Professional Documents
Culture Documents
Edcon MHT Series 100-600KVA (Italy)
Edcon MHT Series 100-600KVA (Italy)
UPS
MHT Series 100-600KVA
Edcon MHT series UPS provide maximum protection and power quality for mission critical loads, including data centers,
industrial processes, telecommunications, security, and electro-medical system.
Mains Bypass
Maximum protection for vital critical networks, security and
industrial applications
Rectifier
= MHT series range from 100 to 600 kVA three-phase models and uses on-line
double conversion technology (VFI) with an in-built isolation transformer on the
inverter output. The load is powered continuously by the inverter with a filtered,
=
Inverter
stabilized and regulated sine wave supply. The input and output EMI filters
Inverter output isolation
transformer considerably increase the immunity of the load to mains disturbances and surges.
Static by-pass
Manual by-pass
Main Features
IGBT-based rectifier technology
Built-in galvanic isolation transformer on the inverter output
IGBT inverter
High overload capacity
High output PF = 0.9 meet high requirements of applications
High efficiency up to 98.5% in ECO-Mode
Large LCD screen with graphic display
High output power factor at 0.9
Can configure as Frequency Converter 50Hz to 60Hz or vice versa
Reliable, filtered, stabilized and regulated sine wave output (double conversion on-line technology VFI according
to EN50091-3 specifications) with filters for atmospheric disturbance suppression
High reliability: IGBT technology, full microprocessor control with no-break static and manual bypasses, extremely
high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting, drives and
industrial processes)
Maximum reliability and power availability connect up to 8 units in parallel or N+1 redundancy
Low input total harmonic distortion
High level diagnostics: event log with 128 messages, states, measurements and alarms available from the built-in
LCD in several languages
edcon
UPS
MHT Series 100-200KVA
Simple to install:
- Capability to install the UPS into any distribution system (neutral not required on rectifier input)
- Capability to separate the rectifier/bypass power networks and of powering these from two separate sources, without
galvanic isolation (necessary on those UPS without an output transformer)
Capability of regulating the output voltage (to offset voltage drops down long cable runs)
Built-in automatic and manual battery test feature, battery deep discharge protection and temperature
compensating charger
Built-in automatic and manual battery test feature, battery deep discharge protection and temperature
compensating charger
Back-feed protection: to avoid energy feeding back into the mains supply should a fault occur
Emergency operation: the UPS can be set to operate only when the mains fails (for emergency lighting)
By pass may be deactivated to allow operation as a frequency converter (at 50 or 60 Hz), or as stabilizer
Back-feed protection: to avoid energy feeding back into the mains supply should a fault occur
Emergency operation: the UPS can be set to operate only when the mains fails (for emergency lighting)
By pass may be deactivated to allow operation as a frequency converter (at 50 or 60 Hz), or as stabilizer
Battery Management
MHT is equipped with battery protection system. There are several features that help to prolong battery life span and
performance, such as:
Cycling charging
Two voltage level charging
Protection against deep discharge
Battery self-test
Compatibility with open vented acid battery
Temperature compensation charging (optional)
Flexible configuration
Bypass 1 Bypass 1
System A System B
=
Battery
Battery
Battery
Bypass 1 Bypass 1
Distribution Redundancy: PSJ
System A System B
Battery
Battery
Battery
Battery
Battery
Parallel up to 8 UPS
Load
Simplified Maintenance
Access for maintenance is entirely from the front of the UPS. With the
door opened and the protective panel removed, the power components
mounted on the sliding tray can be pulled out to provide easy access
to all the electrical and electronic components for maintenance and
repair work. This particular feature means that the MTTR
(Mean Time To Repair) is typically less than 30 minutes.
edcon
UPS
MHT Series 100-600KVA
Large LCD Display
A large amount of maintenance information is available from the front large LCD mimic panel. In addition system operating
parameters are software configurable via a local PC to allow new functions to be added or adjustments made to operating
specifications.
Load on mains
Bypass line indicator
Mains line indicator Load on Inverter
Battery discharging Alarm
Main source
SNMP HP
Router
Power
Messaging
Hub
RS232/USB UPS
Server Local monitoring Remote monitoring
MHT series provides solutions for remote monitoring and power management. With optional SNMP card, UPS can
be easily integrated into any medium and large-size Data Center; UPS status can be monitored by ModBus TCP/IP;
Profibus DP Network; BACnet/ IP and GSM/WIFT ready by means of customized RTG100 dongle.
UPS Monitoring Software supports the following operating systems:
Microsoft Windows 2000, Xp, 2003; Microsoft Vista x86 and x86_64; Microsoft 2008, 2012 x86 and x86_64;
Microsoft 7, 8 x86 and x86_64; Novell NetWare 3.x, 4.x, 5.x, 6; Mac 0S X 10.x.x; Linux kernel 2.4.x and 2.6.x; etc.
edcon
UPS
MHT Series 100-600KVA
MODELS MHT100 MHT120 MHT160 MHT200 MHT250 MHT300 MHT400 MHT500 MHT600
INPUT
Nominal voltage 380-400-415 VAC 3-phase
Voltage tolerance 400V ± 20% @ full load
Frequency 45-65 Hz
Rated frequency 50/60 Hz (auto sensing)
Power factor > 0.9
Harmonic current distortion < 3% THDi
Permitted frequency tolerance ±2% (selectable from ±1% to ±5% from front panel)
Standard features Back feed protection; separate bypass line
BYPASS
Nominal voltage 380-400-415 VAC 3-phase + N
Nominal frequency 50/60Hz (auto sensing)
OUTPUT
Nominal power (kVA) 100 120 160 200 250 300 400 500 600
Active power (kW) 90 108 144 180 225 270 360 450 540
Nominal voltage 380-400-415 VAC 3-phase + N (selectable)
Static stability; Dynamic stability ±1%; ±5% in 10ms
Voltage distortion < 1% with linear load; 3% with non-linear load
Wave form sine wave
Crest factor 3:1
Frequency stability on battery 0,05%
Frequency 50/60 Hz (selectable)
Overload 110% for 60 minutes; 125% for 10 minutes; 150% for 1 minutes
BATTERIES
Type Maintenance-free sealed lead acid; VRLA AGM/ GEL; NiCD
Voltage (Vdc) 480
Maximum recharge current 0.2 x C10
ENVIRONMENTAL
Weight (kg) 656 700 800 910 1060 1400 1400 2100 2400
Dimension (WxDxH) (mm) 800 x 850 x 1900 1000 x 850 x 1900 1500 x 1000 x 1900 2100 x 1000 x 1900
Remote signals Dry contacts (configurable)
Communications Double RS232 + dry contacts + 2 slots communication interface
Operating temperature 0 °C - 40 °C
Relative humidity < 95% non-condensing
Colour White/ Dark grey
Noise level at 1m (dBA) 63 - 68 70 - 72
IP rating IP20
Efficiency up to 98%