Professional Documents
Culture Documents
Control, Signalling and Safety Isolation: Transformers
Control, Signalling and Safety Isolation: Transformers
Control, Signalling and Safety Isolation: Transformers
IP 2x or xxB up to 400 VA
IP xxA above 400 VA - IK 04
Conform to IEC/EN 61558-2-2 and 2-4 or 2-6
UL506 and CSA C22-2-N°66
Products suitable for building into equipment conforming to EN 61131-2, EN 60204-1 and EN 60439-1 standards
Insulated covers up to 1 000 VA provided
Interference/disturbance filter included
Screw fix to mounting plate or clip on to DIN rail up to 250 VA
Supplied with 0V/Earth connection link up to 1 000 VA
Pack Cat. Nos. Single phase Pack Cat. Nos. Single phase
Primary : 230-400 V ± 15 V Safety isolating transformers
Secondary : 24-48 V
Supplied with 2 links Primary : 230-400 V ± 15 V
Power in VA Admissible Secondary : 115-230 V
instantaneous Supplied with 2 links
according to according power
IEC and CSA to UL at cos ϕ = 0·5 Power in VA Admissible
instananeous
1 0442 31 40 40 52 according to according power
IEC and CSA to UL at cos ϕ = 0·5
1 0442 32 63 63 87 24 V 48 V
1 0442 33 100 100 150 1 0442 61 40 40 50
1 0442 34 160 140 250 1 0442 62 63 63 86
1 0442 35 250 210 420 1 0442 63 100 100 150
1 0442 36 400 300 900 1 0442 64 160 140 250
1 0442 37 630 500 1 700 1 0442 65 250 210 430
1 0442 38 1 000 700 2 000 1 0442 66 400 300 1 200
1 0442 39 1 600 700 8 500 1 0442 67 630 500 1 600
1 0442 40 2 500 1 400 3 300 1 0442 68 1 000 700 2 000
1 0442 69 1 600 700 6 100
1 0442 70 2 500 1 300 7 100
Secondary protection 1 0442 71 4 000 2 400 11 400
Transformers can be protected by a gG type fuse
or by a C type circuit breaker
(p. 91 and 79)
106
■ Dimensions ■ Fixing
On perforated plates Lina 25 and on Lina 12.5 plates, see p. 23
Fig. 1 : 40 to 400 VA Fig. 2 : 630 to 1 000 VA On symmetrical rail 4 up to 250 VA
fixing centres pitch 25 mm up to 1 000 VA
F
F Ø
Ø
6
C G
C G
B B
A A
Oblong fixings :
Attachment at
3 points possible
A
Dimensions Fixing(1)
Cat. Nos. Power Fig. (mm) (mm) Weight
(VA) (Kg)
A B C F G Ø
0442 31/61 40 1 94 78 113 50 100 5·2 1·23
0442 32/62 63 1 94 85 113 50 100 5·2 1·56
B
B 0442 33/63 100 1 94 94 113 50 100 5·2 1·95
0442 34/64 160 1 94 112 113 50 100 5·2 2·6
Ø 0442 35/65 250 1 106 123 115 50 100 5·2 3·82
Ø 0442 36/66 400 1 120 140 140 62·5 125 5·2 5·62
0442 37/67 630 2 150 158 206 100 175 7 9·9
G G 0442 38/68 1 000 2 150 199 206 100 175 7 14·9
C
F
Note : 40-250 VA transformers have juxtaposed windings with an insulated barrier to provide
■ Electrical characteristics insulation and interference filtering. Higher ratings have an electrostatic screen
between windings
Single phase 50-60 Hz - Class 1 (1) Up to 250 VA may be fixed to symmetrical 4 DIN rail
Insulation voltage between windings : 4 510 V
Maximum ambient operating temperatures : 50 °C without derating
Voltage adjustment
O O O O O O O O O O O O O O O
+ 15 V 0V – 15 V 230 V 400 V + 15 V 0V – 15 V 230 V 400 V + 15 V 0V – 15 V 230 V 400 V
U supply (U1) U supply (U1) U supply (U1)
1) if U1 > 230 or 400 V if U1 = 230 or 400 V with load I2 = I2n if U1 < 230 or 400 V with load I2 = I2n
