Project: ETAP Page: 1

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Electrical Transient Analyzer Program

Short-Circuit Analysis

IEC 60909 Standard

3-Phase, LG, LL, & LLG Fault Currents

Swing V-Control Load Total

Number of Buses: 8 0 36 44

Line/Cable/
XFMR2 XFMR3 Reactor Busway Impedance Tie PD Total

Number of Branches: 1 0 0 34 0 1 36

Synchronous Power Synchronous Induction Lumped


Generator Grid Motor Machines Load Total

Number of Machines: 1 1 0 17 0 19

System Frequency: 50.00

Unit System: Metric

Project Filename: Planta El Alto (La Paz)

Output Filename: C:\ETAP 2000\Planta El Alto (La Paz)\Untitled.SI2S


Project: ETAP Page: 2

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Adjustments

Apply Individual
Tolerance Adjustments /Global Percent

Transformer Impedance: Yes Individual

Reactor Impedance: Yes Individual

Overload Heater Resistance: No

Transmission Line Length: No

Cable / Busway Length: No

Apply Individual
Temperature Correction Adjustments /Global Degree C

Transmission Line Resistance: Yes Individual

Cable / Busway Resistance: Yes Individual


Project: ETAP Page: 3

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Bus Input Data

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus1 SWNG 11.900 11.900 1 100.00 0.00


Bus16 Load 0.380 0.400 3 95.00 0.00
Bus20 SWNG 0.380 0.400 3 105.26 0.00
Bus22 Load 0.380 0.400 4 95.00 0.00
Bus23 SWNG 0.380 0.400 4 105.26 0.00
Bus24 Load 0.380 0.380 1 100.00 -30.00
Bus27 Load 0.380 0.400 5 100.00 0.00
Bus28 SWNG 0.380 0.400 5 105.26 0.00
Bus31 Load 0.380 0.400 6 100.00 0.00
Bus32 SWNG 0.380 0.400 6 105.26 0.00
Bus35 Load 0.380 0.400 7 100.00 0.00
Bus36 SWNG 0.380 0.400 7 105.26 0.00
Bus39 Load 0.380 0.400 8 100.00 0.00
Bus40 SWNG 0.380 0.400 8 105.26 0.00
Bus42 Load 0.380 0.380 1 100.00 -30.00
Bus44 Load 0.380 0.380 1 100.00 -30.00
Bus49 Load 0.380 0.380 1 100.00 -30.00
Bus51 Load 0.380 0.380 1 100.00 -30.00
Bus53 Load 0.380 0.380 1 100.00 -30.00
Bus55 Load 0.380 0.380 1 100.00 -30.00
Bus56 Load 0.380 0.380 1 100.00 -30.00
Bus58 Load 0.380 0.380 1 100.00 -30.00
Bus60 Load 0.380 0.380 1 100.00 -30.00
Bus62 Load 0.380 0.380 1 100.00 -30.00
Bus63 Load 0.380 0.380 1 100.00 -30.00
Bus64 Load 0.380 0.380 1 100.00 -30.00
Bus65 Load 0.380 0.380 1 100.00 -30.00
Bus66 Load 0.380 0.380 1 100.00 -30.00
Bus67 SWNG 0.380 0.380 2 100.00 0.00
Bus68 Load 0.380 0.380 1 100.00 -30.00
Bus70 Load 0.380 0.380 1 100.00 -30.00
Bus71 Load 0.380 0.380 1 100.00 -30.00
Bus72 Load 0.380 0.380 1 100.00 -30.00
Bus73 Load 0.380 0.380 1 100.00 -30.00
Bus75 Load 0.380 0.380 1 100.00 -30.00
Bus77 Load 0.380 0.380 1 100.00 -30.00
Bus79 Load 0.380 0.380 1 95.00 -30.00
Bus81 Load 0.380 0.380 1 100.00 -30.00
Bus83 Load 0.380 0.380 1 100.00 -30.00
Bus84 Load 0.380 0.380 1 100.00 -30.00
Bus85 Load 0.380 0.380 1 95.00 -30.00
Project: ETAP Page: 4

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Bus Initial Voltage


ID Type Nom. kV Base kV Sub-sys %Mag. Ang.

Bus86 Load 0.380 0.380 1 100.00 -30.00


MCC Load 0.380 0.380 1 95.00 -30.00
TD-100 Load 0.380 0.380 1 100.00 -30.00

44 Buses Total

All voltages reported by ETAP are in % of bus Nominal kV.


Base kV values of buses are calculated and used internally by ETAP .
Project: ETAP Page: 5

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Line/Cable/Busway Input Data

ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line/Busway)

Line/Cable/Busway Length

ID Library Size Adj. (m) % Tol. #/Phase T (°C) R1 X1 Y1 R0 X0 Y0

Cable01 16 100.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable02 16 100.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable03 16 110.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable04 16 110.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable05 6 110.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable06 1.5 110.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable07 4 80.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable08 4 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable09 4 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable10 95 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable011 4 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable012 4 100.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable013 95 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable014 95 120.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable015 25 220.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable016 16 140.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable17 50 30.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable018 16 30.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable19 16 80.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable020 50 50.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable021 16 80.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable022 10 100.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable023 4 115.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable30 10 20.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable31 10 40.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable032 10 50.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable33 10 60.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable034 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable035 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable036 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable37 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable38 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable39 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Cable40 10 150.0 0.0 1 75 0.1070177 0.13226 0.0000503 0.1070177 0.13226 0.000008

Line / Cable / Busway resistances are listed at the specified temperatures.


Project: ETAP Page: 6

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

2-Winding Transformer Input Data

Transformer Rating Z Variation % Tap Setting Adjusted Phase Shift

ID MVA Prim. kV Sec. kV %Z X/R + 5% - 5% % Tol. Prim. Sec. %Z Type Angle

T1 0.300 11.900 0.400 4.00 1.50 0 0 0 0 -5.000 4.00 Dyn 30.00

2-Winding Transformer Grounding Input Data

Grounding
Transformer Rating Conn. Primary Secondary

ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm

T1 0.300 11.900 0.400 D/Y Solid


Project: ETAP Page: 7

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Branch Connections

CKT/Branch Connected Bus ID % Impedance, Pos. Seq., 100 MVAb

ID Type From Bus To Bus R X Z Y

T1 2W XFMR Bus1 Bus24 723.31 1084.96 1303.96

Cable01 Cable Bus20 Bus16 668.86 826.62 1063.34 0.0000008

Cable02 Cable Bus23 Bus22 668.86 826.62 1063.34 0.0000008

Cable03 Cable Bus28 Bus27 735.75 909.29 1169.67 0.0000009

Cable04 Cable Bus32 Bus31 735.75 909.29 1169.67 0.0000009

Cable05 Cable Bus36 Bus35 735.75 909.29 1169.67 0.0000009

Cable06 Cable Bus40 Bus39 735.75 909.29 1169.67 0.0000009

Cable07 Cable MCC Bus42 592.90 732.74 942.57 0.0000006

Cable08 Cable MCC Bus44 889.34 1099.11 1413.85 0.0000009

Cable09 Cable MCC Bus49 889.34 1099.11 1413.85 0.0000009

Cable10 Cable MCC Bus51 889.34 1099.11 1413.85 0.0000009

Cable011 Cable MCC Bus53 889.34 1099.11 1413.85 0.0000009

Cable012 Cable MCC Bus55 741.12 915.93 1178.21 0.0000007

Cable013 Cable MCC Bus56 889.34 1099.11 1413.85 0.0000009

Cable014 Cable MCC Bus58 889.34 1099.11 1413.85 0.0000009

Cable015 Cable MCC Bus60 1630.46 2015.04 2592.07 0.0000016

Cable016 Cable MCC Bus62 1037.57 1282.30 1649.50 0.0000010

Cable17 Cable MCC TD-100 222.34 274.78 353.46 0.0000002

Cable018 Cable MCC Bus63 222.34 274.78 353.46 0.0000002

Cable19 Cable MCC Bus64 592.90 732.74 942.57 0.0000006

Cable020 Cable MCC Bus86 370.56 457.96 589.11 0.0000004

Cable021 Cable MCC Bus65 592.90 732.74 942.57 0.0000006

Cable022 Cable MCC Bus66 741.12 915.93 1178.21 0.0000007

Cable023 Cable MCC Bus68 852.29 1053.32 1354.94 0.0000008

Cable30 Cable TD-100 Bus71 148.22 183.19 235.64 0.0000001

Cable31 Cable TD-100 Bus70 296.45 366.37 471.28 0.0000003

Cable032 Cable TD-100 Bus72 370.56 457.96 589.11 0.0000004

Cable33 Cable TD-100 Bus73 444.67 549.56 706.93 0.0000004

Cable034 Cable TD-100 Bus75 1111.68 1373.89 1767.32 0.0000011

Cable035 Cable TD-100 Bus77 1111.68 1373.89 1767.32 0.0000011

Cable036 Cable TD-100 Bus79 1111.68 1373.89 1767.32 0.0000011

Cable37 Cable TD-100 Bus81 1111.68 1373.89 1767.32 0.0000011

Cable38 Cable TD-100 Bus83 1111.68 1373.89 1767.32 0.0000011

Cable39 Cable TD-100 Bus85 1111.68 1373.89 1767.32 0.0000011

Cable40 Cable TD-100 Bus84 1111.68 1373.89 1767.32 0.0000011

CB3 Tie Breakr Bus24 MCC


Project: ETAP Page: 8

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Power Grid Input Data

% Impedance
Rating 100 MVA Base
Grounding
Power Grid ID Connected Bus ID MVASC kV R X" R/X" Type

U1 Bus1 100000.000 11.900 0.00995 0.09950 0.10 Wye - Solid

Total Connected Power Grids ( = 1 ): 100000.000 MVA

Synchronous Generator Input Data

% Impedance in Machine Base

Synchronous Generator Rating Xd" Grounding Excitation


ID Type MVA kV RPM % PF R Adj. Tol. R/X Xd, sat Conn. Type Amp Type

Gen1 Steam Turbo 0.315 0.380 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%

Total Connected Synchronous Generators ( = 1.00 ) : 0.315 MVA


Project: ETAP Page: 9

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Induction Machine Input Data

Pos. Seq. Imp.


