Benchmarking Infrastructure

PROJECT NAME Mechanization of Berth-6 at Adani Krishnapatnam Port Limited

CLIENT ADANI KRISHNAPATNAM PORT

PMC HOWE ENGINEERING PROJECTS (I) PVT LTD

CONSULTANT KALI-FL CONSULTING ENGINEERS (P) LTD. CHENNAI

DOCUMENT TITLE DESIGN CALCULATION REPORT FOR BC2 TRESTLE FOUNDATIONS

HOWE DOCUMENT
B3027-450-E-CV-DC-006
NO.
Rev. A
Consultant
OE210601-C-CS-DC-1107
Document No.

PREPARED CHECKED APPROVED


REV. BY BY BY
DATE DESCRIPTION
NO.
Init. Sign Init. Sign Init. Sign

A 04-10-2021 FIRST SUBMISSION PSR VV TGB

This Document is the property of HEPIPL. It should not be used, copied or reproduced without their written permission.
14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE DATE
FOUNDATIONS
A
REV NO
B3027-450-E-CV-DC-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: 006

CLIENT :
ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY
PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY


TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY


RRC

FOOTING DESIGN: F1
LOAD DATA FOR FOOTING DESIGN FOR TR1_BC2 (Ref. Dwg: OE210601-S-CS-GA-2029)

Column
Load Case Fx (kN) Fy (kN) Fz (kN)
Mark
1 Dead Load -0.0462 205.884 -1.5771
2 Live Load (WLK) 0 93.1392 -0.0231
3 Live Load (MAT) 0.0042 105.1229 -1.79025
TR1-A 4 Wind +Z 0.2961 438.8265 -172.8951
5 Wind +X -4.4856 0 0
6 Wind -Z -0.2961 -437.3534 172.6998
7 Wind -X 4.51605 0 0

Column
Load Case Fx (kN) Fy (kN) Fz (kN)
Mark
1 Dead Load 0.04515 237.8954 1.5792
2 Live Load (WLK) 0 93.14025 0.0231
3 Live Load (MAT) -0.00735 97.73715 -1.73775
TR1-B 4 Wind +Z -0.2961 -438.9032 -173.28255
5 Wind +X -4.4856 0 0
6 Wind -Z 0.2961 438.4464 172.3113
7 Wind -X 4.44885 0 0

Load data for the footing design @ bottom of the base plate.
Horizontal Vertical Horizontal
Node L/C Fx kN Fy kN Fz kN
101 1.0(DL+LL+ML) -0.042 404.1461 -3.39045
102 1.0(DL+WL +Z) 0.2499 644.7105 -174.4722
103 1.0(DL+WL +X) -4.5318 205.884 -1.5771
104 1.0(DL+WL -Z) -0.3423 -231.4694 171.1227
TR1-A 105 1.0(DL+WL -X) 4.46985 205.884 -1.5771
106 1.0DL+0.8(LL+ML+WL +Z) 0.19404 715.5548 -141.34386
107 1.0DL+0.8(LL+ML+WL +X) -3.63132 364.4936 -3.02778
108 1.0DL+0.8(LL+ML+WL -Z) -0.27972 14.61096 135.13206
109 1.0DL+0.8(LL+ML+WL -X) 3.57 364.4936 -3.02778
101 1.0(DL+LL+ML) 0.0378 428.7728 -0.13545
102 1.0(DL+WL +Z) -0.25095 -201.0078 -171.70335
103 1.0(DL+WL +X) -4.44045 237.8954 1.5792
104 1.0(DL+WL -Z) 0.34125 676.3418 173.8905
TR1-B 105 1.0(DL+WL -X) 4.494 237.8954 1.5792
106 1.0DL+0.8(LL+ML+WL +Z) -0.19761 39.47475 -138.41856
107 1.0DL+0.8(LL+ML+WL +X) -3.54921 390.5973 0.20748
108 1.0DL+0.8(LL+ML+WL -Z) 0.27615 741.3544 138.05652
109 1.0DL+0.8(LL+ML+WL -X) 3.59835 390.5973 0.20748

Depth of the foundation = 2.00 m


The forces are transffered from T.O.C to Bottom of footing with a leverarm (Z) of 3.0m
(Depth of foundation 2.0m + Height of the pedestal above FGL 1.0 = 3.0m)
i.e Fz x Z = Mx and Fx x Z = Mz
*All Dimensions are in meters.
Fy1 Fy2
Fz1 Fz2 B.O.BP/T.O.C
FGL 1.0

C1 C2 1.0
1.4 2.0
0.4
0.6

5.35
14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE DATE
FOUNDATIONS
A
REV NO
B3027-450-E-CV-DC-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: 006

CLIENT :
ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY
PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY


TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY


RRC

Load data for TR18 @ Bottom of the footing


Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
101 1.0(DL+LL+ML) -0.042 404.1461 -3.39045 -10.17 0.00 -0.13
102 1.0(DL+WL +Z) 0.2499 644.7105 -174.4722 -523.42 0.00 0.75
103 1.0(DL+WL +X) -4.5318 205.884 -1.5771 -4.73 0.00 -13.60
104 1.0(DL+WL -Z) -0.3423 -231.4694 171.1227 513.37 0.00 -1.03
TR1-A 105 1.0(DL+WL -X) 4.46985 205.884 -1.5771 -4.73 0.00 13.41
106 1.0DL+0.8(LL+ML+WL +Z) 0.19404 715.5548 -141.34386 -424.03 0.00 0.58
107 1.0DL+0.8(LL+ML+WL +X) -3.63132 364.4936 -3.02778 -9.08 0.00 -10.89
108 1.0DL+0.8(LL+ML+WL -Z) -0.27972 14.61096 135.13206 405.40 0.00 -0.84
109 1.0DL+0.8(LL+ML+WL -X) 3.57 364.4936 -3.02778 -9.08 0.00 10.71
101 1.0(DL+LL+ML) 0.0378 428.7728 -0.13545 -0.41 0.00 0.11
102 1.0(DL+WL +Z) -0.25095 -201.0078 -171.70335 -515.11 0.00 -0.75
103 1.0(DL+WL +X) -4.44045 237.8954 1.5792 4.74 0.00 -13.32
104 1.0(DL+WL -Z) 0.34125 676.3418 173.8905 521.67 0.00 1.02
TR1-B 105 1.0(DL+WL -X) 4.494 237.8954 1.5792 4.74 0.00 13.48
106 1.0DL+0.8(LL+ML+WL +Z) -0.19761 39.47475 -138.41856 -415.26 0.00 -0.59
107 1.0DL+0.8(LL+ML+WL +X) -3.54921 390.5973 0.20748 0.62 0.00 -10.65
108 1.0DL+0.8(LL+ML+WL -Z) 0.27615 741.3544 138.05652 414.17 0.00 0.83
109 1.0DL+0.8(LL+ML+WL -X) 3.59835 390.5973 0.20748 0.62 0.00 10.80
DATE 14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE FOUNDATIONS
REV NO A

PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: B3027-450-E-CV-DC-006

CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY RRC


Base pressure Calculation - F1

Max Diameter of Bar provided in Footing = 20 mm


Length of Column-1 (Clx1) = 0.700 m Fz Clear Cover Provided for Footing = 50 mm
Width of Column-1 (Cly1) = 0.700 m Effective Depth of Footing = 0.54 m
Length of Column-2 (Clx2) = 0.700 m Fy
Width of Column-2 (Cly2) = 0.700 m 1 1.575 2.675 1.575
C/C distance between Columns = 5.350 m P3 P4 Fx (+ve) Lateral
Thickness of Combined Footing = 0.600 m A C1 B
Length of CF (L) = 8.500 m 0.400 Clx1 Clx2
Width of CF (W) = 4.000 m X Fy (+ve) Vertical
Cly1 Cly2 4.000
Distance of Edge from CL of Column-1 (A) = 1.575 m COL-1 COL-2
Distance of Edge from CL of Column-2 (B) = 1.575 m 0.600 W
Distance of CG of Footing from Column-1 (C1) = 2.675 m
Selfweight of CF = 510.0 kN L Y
P1 P2
Height of FFL from FGL = 0.000 m FOOTING CROSS SECTION
Thickness of PCC Paving = 0.000 m 8.500
Soil Load + Paving load = 1188.7 kN FOOTING PLAN VIEW
Level of FFL -61.16 = 4.300 m
Finished GL = 4.300 m RCC 631.571
Founding Depth Considered = 2.300 m Wt. of Soil 762.946
Founding depth from FGL = 2.000 m
Net SBC considered = 100 kN/m2
Gross SBC at founding depth = 136.00 kN/m2
Increase Bearing Capacity for WL/SL = 161.00 kN/m2
Average FGL = 4.300 m

Gross Pressures
Total
Support Fy1 Fx1 Fz1 Mx1 (kN- Mz1 (kN- Fy2 Fx2 Fz2 Mx2 (kN- Mz2 (kN- Res. Lateral Total Total
L/C Vertical P/A Mx/Zx My/Zy P1 P2 P3 P4 SBC Tension
Number (kN) (kN) (kN) m) m) (kN) (kN) (kN) m) m) Force Moment Mx Moment My
Load P
A&B 101 404.146 -0.042 -3.390 -10.171 -0.126 428.773 0.038 -0.135 -0.406 0.113 3.530 2227.436 -10.578 65.860 65.510 -0.470 1.370 66.410 63.670 67.350 64.610 OK OK
102 644.711 0.250 -174.472 -523.417 0.750 -201.008 -0.251 -171.703 -515.110 -0.753 346.180 1838.220 -1038.527 -2262.300 54.070 -45.820 -46.970 -38.720 55.220 52.920 146.860 OK unsafe
103 205.884 -4.532 -1.577 -4.731 -13.595 237.895 -4.440 1.579 4.738 -13.321 8.970 1838.296 0.006 58.710 54.070 0.000 1.220 55.290 52.850 55.290 52.850 OK OK
104 -231.469 -0.342 171.123 513.368 -1.027 676.342 0.341 173.891 521.672 1.024 345.010 1839.389 1035.040 2428.390 54.100 45.660 50.420 150.180 49.340 58.860 -41.980 OK unsafe
105 205.884 4.470 -1.577 -4.731 13.410 237.895 4.494 1.579 4.738 13.482 8.960 1838.296 0.006 112.520 54.070 0.000 2.340 56.410 51.730 56.410 51.730 OK OK
106 715.555 0.194 -141.344 -424.032 0.582 39.475 -0.198 -138.419 -415.256 -0.593 279.760 2149.547 -839.287 -1808.520 63.220 -37.030 -37.550 -11.360 63.740 62.700 137.800 OK unsafe
107 364.494 -3.631 -3.028 -9.083 -10.894 390.597 -3.549 0.207 0.622 -10.648 7.710 2149.608 -8.461 48.290 63.220 -0.370 1.000 63.850 61.850 64.590 62.590 OK OK
108 14.611 -0.280 135.132 405.396 -0.839 741.354 0.276 138.057 414.170 0.828 273.190 2150.482 819.566 1944.030 63.250 36.160 40.360 139.770 59.050 67.450 -13.270 OK unsafe
109 364.494 3.570 -3.028 -9.083 10.710 390.597 3.598 0.207 0.622 10.795 7.700 2149.608 -8.461 91.330 63.220 -0.370 1.900 64.750 60.950 65.490 61.690 OK OK

