description


JP7 Executed (*) The backlighting of the display is controlled automatically.
Not executed The backlighting of the display is always alight.
JP8 Executed (*) The shift to the programming phase is enabled.
Not executed The shift to the programming phase is disabled.

(*) Factory setting


Page 10 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

4.2 Selection jumpers - Relays

Jumper Position Description


JP24 1-2 The relay connected to the contacts 1 and 2 of the terminal block is
controlled by the Excluded signal.
2-3 (*) The relay connected to the contacts 1 and 2 of the terminal block is
controlled by the Fault signal.
JP1 1-2 The relay connected to the contacts 1 and 2 of the terminal block
has a NA contact.
2-3 (*) The relay connected to the contacts 1 and 2 of the terminal block
has a NC contact.
JP23 1-2 (*) The relay connected to the contacts 3 and 4 of the terminal block is
controlled by the Alarm 1 signal.
2-3 The relay connected to the contacts 3 and 4 of the terminal block is
controlled by the Alarm 3 signal
JP2 1-2 (*) The relay connected to the contacts 3 and 4 of the terminal block
has a NA contact.
2-3 The relay connected to the contacts 3 and 4 of the terminal block
has a NC contact.
JP3 1-2 The mains presence relay connected to the contacts 8 and 9 of the
terminal block has a NA contact.
2-3 (*) The mains presence relay connected to the contacts 8 and 9 of the
terminal block has a NC contact.

(*) Factory setting

4.3 Selection jumpers - Lines

Line configuration JP16 JP17


Jumper Jumper
4 open detection line with 4 short circuit isolators 1-2 (*) 2-3 (*)
1 loop line with 2 short circuit isolators 2-3 1-2
2 loop lines with 4 short circuit isolators 2-3 1-2

(*) Factory setting


Page 11 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

5 CPU54-1 Card
The CPU54-1 card is the acquisition unit, process and command of all the functions of
AREA54-1. In fact, on this card you can find both the electronic interfaces towards the field, complete
with short-circuit isolators, and the entire electronic equipment, as well as the microprocessors for
elaborating the various signals and activating the commands such as relays and signaling outputs. In
addition to the connection to the viewing LED module with display, the card can be easily connected
to optional communication modules allowing to enlarge the control panel configuration.

M4 M3
ALIM54 ALIM54
MODULI OPZIONALI - OPTIONAL MODULES

JP22 JP21 JP4 M2


COM1 MODULE COM2 MODULE

JP7

JP8

JP5
JP23

JP24

1 1
LED MODULE

JP3
MODULO LED
LED MODULE

F1 1
JP26
JP17
JP16

1 JP1
1

 JP3

1 JP2

1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17 18 19 20 2122 23 24

000134

Fig. 6 View of the CPU54-1 card


Page 12 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

Terminal Function Description Notes


1 Fault/Excluded relay, 5A 30Vdc potential NA/NC Contact JP1 and JP24 jumpers
2 free relay
3 Alarm 1/Alarm 3 relay, 1A 30Vdc potential NA/NC Contact JP2 and JP23 jumpers
4 free relay
5 C Contact
6 Alarm 2 Relay, 5A 30Vdc potential free NA Contact
7 relay NC Contact
8 Mains presence relay, 1A 30Vdc free NA/NC Contact Jumper JP3
9 contacts.
10 Siren output, 600mA 27Vdc Positive (+) Protected by fuse
11 Negative (-) F1
12 Self-powered siren output, 250mA 27Vdc Positive (+)
13 Negative (-)
14 Transmission Wire color: yellow
15 RS232 (*) Communication serial port Negative Wire color: brown
16 Reception Wire color: blue
17 A1 Detection line Positive (+) JP16 and JP17 jumpers
18 Negative (-)
19 A2 Detection line Positive (+) JP16 and JP17 jumpers
20 Negative (-)
21 B2 Detection line Positive (+) JP16 and JP17 jumpers
22 Negative (-)
23 B1 Detection line Positive (+) JP16 and JP17 jumpers
24 Negative (-)

) (*) If a personal computer is connected, the control panel may signal an earth-leakage fault. Use
this communication port only for the programming phase of the control panel, then remove the
connection. For continuous applications in combination with other software, use the appropriate
MCS54 optional module.