Induction Machine Connected Bus Rating (Motor Base) Grounding

ID Type Qty ID HP/kW kVA kV Amp PF %R % X" R/X" Conn. Type Amp MW/PP

P-100 Motor 1 Bus16 15.00 21.64 0.400 31.23 88.21 7.79 14.74 0.53 Wye Open 0.01
P-102 Motor 1 Bus27 15.00 21.64 0.400 31.24 88.21 7.79 14.74 0.53 Wye Open 0.01
P-500 Motor 1 Bus35 5.50 8.63 0.400 12.46 85.82 9.52 13.68 0.70 Wye Open 0.00
P-501 Motor 1 Bus39 5.50 8.63 0.400 12.46 85.82 9.52 13.68 0.70 Wye Open 0.00
P-104 Motor 1 Bus42 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-105 Motor 1 Bus44 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-106 Motor 1 Bus49 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-107 Motor 1 Bus51 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-108 Motor 1 Bus53 3.00 3.81 0.380 5.79 83.67 11.08 12.45 0.89 Wye Open 0.00
P-502 Motor 1 Bus55 3.00 3.81 0.380 5.79 83.67 11.08 12.45 0.89 Wye Open 0.00
P-503 Motor 1 Bus56 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-504 Motor 1 Bus58 3.00 3.81 0.400 5.50 83.67 11.08 12.45 0.89 Wye Open 0.00
P-505 Motor 1 Bus60 4.00 4.94 0.380 7.50 84.35 10.58 12.88 0.82 Wye Open 0.00
P-600 Motor 1 Bus62 4.00 4.94 0.380 7.50 84.35 10.58 12.88 0.82 Wye Open 0.00
TOMA HIDROLAVORA Motor 1 Bus65 7.80 11.67 0.380 17.73 86.65 8.92 14.08 0.63 Wye Open 0.00

TOMAS INDUSTRIALES Motor 1 Bus66 5.00 7.91 0.380 12.01 85.59 9.69 13.56 0.71 Wye Open 0.00
SCHUKO
COMPRESOR DE AIRE Motor 1 Bus86 30.00 31.87 0.380 48.42 89.17 7.10 15.08 0.47 Wye Open 0.01

Total Connected Induction Machines ( = 17 ): 152.3 kVA


Project: ETAP Page: 10

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

VFD Input Data

AC Rating
% Impedance
kVA kV FLA Input Output Bypass Equipment Base
ID Output Input Output Input Output % EFF % PF Hz % Imax Switch R X

SF-01 22.00 0.400 0.400 31.75 31.75 100.00 100.00 50.00 150.0 No 66.67 0.00

SF-02 16.41 0.400 0.400 31.75 23.68 100.00 74.57 50.00 150.0 No 66.67 0.00

SF-03 22.00 0.400 0.400 31.75 31.75 100.00 100.00 50.00 150.0 No 66.67 0.00

SF-04 22.00 0.400 0.400 31.75 31.75 100.00 100.00 50.00 150.0 No 66.67 0.00

SF-05 7.50 0.400 0.400 10.83 10.83 100.00 100.00 50.00 150.0 No 66.67 0.00

SF-06 7.50 0.400 0.400 10.83 10.83 100.00 100.00 50.00 150.0 No 66.67 0.00
Project: ETAP Page: 11

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

SHORT- CIRCUIT REPORT

Fault at bus: Bus1


Nominal kV = 11.900
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus1 Total 0.00 4851.707 0.00 110.00 110.00 4851.696 4851.696 1.09E-002 1.09E-001 1.09E-002 1.09E-001

Bus24 Bus1 7.11 0.026 65.96 65.26 111.02 0.014 0.000 1.12E+004 1.68E+004

U1 Bus1 110.00 4851.683 110.00 110.00 110.00 4851.683 4851.696 1.09E-002 1.09E-001 1.09E-002 1.09E-001

Bus42 MCC 7.31 0.032 66.03 65.31 111.05 0.016 0.000 8.26E+004 4.83E+005

Bus44 MCC 7.41 0.032 66.07 65.33 111.06 0.016 0.000 8.27E+004 4.84E+005

Bus49 MCC 7.41 0.032 66.07 65.33 111.06 0.016 0.000 8.27E+004 4.84E+005

Bus51 MCC 7.41 0.032 66.07 65.33 111.06 0.016 0.000 8.27E+004 4.84E+005

Bus53 MCC 7.44 0.036 66.08 65.34 111.07 0.018 0.000 7.46E+004 4.37E+005

Bus55 MCC 7.38 0.036 66.06 65.33 111.06 0.018 0.000 7.46E+004 4.37E+005

Bus56 MCC 7.41 0.032 66.07 65.33 111.06 0.016 0.000 8.27E+004 4.84E+005

Bus58 MCC 7.41 0.032 66.07 65.33 111.06 0.016 0.000 8.27E+004 4.84E+005

Bus60 MCC 7.89 0.046 66.25 65.45 111.14 0.023 0.000 4.45E+004 3.41E+005

Bus62 MCC 7.61 0.046 66.14 65.38 111.09 0.023 0.000 4.44E+004 3.40E+005

TD-100 MCC 7.11 0.000 65.96 65.26 111.02 0.000 0.000

Bus63 MCC 7.11 0.000 65.96 65.26 111.02 0.000 0.000

Bus64 MCC 7.11 0.000 65.96 65.26 111.02 0.000 0.000

Bus86 MCC 8.23 0.296 66.44 65.46 111.18 0.144 0.000 6.15E+003 5.30E+004

Bus65 MCC 7.78 0.109 66.22 65.40 111.12 0.053 0.000 1.10E+003 1.45E+005

Bus66 MCC 7.68 0.074 66.18 65.39 111.10 0.036 0.000 1.34E+004 2.14E+005

Bus68 MCC 7.11 0.000 65.96 65.26 111.02 0.000 0.000


Project: ETAP Page: 12

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

(Cont.)

Fault at bus: Bus1


Nominal kV = 11.900
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4851.707 4851.696 4201.698 4851.702
Peak Current (kA), Method C : 11979.910 11979.890 10374.900 11979.900
Breaking Current (kA, rms, symm) : 4851.696 4201.698 4851.702
Steady State Current (kA, rms) : 4851.683 4851.696 4201.698 4851.702

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 13

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus16


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus16 Total 0.00 0.213 0.00 116.09 172.79 0.099 0.099 4.26E+004 5.23E+004 3.04E+005 8.27E+002

Bus20 Bus16 0.37 0.047 0.37 115.91 172.69 0.047 0.099 3.04E+005 8.27E+002 3.04E+005 8.27E+002

P-100 Bus16 99.75 0.187 99.75 99.75 99.75 0.056 0.000 3.60E+004 6.81E+004

SF-01 Bus20 99.75 0.047 99.75 99.75 99.75 0.047 0.099 3.03E+005 4.55E-005 3.03E+005 4.55E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.213 0.099 0.139 0.174
Peak Current (kA), Method C : 0.391 0.181 0.255 0.320
Breaking Current (kA, rms, symm) : 0.099 0.139 0.174
Steady State Current (kA, rms) : 0.047 0.099 0.139 0.174

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 14

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus20


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus20 Total 0.00 0.211 0.00 115.77 172.43 0.099 0.099 4.34E+004 5.27E+004 3.03E+005 4.55E-005

Bus16 Bus20 1.43 0.184 0.43 115.95 172.54 0.056 0.000 3.67E+004 6.89E+004

SF-01 Bus20 99.75 0.048 99.75 99.75 99.75 0.048 0.099 3.03E+005 4.55E-005 3.03E+005 4.55E-005

P-100 Bus16 99.75 0.184 99.75 99.75 99.75 0.056 0.000 3.60E+004 6.81E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.211 0.099 0.138 0.173
Peak Current (kA), Method C : 0.386 0.181 0.253 0.317
Breaking Current (kA, rms, symm) : 0.099 0.138 0.173
Steady State Current (kA, rms) : 0.048 0.099 0.138 0.173

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 15

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus22


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus22 Total 0.00 0.035 0.00 105.00 105.00 0.035 0.035 4.07E+005 8.27E+002 4.07E+005 8.27E+002

Bus23 Bus22 0.27 0.035 0.27 105.00 105.00 0.035 0.035 4.07E+005 8.27E+002 4.07E+005 8.27E+002

SF-02 Bus23 99.75 0.035 99.75 99.75 99.75 0.035 0.035 4.06E+005 6.10E-005 4.06E+005 6.10E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.035 0.035 0.031 0.035
Peak Current (kA), Method C : 0.051 0.051 0.044 0.051
Breaking Current (kA, rms, symm) : 0.035 0.031 0.035
Steady State Current (kA, rms) : 0.035 0.035 0.031 0.035

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 16

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus23


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus23 Total 0.00 0.035 0.00 105.00 105.00 0.035 0.035 4.06E+005 6.10E-005 4.06E+005 6.10E-005

Bus22 Bus23 0.00 0.000 0.00 105.00 105.00 0.000 0.000

SF-02 Bus23 99.75 0.035 99.75 99.75 99.75 0.035 0.035 4.06E+005 6.10E-005 4.06E+005 6.10E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.035 0.035 0.031 0.035
Peak Current (kA), Method C : 0.051 0.051 0.044 0.051
Breaking Current (kA, rms, symm) : 0.035 0.031 0.035
Steady State Current (kA, rms) : 0.035 0.035 0.031 0.035

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 17

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus24


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus24 Total 0.00 13.079 0.00 106.37 106.99 12.662 12.662 6.77E+002 1.01E+003 7.23E+002 1.08E+003

Bus1 Bus24 104.99 12.233 105.00 105.00 105.00 12.234 12.662 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