Area (No
Max. Gross Max. Net % of No
Load Cases ex (m) ey (m) ey/L ex/B K Check x y Contact)
Pr Pressure Contact
(Sqm)
101 1.0(DL+LL+ML) 0.005 0.03 0.004 0.002
102 1.0(DL+WL +Z) 0.565 1.231 0.145 0.142 2.850 154.087 OK 104.126 0.5 0.55 3.225 9.485
Highlighted in Green Cells
103 1.0(DL+WL +X) 0.001 0.032 0.004 0.001
are to be manually enterd
104 1.0(DL+WL -Z) 0.563 1.321 0.156 0.141 2.850 154.185 OK 104.224 0.5 0.55 3.225 9.485
from Chart
105 1.0(DL+WL -X) 0.001 0.062 0.008 0.001
106 1.0DL+0.8(LL+ML+WL +Z) 0.391 0.842 0.1 0.098
107 1.0DL+0.8(LL+ML+WL +X) 0.004 0.023 0.003 0.001
108 1.0DL+0.8(LL+ML+WL -Z) 0.382 0.904 0.107 0.096
109 1.0DL+0.8(LL+ML+WL -X) 0.004 0.043 0.006 0.001
Note: Tension occurs only for the load cases 102 & 104 only. These are with DL + LL+ WL;hence 1.25 factor applied for
All. B C
Hence, The no contact area check is done for these two load cases only Net Pressures
43.971 41.231 44.911 42.171
-61.16 32.781 30.481 124.421
32.851 30.411 32.851 30.411
127.741 26.901 36.421 -64.42
33.971 29.291 33.971 29.291
-33.8 41.301 40.261 115.361
41.411 39.411 42.151 40.151
117.331 36.611 45.011 -35.71
42.311 38.511 43.051 39.251

127.741 41.301 45.011 124.421


-61.16 26.901 30.481 -64.42
DATE 14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE FOUNDATIONS
REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
FOUNDATION DESIGN: F1_TR1 - BC2

The Following Combined Foundation Design is carried out using cantilever foundation slab with Inverted foundation Beam concept:
DESIGN DATA:
Description Notn Value Units
Foundation Length In X-dir Lx = 8.50 m
Foundation Length In Z-dir Lz = 4.00 m
Column1 size parallel to X axis C1x = 0.70 m
Column1 size parallel to Z axis C1z = 0.70 m
Column2 size parallel to X axis C2x = 0.70 m
Column2 size parallel to Z axis C2z = 0.70 m
Width of Foundation Beam Considered Bb = 1 m
Depth of Foundation Beam Considered Db = 1 m
Depth Of Foundation Df = 2.00 m
DESIGN PARAMETERS:
Grade Of Concrete fck = 30 N/mm2
Grade of Steel fy = 500 N/mm2
Clear cover to main reinf. Of FDN slab = 50 mm
Dia of Main Reinforcement for FDN Slab φ1 = 16 mm
Dia of Dist. Reinforcement for FDN Slab φ2 = 12 mm
DESIGN OF CANTILEVER FOUNDATION SLAB:
2
Maximum Design Pressure W = 127.74 kN/m
Minimum Design Pressure W1 = -64.4
Load factor L.F = 1.5
Maximum Factored Design Pressure Wu = 192 kN/m2
Minimum Factored Desin Pressure Wu -97 kN/m2
Assumed Overall Depth of foundation slab D = 600 mm
Effective Depth of foundation slab d1 = 542 mm
Description Notn Formula Value Units
Bottom Reinforcement
Clear span from face of the beam l = (Lz-Bb)/2 1.5 m
Max BM at face of beam Mu = Wu . l 2/2 215.56 kN-m
2
Mu/(bd^2) = 0.73 N/mm
Pt required as per SP-16-Table-4 Pt req = 0.2 %
Area of Reinforcement Required Ast.(r) = 1084 mm2
Required spacing for 16 dia bars S req = 2
1000/[Ast/(π.φ1 /4)] 185 mm c/c
Provide spacing for 16 dia bars S pro 150 mm c/c
Provide Foundation Main Reinf. At Bottom 16 @ 150 mm c/c
Pt for distribution reinforcement = 0.12 %
Area of Reinf. Required Ast.(r) = 0.12% x (1000.D) 720 mm2
Required spacing for 12 dia bars S req = 2
1000/[Ast/(π.φ2 /4)] 157 mm c/c
Provide spacing for 12 dia bars S pro 150 mm c/c
Provide Foundation Dist. Reinf. At Bottom 12 @ 150 mm c/c
Top Reinforcement
Clear span from face of the beam l = (Lz-Bb)/2 1.50 m
Max BM at face of beam Mu = Wu . l 2/2 108.71 kN-m
Mu/(bd^2) = 0.37 N/mm2
Pt required as per SP-16-Table-4 Pt req = 0.2 %
Area of Reinforcement Required Ast.(r) = 1084 mm2
Required spacing for dia bars S req = 2
1000/[Ast/(π.φ1 /4)] 185 mm c/c
Provide spacing for dia bars S pro 150 mm c/c
Provide Foundation Main Reinf. At Bottom 16 @ 150 mm c/c
Pt for distribution reinforcement = 0.12 %
Area of Reinf. Required Ast.(r) = 0.12% x (1000.D) 720 mm2
Required spacing for dia bars S req = 2
1000/[Ast/(π.φ2 /4)] 157 mm c/c
Provide spacing for dia bars S pro 150 mm c/c
Provide Foundation Dist. Reinf. At Bottom 12 @ 150 mm c/c
CHECK FOR BENDING:
Required Depth of Foundation
Sqrt[Mx10^6/(0.133.fck.b)] d req = 232.434504 mm
< Provided,Section is safe in Bending
DATE 14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE FOUNDATIONS
REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
CHECK FOR SHEAR:
Shear Force at dist. "d" from Face of beam Vu = Wu (l - d1) 183.56 kN
Actual Shear stress τv = [Vu / (b x d)] 0.339 N/mm2
Percentage of Main reinf. Provided Pt pro = 0.247 %
2
Allowable Shear Stress as per SP-16-Table-61 0.36 N/mm
β 14.97 Safe in Shear
CHECK FOR PUNCHING SHEAR:
Shear Force at dist. "d/2" from Face of beam Vu = Wu(((Lx/2)*Lz)- 2961.822 kN
(C1x+d1)*(C1y*d1)))
Perimeter bo = 2(C1x+d1+C1y+d1) 4968.000 mm
Actual Shear stress tv = [Vu / (bo x d)] 1.10 N/mm2
Allowable Shear Stress as per tc 0.25 fck 1.37 N/mm2
Safe in Punching Shear
DESIGN OF FOUNDATION BEAM:
1.575 5.35 1.575
(a) (b) (c)

P C1 C2 Q
Wu.Lz
Reaction At C1 & C2 calculation:
Moment at Left of Column 1 (C1) Mc1 = Wu.Lz.a2/2 950.63 kN-m
2
Moment at Column 2 (C2) Mc2 = Wu. Lz.c /2 950.63 kN-m
Reaction At C1 Rc1 = (Wu. Lz. (a+b)2/2 - Mc2)/b 3257.3955 KN
Reaction At C2 Rc2 = Wu.Lz.(a+b+c)-Rc1 3257.3955 KN
Shear Force Calculation
S.Fat dist. d1 from face of column C1 (Left) V1 = Wu.Lz. (a-d1-C1x/2) 230.700246 kN
S.Fat dist. d1 from face of column C1 (Right) V2 = Rc1- Wu.Lz. (a+d1+C1x/2) 1073.79085 kN
S.Fat dist. d1 from face of column C2 (Left) V3 = Rc2- Wu.Lz. (c+d1+C2x/2) 1073.79085 kN
S.Fat dist. d1 from face of column C2 (Right) V4 = Wu.Lz. (c-d1-C2x/2) 230.700246 kN
Point of Zero S.F from point "P" lo = Rc1 / (Wu.Lz) 4.25 m
Bending Moment Calculation
B.M at Face of col. C1 (Left) for Span (a) M1 = Wu.Lz.(a-C1x/2)^2/2 575 KN-m
B.M at Zero S.F in span (b) M2 = Wu.Lz.lo ^2/2-Rc1.(lo-a) 1792 KN-m
B.M at Face of col. C2 (Reght) for Span (c) M3 = Wu.Lz.(c-C2x/2)^2/2 575 KN-m
Check for Bending : dreq = √[Mx106/(0.133.fck.b)]
Max. Bar Dia. Considered φ3 = 20 mm
Effective cover to Beam reinforcement = 76 mm
Effective Depth of FDN Beam d2 = 924 mm
Eff. Depth Required for Span (a) dreq(a) = 380 mm
Eff. Depth Required for Span (b) dreq(b) = 670 mm
Eff. Depth Required for Span (c) dreq(c) = 380 mm
< Provided,Section is safe in Bending
Reinforcement Calculation
Mu/bd2 for span (a) = 0.674
Mu/bd2 for span (b) = 2.099
Mu/bd2 for span (c) = 0.674
Pt required for span (a) Pt (a) = SP-16-Table-4 0.2 %
Pt required for span (b) Pt (b) = SP-16-Table-4 0.53 %
Pt required for span (c) Pt (c ) = SP-16-Table-4 0.2 %
Area of steel Req for Span (a) beam Ast(a) = 1848 mm2
Area of steel Req for Span (b) beam Ast(b) = 4897.2 mm2
Area of steel Req for Span (c) beam Ast(c) = 1848 mm2
Req. No: of bars for Span (a) for 16 mm = [Ast (a)/(π.φ2/4)] 9.2 Nos
Req. No: of bars for Span (b) for 25 mm = [Ast (b)/(π.φ2/4)] 9.98 Nos
Req. No: of bars for Span (c) for 16 mm = [Ast (c)/(π.φ2/4)] 9.2 Nos
Min. No: of bars req. for0.17 % for 25 mm dia = [Ast /(π.φ2/4)] 3.47 Nos
DATE 14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 TRESTLE FOUNDATIONS
REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
Pro. No: of bars for Span (a) for 16 mm = 10 Nos
Pro. No: of bars for Span (b) for 25 mm = 10 Nos
Pro. No: of bars for Span (c) for 16 mm = 10 Nos
Min. No: of bars Pro. for0.17 % for 25 mm dia = 4 Nos
Provided Reinforcement Top Reinf. Bottom Reinf.
For Span (a) 4 Nos 25 Tor 10 Nos 16 Tor
For Span (b) 10 Nos 25 Tor 4 Nos 25 Tor
For Span (c) 4 Nos 25 Tor 10 Nos 16 Tor
Check for Shear:
3
Actual Shear Stress for V1 τv1 = V1.10 / Bb . d2 0.25 N/mm2
Actual Shear Stress for V2 τv2 = V2.103 / Bb . d2 1.16 N/mm2
3
Actual Shear Stress for V3 τv3 = V3.10 / Bb . d2 1.16 N/mm2
3
Actual Shear Stress for V4 τv4 = V4.10 / Bb . d2 0 N/mm2
Pt provided in span (a) Pt(pro) = 100.Ast(a)/(Bb.d2) 0.201 %
Pt provided in span (b) Pt(pro) = 100.Ast(b)/(Bb.d2) 0.531 %
Pt provided in span (c) Pt(pro) = 100.Ast(c)/(Bb.d2) 0.201 %
Allowable Shear Stress for V1 τc1 = SP-16-Table-61 0.335 N/mm2
Allowable Shear Stress for V2 τc2 = SP-16-Table-61 0.51 N/mm2
Allowable Shear Stress for V3 τc3 = SP-16-Table-61 0.51 N/mm2
Allowable Shear Stress for V4 τc4 = SP-16-Table-61 0.335 N/mm2
Shear Check for V1 = Safe in Shear, Provide Nominal Shear Reinf.
Shear Check for V2 = Failed in Shear, Provide Shear Reinf.
Shear Check for V3 = Failed in Shear, Provide Shear Reinf.
Shear Check for V4 = Safe in Shear, Provide Nominal Shear Reinf.
Balance shear for V1 Vus1/d2 = --------------- ------- KN/cm
Balance shear for V2 Vus2/d2 = V2.10^3-tc1.Bb.d2 6.522 KN/cm
Balance shear for V3 Vus3/d2 = V3.10^3-tc1.Bb.d2 6.522 KN/cm
Balance shear for V4 Vus4/d2 = --------------- ------- KN/cm
Shear Reinforcement Required
Required stirrup spacing for V1 in span (a) = 4 Legged 10 Tor @ 200 mm c/c
Required stirrup spacing for V2 in span (b) = 4 Legged 10 Tor @ 205 mm c/c
Required stirrup spacing for V3 in span (b) = 4 Legged 10 Tor @ 205 mm c/c
Required stirrup spacing for V4 in span (c) = 4 Legged 10 Tor @ 200 mm c/c
Provided
Provided stirrup spacing for V1 in span (a) = 4 Legged 10 Tor @ 200 mm c/c
Provided stirrup spacing for V2 in span (b) = 4 Legged 10 Tor @ 200 mm c/c
Provided stirrup spacing for V3 in span (b) = 4 Legged 10 Tor @ 200 mm c/c
Provided stirrup spacing for V4 in span (c) = 4 Legged 10 Tor @ 200 mm c/c
14-08-2021
DESIGN CALCULATION REPORT FOR CONVEYOR BC2 DATE
TRESTLE FOUNDATIONS
A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA B3027-450-E-CV-
PROJECT :
PRADESH HOWE DOC NO: DC-006
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
PREPARED BY
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CHECKED BY
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
APPROVED BY