2) if I2 < I2n (if the load is less than the nominal load reduce
the secondary voltage)
107
0428 99
Connection strip
supplied up to 450 VA
Pack Cat. Nos. Single phase Pack Cat. Nos. Single phase
Safety isolating transformers Isolating transformers
Primary : 230-400 V Primary : 230-400 V
Secondary : 12-24 V Secondary : 115 V
Power in VA Admissible With centre tap
according to instantaneous power Power in VA Admissible
IEC/EN at cos ϕ 0·5 according to instantaneous power
1 0428 40 40 VA 55 IEC/EN at cos 0·5
1 0428 41 63 VA 91 1 6423 62 63 VA 91
1 0428 42 100 VA 140 1 6423 63 100 VA 140
1 0428 43 160 VA 205 1 6423 64 160 VA 205
1 0428 44 220 VA 290 1 6423 65 220 VA 290
1 0428 45 310 VA 345 1 6423 66 310 VA 345
1 0428 47 630 VA 1 520 1 6423 68 630 VA 1 520
Primary : 230-400 V Isolating transformers
Secondary : 24 V Primary : 230-400 V
Power in VA Admissible Secondary : 115-230 V
according to instantaneous power Power in VA Admissible
NEW IEC/EN at cos ϕ 0·5 according to instantaneous power
1 0428 55 40 VA 55 IEC/EN at cos 0·5
1 0428 56 63 VA 91 1 0427 85 40 VA 55
1 0428 57 100 VA 140 1 0427 86 63 VA 91
1 0428 58 160 VA 205 1 0427 87 100 VA 140
1 0428 59 220 VA 290 1 0427 88 160 VA 205
1 0428 60 310 VA 345 1 0427 89 220 VA 290
1 0428 61 450 VA 1 100 1 0427 90 310 VA 345
1 0428 62 630 VA 1 520 1 0427 92 630 VA 1 520
Safety isolating transformers
Primary : 230-400 V Accessories
Secondary : 24-48 V
Power in VA Admissible Clips for fixing up to 160 VA
according to
IEC/EN
instantaneous power
at cos ϕ 0·5
on to rail EN 60715 4
1 0428 70 40 VA 55 10 0044 16 Claw width 10 mm
1 0428 71 63 VA 91 Threaded hole for M4 screws
1 0428 72 100 VA 140 (Use two clips per transformer)
1 0428 73 160 VA 205 Mounting bracket
1 0428 74 220 VA 290
1 0428 75 310 VA 345 5 0428 99 DIN rail mounting bracket
1 0428 77 630 VA 1 520
Note : Other VA ratings available
on request. Please consult us
108
■ Technical information
Conform to IEC/EN 61558-2-4 for 48 V, 115 V and 230 V and IEC/EN 61558-2-6 for 12 V and 24 V secondary
Products suitable for building into equipment conforming to EN 61131-2, EN 60204-1 and EN 60439-1 standards
IP 2x or xxB up to 250 VA - IK 04
Single phase 50-60 Hz - class I
Insulation voltage : Primary/Secondary 4 470 V
Primary/Earth 2 240 V
Secondary/Earth (12 - 24 V) = 250 V ; 48, 115 and 230 V = 1 780 V
Max. ambient operating temperature : 35 °C without derating
Protected against accidental contact with live parts up to 220 VA
■ Dimensions Primary : 230 - 400 V Primary : 230 - 400 V Primary : 230 - 400 V
Secondary : 12 - 0 - 12 V Secondary : 24 - 0 - 24 V Secondary : 115 - 0 - 115 V
Fig. 1 - 40 to 220 VA 0 - 12 - 24 V 0 - 24 - 48 V 0 - 115 - 230 V
Cat. Nos. Cat. Nos. Cat. Nos.
0428 40 to 0428 47 0428 70 to 0428 77 0427 85 to 0427 92
Slotted 230 - 400 230 - 400 230 - 400
B
fixing hole
G F
C A
C
B
Ø
Ø
A
F
F G
0 12 0 24 0 115
G A P max P max P max
■ Electrical characteristics
Dimensions Fixing Total Voltage drop as
No-load Efficiency with Primary connection Secondary connection
Power (mm) (mm) Weight losses % with
Cat. Nos. loss Ucc cable mm2 cable mm2 Fig.