Bus42 MCC 0.20 0.033 0.10 106.40 107.05 0.016 0.000 3.23E+005 3.63E+005

Bus44 MCC 0.31 0.033 0.15 106.42 107.08 0.016 0.000 3.23E+005 3.63E+005

Bus49 MCC 0.31 0.033 0.15 106.42 107.08 0.016 0.000 3.23E+005 3.63E+005

Bus51 MCC 0.31 0.033 0.15 106.42 107.08 0.016 0.000 3.23E+005 3.63E+005

Bus53 MCC 0.34 0.036 0.17 106.43 107.09 0.018 0.000 2.92E+005 3.28E+005

Bus55 MCC 0.28 0.036 0.14 106.42 107.07 0.018 0.000 2.92E+005 3.28E+005

Bus56 MCC 0.31 0.033 0.15 106.42 107.08 0.016 0.000 3.23E+005 3.63E+005

Bus58 MCC 0.31 0.033 0.15 106.42 107.08 0.016 0.000 3.23E+005 3.63E+005

Bus60 MCC 0.80 0.047 0.40 106.51 107.22 0.024 0.000 2.16E+005 2.63E+005

Bus62 MCC 0.51 0.047 0.26 106.46 107.14 0.024 0.000 2.15E+005 2.62E+005

TD-100 MCC 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus63 MCC 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus64 MCC 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus86 MCC 1.17 0.302 0.60 106.55 107.34 0.155 0.000 2.26E+004 4.78E+004

Bus65 MCC 0.69 0.111 0.35 106.49 107.19 0.057 0.000 7.70E+004 1.21E+005

Bus66 MCC 0.58 0.075 0.30 106.47 107.16 0.038 0.000 1.23E+005 1.72E+005

Bus68 MCC 0.00 0.000 0.00 106.37 106.99 0.000 0.000

U1 Bus1 105.00 0.391 105.00 105.00 105.00 0.222 0.000 1.09E-002 1.09E-001 1.09E-002 1.09E-001

P-104 Bus42 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-105 Bus44 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-106 Bus49 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-107 Bus51 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-108 Bus53 105.00 0.036 105.00 105.00 105.00 0.018 0.000 2.91E+005 3.27E+005

P-502 Bus55 105.00 0.036 105.00 105.00 105.00 0.018 0.000 2.91E+005 3.27E+005

P-503 Bus56 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-504 Bus58 99.75 0.033 99.75 99.75 99.75 0.016 0.000 3.22E+005 3.62E+005

P-505 Bus60 105.00 0.047 105.00 105.00 105.00 0.024 0.000 2.14E+005 2.61E+005

P-600 Bus62 105.00 0.047 105.00 105.00 105.00 0.024 0.000 2.14E+005 2.61E+005

Bus71 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000


Project: ETAP Page: 18

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

(Cont.)

Fault at bus: Bus24


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus70 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus72 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus73 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus75 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus77 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus79 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus81 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus83 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus85 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

Bus84 TD-100 0.00 0.000 0.00 106.37 106.99 0.000 0.000

COMPRESOR DE Bus86 105.00 0.302 105.00 105.00 105.00 0.155 0.000 2.23E+004 4.73E+004
AIRE
TOMA Bus65 105.00 0.111 105.00 105.00 105.00 0.057 0.000 7.64E+004 1.21E+005
HIDROLAVORA
TOMAS Bus66 105.00 0.075 105.00 105.00 105.00 0.038 0.000 1.23E+005 1.72E+005
INDUSTRIALES
SCHUKO

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 13.079 12.662 11.161 12.907
Peak Current (kA), Method C : 21.343 20.663 18.213 21.063
Breaking Current (kA, rms, symm) : 12.662 11.161 12.907
Steady State Current (kA, rms) : 12.233 12.662 11.161 12.907

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 19

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus27


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus27 Total 0.00 0.213 0.00 116.11 172.79 0.099 0.099 4.26E+004 5.23E+004 3.04E+005 9.09E+002

Bus28 Bus27 0.40 0.047 0.40 115.91 172.67 0.047 0.099 3.04E+005 9.09E+002 3.04E+005 9.09E+002

P-102 Bus27 99.75 0.187 99.75 99.75 99.75 0.056 0.000 3.60E+004 6.81E+004

SF-03 Bus28 99.75 0.047 99.75 99.75 99.75 0.047 0.099 3.03E+005 4.55E-005 3.03E+005 4.55E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.213 0.099 0.139 0.174
Peak Current (kA), Method C : 0.391 0.181 0.255 0.320
Breaking Current (kA, rms, symm) : 0.099 0.139 0.174
Steady State Current (kA, rms) : 0.047 0.099 0.139 0.174

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 20

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus28


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus28 Total 0.00 0.211 0.00 115.75 172.39 0.099 0.099 4.35E+004 5.27E+004 3.03E+005 4.55E-005

Bus27 Bus28 1.57 0.184 0.48 115.95 172.51 0.056 0.000 3.67E+004 6.90E+004

SF-03 Bus28 99.75 0.048 99.75 99.75 99.75 0.048 0.099 3.03E+005 4.55E-005 3.03E+005 4.55E-005

P-102 Bus27 99.75 0.184 99.75 99.75 99.75 0.056 0.000 3.60E+004 6.81E+004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.211 0.099 0.138 0.173
Peak Current (kA), Method C : 0.386 0.181 0.253 0.317
Breaking Current (kA, rms, symm) : 0.099 0.138 0.173
Steady State Current (kA, rms) : 0.048 0.099 0.138 0.173

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 21

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus31


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus31 Total 0.00 0.047 0.00 105.00 105.00 0.047 0.047 3.04E+005 9.09E+002 3.04E+005 9.09E+002

Bus32 Bus31 0.40 0.047 0.40 105.00 105.00 0.047 0.047 3.04E+005 9.09E+002 3.04E+005 9.09E+002

SF-04 Bus32 99.75 0.047 99.75 99.75 99.75 0.047 0.047 3.03E+005 4.55E-005 3.03E+005 4.55E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.047 0.047 0.041 0.047
Peak Current (kA), Method C : 0.068 0.068 0.059 0.068
Breaking Current (kA, rms, symm) : 0.047 0.041 0.047
Steady State Current (kA, rms) : 0.047 0.047 0.041 0.047

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 22

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus32


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus32 Total 0.00 0.048 0.00 105.00 105.00 0.048 0.048 3.03E+005 4.55E-005 3.03E+005 4.55E-005

Bus31 Bus32 0.00 0.000 0.00 105.00 105.00 0.000 0.000

SF-04 Bus32 99.75 0.048 99.75 99.75 99.75 0.048 0.048 3.03E+005 4.55E-005 3.03E+005 4.55E-005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.048 0.048 0.041 0.048
Peak Current (kA), Method C : 0.069 0.069 0.059 0.069
Breaking Current (kA, rms, symm) : 0.048 0.041 0.048
Steady State Current (kA, rms) : 0.048 0.048 0.041 0.048

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 23

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus35


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus35 Total 0.00 0.085 0.00 121.07 173.71 0.035 0.035 1.18E+005 1.22E+005 8.90E+005 9.09E+002

Bus36 Bus35 0.14 0.016 0.14 121.00 173.67 0.016 0.035 8.90E+005 9.09E+002 8.90E+005 9.09E+002

P-500 Bus35 99.75 0.075 99.75 99.75 99.75 0.020 0.000 1.10E+005 1.58E+005

SF-05 Bus36 99.75 0.016 99.75 99.75 99.75 0.016 0.035 8.89E+005 1.33E-004 8.89E+005 1.33E-004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.085 0.035 0.055 0.067
Peak Current (kA), Method C : 0.144 0.059 0.092 0.113
Breaking Current (kA, rms, symm) : 0.035 0.055 0.067
Steady State Current (kA, rms) : 0.016 0.035 0.055 0.067

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 24

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus36


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus36 Total 0.00 0.084 0.00 120.92 173.57 0.035 0.035 1.18E+005 1.23E+005 8.89E+005 1.33E-004

Bus35 Bus36 0.63 0.074 0.17 121.00 173.61 0.020 0.000 1.11E+005 1.59E+005

SF-05 Bus36 99.75 0.016 99.75 99.75 99.75 0.016 0.035 8.89E+005 1.33E-004 8.89E+005 1.33E-004

P-500 Bus35 99.75 0.074 99.75 99.75 99.75 0.020 0.000 1.10E+005 1.58E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.084 0.035 0.054 0.066
Peak Current (kA), Method C : 0.143 0.059 0.092 0.112
Breaking Current (kA, rms, symm) : 0.035 0.054 0.066
Steady State Current (kA, rms) : 0.016 0.035 0.054 0.066

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 25

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus39


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus39 Total 0.00 0.085 0.00 121.07 173.71 0.035 0.035 1.18E+005 1.22E+005 8.90E+005 9.09E+002

Bus40 Bus39 0.14 0.016 0.14 121.00 173.67 0.016 0.035 8.90E+005 9.09E+002 8.90E+005 9.09E+002

P-501 Bus39 99.75 0.075 99.75 99.75 99.75 0.020 0.000 1.10E+005 1.58E+005

SF-06 Bus40 99.75 0.016 99.75 99.75 99.75 0.016 0.035 8.89E+005 1.33E-004 8.89E+005 1.33E-004

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.085 0.035 0.055 0.067
Peak Current (kA), Method C : 0.144 0.059 0.092 0.113
Breaking Current (kA, rms, symm) : 0.035 0.055 0.067
Steady State Current (kA, rms) : 0.016 0.035 0.055 0.067

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 26

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus40


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus40 Total 0.00 0.084 0.00 120.92 173.57 0.035 0.035 1.18E+005 1.23E+005 8.89E+005 1.33E-004

Bus39 Bus40 0.63 0.074 0.17 121.00 173.61 0.020 0.000 1.11E+005 1.59E+005

SF-06 Bus40 99.75 0.016 99.75 99.75 99.75 0.016 0.035 8.89E+005 1.33E-004 8.89E+005 1.33E-004

P-501 Bus39 99.75 0.074 99.75 99.75 99.75 0.020 0.000 1.10E+005 1.58E+005

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 0.084 0.035 0.054 0.066
Peak Current (kA), Method C : 0.143 0.059 0.092 0.112
Breaking Current (kA, rms, symm) : 0.035 0.054 0.066
Steady State Current (kA, rms) : 0.016 0.035 0.054 0.066

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 27

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus42


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus42 Total 0.00 7.408 0.00 105.87 106.20 7.262 7.262 1.27E+003 1.74E+003 1.32E+003 1.82E+003

MCC Bus42 45.75 7.375 44.95 105.83 106.14 7.246 7.262 1.27E+003 1.75E+003 1.32E+003 1.82E+003

P-104 Bus42 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus44 MCC 45.92 0.019 45.04 105.86 106.19 0.009 0.000 3.23E+005 3.63E+005