DESIGN OF PEDESTAL/COLUMN: TR1

Input Data for Columns:


Height of the pedestal = 2.00 m
Size of column along x-x dir. = 0.70 m Y
Size of column along y-y dir. = 0.70 m
Effective of column in x-x dir. = 4 m
Effective of column in y-y dir. = 4 m X X
Check for slender in x-x dir. = 5.7143 Short column
Check for slender in y-y dir. = 5.7143 Short column
Eccentricity in x-x dir. = 0.000
Eccentricity in y-y dir. = 0.000 Y
Load Case No: 104
P = 348 kN P = 232 kN
My = 3 kNm Fx = 1 kN
Mx = 516 kNm Fz = 172 kN

Moment due to slender ness effect in x-x = 0 kNm


Moment due to slender ness effect in y-y = 0 kNm
Design My = 3 kNm
Design Mx = 516 kNm
Grade of concrete = M 30
Grade of steel = Fe 500
Assume percentage of steel = 1.25 %
Pu 0.0237
=
fck*b*D
P 0.042
=
fck
Min. Clear cover to any reinforcement = 50 mm
Dia. Of stirrup = 8 mm
Dia. Of main bar = 20 mm
d' = 68 mm
d'/D = 0.0971 Say 0.1
From SP:16,Chart:48 Mu 0.065
=
fck*b*D2

Mux = 668.85 kNm


Muy = 668.85 kNm
Mx My = 0.8 OK
+
Mux Muy
Area of steel required = 6125 mm2
Provide 20 no's of 20 mm Dia. Bars + = 6283.2 mm2
And 0 no's of 0 mm Dia. Bars = 0 mm2
Lateral Ties: = 6283.2 mm2 OK

Dia. Of tie reinforcement = > 5 mm


> 6 mm
Provide of dia. Of tie reinforcement = 8 mm
Spacing = < 300 mm
< 320 mm
Provide spacing = 150 mm
04-10-2021
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU DATE
FOUNDATION
A
REV NO
B3027-450-E-CV-DC-
PROJECT :
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: XXX

CLIENT :
ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY
PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY


TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY


RRC

FOOTING DESIGN: F4
LOAD DATA FOR FOOTING DESIGN FOR TR3_BC2 (Ref. Dwg: OE210601-S-CS-GA-2029)

Column
Load Case Fx (kN) Fy (kN) Fz (kN)
Mark
1 Dead Load 1.070 254.630 -1.580
2 Live Load (WLK) 0.780 124.030 0.020
3 Live Load (MAT) 0.360 98.720 -1.410
TR3-A 4 Wind +Z 0.290 790.350 -165.160
5 Wind +X -12.010 1.960 0.010
6 Wind -Z -0.270 -781.050 164.070
7 Wind -X 12.020 -2.390 0.090

Column
Load Case Fx (kN) Fy (kN) Fz (kN)
Mark
1 Dead Load 1.210 279.170 1.470
2 Live Load (WLK) 0.730 110.410 0.070
3 Live Load (MAT) 0.330 85.610 -1.370
TR3-B 4 Wind +Z -0.290 -790.470 -165.830
5 Wind +X -12.010 2.000 0.010
6 Wind -Z 0.260 783.170 163.410
7 Wind -X 12.000 -1.530 0.090

Load data for the footing design @ bottom of the base plate. 0
Horizontal Vertical Horizontal
Node L/C Fx kN Fy kN Fz kN
101 1.0(DL+LL+ML) 2.21 477.38 -2.97
102 1.0(DL+WL +Z) 1.36 1044.98 -166.74
103 1.0(DL+WL +X) -10.94 256.59 -1.57
104 1.0(DL+WL -Z) 0.8 -526.42 162.49
TR3-A 105 1.0(DL+WL -X) 13.09 252.24 -1.49
106 1.0DL+0.8(LL+ML+WL +Z) 2.214 1065.11 -134.82
107 1.0DL+0.8(LL+ML+WL +X) -7.626 434.398 -2.684
108 1.0DL+0.8(LL+ML+WL -Z) 1.766 -192.01 128.564
109 1.0DL+0.8(LL+ML+WL -X) 11.598 430.918 -2.62
101 1.0(DL+LL+ML) 2.27 475.19 0.17
102 1.0(DL+WL +Z) 0.92 -511.3 -164.36
103 1.0(DL+WL +X) -10.8 281.17 1.48
104 1.0(DL+WL -Z) 1.47 1062.34 164.88
TR3-B 105 1.0(DL+WL -X) 13.21 277.64 1.56
106 1.0DL+0.8(LL+ML+WL +Z) 1.826 -196.39 -132.234
107 1.0DL+0.8(LL+ML+WL +X) -7.55 437.586 0.438
108 1.0DL+0.8(LL+ML+WL -Z) 2.266 1062.522 131.158
109 1.0DL+0.8(LL+ML+WL -X) 11.658 434.762 0.502

Depth of the foundation = 2.00 m


The forces are transffered from T.O.C to Bottom of footing with a leverarm (Z) of 3.0m
(Depth of foundation 2.0m + Height of the pedestal above FGL 1.0 = 3.0m)
i.e Fz x Z = Mx and Fx x Z = Mz
*All Dimensions are in meters.
Fy1 Fy2
Fz1 Fz2 B.O.BP/T.O.C
FGL 1.0

C1 C2 0.9
1.3 2.0
0.4
0.7

5.35
04-10-2021
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU DATE
FOUNDATION
A
REV NO
B3027-450-E-CV-DC-
PROJECT :
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: XXX

CLIENT :
ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY
PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY


TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY


RRC

Load data for TR18 @ Bottom of the footing


Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
101 1.0(DL+LL+ML) 2.21 477.38 -2.97 -8.91 0.00 6.63
102 1.0(DL+WL +Z) 1.36 1044.98 -166.74 -500.22 0.00 4.08
103 1.0(DL+WL +X) -10.94 256.59 -1.57 -4.71 0.00 -32.82
104 1.0(DL+WL -Z) 0.8 -526.42 162.49 487.47 0.00 2.40
TR3-A 105 1.0(DL+WL -X) 13.09 252.24 -1.49 -4.47 0.00 39.27
106 1.0DL+0.8(LL+ML+WL +Z) 2.214 1065.11 -134.82 -404.46 0.00 6.64
107 1.0DL+0.8(LL+ML+WL +X) -7.626 434.398 -2.684 -8.05 0.00 -22.88
108 1.0DL+0.8(LL+ML+WL -Z) 1.766 -192.01 128.564 385.69 0.00 5.30
109 1.0DL+0.8(LL+ML+WL -X) 11.598 430.918 -2.62 -7.86 0.00 34.79
101 1.0(DL+LL+ML) 2.27 475.19 0.17 0.51 0.00 6.81
102 1.0(DL+WL +Z) 0.92 -511.3 -164.36 -493.08 0.00 2.76
103 1.0(DL+WL +X) -10.8 281.17 1.48 4.44 0.00 -32.40
104 1.0(DL+WL -Z) 1.47 1062.34 164.88 494.64 0.00 4.41
TR3-B 105 1.0(DL+WL -X) 13.21 277.64 1.56 4.68 0.00 39.63
106 1.0DL+0.8(LL+ML+WL +Z) 1.826 -196.39 -132.234 -396.70 0.00 5.48
107 1.0DL+0.8(LL+ML+WL +X) -7.55 437.586 0.438 1.31 0.00 -22.65
108 1.0DL+0.8(LL+ML+WL -Z) 2.266 1062.522 131.158 393.47 0.00 6.80
109 1.0DL+0.8(LL+ML+WL -X) 11.658 434.762 0.502 1.51 0.00 34.97
DATE 04-10-2021
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU FOUNDATION
REV NO A

PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH HOWE DOC NO: B3027-450-E-CV-DC-XXX

CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PREPARED BY PSR

CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. CHECKED BY TGB

CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. APPROVED BY RRC


Base pressure Calculation - F4

Max Diameter of Bar provided in Footing = 20 mm


Length of Column-1 (Clx1) = 0.900 m Fz Clear Cover Provided for Footing = 50 mm
Width of Column-1 (Cly1) = 0.600 m Effective Depth of Footing = 0.64 m
Length of Column-2 (Clx2) = 0.900 m Fy
Width of Column-2 (Cly2) = 0.600 m 1 2.075 2.675 2.075
C/C distance between Columns = 5.350 m P3 P4 Fx (+ve) Lateral
Thickness of Combined Footing = 0.700 m A C1 B
Length of CF (L) = 9.500 m 0.400 Clx1 Clx2
Width of CF (W) = 4.500 m X Fy (+ve) Vertical
Cly1 Cly2 4.500
Distance of Edge from CL of Column-1 (A) = 2.075 m COL-1 COL-2
Distance of Edge from CL of Column-2 (B) = 2.075 m 0.700 W
Distance of CG of Footing from Column-1 (C1) = 2.675 m
Selfweight of CF = 748.1 kN L Y
P1 P2
Height of FFL from FGL = 0.000 m FOOTING CROSS SECTION
Thickness of PCC Paving = 0.000 m 9.500
Soil Load + Paving load = 1500.1 kN FOOTING PLAN VIEW
Level of FFL -57.308 = 4.300 m
Finished GL = 4.300 m RCC 965.671
Founding Depth Considered = 2.300 m Wt. of Soil 833.08
Founding depth from FGL = 2.000 m
Net SBC considered = 100 kN/m2
Gross SBC at founding depth 0 = 136.00 kN/m2
Increase Bearing Capacity for WL/SL = 161.00 kN/m2
Average FGL = 4.300 m