(VA) (kg) @ 100% %
A B C F G Ø (W) cos ϕ cos ϕ cos ϕ cos ϕ
load (W) 1 0·45 1 0·45 flexible rigid ø mm flexible rigid ø mm
Primary 230-400 V - 24 V or 2 x 12 V secondary
0428 40 40 84 70 98 40 86 4·5 0·9 3·7 13·1 18·3 12·7 0·75 0·6 15·6 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 41 63 84 77 98 40 86 4·5 1·3 4·9 16·3 13·5 10·2 0·8 0·6 11·8 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 42 100 84 86 98 40 86 4·5 1·6 6·2 21·0 10·5 8·7 0·8 0·7 9·5 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 43 160 84 104 98 40 86 4·5 2·4 9·1 31·8 8·8 7·4 0·8 0·7 7·9 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 44 220 96 115 110 40 98 4·5 3·4 12·6 40·0 6·9 6·3 0·85 0·7 6·5 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 45 310 106 123 115 50 100 5·2 3·8 14·2 54·9 7·3 6·2 0·85 0·7 8·2 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 2
0428 47 630 126 126 141 90 105 6·5 8·0 25·5 62·4 4·3 2·6 0·91 0·82 3·5 1 to 4 1 to 4 4·5 1 to 16 1 to 25 6·5 3
Primary 230-400 V - 24 V secondary
0428 55 40 84 70 98 40 86 4·5 0·9 3·7 13·1 18·3 12·7 0·75 0·58 15·6 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 56 63 84 77 98 40 86 4·5 1·3 4·9 16·3 13·5 10·2 0·79 0·64 11·8 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 57 100 84 86 98 40 86 4·5 1·6 6·2 21·0 10·5 8·7 0·83 0·68 9·5 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 58 160 84 104 98 40 86 4·5 2·4 9·1 31·8 8·8 7·4 0·83 0·69 7·9 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 59 220 96 115 110 40 98 4·5 3·4 12·6 40·0 6·9 6·3 0·85 0·71 6·5 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 60 310 106 123 115 50 100 5·2 3·82 14·2 54·9 7·3 6·2 0·85 0·72 8·2 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 2
0428 61 630 126 126 126 90 94 6·5 6·0 21·8 63·9 6·0 3·2 0·88 0·76 4·9 1 to 4 1 to 4 4·5 1 to 16 1 to 25 6·5 3
0428 62 630 126 126 141 90 105 6·5 8·0 25·5 62·4 4·3 2·6 0·91 0·82 3·5 1 to 4 1 to 4 4·5 1 to 16 1 to 25 6·5 3
Primary 230-400 V - 48 V or 2 x 24 V secondary
0428 70 40 84 77 98 40 86 4·5 1·3 3·7 12·9 18·0 12·5 0·8 0·6 15·4 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 71 63 84 86 98 40 86 4·5 1·6 4·9 16·5 13·7 10·3 0·8 0·6 11·9 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 72 100 84 104 98 40 86 4·5 2·4 6·2 21·0 10·4 8·7 0·8 0·7 9·4 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 73 160 84 104 98 40 86 4·5 2·4 9·1 31·6 8·7 7·3 0·8 0·7 7·8 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 74 220 96 115 110 40 98 4·5 3·4 12·6 39·5 6·7 6·2 0·85 0·7 6·3 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0428 75 310 106 123 115 50 100 5·2 3·8 14·2 54·9 7·3 6·2 0·85 0·7 8·2 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 2
0428 77 630 126 126 141 90 105 6·5 8·0 25·5 63·3 4·2 2·6 0·9 0·8 3·5 1 to 4 1 to 4 4·5 1 to 16 1 to 25 6·5 3
Primary 230-400 V - 115-230 V secondary
0427 85 40 84 70 98 40 86 4·5 1·0 3·7 10·9 18·5 12·7 0·75 0·58 15·7 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0427 86 63 84 77 98 40 86 4·5 1·3 4·9 15·6 12·5 9·7 0·80 0·65 11·0 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0427 87 100 84 86 98 40 86 4·5 1·6 6·2 21·1 10·7 8·9 0·83 0·68 9·7 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0427 88 160 84 104 98 40 88 4·5 2·4 9·1 32·3 8·8 7·3 0·83 0·69 7·9 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0427 89 220 96 115 110 40 98 4·5 3·4 12·6 40·1 6·8 6·2 0·85 0·71 6·4 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 1