Bus49 MCC 45.92 0.019 45.04 105.86 106.19 0.009 0.000 3.23E+005 3.63E+005

Bus51 MCC 45.92 0.019 45.04 105.86 106.19 0.009 0.000 3.23E+005 3.63E+005

Bus53 MCC 45.94 0.021 45.05 105.86 106.19 0.010 0.000 2.92E+005 3.28E+005

Bus55 MCC 45.91 0.021 45.03 105.86 106.19 0.010 0.000 2.92E+005 3.28E+005

Bus56 MCC 45.92 0.019 45.04 105.86 106.19 0.009 0.000 3.23E+005 3.63E+005

Bus58 MCC 45.92 0.019 45.04 105.86 106.19 0.009 0.000 3.23E+005 3.63E+005

Bus60 MCC 46.20 0.027 45.18 105.91 106.27 0.014 0.000 2.16E+005 2.63E+005

Bus62 MCC 46.04 0.027 45.10 105.88 106.22 0.014 0.000 2.15E+005 2.62E+005

TD-100 MCC 45.75 0.000 44.95 105.83 106.14 0.000 0.000

Bus63 MCC 45.75 0.000 44.95 105.83 106.14 0.000 0.000

Bus64 MCC 45.75 0.000 44.95 105.83 106.14 0.000 0.000

Bus86 MCC 46.41 0.171 45.29 105.94 106.33 0.089 0.000 2.26E+004 4.78E+004

Bus65 MCC 46.14 0.063 45.15 105.90 106.25 0.032 0.000 7.70E+004 1.21E+005

Bus66 MCC 46.08 0.043 45.12 105.89 106.24 0.022 0.000 1.23E+005 1.72E+005

Bus68 MCC 45.75 0.000 44.95 105.83 106.14 0.000 0.000

Bus1 Bus24 105.00 6.916 105.00 105.00 105.00 7.010 7.262 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.408 7.262 6.358 7.346
Peak Current (kA), Method C : 11.851 11.619 10.172 11.753
Breaking Current (kA, rms, symm) : 7.262 6.358 7.346
Steady State Current (kA, rms) : 7.108 7.262 6.358 7.346

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 28

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus44


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus44 Total 0.00 6.090 0.00 105.75 106.03 5.986 5.986 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus44 56.36 6.057 55.55 105.69 105.95 5.970 5.986 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-105 Bus44 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus42 MCC 56.46 0.015 55.60 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 56.52 0.017 55.63 105.73 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 56.49 0.017 55.62 105.72 105.98 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus58 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.60 0.022 55.67 105.74 106.01 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus86 MCC 56.90 0.140 55.83 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.72 105.75 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.02 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.775 5.986 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.090 5.986 5.233 6.046
Peak Current (kA), Method C : 9.701 9.536 8.337 9.631
Breaking Current (kA, rms, symm) : 5.986 5.233 6.046
Steady State Current (kA, rms) : 5.876 5.986 5.233 6.046

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 29

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus49


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus49 Total 0.00 6.090 0.00 105.75 106.03 5.986 5.986 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus49 56.36 6.057 55.55 105.69 105.95 5.970 5.986 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-106 Bus49 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus42 MCC 56.46 0.015 55.60 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 56.52 0.017 55.63 105.73 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 56.49 0.017 55.62 105.72 105.98 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus58 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.60 0.022 55.67 105.74 106.01 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus86 MCC 56.90 0.140 55.83 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.72 105.75 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.02 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.775 5.986 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.090 5.986 5.233 6.046
Peak Current (kA), Method C : 9.701 9.536 8.337 9.631
Breaking Current (kA, rms, symm) : 5.986 5.233 6.046
Steady State Current (kA, rms) : 5.876 5.986 5.233 6.046

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 30

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus51


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus51 Total 0.00 6.090 0.00 105.75 106.03 5.986 5.986 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus51 56.36 6.057 55.55 105.69 105.95 5.970 5.986 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-107 Bus51 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus42 MCC 56.46 0.015 55.60 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 56.52 0.017 55.63 105.73 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 56.49 0.017 55.62 105.72 105.98 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus58 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.60 0.022 55.67 105.74 106.01 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus86 MCC 56.90 0.140 55.83 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.72 105.75 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.02 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.775 5.986 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.090 5.986 5.233 6.046
Peak Current (kA), Method C : 9.701 9.536 8.337 9.631
Breaking Current (kA, rms, symm) : 5.986 5.233 6.046
Steady State Current (kA, rms) : 5.876 5.986 5.233 6.046

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 31

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus53


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus53 Total 0.00 6.092 0.00 105.76 106.05 5.988 5.988 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus53 56.36 6.056 55.55 105.70 105.95 5.969 5.988 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-108 Bus53 105.00 0.036 105.00 105.00 105.00 0.018 0.000 2.91E+005 3.27E+005

Bus42 MCC 56.45 0.015 55.60 105.72 105.98 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 56.50 0.015 55.62 105.73 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 56.50 0.015 55.62 105.73 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 56.50 0.015 55.62 105.73 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus55 MCC 56.49 0.017 55.61 105.72 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 56.50 0.015 55.62 105.73 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus58 MCC 56.50 0.015 55.62 105.73 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.59 0.022 55.67 105.74 106.02 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.70 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.70 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.70 105.95 0.000 0.000

Bus86 MCC 56.89 0.140 55.82 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.71 105.76 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.03 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.70 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.776 5.988 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.092 5.988 5.235 6.048
Peak Current (kA), Method C : 9.706 9.539 8.340 9.635
Breaking Current (kA, rms, symm) : 5.988 5.235 6.048
Steady State Current (kA, rms) : 5.876 5.988 5.235 6.048

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 32

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus55


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus55 Total 0.00 6.687 0.00 105.81 106.12 6.564 6.564 1.41E+003 1.92E+003 1.46E+003 2.00E+003

MCC Bus55 51.57 6.650 50.76 105.76 106.04 6.546 6.564 1.42E+003 1.93E+003 1.46E+003 2.00E+003

P-502 Bus55 105.00 0.036 105.00 105.00 105.00 0.018 0.000 2.91E+005 3.27E+005

Bus42 MCC 51.68 0.017 50.81 105.78 106.07 0.009 0.000 3.23E+005 3.63E+005

Bus44 MCC 51.73 0.017 50.84 105.79 106.08 0.009 0.000 3.23E+005 3.63E+005

Bus49 MCC 51.73 0.017 50.84 105.79 106.08 0.009 0.000 3.23E+005 3.63E+005

Bus51 MCC 51.73 0.017 50.84 105.79 106.08 0.009 0.000 3.23E+005 3.63E+005

Bus53 MCC 51.74 0.019 50.85 105.79 106.09 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 51.73 0.017 50.84 105.79 106.08 0.009 0.000 3.23E+005 3.63E+005

Bus58 MCC 51.73 0.017 50.84 105.79 106.08 0.009 0.000 3.23E+005 3.63E+005

Bus60 MCC 51.98 0.024 50.97 105.84 106.15 0.012 0.000 2.16E+005 2.63E+005

Bus62 MCC 51.83 0.024 50.89 105.81 106.11 0.012 0.000 2.15E+005 2.62E+005

TD-100 MCC 51.57 0.000 50.76 105.76 106.04 0.000 0.000

Bus63 MCC 51.57 0.000 50.76 105.76 106.04 0.000 0.000

Bus64 MCC 51.57 0.000 50.76 105.76 106.04 0.000 0.000

Bus86 MCC 52.16 0.154 51.06 105.86 106.21 0.080 0.000 2.26E+004 4.78E+004

Bus65 MCC 51.92 0.057 50.94 105.82 106.14 0.029 0.000 7.70E+004 1.21E+005

Bus66 MCC 51.87 0.038 50.91 105.81 106.12 0.020 0.000 1.23E+005 1.72E+005

Bus68 MCC 51.57 0.000 50.76 105.76 106.04 0.000 0.000

Bus1 Bus24 105.00 6.238 105.00 105.00 105.00 6.334 6.564 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.687 6.564 5.743 6.635
Peak Current (kA), Method C : 10.673 10.477 9.166 10.590
Breaking Current (kA, rms, symm) : 6.564 5.743 6.635
Steady State Current (kA, rms) : 6.434 6.564 5.743 6.635

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 33

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus56


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus56 Total 0.00 6.090 0.00 105.75 106.03 5.986 5.986 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus56 56.36 6.057 55.55 105.69 105.95 5.970 5.986 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-503 Bus56 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus42 MCC 56.46 0.015 55.60 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 56.52 0.017 55.63 105.73 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 56.49 0.017 55.62 105.72 105.98 0.009 0.000 2.92E+005 3.28E+005

Bus58 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.60 0.022 55.67 105.74 106.01 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus86 MCC 56.90 0.140 55.83 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.72 105.75 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.02 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.775 5.986 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.090 5.986 5.233 6.046
Peak Current (kA), Method C : 9.701 9.536 8.337 9.631
Breaking Current (kA, rms, symm) : 5.986 5.233 6.046
Steady State Current (kA, rms) : 5.876 5.986 5.233 6.046

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 34

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus58


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus58 Total 0.00 6.090 0.00 105.75 106.03 5.986 5.986 1.56E+003 2.10E+003 1.61E+003 2.18E+003

MCC Bus58 56.36 6.057 55.55 105.69 105.95 5.970 5.986 1.57E+003 2.12E+003 1.61E+003 2.18E+003

P-504 Bus58 99.75 0.033 99.75 99.75 99.75 0.017 0.000 3.22E+005 3.62E+005

Bus42 MCC 56.46 0.015 55.60 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 56.52 0.017 55.63 105.73 105.99 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 56.49 0.017 55.62 105.72 105.98 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 56.50 0.015 55.62 105.72 105.99 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 56.73 0.022 55.74 105.77 106.05 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 56.60 0.022 55.67 105.74 106.01 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus63 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus64 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus86 MCC 56.90 0.140 55.83 105.79 106.11 0.073 0.000 2.26E+004 4.78E+004

Bus65 MCC 56.68 0.052 55.72 105.75 106.04 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 56.63 0.035 55.69 105.75 106.02 0.018 0.000 1.23E+005 1.72E+005