Reference Description
F1 1A Siren output fuse
M2 Power supply connector
M4 Power supply control connector
JP21 MMS54 connector
JP22 MCS54 connector
JP5 LED module connector
Page 13 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

6 ALIM54 Module
The ALIM54 module is the power supplier section of the AREA54-1 control panel. The
module supplies the internal boards, the battery charger section and also provide a 600 mA - 27 VDC
for field .

M2 JP4
CPU54-1 CPU54-1 nr.2 12V 7,5 Ah
nr.2 12V 15 Ah

M3 M4 JP2 M5
Batteria Batteria
- Battery Battery
-
+
F2 +
-
-
+
+ OUT: 27 VDC
600 mA nom
F1 NON RIMUOVERE
2° Trasformatore
2° Transformer
DO NOT REMOVE

1° Trasformatore
F3 1° Transformer
F
N 230 VAC 50 Hz

000135

Reference Description
F1 1A Fuse – Field output 27Vdc
F2 4A Fuse – Batteries
F3 2A Fuse – Mains power supply
M3 CPU54-1 connector
M4 Power supply control connector
M5 Not used.
JP2 Short-circuit to switch on the control panel without main voltage.
Page 14 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

7 Detection line configuration


AREA54-1 detection lines can be set in three different combination; each of them fully complies the
standards. Four short circuit isolator are integrated on the CPU54-1 board.
The three detection lines styles are described here below, and shown in Fig. 7-8-9:

• Four open lines (class B) with an isolator each; configuration allows to connect up to 32
devices. Further isolator are non required (Fig. 7)
• One loop line (class A) having an isolator on each circuit termination. Up to three field
isolator must be used depend by number of the connected device (Fig. 8)
• Two loop lines (class A) having an isolator on each circuit termination. This configuration
allows to connect up to 64 devices on each line. One field isolator must be used (on each
loop), depending on the number of the connected devices (Fig. 9)

Regardless of the line configuration, the addresses of the devices are unique and should not be
repeated. There is no relationship or binding between the device address and the line where it is
installed.

Fig. 7 Fig. 8 Fig. 9

ISO ISO ISO ISO ISO ISO ISO ISO ISO ISO ISO ISO
17 18 19 20 2122 23 24 17 18 19 20 2122 23 24 17 18 19 20 2122 23 24

LA1 LA2 LB2 LB1 000138 ISO ISO


ISO ISO
000155
LA LB 000156

ISO
Page 15 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

8 Detection lines
8.1 Class A circuit wiring

Schermo da collegare Alla Centrale


a terra lato Centrale To Control panel
Shield to be ground connected to
the Control Panel side

Linea 1A Linea 1B

P/410 ZB/200
ON
1 2 3 4 5 6 7 8 9 10

3
1 2 45

ZB/200
Section 1 Protected Area
Area Protetta Sezione 1

Section 3 Protected Area


Area Protetta Sezione 3
3
1 2 45
P/420
ON
1 2 3 4 5 6 7 8 9 10

MAS/2000 ON
1 2 3 4 5 6 7 8 9 10

3 3 ISOLATORE ESTERNO 2
1 2 45 1 2 45
EXT.ISOLATOR 2

ISOLATORE ESTERNO 1
EXT.ISOLATOR 1 000161
ZB/200 ZB/200

Area Protetta Sezione 2


Section 2 Protected Area

Fig. 10 Class A circuit wiring


Page 16 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

8.1.1 Loop connection operation - class A

The loop connection ensures the system integrity also against malfunctions due to the
opening or the short-circuit of the detection line.
In normal operation, the control panel dialogues with the detectors sending the code from
both sides of the loop; therefore, a line opening does not affect the communication: in such a case,
the control panel notifies the opening occurred, while the system continues functioning. In the event of
a line short-circuit, the intervention of the short-circuit isolators, systematically located on each
detector group, allows the isolation of the line section affected by the above short-circuit. In this case,
the control panel detects a fault condition due to the communication failure with the detectors
enclosed between the isolators isolating the short-circuit. As an example and with reference to Figure
9, should a short-circuit occur in the Section 2 Protected Area, the intervention of the external
isolators 1 and 2 allows the system to continue functioning; however, the control panel will notify the
communication failure with the devices in this area. Pursuant to the current regulations, the maximum
number of detectors allowed which can be connected between two short-circuit isolators is 32.
Branches and T-junctions are not allowed in the class A connection type.