Gross Pressures
Total
Support Fy1 Fx1 Fz1 Mx1 (kN- Mz1 (kN- Fy2 Fx2 Fz2 Mx2 (kN- Mz2 (kN- Res. Lateral Total Total
L/C Vertical P/A Mx/Zx My/Zy P1 P2 P3 P4 SBC Tension
Number (kN) (kN) (kN) m) m) (kN) (kN) (kN) m) m) Force Moment Mx Moment My
Load P
A&B 101 477.380 2.210 -2.970 -8.910 6.630 475.190 2.270 0.170 0.510 6.810 5.280 2751.321 -8.400 7.580 64.360 -0.260 0.110 64.210 63.990 64.730 64.510 OK OK
102 1044.980 1.360 -166.740 -500.220 4.080 -511.300 0.920 -164.360 -493.080 2.760 331.110 2332.431 -993.300 -4156.210 54.560 -30.980 -61.400 -37.820 84.980 24.140 146.940 OK unsafe
103 256.590 -10.940 -1.570 -4.710 -32.820 281.170 -10.800 1.480 4.440 -32.400 21.740 2336.511 -0.270 0.530 54.660 -0.010 0.010 54.660 54.640 54.680 54.660 OK OK
104 -526.420 0.800 162.490 487.470 2.400 1062.340 1.470 164.880 494.640 4.410 327.380 2334.671 982.110 4256.740 54.610 30.630 62.890 148.130 22.350 86.870 -38.910 OK unsafe
105 252.240 13.090 -1.490 -4.470 39.270 277.640 13.210 1.560 4.680 39.630 26.300 2328.631 0.210 146.850 54.470 0.010 2.170 56.650 52.310 56.630 52.290 OK OK
106 1065.110 2.214 -134.820 -404.460 6.642 -196.390 1.826 -132.234 -396.702 5.478 267.080 2667.471 -801.162 -3362.390 62.400 -24.990 -49.680 -12.270 87.090 37.710 137.070 OK unsafe
107 434.398 -7.626 -2.684 -8.052 -22.878 437.586 -7.550 0.438 1.314 -22.650 15.340 2670.735 -6.738 -37.000 62.470 -0.210 -0.550 61.710 62.810 62.130 63.230 OK OK
108 -192.010 1.766 128.564 385.692 5.298 1062.522 2.266 131.158 393.474 6.798 259.750 2669.263 779.166 3367.970 62.440 24.300 49.760 136.500 36.980 87.900 -11.620 OK unsafe
109 430.918 11.598 -2.620 -7.860 34.794 434.762 11.658 0.502 1.506 34.974 23.350 2664.431 -6.354 80.050 62.330 -0.200 1.180 63.310 60.950 63.710 61.350 OK OK

Area (No
Max. Gross Max. Net % of No
Load Cases ex (m) ey (m) ey/L ex/B K Check x y Contact)
Pr Pressure Contact
(Sqm)
101 1.0(DL+LL+ML) 0.004 0.003 0.001 0.001
102 1.0(DL+WL +Z) 0.426 1.782 0.188 0.095 2.900 158.224 OK 105.634 0.39 0.7 3.428 8.018
Highlighted in Green Cells
103 1.0(DL+WL +X) 0.001 0.001 0.001 0.001
are to be manually enterd
104 1.0(DL+WL -Z) 0.421 1.824 0.192 0.094 2.900 158.376 OK 105.786 0.39 0.7 3.428 8.018
from Chart
105 1.0(DL+WL -X) 0.001 0.064 0.007 0.001
106 1.0DL+0.8(LL+ML+WL +Z) 0.301 1.261 0.133 0.067
107 1.0DL+0.8(LL+ML+WL +X) 0.003 0.014 0.002 0.001
108 1.0DL+0.8(LL+ML+WL -Z) 0.292 1.262 0.133 0.065
109 1.0DL+0.8(LL+ML+WL -X) 0.003 0.031 0.004 0.001
Note: Tension occurs only for the load cases 102 & 104 only. These are with DL + LL+ WL;hence 1.25 factor applied for
All. B C
Hence, The no contact area check is done for these two load cases only Net Pressures
44.723 44.503 45.243 45.023
-57.308 65.493 4.653 127.453
35.173 35.153 35.193 35.173
128.643 2.863 67.383 -58.398
37.163 32.823 37.143 32.803
-31.758 67.603 18.223 117.583
42.223 43.323 42.643 43.743
117.013 17.493 68.413 -31.108
43.823 41.463 44.223 41.863

128.643 67.603 68.413 127.453


-57.308 2.863 4.653 -58.398
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU DATE 04-10-2021
FOUNDATION REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-XXX
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
FOUNDATION DESIGN: F4_TR3 - BC2

The Following Combined Foundation Design is carried out using cantilever foundation slab with Inverted foundation Beam concept:
DESIGN DATA:
Description Notn Value Units
Foundation Length In X-dir Lx = 9.50 m
Foundation Length In Z-dir Lz = 4.50 m
Column1 size parallel to X axis C1x = 0.90 m
Column1 size parallel to Z axis C1z = 0.60 m
Column2 size parallel to X axis C2x = 0.90 m
Column2 size parallel to Z axis C2z = 0.60 m
Width of Foundation Beam Considered Bb = 1.3 m
Depth of Foundation Beam Considered Db = 1.1 m
Depth Of Foundation Df = 2.00 m
DESIGN PARAMETERS:
Grade Of Concrete fck = 30 N/mm2
Grade of Steel fy = 500
Clear cover to main reinf. Of FDN slab = 50 mm
Dia of Main Reinforcement for FDN Slab φ1 = 16 mm
Dia of Dist. Reinforcement for FDN Slab φ2 = 16 mm
DESIGN OF CANTILEVER FOUNDATION SLAB:
2
Maximum Design Pressure W = 128.64 kN/m
Minimum Design Pressure W1 = -58.4
Load factor L.F = 1.5
Maximum Factored Design Pressure Wu = 193 kN/m2
2
Minimum Factored Desin Pressure Wu -88 kN/m
Assumed Overall Depth of foundation slab D = 700 mm
Effective Depth of foundation slab d1 = 642 mm
Description Notn Formula Value Units
Bottom Reinforcement
Clear span from face of the beam l = (Lz-Bb)/2 1.6 m
Max BM at face of beam Mu = Wu . l 2/2 246.99 kN-m
Mu/(bd^2) = 0.60 N/mm2
Pt required as per SP-16-Table-4 Pt req = 0.2 %
Area of Reinforcement Required Ast.(r) = 1284 mm2
Required spacing for 16 dia bars S req = 1000/[Ast/(π.φ1 /4)]
2
157 mm c/c
Provide spacing for 16 dia bars S pro 150 mm c/c
Provide Foundation Main Reinf. At Bottom 16 @ 150 mm c/c
Pt for distribution reinforcement = 0.12 %
Area of Reinf. Required Ast.(r) = 0.12% x (1000.D) 840 mm2
Required spacing for 16 dia bars S req = 1000/[Ast/(π.φ2 /4)]
2
239 mm c/c
Provide spacing for 16 dia bars S pro 200 mm c/c
Provide Foundation Dist. Reinf. At Bottom 16 @ 200 mm c/c
Top Reinforcement
Clear span from face of the beam l = (Lz-Bb)/2 1.60 m
Max BM at face of beam Mu = Wu . l 2/2 112.12 kN-m
2
Mu/(bd^2) = 0.27 N/mm
Pt required as per SP-16-Table-4 Pt req = 0.2 %
Area of Reinforcement Required Ast.(r) = 1284 mm2
Required spacing for dia bars S req = 1000/[Ast/(π.φ12/4)] 157 mm c/c
Provide spacing for dia bars S pro 150 mm c/c
Provide Foundation Main Reinf. At Bottom 16 @ 150 mm c/c
Pt for distribution reinforcement = 0.12 %
Area of Reinf. Required Ast.(r) = 0.12% x (1000.D) 840 mm2
Required spacing for dia bars S req = 1000/[Ast/(π.φ2 /4)]
2
239 mm c/c
Provide spacing for dia bars S pro 200 mm c/c
Provide Foundation Dist. Reinf. At Bottom 16 @ 200 mm c/c
CHECK FOR BENDING:
Required Depth of Foundation
Sqrt[Mx10^6/(0.133.fck.b)] d req = 248.803936 mm
< Provided,Section is safe in Bending
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU DATE 04-10-2021
FOUNDATION REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-XXX
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
CHECK FOR SHEAR:
Shear Force at dist. "d" from Face of beam Vu = Wu (l - d1) 184.86 kN
Actual Shear stress τv = [Vu / (b x d)] 0.288 N/mm2
Percentage of Main reinf. Provided Pt pro = 0.209 %
2
Allowable Shear Stress as per SP-16-Table-61 0.33 N/mm
β 17.73 Safe in Shear
CHECK FOR PUNCHING SHEAR:
Shear Force at dist. "d/2" from Face of beam Vu = Wu(((Lx/2)*Lz)- 3755.058 kN
(C1x+d1)*(C1y*d1)))
Perimeter bo = 2(C1x+d1+C1y+d1) 5568.000 mm
Actual Shear stress tv = [Vu / (bo x d)] 1.05 N/mm2
Allowable Shear Stress as per tc 0.25 fck 1.37 N/mm2
Safe in Punching Shear
DESIGN OF FOUNDATION BEAM:
2.075 5.35 2.075
(a) (b) (c)