Bus68 MCC 56.36 0.000 55.55 105.69 105.95 0.000 0.000

Bus1 Bus24 105.00 5.680 105.00 105.00 105.00 5.775 5.986 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.090 5.986 5.233 6.046
Peak Current (kA), Method C : 9.701 9.536 8.337 9.631
Breaking Current (kA, rms, symm) : 5.986 5.233 6.046
Steady State Current (kA, rms) : 5.876 5.986 5.233 6.046

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 35

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus60


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus60 Total 0.00 4.231 0.00 105.67 105.93 4.167 4.167 2.28E+003 3.00E+003 2.35E+003 3.10E+003

MCC Bus60 71.39 4.184 70.68 105.52 105.70 4.143 4.167 2.31E+003 3.03E+003 2.35E+003 3.10E+003

P-505 Bus60 105.00 0.047 105.00 105.00 105.00 0.024 0.000 2.14E+005 2.61E+005

Bus42 MCC 71.45 0.011 70.72 105.53 105.71 0.005 0.000 3.23E+005 3.63E+005

Bus44 MCC 71.48 0.011 70.73 105.54 105.72 0.005 0.000 3.23E+005 3.63E+005

Bus49 MCC 71.48 0.011 70.73 105.54 105.72 0.005 0.000 3.23E+005 3.63E+005

Bus51 MCC 71.48 0.011 70.73 105.54 105.72 0.005 0.000 3.23E+005 3.63E+005

Bus53 MCC 71.49 0.012 70.74 105.54 105.73 0.006 0.000 2.92E+005 3.28E+005

Bus55 MCC 71.47 0.012 70.73 105.54 105.72 0.006 0.000 2.92E+005 3.28E+005

Bus56 MCC 71.48 0.011 70.73 105.54 105.72 0.005 0.000 3.23E+005 3.63E+005

Bus58 MCC 71.48 0.011 70.73 105.54 105.72 0.005 0.000 3.23E+005 3.63E+005

Bus62 MCC 71.55 0.015 70.77 105.55 105.74 0.008 0.000 2.15E+005 2.62E+005

TD-100 MCC 71.39 0.000 70.68 105.52 105.70 0.000 0.000

Bus63 MCC 71.39 0.000 70.68 105.52 105.70 0.000 0.000

Bus64 MCC 71.39 0.000 70.68 105.52 105.70 0.000 0.000

Bus86 MCC 71.76 0.097 70.87 105.58 105.81 0.051 0.000 2.26E+004 4.78E+004

Bus65 MCC 71.61 0.036 70.80 105.56 105.76 0.018 0.000 7.70E+004 1.21E+005

Bus66 MCC 71.57 0.024 70.78 105.55 105.75 0.012 0.000 1.23E+005 1.72E+005

Bus68 MCC 71.39 0.000 70.68 105.52 105.70 0.000 0.000

Bus1 Bus24 105.00 3.928 105.00 105.00 105.00 4.011 4.167 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.231 4.167 3.639 4.204
Peak Current (kA), Method C : 6.702 6.600 5.764 6.659
Breaking Current (kA, rms, symm) : 4.167 3.639 4.204
Steady State Current (kA, rms) : 4.098 4.167 3.639 4.204

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 36

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus62


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus62 Total 0.00 5.604 0.00 105.76 106.04 5.509 5.509 1.70E+003 2.28E+003 1.76E+003 2.37E+003

MCC Bus62 60.33 5.557 59.55 105.66 105.89 5.485 5.509 1.72E+003 2.30E+003 1.76E+003 2.37E+003

P-600 Bus62 105.00 0.047 105.00 105.00 105.00 0.024 0.000 2.14E+005 2.61E+005

Bus42 MCC 60.42 0.014 59.59 105.67 105.92 0.007 0.000 3.23E+005 3.63E+005

Bus44 MCC 60.46 0.014 59.61 105.68 105.93 0.007 0.000 3.23E+005 3.63E+005

Bus49 MCC 60.46 0.014 59.61 105.68 105.93 0.007 0.000 3.23E+005 3.63E+005

Bus51 MCC 60.46 0.014 59.61 105.68 105.93 0.007 0.000 3.23E+005 3.63E+005

Bus53 MCC 60.48 0.016 59.62 105.69 105.93 0.008 0.000 2.92E+005 3.28E+005

Bus55 MCC 60.45 0.016 59.61 105.68 105.93 0.008 0.000 2.92E+005 3.28E+005

Bus56 MCC 60.46 0.014 59.61 105.68 105.93 0.007 0.000 3.23E+005 3.63E+005

Bus58 MCC 60.46 0.014 59.61 105.68 105.93 0.007 0.000 3.23E+005 3.63E+005

Bus60 MCC 60.67 0.020 59.72 105.72 105.99 0.010 0.000 2.16E+005 2.63E+005

TD-100 MCC 60.33 0.000 59.55 105.66 105.89 0.000 0.000

Bus63 MCC 60.33 0.000 59.55 105.66 105.89 0.000 0.000

Bus64 MCC 60.33 0.000 59.55 105.66 105.89 0.000 0.000

Bus86 MCC 60.83 0.129 59.80 105.74 106.04 0.067 0.000 2.26E+004 4.78E+004

Bus65 MCC 60.63 0.047 59.70 105.71 105.98 0.024 0.000 7.70E+004 1.21E+005

Bus66 MCC 60.58 0.032 59.67 105.70 105.96 0.017 0.000 1.23E+005 1.72E+005

Bus68 MCC 60.33 0.000 59.55 105.66 105.89 0.000 0.000

Bus1 Bus24 105.00 5.217 105.00 105.00 105.00 5.310 5.509 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 5.604 5.509 4.816 5.564
Peak Current (kA), Method C : 8.915 8.763 7.661 8.850
Breaking Current (kA, rms, symm) : 5.509 4.816 5.564
Steady State Current (kA, rms) : 5.407 5.509 4.816 5.564

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 37

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus63


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus63 Total 0.00 10.148 0.00 106.08 106.53 9.896 9.896 8.99E+002 1.29E+003 9.46E+002 1.36E+003

MCC Bus63 23.61 10.148 23.02 106.08 106.53 9.896 9.896 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus42 MCC 23.76 0.025 23.10 106.11 106.58 0.013 0.000 3.23E+005 3.63E+005

Bus44 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus49 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus51 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus53 MCC 23.87 0.028 23.15 106.13 106.61 0.014 0.000 2.92E+005 3.28E+005

Bus55 MCC 23.82 0.028 23.13 106.12 106.60 0.014 0.000 2.92E+005 3.28E+005

Bus56 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus58 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus60 MCC 24.23 0.036 23.34 106.20 106.71 0.018 0.000 2.16E+005 2.63E+005

Bus62 MCC 24.00 0.036 23.22 106.16 106.65 0.018 0.000 2.15E+005 2.62E+005

TD-100 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus64 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus86 MCC 24.51 0.234 23.48 106.23 106.80 0.121 0.000 2.26E+004 4.78E+004

Bus65 MCC 24.14 0.086 23.29 106.18 106.69 0.044 0.000 7.70E+004 1.21E+005

Bus66 MCC 24.06 0.058 23.25 106.17 106.66 0.030 0.000 1.23E+005 1.72E+005

Bus68 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus1 Bus24 104.99 9.492 105.00 105.00 105.00 9.561 9.896 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 10.148 9.896 8.689 10.043
Peak Current (kA), Method C : 16.386 15.979 14.030 16.216
Breaking Current (kA, rms, symm) : 9.896 8.689 10.043
Steady State Current (kA, rms) : 9.632 9.896 8.689 10.043

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 38

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus64


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus64 Total 0.00 7.385 0.00 105.80 106.11 7.251 7.251 1.27E+003 1.75E+003 1.32E+003 1.82E+003

MCC Bus64 45.82 7.385 44.99 105.80 106.11 7.251 7.251 1.27E+003 1.75E+003 1.32E+003 1.82E+003

Bus42 MCC 45.93 0.019 45.04 105.83 106.14 0.009 0.000 3.23E+005 3.63E+005

Bus44 MCC 45.99 0.019 45.07 105.84 106.16 0.009 0.000 3.23E+005 3.63E+005

Bus49 MCC 45.99 0.019 45.07 105.84 106.16 0.009 0.000 3.23E+005 3.63E+005

Bus51 MCC 45.99 0.019 45.07 105.84 106.16 0.009 0.000 3.23E+005 3.63E+005

Bus53 MCC 46.01 0.021 45.08 105.84 106.16 0.010 0.000 2.92E+005 3.28E+005

Bus55 MCC 45.98 0.021 45.07 105.83 106.15 0.010 0.000 2.92E+005 3.28E+005

Bus56 MCC 45.99 0.019 45.07 105.84 106.16 0.009 0.000 3.23E+005 3.63E+005

Bus58 MCC 45.99 0.019 45.07 105.84 106.16 0.009 0.000 3.23E+005 3.63E+005

Bus60 MCC 46.27 0.026 45.22 105.89 106.23 0.014 0.000 2.16E+005 2.63E+005

Bus62 MCC 46.10 0.027 45.13 105.86 106.19 0.014 0.000 2.15E+005 2.62E+005

TD-100 MCC 45.82 0.000 44.99 105.80 106.11 0.000 0.000

Bus63 MCC 45.82 0.000 44.99 105.80 106.11 0.000 0.000

Bus86 MCC 46.47 0.170 45.32 105.91 106.30 0.089 0.000 2.26E+004 4.78E+004

Bus65 MCC 46.21 0.063 45.19 105.87 106.22 0.032 0.000 7.70E+004 1.21E+005

Bus66 MCC 46.15 0.042 45.15 105.87 106.20 0.022 0.000 1.23E+005 1.72E+005

Bus68 MCC 45.82 0.000 44.99 105.80 106.11 0.000 0.000

Bus1 Bus24 105.00 6.908 105.00 105.00 105.00 7.006 7.251 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.385 7.251 6.344 7.329
Peak Current (kA), Method C : 11.816 11.602 10.150 11.726
Breaking Current (kA, rms, symm) : 7.251 6.344 7.329
Steady State Current (kA, rms) : 7.108 7.251 6.344 7.329

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 39

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus65


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus65 Total 0.00 7.461 0.00 106.00 106.43 7.289 7.289 1.25E+003 1.73E+003 1.32E+003 1.82E+003

MCC Bus65 45.60 7.350 44.87 105.88 106.23 7.233 7.289 1.28E+003 1.76E+003 1.32E+003 1.82E+003