8.1.2 Loop line electrical characteristics

• Cable to be used: 2 x 1.5 mm² shielded


• Total loop line maximum length: 800 m
• Cable total resistance: lower than 30 Ohm
Page 17 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

8.2 Class B circuit wiring

Alla Centrale Schermo da collegare


To Control panel a terra lato Centrale

Linea 1A Shield to be ground connected to


the Control Panel side

P/410 Linea 1B
ON
1 2 3 4 5 6 7 8 9 10

Area Protetta Sezione 2


Section 2 Protected Area
ZB/200 ZB/200

3 3
1 2 45 1 2 45
ZB/200
Section 1 Protected Area
Area Protetta Sezione 1

3 ISOLATORE ESTERNO 1
1 2 45
EXT.ISOLATOR 1

Area Protetta Sezione 3


Section 3 Protected Area
P/420
ON
1 2 3 4 5 6 7 8 9 10

ZB/200

MAS/2000 3
ON
1 2 45
1 2 3 4 5 6 7 8 9 10

ISOLATORE ESTERNO 2
EXT.ISOLATOR 2

000162

Fig. 11 Class B circuit wiring


Page 18 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

8.2.1 Open line connection operation – class B

The open line or class B connection ensures a superior installation versatility in comparison
with the loop line; however, the system is always able to signal any malfunctions due to the opening
or the short-circuit of the detection line. As for the loop line, the opening of a stub involves the failure
of communication with the device; the control panel will therefore notify such anomaly as a field fault.
In the event of a short-circuit, the isolator isolates the involved stub; the control panel will notify the
communication failure with the isolated devices. Please note that up to 32 devices must be installed
on each stub.

8.2.2 Open line electrical characteristics

- Cable to be used: 2 x 1.5 mm² shielded.


- Total open line maximum length: 1000 m.
- Cable total resistance: lower than 30 Ohm

Note: the total maximum length of the open line is the sum of the lengths of all the branches.
Page 19 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

8.3 Test procedure for the Detection Lines

Before connecting the conductors and the shield of the line cable to the line terminals of the
control panel, check the following list:
• Verify the electric resistance of the detection cable which should be less than 30 Ohm.
• Verify the electric isolation between the detection line conductors by checking using an ohm meter
that there is a resistance higher than 0,7M Ohm between the positive and the negative.
• Verify the electric isolation between the conductors and the line cable shield, by checking using an
ohm meter that there is a resistance higher than 15M Ohm between each single conductor and the
shield.
• Verify the electrical isolation between the line cable shield and the earth conductor by checking
that there is a resistance higher than 15M Ohm between these.
• Proceed to the connection of the conductors and the line cable shield to the terminals of the control
panel and to the earth connection.

8.3.1 Measurement for loop line connections - class A

If you want to determine the resistance of the line cable, short the two conductors at one end
and then measure using an ohm meter at the opposite end.

Note: you should remove any short-circuit isolators on the detection line, before measuring.

8.3.2 Measurement for open line connections - class B

If you want to determine the resistance of the line cable, short the two conductors at the end
of every single branch, then measure using an ohm meter between the conductors to be connected to
the control panel terminals.

Note: you should remove any short-circuit isolators on the detection line, before measuring.
Page 20 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

9 Addressing
AREA54-1 is able to manage up to 128 devices located on the detection lines. If you want to
assign an address, you should meet the following conditions:

• it is a unique address: no duplicates are permitted even on a different stub;


• the address is within the range 1-128, the micro-switch configuration should be respected;
• the address should be set before powering the device;
• there is no correlation between device type and address;
• a progressive addressing is not binding, the address can be random.