0427 90 310 106 123 115 50 100 5·2 3·8 14·2 54·0 7·3 6·2 0·85 0·7 8·2 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 2
0427 92 630 126 126 123 90 105 6·5 7·8 25·5 64·6 4·3 2·6 0·91 0·81 3·5 1 to 4 1 to 4 4·5 1 to 4 1 to 4 4·5 3
109
In equipment containing control devices, the transformer ■ Determination of the rated power of a transformer
power depends on the maximum power required at a given For control transformers, in particular, simply start with an inrush
moment (inrush power), the permanent power, the voltage power at cos ϕ 0·5 and read the size from the table below
drop and power factor
When determining the permissible instantaneous power (inrush power) Rated
required, the following factors should always be taken into account : power Admissible instantaneous power in VA IEC/EN 61558-2-2
in VA with cos ϕ of :
• two inrush currents cannot occur at the same time IEC and CSA 0·2 0·3 0·4 0·5 0·6 0·7 0·8 0·9 1
• power factor cos ϕ equals 0·5
• at maximum, 80% of devices are supplied at the same time (this 40 90 80 72 66 61 57 53 51 53
percentage can be calculated precisely for each device) 63 160 140 130 120 110 100 90 90 90
100 240 190 170 160 150 140 130 130 140
■ Determination of the inrush power 160 480 400 350 300 270 240 220 200 190
250 830 690 590 510 450 400 360 330 310
Where a simplified calculation of the power is required, the following 1 600 1 400 1 200 1 000 900 800 800 700
400 700
formula can be used :
630 2 000 1 800 1 500 1 400 1 200 1 100 1 100 1 000 1 000
P inrush = 0·8 (ΣPm + ΣPv + Pa) 1 000 5 400 4 600 4 000 3 600 3 200 3 000 2 700 2 600 2 500
ΣPm : sum of all contactor steady state power levels (holding power) 1 600 9 000 8 000 7 200 6 600 6 100 5 700 5 400 5 300 5 600
ΣPv : sum of all power levels of indicators and LEDs(1) 2 500 7 300 6 600 6 000 5 700 5 200 4 900 4 700 4 600 5 100
Pa : inrush power of the largest contactor 4 000 34 500 28 800 24 400 17 000 16 600 16 400 14 800 13 400 12 400
Example : From the example above, an inrush of 460 VA at cos ϕ 0·5 gives a
transformer size of 250 VA
A machine tool control cabinet comprising :
• 10 contactors for 4 kW motors, with a steady state power of 8 VA
• 2 contactors for 18·5 kW motor, with a steady state power of 20 VA ■ Checking the selection
• 1 contactor for 45 kW motor, with a steady state power of 20 VA, As a precaution, make the following checks on each of your devices :
and an inrush power of 250 VA cos ϕ 0·5
• 20 remote control relays, with a steady state power of 4 VA - first calculate the sum of the steady state power for the coils and the
• 30 signalling LEDs, with a consumption of 1 VA each LEDs powered at the same time
- then apply a coefficient : use either our hypothetical figure of 80%
- ΣPm = 220 VA { (10 x 8 VA) + (2 x 20 VA) + (1 x 20 VA) + (20 x 4 VA)} of devices at steady state power, or the actual calculation for your
- ΣPv = 30 VA (30 x 1 VA) equipment
- Pa = 250 VA - the power of the chosen transformer shall be greater than or equal to
the result of the calculation
P inrush = 0·8 (220 + 30 + 250) = 400 VA at cos ϕ 0·5
(1) LED = Light Emitting Diode
V I
• Electric shock protection
- Protection against direct and indirect contact by :
110
■ Primary protection 15 m
Transformer Operation
protection Circuit protection
Minimum protection rating for primary supply of the transformer : 25 A gG
111