TOMA Bus65 105.00 0.112 105.00 105.00 105.00 0.057 0.000 7.64E+004 1.21E+005
HIDROLAVORA

Bus42 MCC 45.71 0.019 44.93 105.90 106.26 0.009 0.000 3.23E+005 3.63E+005

Bus44 MCC 45.77 0.019 44.96 105.91 106.27 0.009 0.000 3.23E+005 3.63E+005

Bus49 MCC 45.77 0.019 44.96 105.91 106.27 0.009 0.000 3.23E+005 3.63E+005

Bus51 MCC 45.77 0.019 44.96 105.91 106.27 0.009 0.000 3.23E+005 3.63E+005

Bus53 MCC 45.79 0.021 44.97 105.92 106.28 0.010 0.000 2.92E+005 3.28E+005

Bus55 MCC 45.76 0.021 44.95 105.91 106.27 0.010 0.000 2.92E+005 3.28E+005

Bus56 MCC 45.77 0.019 44.96 105.91 106.27 0.009 0.000 3.23E+005 3.63E+005

Bus58 MCC 45.77 0.019 44.96 105.91 106.27 0.009 0.000 3.23E+005 3.63E+005

Bus60 MCC 46.05 0.027 45.10 105.97 106.35 0.014 0.000 2.16E+005 2.63E+005

Bus62 MCC 45.88 0.027 45.02 105.93 106.31 0.014 0.000 2.15E+005 2.62E+005

TD-100 MCC 45.60 0.000 44.87 105.88 106.23 0.000 0.000

Bus63 MCC 45.60 0.000 44.87 105.88 106.23 0.000 0.000

Bus64 MCC 45.60 0.000 44.87 105.88 106.23 0.000 0.000

Bus86 MCC 46.25 0.171 45.21 105.99 106.42 0.089 0.000 2.26E+004 4.78E+004

Bus66 MCC 45.93 0.043 45.04 105.94 106.32 0.022 0.000 1.23E+005 1.72E+005

Bus68 MCC 45.60 0.000 44.87 105.88 106.23 0.000 0.000

Bus1 Bus24 105.00 6.934 105.00 105.00 105.00 7.019 7.289 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.461 7.289 6.394 7.390
Peak Current (kA), Method C : 11.944 11.668 10.235 11.830
Breaking Current (kA, rms, symm) : 7.289 6.394 7.390
Steady State Current (kA, rms) : 7.108 7.289 6.394 7.390

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 40

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus66


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus66 Total 0.00 6.716 0.00 105.89 106.26 6.579 6.579 1.41E+003 1.92E+003 1.46E+003 2.00E+003

MCC Bus66 51.49 6.640 50.72 105.79 106.09 6.540 6.579 1.42E+003 1.94E+003 1.46E+003 2.00E+003

TOMAS Bus66 105.00 0.076 105.00 105.00 105.00 0.039 0.000 1.23E+005 1.72E+005
INDUSTRIALES
SCHUKO

Bus42 MCC 51.60 0.017 50.77 105.81 106.11 0.009 0.000 3.23E+005 3.63E+005

Bus44 MCC 51.65 0.017 50.80 105.82 106.13 0.009 0.000 3.23E+005 3.63E+005

Bus49 MCC 51.65 0.017 50.80 105.82 106.13 0.009 0.000 3.23E+005 3.63E+005

Bus51 MCC 51.65 0.017 50.80 105.82 106.13 0.009 0.000 3.23E+005 3.63E+005

Bus53 MCC 51.66 0.019 50.81 105.82 106.13 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 51.64 0.019 50.79 105.82 106.13 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 51.65 0.017 50.80 105.82 106.13 0.009 0.000 3.23E+005 3.63E+005

Bus58 MCC 51.65 0.017 50.80 105.82 106.13 0.009 0.000 3.23E+005 3.63E+005

Bus60 MCC 51.90 0.024 50.93 105.87 106.20 0.012 0.000 2.16E+005 2.63E+005

Bus62 MCC 51.75 0.024 50.85 105.84 106.16 0.012 0.000 2.15E+005 2.62E+005

TD-100 MCC 51.49 0.000 50.72 105.79 106.09 0.000 0.000

Bus63 MCC 51.49 0.000 50.72 105.79 106.09 0.000 0.000

Bus64 MCC 51.49 0.000 50.72 105.79 106.09 0.000 0.000

Bus86 MCC 52.08 0.154 51.02 105.89 106.26 0.080 0.000 2.26E+004 4.78E+004

Bus65 MCC 51.84 0.057 50.90 105.85 106.19 0.029 0.000 7.70E+004 1.21E+005

Bus68 MCC 51.49 0.000 50.72 105.79 106.09 0.000 0.000

Bus1 Bus24 105.00 6.247 105.00 105.00 105.00 6.338 6.579 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.716 6.579 5.762 6.658
Peak Current (kA), Method C : 10.722 10.503 9.199 10.630
Breaking Current (kA, rms, symm) : 6.579 5.762 6.658
Steady State Current (kA, rms) : 6.434 6.579 5.762 6.658

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 41

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus67


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus67 Total 0.00 2.767 0.00 91.96 93.23 3.575 3.575 3.03E+002 5.76E+003 3.03E+002 2.12E+003

Gen1 Bus67 105.00 2.767 105.00 105.00 105.00 3.575 3.575 3.03E+002 5.76E+003 3.03E+002 2.12E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 2.767 3.575 2.457 3.404
Peak Current (kA), Method C : 6.437 8.316 5.714 7.917
Breaking Current (kA, rms, symm) : 3.575 2.457 3.404
Steady State Current (kA, rms) : 0.901 3.575 2.457 3.404

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 42

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus68


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus68 Total 0.00 6.203 0.00 105.68 105.93 6.108 6.108 1.53E+003 2.07E+003 1.58E+003 2.14E+003

MCC Bus68 55.31 6.203 54.47 105.68 105.93 6.108 6.108 1.53E+003 2.07E+003 1.58E+003 2.14E+003

Bus42 MCC 55.41 0.016 54.52 105.70 105.95 0.008 0.000 3.23E+005 3.63E+005

Bus44 MCC 55.46 0.016 54.54 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus49 MCC 55.46 0.016 54.54 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus51 MCC 55.46 0.016 54.54 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus53 MCC 55.47 0.017 54.55 105.71 105.97 0.009 0.000 2.92E+005 3.28E+005

Bus55 MCC 55.45 0.017 54.54 105.71 105.96 0.009 0.000 2.92E+005 3.28E+005

Bus56 MCC 55.46 0.016 54.54 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus58 MCC 55.46 0.016 54.54 105.71 105.97 0.008 0.000 3.23E+005 3.63E+005

Bus60 MCC 55.69 0.022 54.66 105.75 106.03 0.011 0.000 2.16E+005 2.63E+005

Bus62 MCC 55.56 0.022 54.59 105.73 105.99 0.011 0.000 2.15E+005 2.62E+005

TD-100 MCC 55.31 0.000 54.47 105.68 105.93 0.000 0.000

Bus63 MCC 55.31 0.000 54.47 105.68 105.93 0.000 0.000

Bus64 MCC 55.31 0.000 54.47 105.68 105.93 0.000 0.000

Bus86 MCC 55.86 0.143 54.75 105.77 106.09 0.075 0.000 2.26E+004 4.78E+004

Bus65 MCC 55.64 0.053 54.64 105.74 106.02 0.027 0.000 7.70E+004 1.21E+005

Bus66 MCC 55.59 0.036 54.61 105.73 106.01 0.018 0.000 1.23E+005 1.72E+005

Bus1 Bus24 105.00 5.802 105.00 105.00 105.00 5.901 6.108 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 6.203 6.108 5.335 6.162
Peak Current (kA), Method C : 9.887 9.736 8.503 9.822
Breaking Current (kA, rms, symm) : 6.108 5.335 6.162
Steady State Current (kA, rms) : 6.006 6.108 5.335 6.162

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 43

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus70


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus70 Total 0.00 7.811 0.00 105.85 106.17 7.661 7.661 1.20E+003 1.66E+003 1.24E+003 1.73E+003

TD-100 Bus70 24.23 7.811 23.76 105.85 106.17 7.661 7.661 1.20E+003 1.66E+003 1.24E+003 1.73E+003

MCC TD-100 42.40 7.811 41.59 105.85 106.17 7.661 7.661 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus72 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus73 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus75 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus77 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus79 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus81 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus83 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus85 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

Bus84 TD-100 24.23 0.000 23.76 105.85 106.17 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.811 7.661 6.706 7.748
Peak Current (kA), Method C : 12.514 12.274 10.744 12.413
Breaking Current (kA, rms, symm) : 7.661 6.706 7.748
Steady State Current (kA, rms) : 7.502 7.661 6.706 7.748

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 44

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus71


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus71 Total 0.00 8.828 0.00 105.95 106.33 8.636 8.636 1.05E+003 1.47E+003 1.09E+003 1.54E+003

TD-100 Bus71 13.69 8.828 13.39 105.95 106.33 8.636 8.636 1.05E+003 1.47E+003 1.09E+003 1.54E+003

MCC TD-100 34.23 8.828 33.49 105.95 106.33 8.636 8.636 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus70 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus72 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus73 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus75 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus77 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus79 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus81 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus83 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus85 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

Bus84 TD-100 13.69 0.000 13.39 105.95 106.33 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 8.828 8.636 7.570 8.747
Peak Current (kA), Method C : 14.191 13.884 12.169 14.062
Breaking Current (kA, rms, symm) : 8.636 7.570 8.747
Steady State Current (kA, rms) : 8.434 8.636 7.570 8.747

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 45

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus72


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus72 Total 0.00 7.385 0.00 105.80 106.11 7.251 7.251 1.27E+003 1.75E+003 1.32E+003 1.82E+003

TD-100 Bus72 28.64 7.385 28.12 105.80 106.11 7.251 7.251 1.27E+003 1.75E+003 1.32E+003 1.82E+003

MCC TD-100 45.82 7.385 44.99 105.80 106.11 7.251 7.251 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus70 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus73 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus75 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus77 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus79 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus81 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus83 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus85 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