P C1 C2 Q
Wu.Lz
Reaction At C1 & C2 calculation:
Moment at Left of Column 1 (C1) Mc1 = Wu.Lz.a2/2 1869.37 kN-m
2
Moment at Column 2 (C2) Mc2 = Wu. Lz.c /2 1869.37 kN-m
Reaction At C1 Rc1 = (Wu. Lz. (a+b)2/2 - Mc2)/b 4124.61619 KN
Reaction At C2 Rc2 = Wu.Lz.(a+b+c)-Rc1 4124.61619 KN
Shear Force Calculation
S.Fat dist. d1 from face of column C1 (Left) V1 = Wu.Lz. (a-d1-C1x/2) 521.87249 kN
S.Fat dist. d1 from face of column C1 (Right) V2 = Rc1- Wu.Lz. (a+d1+C1x/2) 1042.87664 kN
S.Fat dist. d1 from face of column C2 (Left) V3 = Rc2- Wu.Lz. (c+d1+C2x/2) 1042.87664 kN
S.Fat dist. d1 from face of column C2 (Right) V4 = Wu.Lz. (c-d1-C2x/2) 521.87249 kN
Point of Zero S.F from point "P" lo = Rc1 / (Wu.Lz) 4.75 m
Bending Moment Calculation
B.M at Face of col. C1 (Left) for Span (a) M1 = Wu.Lz.(a-C1x/2)^2/2 1146 KN-m
B.M at Zero S.F in span (b) M2 = Wu.Lz.lo ^2/2-Rc1.(lo-a) 1237 KN-m
B.M at Face of col. C2 (Reght) for Span (c) M3 = Wu.Lz.(c-C2x/2)^2/2 1146 KN-m
Check for Bending : dreq = √[Mx106/(0.133.fck.b)]
Max. Bar Dia. Considered φ3 = 20 mm
Effective cover to Beam reinforcement = 76 mm
Effective Depth of FDN Beam d2 = 1024 mm
Eff. Depth Required for Span (a) dreq(a) = 470 mm
Eff. Depth Required for Span (b) dreq(b) = 488 mm
Eff. Depth Required for Span (c) dreq(c) = 470 mm
< Provided,Section is safe in Bending
Reinforcement Calculation
Mu/bd2 for span (a) = 0.842
Mu/bd2 for span (b) = 0.908
Mu/bd2 for span (c) = 0.842
Pt required for span (a) Pt (a) = SP-16-Table-4 0.201 %
Pt required for span (b) Pt (b) = SP-16-Table-4 0.217 %
Pt required for span (c) Pt (c ) = SP-16-Table-4 0.201 %
Area of steel Req for Span (a) beam Ast(a) = 2676 mm2
Area of steel Req for Span (b) beam Ast(b) = 2888.704 mm2
Area of steel Req for Span (c) beam Ast(c) = 2675.712 mm2
Req. No: of bars for Span (a) for 20 mm = [Ast (a)/(π.φ2/4)] 8.52 Nos
Req. No: of bars for Span (b) for 20 mm = [Ast (b)/(π.φ2/4)] 9.2 Nos
Req. No: of bars for Span (c) for 20 mm = [Ast (c)/(π.φ2/4)] 8.52 Nos
Min. No: of bars req. for0.17 % for 20 mm dia = [Ast /(π.φ2/4)] 7.74 Nos
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED TRESTLE & VGTU DATE 04-10-2021
FOUNDATION REV NO A
HOWE DOC B3027-450-E-
PROJECT : MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA PRADESH
NO: CV-DC-XXX
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CLIENT'S CHECKED
HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CONSULTANT : BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
BY
Pro. No: of bars for Span (a) for 20 mm = 10 Nos
Pro. No: of bars for Span (b) for 20 mm = 10 Nos
Pro. No: of bars for Span (c) for 20 mm = 10 Nos
Min. No: of bars Pro. for0.17 % for 20 mm dia = 8 Nos
Provided Reinforcement Top Reinf. Bottom Reinf.
For Span (a) 8 Nos 20 Tor 10 Nos 20 Tor
For Span (b) 10 Nos 20 Tor 8 Nos 20 Tor
For Span (c) 8 Nos 20 Tor 10 Nos 20 Tor
Check for Shear:
3
Actual Shear Stress for V1 τv1 = V1.10 / Bb . d2 0.39 N/mm2
Actual Shear Stress for V2 τv2 = V2.103 / Bb . d2 0.78 N/mm2
3
Actual Shear Stress for V3 τv3 = V3.10 / Bb . d2 0.78 N/mm2
3
Actual Shear Stress for V4 τv4 = V4.10 / Bb . d2 0 N/mm2
Pt provided in span (a) Pt(pro) = 100.Ast(a)/(Bb.d2) 0.236 %
Pt provided in span (b) Pt(pro) = 100.Ast(b)/(Bb.d2) 0.236 %
Pt provided in span (c) Pt(pro) = 100.Ast(c)/(Bb.d2) 0.236 %
Allowable Shear Stress for V1 τc1 = SP-16-Table-61 0.36 N/mm2
Allowable Shear Stress for V2 τc2 = SP-16-Table-61 0.36 N/mm2
Allowable Shear Stress for V3 τc3 = SP-16-Table-61 0.36 N/mm2
Allowable Shear Stress for V4 τc4 = SP-16-Table-61 0.36 N/mm2
Shear Check for V1 = Failed in Shear, Provide Shear Reinf.
Shear Check for V2 = Failed in Shear, Provide Shear Reinf.
Shear Check for V3 = Failed in Shear, Provide Shear Reinf.
Shear Check for V4 = Failed in Shear, Provide Shear Reinf.
Balance shear for V1 Vus1/d2 = V1.10^3-tc1.Bb.d2 0.417 KN/cm
Balance shear for V2 Vus2/d2 = V2.10^3-tc1.Bb.d2 5.505 KN/cm
Balance shear for V3 Vus3/d2 = V3.10^3-tc1.Bb.d2 5.505 KN/cm
Balance shear for V4 Vus4/d2 = V4.10^3-tc1.Bb.d2 0.417 KN/cm
Shear Reinforcement Required
Required stirrup spacing for V1 in span (a) = 4 Legged 8 Tor @ 2095 mm c/c
Required stirrup spacing for V2 in span (b) = 4 Legged 8 Tor @ 155 mm c/c
Required stirrup spacing for V3 in span (b) = 4 Legged 8 Tor @ 155 mm c/c
Required stirrup spacing for V4 in span (c) = 4 Legged 8 Tor @ 2095 mm c/c
Provided
Provided stirrup spacing for V1 in span (a) = 4 Legged 8 Tor @ 200 mm c/c
Provided stirrup spacing for V2 in span (b) = 4 Legged 8 Tor @ 155 mm c/c
Provided stirrup spacing for V3 in span (b) = 4 Legged 8 Tor @ 155 mm c/c
Provided stirrup spacing for V4 in span (c) = 4 Legged 8 Tor @ 200 mm c/c
04-10-2021
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED DATE
TRESTLE & VGTU FOUNDATION
A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA B3027-450-E-CV-
PROJECT :
PRADESH HOWE DOC NO: DC-XXX
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
PREPARED BY
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CHECKED BY
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
APPROVED BY
DESIGN OF PEDESTAL/COLUMN: TR3 F4 Axial compression

Input Data for Columns:


Height of the pedestal = 1.90 m
Size of column along x-x dir. = 0.90 m Y
Size of column along y-y dir. = 0.60 m
Effective of column in x-x dir. = 3.8 m
Effective of column in y-y dir. = 3.8 m X X
Check for slender in x-x dir. = 4.2222 Short column
Check for slender in y-y dir. = 6.3333 Short column
Eccentricity in x-x dir. = 0.000
Eccentricity in y-y dir. = 0.000 Y
Load Case No: 102
P = 1567.5 kN P = 1045 kN
My = 3.876 kNm Fx = 1 kN
Mx = 475.95 kNm Fz = 167 kN

Moment due to slender ness effect in x-x = 0 kNm


Moment due to slender ness effect in y-y = 0 kNm
Design My = 3.876 kNm
Design Mx = 475.95 kNm
0 Grade of concrete = M 30
Grade of steel = Fe 500
Assume percentage of steel = 0.80 %
Pu 0.0968
=
fck*b*D
P 0.027
=
fck
Min. Clear cover to any reinforcement = 50 mm
Dia. Of stirrup = 8 mm
Dia. Of main bar = 20 mm
d' = 68 mm
d'/D = 0.0756 Say 0.1
From SP:16,Chart:48 Mu 0.08
=
fck*b*D2

Mux = 1166.4 kNm


Muy = 777.6 kNm
Mx My = 0.4 OK
+
Mux Muy
Area of steel required = 4320 mm2
Provide 4 no's of 20 mm Dia. Bars + = 1256.6 mm2
And 16 no's of 16 mm Dia. Bars = 3217 mm2
Lateral Ties: = 4473.6 mm2 OK

Dia. Of tie reinforcement = > 5 mm


> 6 mm
Provide of dia. Of tie reinforcement = 8 mm
Spacing = < 300 mm
< 320 mm
Provide spacing = 150 mm
04-10-2021
DESIGN CALCULATION REPORT FOR BC2 – 4 LEGGED DATE
TRESTLE & VGTU FOUNDATION
A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA B3027-450-E-CV-
PROJECT :
PRADESH HOWE DOC NO: DC-XXX
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
PREPARED BY
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. TGB
CHECKED BY
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. RRC
APPROVED BY
DESIGN OF PEDESTAL/COLUMN: TR3 F4 Axial Tension

Input Data for Columns:


Height of the pedestal = 1.90 m
Size of column along x-x dir. = 0.90 m Y
Size of column along y-y dir. = 0.60 m
Effective of column in x-x dir. = 3.8 m
Effective of column in y-y dir. = 3.8 m X X
Check for slender in x-x dir. = 4.2222 Short column
Check for slender in y-y dir. = 6.3333 Short column
Eccentricity in x-x dir. = 0.000
Eccentricity in y-y dir. = 0.000 Y
Load Case No: 104
P = -790.5 kN P = -527 kN
My = 2.28 kNm Fx = 1 kN
Mx = 464.55 kNm Fz = 163 kN

Moment due to slender ness effect in x-x = 0 kNm


Moment due to slender ness effect in y-y = 0 kNm
Design My = 2.28 kNm
Design Mx = 464.55 kNm
0 Grade of concrete = M 30
Grade of steel = Fe 500
Assume percentage of steel = 0.80 %
Pu -0.049
=
fck*b*D
P 0.027
=
fck
Min. Clear cover to any reinforcement = 50 mm
Dia. Of stirrup = 8 mm
Dia. Of main bar = 20 mm
d' = 68 mm
d'/D = 0.0756 Say 0.1
From SP:16,Chart:83 Mu 0.035
=
fck*b*D2

Mux = 510.3 kNm


Muy = 340.2 kNm
Mx My = 0.9 OK
+
Mux Muy
Area of steel required = 4320 mm2
Provide 16 no's of 20 mm Dia. Bars + = 5026.5 mm2
And 0 no's of 16 mm Dia. Bars = 0 mm2
Lateral Ties: = 5026.5 mm2 OK

Dia. Of tie reinforcement = > 5 mm


> 6 mm
Provide of dia. Of tie reinforcement = 8 mm
Spacing = < 300 mm
< 320 mm
Provide spacing = 150 mm
Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 2 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

1. INTRODUCTION
1.1. SCOPE
This document shows the structural design calculation for the BC2 – 4 Legged trestle, Staircase
foundations and VGTU sub structure details. The type of foundation used for Trestles and VGTU is
combined Raft for total structure including Take-up post, sheaves and winch. The loads from the trestles
and VGTU columns, take-up tower, sheaves and winch loads are transferred to the respective RCC
pedestals. In turn the pedestals transfer the loads to the Raft foundation.
Foundation Load data as per drawing B3027-450-E-ST-DG-018 (REV-B)
1.2. UNITS OF MEASUREMENTS
Units of measurements used in analysis shall be of SI Units.

1.3. MATERIAL PROPERTIES


a) Concrete
Grade of concrete shall be M30
b) Reinforcement
Reinforcement steel will be of high yield strength deformed TMT steel bars of grade Fe-500 and
shall conform to IS:1786.

c) Unit Weight of Materials : RCC 25kN/m3

2. DESIGN PHILOSOPHY
The critical section for moment is at the face of the pedestal. So the elements at the pedestal locations
are skipped for design, Similarly shear force is averaged at distance ‘d’ from face of column.

While considering the design moment value across a section for a particular load case, for both top and
bottom rebar only the elements with positive or negative values are considered according to the sign
convention

The critical section for one way shear is at a distance of ‘d’ from the face of the pedestal/column,
where ‘d’ is the effective depth of footing.

The Design moments are calculated as per Wooden Armer Equations as follows

Finite elements results are in parameters M x, My and Mxy. But the result parameters should be modified as
per Wood-Armer equations.

The values of design moments, Mxd and Myd calculated based on following equations.

