Professional Documents
Culture Documents
Power Quality: Limitation of Voltage Fluctuations Induced by The DER
Power Quality: Limitation of Voltage Fluctuations Induced by The DER
When the PCC is at medium voltage, the DER shall not cause step or ramp
changes in the RMS voltage at the PCC exceeding 3% of nominal and
exceeding 3% per second averaged over a period of one second.
When the PCC is at low voltage, the DER shall not cause step or ramp
changes in the RMS voltage exceeding 5% of nominal and exceeding 5%
per second averaged over a period of one second. Any exception to the limits
is subject to approval by the Area EPS operator with consideration of other
sources of RVC within the Area EPS. These RVC limits shall apply to sudden
changes due to frequent energization of transformers, frequent switching of
capacitors or from abrupt output variations caused by DER mis operation.
These RVC limits shall not apply to infrequent events such as switching,
unplanned tripping, or transformer energization related to commissioning,
fault restoration, or maintenance.
Flicker
The DER contribution (emission values) to the flicker, measured at the
PCC, shall not exceed the greater of the limits listed in Table 25. Any
exception to the limits shall be approved by the Area EPS operator with
consideration of other sources of flicker within the Area EPS.
Table 25 —Minimum individual DER flicker emission limits
EPst EPlt
0.35 0.25
95% probability value should not exceed the emission limit based on a one
week measurement period.
Assessment and measurement methods for flicker are defined in IEEE
Std 1453 . In addition, the following shall apply:
➢ EPst is the emission limit for the short-term flicker severity, Pst If not
specified differently, the Pst evaluation time is 600 s.
➢ EPlt is the emission limit for long-term flicker severity, Plt. If not
specified differently, the Plt evaluation time is 2 h. Plt can be
calculated
b) The DER shall not cause the line-to-line fundamental frequency voltage
on any portion of the Area EPS to exceed 138% of its nominal line-to-line
fundamental frequency voltage for a duration exceeding one fundamental
frequency period.
Intentional islanding
General
An intentional island can be an intentional Area EPS Island or an intentional
Local EPS Island. An intentional island that includes any portion of the Area
EPS is an intentional Area EPS Island. An intentional Area EPS island, while
islanded, shall be designed and operated in coordination with the Area EPS
operator.
An intentional island that is totally within the bounds of a Local EPS is an
intentional Local EPS island. DER that support intentional Local EPS islands,
while interconnected to an Area EPS that is not islanded, shall be subject to
all requirements for interconnection of DER to Area EPS specified in Clause
4 through 8.1 of this standard. There are two means by which an intentional
island system can transition to an islanded condition: scheduled and
unscheduled.
Scheduled intentional islands
Scheduled intentional islands are formed through DER operator or Area
EPS operator manual action or other operating dispatch means (e.g.,
Energy Management System or Automatic Generator Control action)
that trigger the transition from being in parallel and synchronized with the
Area EPS, to operation as an islanded system. Reasons for forming a
scheduled intentional island can include enhanced reliability, economic
dispatch decisions for self-supply or import/export of power with or through
the Area EPS, or pre-emptive Area EPS operator action to island ahead of
inclement weather.
a) The net active power exported across the point of common coupling
into the Area EPS is continuously maintained at a value less than 10% of
the aggregate rating of DER connected to the Local EPS prior to any
voltage disturbance, and the Local EPS disconnects from the Area EPS,
along with Local EPS load to intentionally form a Local EPS island, or
2) If any of the trip conditions described in Clause 6 are met (i.e., where
Clause 6 would allow or mandate tripping, the intentional island may
transition to intentional island mode), or
3) If the conditions of 8.1 are met (i.e., the DER detects an island and the
DER ceases to energize the Area EPS under 8.1), the intentional island
may enter intentional island mode instead of ceasing to energize the Area
EPS, provided that the intentional island does not energize any part of the
Area EPS that is outside the defined intentional island).
Reconnection of an intentional island to the Area EPS
An intentional island that has disconnected from the rest of the Area EPS
may reconnect to the rest of the Area EPS when the conditions are met at
the intentional island point of common coupling.
When the intentional island reconnects to the Area EPS, the conditions
shall be met When entering service, the DER shall not energize the Area
EPS until the applicable voltage and system frequency are within the
ranges specified in Table 4 and the permit service setting is set to
“Enabled”.
Table 4—Enter service criteria for DER of Category I, Category II, and
Category III