Bus84 TD-100 28.64 0.000 28.12 105.80 106.11 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.385 7.251 6.344 7.329
Peak Current (kA), Method C : 11.816 11.602 10.150 11.726
Breaking Current (kA, rms, symm) : 7.251 6.344 7.329
Steady State Current (kA, rms) : 7.108 7.251 6.344 7.329

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 46

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus73


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus73 Total 0.00 7.004 0.00 105.76 106.05 6.883 6.883 1.34E+003 1.84E+003 1.39E+003 1.91E+003

TD-100 Bus73 32.59 7.004 32.03 105.76 106.05 6.883 6.883 1.34E+003 1.84E+003 1.39E+003 1.91E+003

MCC TD-100 48.88 7.004 48.04 105.76 106.05 6.883 6.883 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus70 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus72 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus75 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus77 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus79 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus81 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus83 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus85 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

Bus84 TD-100 32.59 0.000 32.03 105.76 106.05 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 7.004 6.883 6.018 6.953
Peak Current (kA), Method C : 11.192 10.999 9.618 11.111
Breaking Current (kA, rms, symm) : 6.883 6.018 6.953
Steady State Current (kA, rms) : 6.754 6.883 6.018 6.953

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 47

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus75


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus75 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus75 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 48

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus77


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus77 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus77 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 49

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus79


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus79 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus79 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 50

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus81


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus81 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus81 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 51

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus83


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus83 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus83 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 52

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus84


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus84 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus84 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus85 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 53

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus85


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus85 Total 0.00 4.780 0.00 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

TD-100 Bus85 55.60 4.780 54.95 105.53 105.71 4.724 4.724 2.01E+003 2.66E+003 2.06E+003 2.73E+003

MCC TD-100 66.73 4.780 65.94 105.53 105.71 4.724 4.724 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus70 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus72 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus73 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus75 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus77 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus79 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus81 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus83 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

Bus84 TD-100 55.60 0.000 54.95 105.53 105.71 0.000 0.000

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 4.780 4.724 4.118 4.756
Peak Current (kA), Method C : 7.586 7.496 6.535 7.547
Breaking Current (kA, rms, symm) : 4.724 4.118 4.756
Steady State Current (kA, rms) : 4.663 4.724 4.118 4.756

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 54

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: Bus86


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

Bus86 Total 0.00 8.990 0.00 106.28 106.93 8.717 8.717 1.02E+003 1.45E+003 1.09E+003 1.54E+003

MCC Bus86 33.69 8.690 33.21 106.09 106.58 8.565 8.717 1.07E+003 1.49E+003 1.09E+003 1.54E+003

COMPRESOR DE Bus86 105.00 0.305 105.00 105.00 105.00 0.157 0.000 2.23E+004 4.73E+004
AIRE

Bus42 MCC 33.83 0.022 33.28 106.12 106.62 0.011 0.000 3.23E+005 3.63E+005

Bus44 MCC 33.90 0.022 33.31 106.13 106.64 0.011 0.000 3.23E+005 3.63E+005

Bus49 MCC 33.90 0.022 33.31 106.13 106.64 0.011 0.000 3.23E+005 3.63E+005

Bus51 MCC 33.90 0.022 33.31 106.13 106.64 0.011 0.000 3.23E+005 3.63E+005

Bus53 MCC 33.92 0.025 33.32 106.13 106.64 0.012 0.000 2.92E+005 3.28E+005

Bus55 MCC 33.88 0.025 33.30 106.13 106.63 0.012 0.000 2.92E+005 3.28E+005

Bus56 MCC 33.90 0.022 33.31 106.13 106.64 0.011 0.000 3.23E+005 3.63E+005

Bus58 MCC 33.90 0.022 33.31 106.13 106.64 0.011 0.000 3.23E+005 3.63E+005

Bus60 MCC 34.24 0.032 33.48 106.19 106.73 0.016 0.000 2.16E+005 2.63E+005

Bus62 MCC 34.04 0.032 33.38 106.15 106.68 0.016 0.000 2.15E+005 2.62E+005

TD-100 MCC 33.69 0.000 33.21 106.09 106.58 0.000 0.000

Bus63 MCC 33.69 0.000 33.21 106.09 106.58 0.000 0.000

Bus64 MCC 33.69 0.000 33.21 106.09 106.58 0.000 0.000

Bus65 MCC 34.16 0.075 33.45 106.17 106.71 0.039 0.000 7.70E+004 1.21E+005

Bus66 MCC 34.09 0.051 33.41 106.16 106.69 0.026 0.000 1.23E+005 1.72E+005

Bus68 MCC 33.69 0.000 33.21 106.09 106.58 0.000 0.000

Bus1 Bus24 104.99 8.318 105.00 105.00 105.00 8.376 8.717 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 8.990 8.717 7.677 8.880
Peak Current (kA), Method C : 14.492 14.051 12.376 14.314
Breaking Current (kA, rms, symm) : 8.717 7.677 8.880
Steady State Current (kA, rms) : 8.434 8.717 7.677 8.880

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 55

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Fault at bus: TD-100


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

TD-100 Total 0.00 10.148 0.00 106.08 106.53 9.896 9.896 8.99E+002 1.29E+003 9.46E+002 1.36E+003

MCC TD-100 23.61 10.148 23.02 106.08 106.53 9.896 9.896 8.99E+002 1.29E+003 9.46E+002 1.36E+003

Bus71 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus70 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus72 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus73 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus75 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus77 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus79 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus81 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus83 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus85 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus84 TD-100 0.00 0.000 0.00 106.08 106.53 0.000 0.000

Bus42 MCC 23.76 0.025 23.10 106.11 106.58 0.013 0.000 3.23E+005 3.63E+005

Bus44 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus49 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus51 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus53 MCC 23.87 0.028 23.15 106.13 106.61 0.014 0.000 2.92E+005 3.28E+005

Bus55 MCC 23.82 0.028 23.13 106.12 106.60 0.014 0.000 2.92E+005 3.28E+005

Bus56 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus58 MCC 23.84 0.025 23.14 106.13 106.60 0.013 0.000 3.23E+005 3.63E+005

Bus60 MCC 24.23 0.036 23.34 106.20 106.71 0.018 0.000 2.16E+005 2.63E+005

Bus62 MCC 24.00 0.036 23.22 106.16 106.65 0.018 0.000 2.15E+005 2.62E+005

Bus63 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus64 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus86 MCC 24.51 0.234 23.48 106.23 106.80 0.121 0.000 2.26E+004 4.78E+004

Bus65 MCC 24.14 0.086 23.29 106.18 106.69 0.044 0.000 7.70E+004 1.21E+005

Bus66 MCC 24.06 0.058 23.25 106.17 106.66 0.030 0.000 1.23E+005 1.72E+005

Bus68 MCC 23.61 0.000 23.02 106.08 106.53 0.000 0.000

Bus1 Bus24 104.99 9.492 105.00 105.00 105.00 9.561 9.896 * 7.23E+002 1.09E+003 7.23E+002 1.08E+003
Project: ETAP Page: 56

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

(Cont.)

Fault at bus: TD-100


Nominal kV = 0.380
Voltage c Factor = 1.05 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"

From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0

3-Phase L-G L-L L-L-G


Initial Symmetrical Current (kA, rms) : 10.148 9.896 8.689 10.043
Peak Current (kA), Method C : 16.386 15.979 14.030 16.216
Breaking Current (kA, rms, symm) : 9.896 8.689 10.043
Steady State Current (kA, rms) : 9.632 9.896 8.689 10.043

# Indicates a fault current contribution from a three-winding transformer.


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer.
Project: ETAP Page: 57

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Short-Circuit Summary Report