For top reinforcement the program computes as given in below equations:

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 3 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Mx1 = Mx + abs(Mxy)

My1 = My + abs(Mxy)

Mx2 = Mx + abs(Mxy2/My)

My2 = My + abs(Mxy2/Mx)

If both Mx1 and My1 are positive, Mxd = Mx1 and Myd = My1

If both Mx1 and My1 are negative, Mxd = Mx1 and Myd = My1

If Mx1 is negative and My1 is positive,Mxd = 0 and Myd = My2

If My1 is negative and Mx1 is positive,Mxd = Mx2 and Myd = 0

For bottom reinforcement the program computes as given in below equations:

Mx1 = Mx - abs(Mxy)

My1 = My - abs(Mxy)

Mx2 = Mx - abs(Mxy2/My)

My2 = My - abs(Mxy2/Mx)

If both Mx1 and My1 are positive, Mxd = 0 and Myd = 0

If both Mx1 and My1 are negative, Mxd = Mx1 and Myd = My1

If Mx1 is negative and My1 is positive,Mxd = Mx2 and Myd = 0

If My1 is negative and Mx1 is positive,Mxd = 0 and Myd = My2

Mxd amd Myd are then used in lieu of Mx and My for calculations of the required reinforcing.

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 4 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3. DESIGN OF VGTU FOUNDATION FOR BC-2_TR2A & TR2B


3.1. Load data for BC-2_TR2A & TR2B:

LOAD DATA TRESTLE TR-2A - (B.P-2)

Horizontal Vertical Horizontal


TRESTLE MARKING LOAD CASE
Fx kN Fy kN Fz kN
DEAD LOAD -18.38 -131.28 6.13
LIVE LOAD (WALKWAY) -9.63 -54.35 4.63
LIVE LOAD (MATERIAL) -8.08 -132.22 0.17
LINE-A W L ACROSS (+) 50 M/S -11.80 -89.91 36.84
W L ALONG (+) 50 M/S 104.07 449.66 -57.86
W L ACROSS (-) 50 M/S 11.07 87.71 -37.10
W L ALONG (-) 50 M/S -101.20 -441.21 56.78
DEAD LOAD -2.57 -149.97 -0.63
LIVE LOAD (WALKWAY) -1.75 -62.16 -7.92
LIVE LOAD (MATERIAL) -1.97 -164.33 2.56
LINE B W L ACROSS (+) 50 M/S -0.05 79.52 37.59
W L ALONG (+) 50 M/S -1.05 -107.56 -56.93
W L ACROSS (-) 50 M/S 0.29 -79.65 -36.68
W L ALONG (-) 50 M/S 1.32 104.97 56.11

LOAD DATA TRESTLE TR-2B - (B.P-2)

Horizontal Vertical Horizontal


TRESTLE MARKING LOAD CASE
Fx kN Fy kN Fz kN
DEAD LOAD 22.79 -206.26 7.11
LIVE LOAD (WALKWAY) 10.31 -109.79 9.00
LIVE LOAD (MATERIAL) 31.40 -221.23 14.94
LINE-A W L ACROSS (+) 50 M/S 14.15 -243.49 100.08
W L ALONG (+) 50 M/S 98.29 -431.24 57.98
W L ACROSS (-) 50 M/S -14.31 239.06 -98.94
W L ALONG (-) 50 M/S -97.11 423.13 -57.09
DEAD LOAD 1.68 -180.43 -5.49
LIVE LOAD (WALKWAY) 0.37 -80.03 -4.70
LIVE LOAD (MATERIAL) 0.44 -118.03 14.30
LINE B W L ACROSS (+) 50 M/S 0.73 175.33 99.99
W L ALONG (+) 50 M/S 3.88 46.84 57.55
W L ACROSS (-) 50 M/S -0.37 -171.97 -98.14
W L ALONG (-) 50 M/S -4.50 -45.62 -56.56

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 5 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Load data on Raft: (Sheave, Winch, Take-up Guide post, safety guard and Handrail
Load data for Sheave

For each sheave having a horizontal force of 25kN and Resultant force of 25kn with an
angle of 60o.
Horizontal force (Fx) due to inclined force = Cos 60o x 25 = 12.5 kN
Horizontal force (Fz) due to inclined force = Sin 60o x 25 = 21.65 kN
The horizontal load applied in each sheave for footing design.

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 6 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Winch load data:

Load data for safety guard, Take-up guide post and Removable hand rail

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 7 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.2. Details of Raft foundation:


Size of the Raft footing = 9.8m x 8.0m x 0.75m
Depth of the footing below ground level = 2.0m
Height of the pedestal above ground = 1.0m
Thickness of the Raft = 0.75m
Size of the pedestal, PD1 = 800mmx600mm

Size of the sheave pedestal, P4 = 500mm x 500mm

Size of the winch pedestal, P3 = 400mm x 400mm

Size of the Post pedestal, P1 = 500mm x 500mm

Size of the sheave pedestal, P2 = 550mm x 550mm

Depth of the soil filling, (2.0-0.75 = 1.25m) = 1.25m


Density of soil, Ys = 18 kN/m3
Weight of the soil = 18 x 1.25 = 22.5 kN/m2
Self weight of the raft, pedestal & plinth beam defined in STAAD.

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 8 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.3. Base pressure calculation:

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 9 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.4. Design of Raft for Bending


ELEMENTS HIGHLIGHTED CONSIDERED FOR MOMENT DESIGN

PLATE MOMENT SUMMARY

Bending Moment
Plate L/C Mx (kNm/m) My (kNm/m) Mxy (kNm/m)
Max Qx 182 109 1.0 DL + 1.0 WL -X -97.54 -1.34 26.59
Min Qx 191 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X 47.56 -1.72 -33.29
Max Qy 1946 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X -2.10 15.27 -31.76
Min Qy 1951 109 1.0 DL + 1.0 WL -X 0.45 23.09 28.38
Max Sx 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Min Sx 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Max Sy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Min Sy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Max Sxy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Min Sxy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) -1.11 -1.34 0.82
Max Mx 174 107 1.0 DL + 1.0 WL +X 257.36 56.25 -46.19
Min Mx 174 109 1.0 DL + 1.0 WL -X -270.84 -79.56 26.66
Max My 1995 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X 5.14 147.63 -63.88
Min My 299 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X -62.92 -120.01 -70.05
Max Mxy 1344 109 1.0 DL + 1.0 WL -X -101.32 -32.12 102.71
Min Mxy 1379 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X 1.32 -12.18 -138.87

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 10 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Top Design Moments


Mx1 My1 Mx2 My2 Mxd Myd
(kN-m) (kN-m) (kN-m) (kN-m) (kN-m) (kN-m)
-70.95 25.25 428.88 5.91 0.00 5.91
80.85 31.57 692.33 21.59 80.85 31.57
29.67 47.04 63.96 496.64 29.67 47.04
28.83 51.47 35.34 1808.95 28.83 51.47
-0.29 -0.52 -0.61 -0.74 0.00 0.00
-0.29 -0.52 -0.61 -0.74 0.00 0.00
-0.29 -0.52 -0.61 -0.74 0.00 0.00
-0.29 -0.52 -0.61 -0.74 0.00 0.00
-0.29 -0.52 -0.61 -0.74 0.00 0.00
-0.29 -0.52 -0.61 -0.74 0.00 0.00
303.56 102.45 295.29 64.55 303.56 102.45
-244.18 -52.89 -261.91 -76.93 0.00 0.00
69.02 211.51 32.78 941.07 69.02 211.51
7.13 -49.97 -22.04 -42.03 -22.04 0.00
1.39 70.59 227.10 72.00 1.39 70.59
140.19 126.69 1584.62 14641.77 140.19 126.69

303.56 275.83 665.00 OK 0.25 1642 191 175 1795 OK


Max. Eff. Eff. Min.
Load pt Ast Bar Spacing Ast pt.
Moment Depth Depth Depth Mu/bd2 pt. Ast
Factor reqd. reqd. dia (mm) Prov. Prov.
(Top) reqd. Prov. reqd.
(kN-m) (mm) (mm) Check 0 (N/mm2) (%) (%) (mm2) (mm) Reqd Prod (mm2) Check 0 (%)
5.91 38.49 665.00 OK 1 1.5 0.02 0.00 0.12 900 20 349 175 1795 OK 1 0.27
80.85 142.35 665.00 OK 1 1.5 0.27 0.06 0.12 900 20 349 175 1795 OK 1 0.27
47.04 108.58 665.00 OK 1 1.5 0.16 0.04 0.12 900 20 349 175 1795 OK 1 0.27
51.47 113.58 665.00 OK 1 1.5 0.17 0.04 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
303.56 275.83 665.00 OK 1 1.5 1.03 0.25 0.12 1642 20 191 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
211.51 230.24 665.00 OK 1 1.5 0.72 0.17 0.12 1129 20 278 175 1795 OK 1 0.27
22.04 74.32 665.00 OK 1 1.5 0.07 0.02 0.12 900 20 349 175 1795 OK 1 0.27
70.59 133.01 665.00 OK 1 1.5 0.24 0.06 0.12 900 20 349 175 1795 OK 1 0.27
140.19 187.44 665.00 OK 1 1.5 0.48 0.11 0.12 900 20 349 175 1795 OK 1 0.27

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 11 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Bottom Design Moments


Mx1 My1 Mx2 My2 Mxd Myd
(kN-m) (kN-m) (kN-m) (kN-m) (kN-m) (kN-m)
-124.13 -27.93 -623.95 -8.59 -124.13 -27.93
14.27 -35.01 -597.21 -25.02 0.00 -25.02
-33.86 -16.49 -68.15 -466.10 -33.86 -16.49
-27.93 -5.29 -34.44 -1762.78 -27.93 -5.29
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
-1.93 -2.16 -1.61 -1.94 -1.93 -2.16
211.17 10.06 219.43 47.96 0.00 0.00
-297.51 -106.22 -279.78 -82.18 -297.51 -106.22
-58.74 83.75 -22.50 -645.81 -22.50 0.00
-132.96 -190.06 -103.80 -197.99 -132.96 -190.06
-204.04 -134.84 -429.75 -136.25 -204.04 -134.84
-137.55 -151.05 -1581.98 -14666.13 -137.55 -151.05

297.51 273.06 665.00 OK 1608 195 175 1795 OK 0.27


Max. Eff. Eff. Min.
Load pt Ast Bar Ast pt.
Moment Depth Depth Depth Mu/bd2 pt. Spacing (mm) Ast
Factor reqd. reqd. dia Prov. Prov.
(Bottom) reqd. Pro. reqd.
(kN-m) (mm) (mm) Check 0 (N/mm2) (%) (%) (mm2) (mm) (Reqd) (Prod) (mm2) Check 0 (%)
124.13 176.38 665.00 OK 1 1.5 0.42 0.10 0.12 900 20 349 175 1795 OK 1 0.27
25.02 79.19 665.00 OK 1 1.5 0.08 0.02 0.12 900 20 349 175 1795 OK 1 0.27
33.86 92.12 665.00 OK 1 1.5 0.11 0.03 0.12 900 20 349 175 1795 OK 1 0.27
27.93 83.67 665.00 OK 1 1.5 0.09 0.02 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
2.16 23.27 665.00 OK 1 1.5 0.01 0.00 0.12 900 20 349 175 1795 OK 1 0.27
0.00 0.00 665.00 OK 1 1.5 0.00 0.00 0.12 900 20 349 175 1795 OK 1 0.27
297.51 273.06 665.00 OK 1 1.5 1.01 0.24 0.12 1608 20 195 175 1795 OK 1 0.27
22.50 75.09 665.00 OK 1 1.5 0.08 0.02 0.12 900 20 349 175 1795 OK 1 0.27
190.06 218.25 665.00 OK 1 1.5 0.64 0.15 0.12 1012 20 311 175 1795 OK 1 0.27
204.04 226.14 665.00 OK 1 1.5 0.69 0.16 0.12 1088 20 289 175 1795 OK 1 0.27
151.05 194.57 665.00 OK 1 1.5 0.51 0.12 0.12 900 20 349 175 1795 OK 1 0.27