ON ON ON
1 2 3 4 5 6 7 8 910
001 1 2 3 4 5 6 7 8 910
012 1 2 3 4 5 6 7 8 910
023
ON ON ON
1 2 3 4 5 6 7 8 910
002 1 2 3 4 5 6 7 8 910
013 1 2 3 4 5 6 7 8 910
024
ON ON ON
1 2 3 4 5 6 7 8 910
003 1 2 3 4 5 6 7 8 910
014 1 2 3 4 5 6 7 8 910
025
ON ON ON
1 2 3 4 5 6 7 8 910
004 1 2 3 4 5 6 7 8 910
015 1 2 3 4 5 6 7 8 910
026
ON ON ON
1 2 3 4 5 6 7 8 910
005 1 2 3 4 5 6 7 8 910
016 1 2 3 4 5 6 7 8 910
027
ON ON ON
1 2 3 4 5 6 7 8 910
006 1 2 3 4 5 6 7 8 910
017 1 2 3 4 5 6 7 8 910
028
ON ON ON
1 2 3 4 5 6 7 8 910
007 1 2 3 4 5 6 7 8 910
018 1 2 3 4 5 6 7 8 910
029
ON ON ON
1 2 3 4 5 6 7 8 910
008 1 2 3 4 5 6 7 8 910
019 1 2 3 4 5 6 7 8 910
030
ON ON ON
1 2 3 4 5 6 7 8 910
009 1 2 3 4 5 6 7 8 910
020 1 2 3 4 5 6 7 8 910
031
ON ON ON
1 2 3 4 5 6 7 8 910
010 1 2 3 4 5 6 7 8 910
021 1 2 3 4 5 6 7 8 910
032
ON ON
1 2 3 4 5 6 7 8 910
011 1 2 3 4 5 6 7 8 910
022
000075
Page 21 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

ON ON ON
1 2 3 4 5 6 7 8 9 10
033 1 2 3 4 5 6 7 8 9 10
044 1 2 3 4 5 6 7 8 9 10
055
ON ON ON
1 2 3 4 5 6 7 8 9 10
034 1 2 3 4 5 6 7 8 9 10
045 1 2 3 4 5 6 7 8 910
056
ON ON ON
1 2 3 4 5 6 7 8 9 10
035 1 2 3 4 5 6 7 8 9 10
046 1 2 3 4 5 6 7 8 910
057
ON ON ON
1 2 3 4 5 6 7 8 9 10
036 1 2 3 4 5 6 7 8 9 10
047 1 2 3 4 5 6 7 8 9 10
058
ON ON ON
1 2 3 4 5 6 7 8 9 10
037 1 2 3 4 5 6 7 8 9 10
048 1 2 3 4 5 6 7 8 9 10
059
ON ON ON
1 2 3 4 5 6 7 8 9 10
038 1 2 3 4 5 6 7 8 9 10
049 1 2 3 4 5 6 7 8 910
060
ON ON ON
1 2 3 4 5 6 7 8 9 10
039 1 2 3 4 5 6 7 8 9 10
050 1 2 3 4 5 6 7 8 910
061
ON ON ON
1 2 3 4 5 6 7 8 9 10
040 1 2 3 4 5 6 7 8 9 10
051 1 2 3 4 5 6 7 8 9 10
062
ON ON ON
1 2 3 4 5 6 7 8 9 10
041 1 2 3 4 5 6 7 8 9 10
052 1 2 3 4 5 6 7 8 9 10
063
ON ON ON
1 2 3 4 5 6 7 8 9 10
042 1 2 3 4 5 6 7 8 9 10
053 1 2 3 4 5 6 7 8 910
064
ON ON
1 2 3 4 5 6 7 8 9 10
043 1 2 3 4 5 6 7 8 9 10
054
000076
Page 22 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