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus1 11.900 4851.707 11979.910 4851.683 4851.696 11979.890 4851.696 4851.696 4201.698 10374.900 4201.698 4201.698 4851.702 11979.900 4851.702 4851.702
Bus16 0.380 0.213 0.391 0.047 0.099 0.181 0.099 0.099 0.139 0.255 0.139 0.139 0.174 0.320 0.174 0.174
Bus20 0.380 0.211 0.386 0.048 0.099 0.181 0.099 0.099 0.138 0.253 0.138 0.138 0.173 0.317 0.173 0.173
Bus22 0.380 0.035 0.051 0.035 0.035 0.051 0.035 0.035 0.031 0.044 0.031 0.031 0.035 0.051 0.035 0.035
Bus23 0.380 0.035 0.051 0.035 0.035 0.051 0.035 0.035 0.031 0.044 0.031 0.031 0.035 0.051 0.035 0.035
Bus24 0.380 13.079 21.343 12.233 12.662 20.663 12.662 12.662 11.161 18.213 11.161 11.161 12.907 21.063 12.907 12.907
Bus27 0.380 0.213 0.391 0.047 0.099 0.181 0.099 0.099 0.139 0.255 0.139 0.139 0.174 0.320 0.174 0.174
Bus28 0.380 0.211 0.386 0.048 0.099 0.181 0.099 0.099 0.138 0.253 0.138 0.138 0.173 0.317 0.173 0.173
Bus31 0.380 0.047 0.068 0.047 0.047 0.068 0.047 0.047 0.041 0.059 0.041 0.041 0.047 0.068 0.047 0.047
Bus32 0.380 0.048 0.069 0.048 0.048 0.069 0.048 0.048 0.041 0.059 0.041 0.041 0.048 0.069 0.048 0.048
Bus35 0.380 0.085 0.144 0.016 0.035 0.059 0.035 0.035 0.055 0.092 0.055 0.055 0.067 0.113 0.067 0.067
Bus36 0.380 0.084 0.143 0.016 0.035 0.059 0.035 0.035 0.054 0.092 0.054 0.054 0.066 0.112 0.066 0.066
Bus39 0.380 0.085 0.144 0.016 0.035 0.059 0.035 0.035 0.055 0.092 0.055 0.055 0.067 0.113 0.067 0.067
Bus40 0.380 0.084 0.143 0.016 0.035 0.059 0.035 0.035 0.054 0.092 0.054 0.054 0.066 0.112 0.066 0.066
Bus42 0.380 7.408 11.851 7.108 7.262 11.619 7.262 7.262 6.358 10.172 6.358 6.358 7.346 11.753 7.346 7.346
Bus44 0.380 6.090 9.701 5.876 5.986 9.536 5.986 5.986 5.233 8.337 5.233 5.233 6.046 9.631 6.046 6.046
Bus49 0.380 6.090 9.701 5.876 5.986 9.536 5.986 5.986 5.233 8.337 5.233 5.233 6.046 9.631 6.046 6.046
Bus51 0.380 6.090 9.701 5.876 5.986 9.536 5.986 5.986 5.233 8.337 5.233 5.233 6.046 9.631 6.046 6.046
Bus53 0.380 6.092 9.706 5.876 5.988 9.539 5.988 5.988 5.235 8.340 5.235 5.235 6.048 9.635 6.048 6.048
Bus55 0.380 6.687 10.673 6.434 6.564 10.477 6.564 6.564 5.743 9.166 5.743 5.743 6.635 10.590 6.635 6.635
Bus56 0.380 6.090 9.701 5.876 5.986 9.536 5.986 5.986 5.233 8.337 5.233 5.233 6.046 9.631 6.046 6.046
Bus58 0.380 6.090 9.701 5.876 5.986 9.536 5.986 5.986 5.233 8.337 5.233 5.233 6.046 9.631 6.046 6.046
Bus60 0.380 4.231 6.702 4.098 4.167 6.600 4.167 4.167 3.639 5.764 3.639 3.639 4.204 6.659 4.204 4.204
Bus62 0.380 5.604 8.915 5.407 5.509 8.763 5.509 5.509 4.816 7.661 4.816 4.816 5.564 8.850 5.564 5.564
Bus63 0.380 10.148 16.386 9.632 9.896 15.979 9.896 9.896 8.689 14.030 8.689 8.689 10.043 16.216 10.043 10.043
Bus64 0.380 7.385 11.816 7.108 7.251 11.602 7.251 7.251 6.344 10.150 6.344 6.344 7.329 11.726 7.329 7.329
Bus65 0.380 7.461 11.944 7.108 7.289 11.668 7.289 7.289 6.394 10.235 6.394 6.394 7.390 11.830 7.390 7.390
Bus66 0.380 6.716 10.722 6.434 6.579 10.503 6.579 6.579 5.762 9.199 5.762 5.762 6.658 10.630 6.658 6.658
Bus67 0.380 2.767 6.437 0.901 3.575 8.316 3.575 3.575 2.457 5.714 2.457 2.457 3.404 7.917 3.404 3.404
Bus68 0.380 6.203 9.887 6.006 6.108 9.736 6.108 6.108 5.335 8.503 5.335 5.335 6.162 9.822 6.162 6.162
Bus70 0.380 7.811 12.514 7.502 7.661 12.274 7.661 7.661 6.706 10.744 6.706 6.706 7.748 12.413 7.748 7.748
Bus71 0.380 8.828 14.191 8.434 8.636 13.884 8.636 8.636 7.570 12.169 7.570 7.570 8.747 14.062 8.747 8.747
Bus72 0.380 7.385 11.816 7.108 7.251 11.602 7.251 7.251 6.344 10.150 6.344 6.344 7.329 11.726 7.329 7.329
Bus73 0.380 7.004 11.192 6.754 6.883 10.999 6.883 6.883 6.018 9.618 6.018 6.018 6.953 11.111 6.953 6.953
Bus75 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus77 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus79 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Project: ETAP Page: 58

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

3-Phase, LG, LL, LLG Fault Currents

Bus 3-Phase Fault Line-to-Ground Fault Line-to-Line Fault *Line-to-Line-to-Ground


ID kV I"k ip Ik I"k ip Ib Ik I"k ip Ib Ik I"k ip Ib Ik

Bus81 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus83 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus84 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus85 0.380 4.780 7.586 4.663 4.724 7.496 4.724 4.724 4.118 6.535 4.118 4.118 4.756 7.547 4.756 4.756
Bus86 0.380 8.990 14.492 8.434 8.717 14.051 8.717 8.717 7.677 12.376 7.677 7.677 8.880 14.314 8.880 8.880
TD-100 0.380 10.148 16.386 9.632 9.896 15.979 9.896 9.896 8.689 14.030 8.689 8.689 10.043 16.216 10.043 10.043

All fault currents are in rms kA. Current ip is calculated using Method C.

* LLG fault current is the larger of the two faulted line currents.
Project: ETAP Page: 59

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Sequence Impedance Summary Report

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus1 11.900 0.00016 0.00155 0.00156 0.00015 0.00155 0.00156 0.00015 0.00155 0.00156 0.00000 0.00000 0.00000

Bus16 0.380 0.68196 0.83712 1.07974 1.05781 1.43820 1.78533 4.85933 0.01323 4.85935 0.00000 0.00000 0.00000

Bus20 0.380 0.69420 0.84289 1.09196 1.07164 1.43928 1.79442 4.84863 0.00000 4.84863 0.00000 0.00000 0.00000

Bus22 0.380 6.51282 0.01323 6.51283 6.51282 0.01323 6.51283 6.51282 0.01323 6.51283 0.00000 0.00000 0.00000

Bus23 0.380 6.50212 0.00000 6.50212 6.50212 0.00000 6.50212 6.50212 0.00000 6.50212 0.00000 0.00000 0.00000

Bus24 0.380 0.00977 0.01465 0.01761 0.00991 0.01519 0.01814 0.01044 0.01567 0.01883 0.00000 0.00000 0.00000

Bus27 0.380 0.68189 0.83716 1.07972 1.05760 1.43829 1.78527 4.86040 0.01455 4.86042 0.00000 0.00000 0.00000

Bus28 0.380 0.69534 0.84350 1.09316 1.07281 1.43947 1.79527 4.84863 0.00000 4.84863 0.00000 0.00000 0.00000

Bus31 0.380 4.86040 0.01455 4.86042 4.86040 0.01455 4.86042 4.86040 0.01455 4.86042 0.00000 0.00000 0.00000

Bus32 0.380 4.84863 0.00000 4.84863 4.84863 0.00000 4.84863 4.84863 0.00000 4.84863 0.00000 0.00000 0.00000

Bus35 0.380 1.88052 1.95786 2.71470 2.76238 3.69897 4.61661 14.23441 0.01455 14.23442 0.00000 0.00000 0.00000

Bus36 0.380 1.89318 1.96530 2.72884 2.77713 3.70173 4.62766 14.22264 0.00000 14.22264 0.00000 0.00000 0.00000

Bus39 0.380 1.88052 1.95786 2.71470 2.76238 3.69897 4.61661 14.23441 0.01455 14.23442 0.00000 0.00000 0.00000

Bus40 0.380 1.89318 1.96530 2.72884 2.77713 3.70173 4.62766 14.22264 0.00000 14.22264 0.00000 0.00000 0.00000

Bus42 0.380 0.01828 0.02515 0.03110 0.01843 0.02574 0.03166 0.01901 0.02625 0.03241 0.00000 0.00000 0.00000

Bus44 0.380 0.02253 0.03039 0.03783 0.02268 0.03101 0.03842 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus49 0.380 0.02253 0.03039 0.03783 0.02268 0.03101 0.03842 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus51 0.380 0.02253 0.03039 0.03783 0.02268 0.03101 0.03842 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus53 0.380 0.02252 0.03037 0.03781 0.02267 0.03100 0.03841 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus55 0.380 0.02040 0.02776 0.03445 0.02055 0.02837 0.03503 0.02115 0.02889 0.03580 0.00000 0.00000 0.00000

Bus56 0.380 0.02253 0.03039 0.03783 0.02268 0.03101 0.03842 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus58 0.380 0.02253 0.03039 0.03783 0.02268 0.03101 0.03842 0.02329 0.03154 0.03920 0.00000 0.00000 0.00000

Bus60 0.380 0.03299 0.04330 0.05444 0.03320 0.04411 0.05520 0.03399 0.04476 0.05621 0.00000 0.00000 0.00000

Bus62 0.380 0.02459 0.03294 0.04110 0.02476 0.03361 0.04175 0.02543 0.03418 0.04260 0.00000 0.00000 0.00000

Bus63 0.380 0.01298 0.01862 0.02270 0.01312 0.01916 0.02322 0.01366 0.01963 0.02392 0.00000 0.00000 0.00000

Bus64 0.380 0.01833 0.02523 0.03119 0.01847 0.02577 0.03171 0.01901 0.02625 0.03241 0.00000 0.00000 0.00000

Bus65 0.380 0.01812 0.02500 0.03087 0.01831 0.02567 0.03153 0.01901 0.02625 0.03241 0.00000 0.00000 0.00000

Bus66 0.380 0.02029 0.02765 0.03430 0.02047 0.02832 0.03495 0.02115 0.02889 0.03580 0.00000 0.00000 0.00000

Bus67 0.380 0.00438 0.08313 0.08325 0.00875 0.07876 0.07924 0.00438 0.03063 0.03094 0.00000 0.00000 0.00000

Bus68 0.380 0.02208 0.02986 0.03714 0.02221 0.03040 0.03765 0.02275 0.03088 0.03835 0.00000 0.00000 0.00000

Bus70 0.380 0.01726 0.02391 0.02949 0.01740 0.02445 0.03001 0.01794 0.02493 0.03071 0.00000 0.00000 0.00000

Bus71 0.380 0.01512 0.02127 0.02610 0.01526 0.02181 0.02661 0.01580 0.02228 0.02731 0.00000 0.00000 0.00000

Bus72 0.380 0.01833 0.02523 0.03119 0.01847 0.02577 0.03171 0.01901 0.02625 0.03241 0.00000 0.00000 0.00000

Bus73 0.380 0.01940 0.02656 0.03289 0.01954 0.02710 0.03341 0.02008 0.02757 0.03411 0.00000 0.00000 0.00000
Project: ETAP Page: 60

Location: 20.0.0C Date: 14-12-2021

Contract: SN:

Engineer: Revision: Base


Study Case: SC
Filename: Planta El Alto (La Paz) Config.: Normal

Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)

ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance

Bus75 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus77 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus79 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus81 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus83 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus84 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus85 0.380 0.02904 0.03846 0.04819 0.02917 0.03900 0.04870 0.02971 0.03947 0.04940 0.00000 0.00000 0.00000

Bus86 0.380 0.01476 0.02094 0.02562 0.01501 0.02166 0.02635 0.01580 0.02228 0.02731 0.00000 0.00000 0.00000

TD-100 0.380 0.01298 0.01862 0.02270 0.01312 0.01916 0.02322 0.01366 0.01963 0.02392 0.00000 0.00000 0.00000