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 12 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.5. Design of Raft for shear


ELEMENTS HIGHLIGHTED CONSIDERED FOR SHEAR DESIGN

PLATE SHEAR STRESS SUMMARY

Shear Stress (N/mm2)


Plate L/C SQX (local) SQY (local)
Max Qx 182 109 1.0 DL + 1.0 WL -X 0.424 -0.004
Min Qx 191 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X -0.525 -0.008
Max Qy 1946 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X 0.013 0.569
Min Qy 1951 109 1.0 DL + 1.0 WL -X -0.001 -0.348
Max Sx 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Min Sx 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Max Sy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Min Sy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Max Sxy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Min Sxy 2744 101 1.0 DL + 1.0 LL (WLK) + 1.0 LL (MAT) 0.002 0.006
Max Mx 39 107 1.0 DL + 1.0 WL +X -0.251 0.043
Min Mx 39 109 1.0 DL + 1.0 WL -X 0.154 -0.051
Max My 1995 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X -0.016 0.140
Min My 171 109 1.0 DL + 1.0 WL -X -0.189 0.017
Max Mxy 1390 109 1.0 DL + 1.0 WL -X 0.042 0.023
Min Mxy 1418 103 1.0 DL + 0.8 LL (WLK) + 0.8 LL (MAT) + 0.8 W.L +X -0.099 0.127

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 13 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.6. Design of Pedestal


4.6.1 Design of Pedestal, PD1

C O L U M N N O. 5 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 2000.0 mm CROSS SECTION: 600.0 mm X 800.0 mm COVER: 40.0 mm

** GUIDING LOAD CASE: 220 END JOINT: 5 TENSION COLUMN

REQD. STEEL AREA : 6144.00 Sq.mm.


REQD. CONCRETE AREA: 473856.00 Sq.mm.
MAIN REINFORCEMENT : Provide 20 - 20 dia. (1.31%, 6283.19 Sq.mm.)
(Equally distributed)
TIE REINFORCEMENT : Provide 8 mm dia. rectangular ties @ 300 mm c/c

SECTION CAPACITY BASED ON REINFORCEMENT REQUIRED (KNS-MET)


----------------------------------------------------------
Puz : 8701.06 Muz1 : 774.02 Muy1 : 557.77

INTERACTION RATIO: 0.97 (as per Cl. 39.6, IS456:2000)

SECTION CAPACITY BASED ON REINFORCEMENT PROVIDED (KNS-MET)


----------------------------------------------------------
WORST LOAD CASE: 224
END JOINT: 5 Puz : 8751.37 Muz : 760.81 Muy : 548.83 IR: 0.97

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 14 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

4.6.2 Design of Pedestal, P2

C O L U M N N O. 3565 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 2625.0 mm CROSS SECTION: 550.0 mm X 550.0 mm COVER: 40.0 mm

** GUIDING LOAD CASE: 201 END JOINT: 1567 TENSION COLUMN

REQD. STEEL AREA : 2420.00 Sq.mm.


REQD. CONCRETE AREA: 300080.00 Sq.mm.
MAIN REINFORCEMENT : Provide 8 - 20 dia. (0.83%, 2513.27 Sq.mm.)
(Equally distributed)
TIE REINFORCEMENT : Provide 8 mm dia. rectangular ties @ 300 mm c/c

SECTION CAPACITY BASED ON REINFORCEMENT REQUIRED (KNS-MET)


----------------------------------------------------------
Puz : 4958.58 Muz1 : 242.27 Muy1 : 242.27

INTERACTION RATIO: 0.41 (as per Cl. 39.6, IS456:2000)

SECTION CAPACITY BASED ON REINFORCEMENT PROVIDED (KNS-MET)


----------------------------------------------------------
WORST LOAD CASE: 201
END JOINT: 3673 Puz : 1093.27 Muz : 0.00 Muy : 0.00 IR: 0.03

4.6.3 Design of Pedestal, P3

C O L U M N N O. 3583 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 2350.0 mm CROSS SECTION: 400.0 mm X 400.0 mm COVER: 40.0 mm

** GUIDING LOAD CASE: 201 END JOINT: 1057 TENSION COLUMN

REQD. STEEL AREA : 1280.00 Sq.mm.


REQD. CONCRETE AREA: 158720.00 Sq.mm.
MAIN REINFORCEMENT : Provide 8 - 16 dia. (1.01%, 1608.50 Sq.mm.)
(Equally distributed)
TIE REINFORCEMENT : Provide 8 mm dia. rectangular ties @ 255 mm c/c

SECTION CAPACITY BASED ON REINFORCEMENT REQUIRED (KNS-MET)


----------------------------------------------------------
Puz : 2622.72 Muz1 : 88.88 Muy1 : 88.88

INTERACTION RATIO: 0.06 (as per Cl. 39.6, IS456:2000)

SECTION CAPACITY BASED ON REINFORCEMENT PROVIDED (KNS-MET)


----------------------------------------------------------
WORST LOAD CASE: 201
END JOINT: 1057 Puz : 2741.47 Muz : 113.50 Muy : 113.50 IR: 0.05

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 15 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

4.6.4 Design of Pedestal, P4

C O L U M N N O. 3572 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 1000.0 mm CROSS SECTION: 500.0 mm X 500.0 mm COVER: 40.0 mm

** GUIDING LOAD CASE: 207 END JOINT: 3679 TENSION COLUMN

REQD. STEEL AREA : 2000.00 Sq.mm.


REQD. CONCRETE AREA: 248000.00 Sq.mm.
MAIN REINFORCEMENT : Provide 8 - 20 dia. (1.0%, 2512 Sq.mm.)
(Equally distributed)
TIE REINFORCEMENT : Provide 8 mm dia. rectangular ties @ 255 mm c/c

SECTION CAPACITY BASED ON REINFORCEMENT REQUIRED (KNS-MET)


----------------------------------------------------------
Puz : 4098.00 Muz1 : 180.24 Muy1 : 180.24

INTERACTION RATIO: 0.23 (as per Cl. 39.6, IS456:2000)

SECTION CAPACITY BASED ON REINFORCEMENT PROVIDED (KNS-MET)


----------------------------------------------------------
WORST LOAD CASE: 219
END JOINT: 3679 Puz : 4247.21 Muz : 218.53 Muy : 218.53 IR: 0.24

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 16 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

3.7. Design of Plinth beam


VGTU Plinth beam - PB01 & PB02
B E A M N O. 3028 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 6000.0 mm SIZE: 300.0 mm X 600.0 mm COVER: 25.0 mm

SUMMARY OF REINF. AREA (Sq.mm)


----------------------------------------------------------------------------
SECTION 0.0 mm 1500.0 mm 3000.0 mm 4500.0 mm 6000.0 mm
----------------------------------------------------------------------------
TOP 679.56 293.24 289.17 303.70 705.60
REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)

BOTTOM 576.58 337.70 289.17 320.39 555.89


REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)
----------------------------------------------------------------------------

STAAD SPACE -- PAGE NO. 67

SUMMARY OF PROVIDED REINF. AREA


----------------------------------------------------------------------------
SECTION 0.0 mm 1500.0 mm 3000.0 mm 4500.0 mm 6000.0 mm
----------------------------------------------------------------------------
TOP 4-16í 3-16í 3-16í 3-16í 4-16í
REINF. 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s)

BOTTOM 3-16í 3-16í 3-16í 3-16í 3-16í


REINF. 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s)

SHEAR 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í


REINF. @ 200 mm c/c @ 200 mm c/c @ 200 mm c/c @ 200 mm c/c @ 200 mm c/c
----------------------------------------------------------------------------

SHEAR DESIGN RESULTS AT DISTANCE d (EFFECTIVE DEPTH) FROM FACE OF THE SUPPORT
-----------------------------------------------------------------------------

SHEAR DESIGN RESULTS AT 867.0 mm AWAY FROM START SUPPORT


VY = 33.86 MX = -9.45 LD= 222
Provide 2 Legged 8í @ 200 mm c/c

SHEAR DESIGN RESULTS AT 867.0 mm AWAY FROM END SUPPORT


VY = -34.87 MX = 10.61 LD= 220
Provide 2 Legged 8í @ 200 mm c/c

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 17 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Sheave Plinth beam - B01 to B04

B E A M N O. 3054 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 2200.0 mm SIZE: 300.0 mm X 300.0 mm COVER: 25.0 mm

STAAD SPACE -- PAGE NO. 69

SUMMARY OF REINF. AREA (Sq.mm)


----------------------------------------------------------------------------
SECTION 0.0 mm 550.0 mm 1100.0 mm 1650.0 mm 2200.0 mm
----------------------------------------------------------------------------
TOP 136.17 136.17 136.17 136.17 136.17
REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)

BOTTOM 0.00 0.00 0.00 0.00 0.00


REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)
----------------------------------------------------------------------------

SUMMARY OF PROVIDED REINF. AREA


----------------------------------------------------------------------------
SECTION 0.0 mm 550.0 mm 1100.0 mm 1650.0 mm 2200.0 mm
----------------------------------------------------------------------------
TOP 3-16í 3-16í 3-16í 3-16í 3-16í
REINF. 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s)

BOTTOM 2-16í 2-16í 2-16í 2-16í 2-16í


REINF. 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s)

SHEAR 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í


REINF. @ 125 mm c/c @ 125 mm c/c @ 125 mm c/c @ 125 mm c/c @ 125 mm c/c

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 18 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

4. DESIGN OF STAIRCASE FOUNDATION of VGTU_TR2A & TR2B Line C


4.1. Load data for Staircase_TR2A & TR2B Line C:
LOAD DATA TRESTLE TR-2A - (B.P-3)

Horizontal Vertical Horizontal


TRESTLE MARKING LOAD CASE
Fx kN Fy kN Fz kN
DEAD LOAD -3.34 -17.89 -3.50
LIVE LOAD (WALKWAY) -0.18 0.56 -1.03
LIVE LOAD (MATERIAL) 1.09 2.34 -3.30
LINE-C W L ACROSS (+) 50 M/S 5.01 10.20 3.92
W L ALONG (+) 50 M/S 23.60 38.33 -0.77
W L ACROSS (-) 50 M/S -4.74 -9.08 -3.35
W L ALONG (-) 50 M/S -22.69 -37.23 0.81

LOAD DATA TRESTLE TR-2B - (B.P-3)

Horizontal Vertical Horizontal


TRESTLE MARKING LOAD CASE
Fx kN Fy kN Fz kN
DEAD LOAD 3.14 -24.01 0.00
LIVE LOAD (WALKWAY) 0.89 -6.98 0.00
LIVE LOAD (MATERIAL) 1.02 -2.89 0.00
LINE-C W L ACROSS (+) 50 M/S -8.04 68.40 1.55
W L ALONG (+) 50 M/S 15.51 5.69 -0.01
W L ACROSS (-) 50 M/S 8.04 -67.50 -0.95
W L ALONG (-) 50 M/S -15.78 -5.60 0.02