ON ON ON
1 2 3 4 5 6 7 8 9 10
065 1 2 3 4 5 6 7 8 910
076 1 2 3 4 5 6 7 8 9 10
087
ON ON ON
1 2 3 4 5 6 7 8 9 10
066 1 2 3 4 5 6 7 8 910
077 1 2 3 4 5 6 7 8 910
088
ON ON ON
1 2 3 4 5 6 7 8 9 10
067 1 2 3 4 5 6 7 8 910
078 1 2 3 4 5 6 7 8 910
089
ON ON ON
1 2 3 4 5 6 7 8 9 10
068 1 2 3 4 5 6 7 8 910
079 1 2 3 4 5 6 7 8 9 10
090
ON ON ON
1 2 3 4 5 6 7 8 9 10
069 1 2 3 4 5 6 7 8 910
080 1 2 3 4 5 6 7 8 9 10
091
ON ON ON
1 2 3 4 5 6 7 8 9 10
070 1 2 3 4 5 6 7 8 910
081 1 2 3 4 5 6 7 8 910
092
ON ON ON
1 2 3 4 5 6 7 8 9 10
071 1 2 3 4 5 6 7 8 910
082 1 2 3 4 5 6 7 8 910
093
ON ON ON
1 2 3 4 5 6 7 8 9 10
072 1 2 3 4 5 6 7 8 910
083 1 2 3 4 5 6 7 8 9 10
094
ON ON ON
1 2 3 4 5 6 7 8 9 10
073 1 2 3 4 5 6 7 8 910
084 1 2 3 4 5 6 7 8 9 10
095
ON ON ON
1 2 3 4 5 6 7 8 9 10
074 1 2 3 4 5 6 7 8 910
085 1 2 3 4 5 6 7 8 910
096
ON ON
1 2 3 4 5 6 7 8 9 10
075 1 2 3 4 5 6 7 8 910
086
000077
Page 23 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

ON ON ON
1 2 3 4 5 6 7 8 910
097 1 2 3 4 5 6 7 8 910
108 1 2 3 4 5 6 7 8 910
119
ON ON ON
1 2 3 4 5 6 7 8 910
098 1 2 3 4 5 6 7 8 910
109 1 2 3 4 5 6 7 8 910
120
ON ON ON
1 2 3 4 5 6 7 8 910
099 1 2 3 4 5 6 7 8 910
110 1 2 3 4 5 6 7 8 910
121
ON ON ON
1 2 3 4 5 6 7 8 910
100 1 2 3 4 5 6 7 8 910
111 1 2 3 4 5 6 7 8 910
122
ON ON ON
1 2 3 4 5 6 7 8 910
101 1 2 3 4 5 6 7 8 910
112 1 2 3 4 5 6 7 8 910
123
ON ON ON
1 2 3 4 5 6 7 8 910
102 1 2 3 4 5 6 7 8 910
113 1 2 3 4 5 6 7 8 910
124
ON ON ON
1 2 3 4 5 6 7 8 910
103 1 2 3 4 5 6 7 8 910
114 1 2 3 4 5 6 7 8 910
125
ON ON ON
1 2 3 4 5 6 7 8 910
104 1 2 3 4 5 6 7 8 910
115 1 2 3 4 5 6 7 8 910
126
ON ON ON
1 2 3 4 5 6 7 8 910
105 1 2 3 4 5 6 7 8 910
116 1 2 3 4 5 6 7 8 910
127
ON ON ON
1 2 3 4 5 6 7 8 910
106 1 2 3 4 5 6 7 8 910
117 1 2 3 4 5 6 7 8 910
128
ON ON
1 2 3 4 5 6 7 8 910
107 1 2 3 4 5 6 7 8 910
118
000078
Page 24 / 24
AREA54-1 DS80SC39-002
16 Bit multiprocessor modular analogue Control Panel
LBT80270
INSTALLATION MANUAL IS7084-AB

ELKRON S.p.A.
Via Cimarosa, 39 – 10154 Torino (TO) – Italy
Tel. +39 (0)11.3986711 – Fax +39 (0)11.3986790
Sede Milano: Via Gadames,109 – 20151 (Mi) – Italy
Tel. +39 (0)2.334491 – Fax +39 (0)2.33449213
www.elkron.it – mail to: info@elkron.it