Load Data at base of the foundation:


TR2A_Line C
Load Comb Fx (kN) Fy (kN) Fz (kN) Mx (kN-m) My (kN-m) Mz (kN-m)
101 1.0(DL+LL+ML) 2.430 14.990 7.830 23.490 0.000 7.290
102 1.0(DL+WL +Z) -1.670 7.690 -0.420 -1.260 0.000 -5.010
103 1.0(DL+WL +X) -20.260 -20.440 4.270 12.810 0.000 -60.780
104 1.0(DL+WL -Z) 8.080 26.970 6.850 20.550 0.000 24.240
105 1.0(DL+WL -X) 26.030 55.120 2.690 8.070 0.000 78.090
106 1.0DL+0.8(LL+ML+WL +Z) -1.396 7.410 3.828 11.484 0.000 -4.188
107 1.0DL+0.8(LL+ML+WL +X) -16.268 -15.094 7.580 22.740 0.000 -48.804
108 1.0DL+0.8(LL+ML+WL -Z) 6.404 22.834 9.644 28.932 0.000 19.212
109 1.0DL+0.8(LL+ML+WL -X) 20.764 45.354 6.316 18.948 0.000 62.292

TR2B_Line C
Load Comb Fx (kN) Fy (kN) Fz (kN) Mx (kN-m) My (kN-m) Mz (kN-m)
101 1.0(DL+LL+ML) -5.050 33.880 0.000 0.000 0.000 -12.625
102 1.0(DL+WL +Z) 4.900 -44.390 -1.550 -4.650 0.000 14.700
103 1.0(DL+WL +X) -18.650 18.320 0.010 0.030 0.000 -55.950
104 1.0(DL+WL -Z) -11.180 91.510 0.950 2.850 0.000 -33.540
105 1.0(DL+WL -X) 12.640 29.610 -0.020 -0.060 0.000 37.920
106 1.0DL+0.8(LL+ML+WL +Z) 1.764 -22.814 -1.240 -3.720 0.000 5.292
107 1.0DL+0.8(LL+ML+WL +X) -17.076 27.354 0.008 0.024 0.000 -51.228
108 1.0DL+0.8(LL+ML+WL -Z) -11.100 85.906 0.760 2.280 0.000 -33.300
109 1.0DL+0.8(LL+ML+WL -X) 7.956 36.386 -0.016 -0.048 0.000 23.868

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 19 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

4.2. Details of foundation: for Maximum Axial compression & Moment F3


Refer Attachment -1

4.3. Details of Raft foundation: for Maximum Axial Tension & Moment F3
Refer Attachment -1

4.4. Design of Pedestal PD2


Refer Attachment -1

5. DESIGN OF TRESTLE FOUNDATION OF BC2_TR3A & TR3B


Refer Attachment -1

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


Date 04.10.2021
DESIGN CALCULATION REPORT FOR BC2 TRESTLE
FOUNDATIONS Rev A
Page 20 of 21
PROJECT: MECHANIZATION OF BERTH-6 AT ADANI KRISHNAPATNAM PORT LIMITED

Attachment -1

HOWE NO: B3027-450-E-CV-DC-006 KFL DOC NO: OE210601-C-CS-DC-1107


DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRAHOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. BY PSR
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. BY VV
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. BY TGB

Design of Isolated Footing :- F3 Tension +Bending TR2B - C Concrete Grade = M30


Unfactored col. load without selfwt. of footing = -44 kN Fy= 500 N/mm²
Unfactored Moment @ x axis = 4.65 kN.m
Unfactored Moment @ y axis = 14.70 kN.m
Pedestal / Column Size Footing depth effe. Cover to reinf Effe. depth
Pb Pd At face D At edge d 50 mm 450 mm
500 mm 400 mm 500 mm 500 mm
Footing size Fb= 1800 mm Fd= 1800 mm Footing Depth from NGL = 2.00 m
Net Soil Bearing Capacity SBC = 125 kN/m² Density of Soil = 18.00 kN/m3
Gross Soil Bearing Capacity SBC = 161 kN/m²
Self-weight of footing = 40.50 kN Wt. of Soil above FTG.= 87.48 kN
Total Load P = 84 kN
p max x
The unfactored stresses are : 1 Fb 2
P/A = 25.80 kN/m² B Pb
Mx/Zx = 4.78 kN/m² Pd

My/Zy = 15.12 kN/m² Fd


X
Pressure at 1 = P/A + Mx/Zx + My/Zy = 45.71 kN/m²
Pressure at 2 = P/A + Mx/Zx - My/Zy = 15.46 kN/m² Y
3 A 4 p min x
Pressure at 3 = P/A - Mx/Zx + My/Zy = 36.14 kN/m²

p min y
p max y

Pressure at 4 = P/A - Mx/Zx - My/Zy = 5.89 kN/m²


Max pressure < SBC hence, Footing Size is OK!
There is no tension hence, Footing Size is OK!
in X-direction in Y-direction
Offset A & B = 650.00 mm 700.00 mm
p maximum (P without soil weight & selfwt.) = 6.21 kN/m² 6.21 kN/m²
p minimum (P without soil weight & selfwt.) = -3.36 kN/m² -3.36 kN/m²
Facored Moment @ yy & Moment @ xx 3.54 kN.m 4.11 kN.m
d effective required 46 mm 45 mm
Cross section area at face 0.900 m² 0.900 m²
Reinforcement required 18 mm² 21 mm²
Minimum 0.12% reinf. 1080 mm² 1080 mm²
Reinf. Bar Dia 12 mm 12 mm
Spacing of bars 191 mm 191 mm
Nos. of bars required 10 nos. 10 nos.
Provided reinf. % 0.126 % 0.126 %

Page 1 of 2
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
Check for One Way Shear at d distance from face of column/pedestal
Effective depth at d distance 440.00 mm 440.00 mm
Top width of ftg at d distance 1300.00 mm 1400.00 mm
Cross section area at d distance 682000 mm² 704000 mm²
Shear Force at d distance 3.35 kN 4.19 kN
Shear stress at d distance tv 0.005 N/mm² 0.006 N/mm²
Provided reinf. % at d distance 0.166 % 0.161 %
Permissible Shear Stress tc 0.307 N/mm² 0.303 N/mm²
tv<tc, OK ! tv<tc, OK !
Check for two way (Punching) Shear at d/2 distance from face of col./pedestal
Perimeter at crictical section = 3600.00 mm Area resisting shear = 1800000 mm²
Effective depth at critical section = 500.00 mm Design shear = 94.14 kN
tc = 1.37 N/mm² ks = 1 tc' = 1.37 N/mm²
tv = 0.05 N/mm² tv < tc, hence, O.K.
Check for bearing pressure at column base
Actual bearing stress = Pu / (axb) = -0.333 N/mm²
A1 (= Fb x Fd ) = 3240000 mm² A2 (= Pb x Pd ) = 200000 mm²
Perm. Bearing Stress=0.45 x Fck x sqrt(A1/A2) = 54.3 N/mm² Safe O.K.

Page 2 of 2
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS REV NO A
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. VV
BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. TGB
BY
Design of Isolated Footing :- F3 Compression +Bending TR2A - C Concrete Grade = M30
Unfactored col. load without selfwt. of footing = 55 kN Fy= 500 N/mm²
Unfactored Moment @ x axis = 8.07 kN.m
Unfactored Moment @ y axis = 78.09 kN.m
Pedestal / Column Size Footing depth effe. Cover to reinf Effe. depth
Pb Pd At face D At edge d 50 mm 450 mm
500 mm 400 mm 500 mm 500 mm
Footing size Fb= 2200 mm Fd= 2200 mm Footing Depth from NGL = 2.00 m
Net Soil Bearing Capacity SBC = 125 kN/m² Density of Soil = 18.00 kN/m3
Gross Soil Bearing Capacity SBC = 161 kN/m²
Self-weight of footing = 60.50 kN Wt. of Soil above FTG.= 130.68 kN
Total Load P = 246 kN
p max x
The unfactored stresses are : 1 Fb 2
P/A = 50.86 kN/m² B Pb
Mx/Zx = 4.55 kN/m² Pd

My/Zy = 44.00 kN/m² Fd


X
Pressure at 1 = P/A + Mx/Zx + My/Zy = 99.41 kN/m²
Pressure at 2 = P/A + Mx/Zx - My/Zy = 11.41 kN/m² Y
3 A 4 p min x
Pressure at 3 = P/A - Mx/Zx + My/Zy = 90.32 kN/m²

p min y
p max y

Pressure at 4 = P/A - Mx/Zx - My/Zy = 2.31 kN/m²


Max pressure < SBC hence, Footing Size is OK!
There is no tension hence, Footing Size is OK!
in X-direction in Y-direction
Offset A & B = 850.00 mm 900.00 mm
p maximum (P without soil weight & selfwt.) = 59.91 kN/m² 59.91 kN/m²
p minimum (P without soil weight & selfwt.) = 50.82 kN/m² 50.82 kN/m²
Facored Moment @ yy & Moment @ xx 71.42 kN.m 80.07 kN.m
d effective required 208 mm 197 mm
Cross section area at face 1.100 m² 1.100 m²
Reinforcement required 378 mm² 422 mm²
Minimum 0.12% reinf. 1320 mm² 1320 mm²
Reinf. Bar Dia 12 mm 12 mm
Spacing of bars 193 mm 193 mm
Nos. of bars required 12 nos. 12 nos.
Provided reinf. % 0.123 % 0.123 %
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS REV NO A
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. VV
BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. TGB
BY
Check for One Way Shear at d distance from face of column/pedestal
Effective depth at d distance 440.00 mm 440.00 mm
Top width of ftg at d distance 1300.00 mm 1400.00 mm
Cross section area at d distance 770000 mm² 792000 mm²
Shear Force at d distance 79.09 kN 88.97 kN
Shear stress at d distance tv 0.103 N/mm² 0.112 N/mm²
Provided reinf. % at d distance 0.176 % 0.171 %
Permissible Shear Stress tc 0.316 N/mm² 0.312 N/mm²
tv<tc, OK ! tv<tc, OK !
Check for two way (Punching) Shear at d/2 distance from face of col./pedestal
Perimeter at crictical section = 3600.00 mm Area resisting shear = 1800000 mm²
Effective depth at critical section = 500.00 mm Design shear = 307.66 kN
tc = 1.37 N/mm² ks = 1 tc' = 1.37 N/mm²
tv = 0.17 N/mm² tv < tc, hence, O.K.
Check for bearing pressure at column base
Actual bearing stress = Pu / (axb) = 0.413 N/mm²
A1 (= Fb x Fd ) = 4840000 mm² A2 (= Pb x Pd ) = 200000 mm²
Perm. Bearing Stress=0.45 x Fck x sqrt(A1/A2) = 66.4 N/mm² Safe O.K.
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRAHOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. BY PSR
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. BY TGB
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. BY RRC

Design of Isolated Footing :- F3 Tension +Bending TR2A - C Concrete Grade = M30


Unfactored col. load without selfwt. of footing = -20 kN Fy= 500 N/mm²
Unfactored Moment @ x axis = 12.81 kN.m
Unfactored Moment @ y axis = 60.78 kN.m
Pedestal / Column Size Footing depth effe. Cover to reinf Effe. depth
Pb Pd At face D At edge d 50 mm 450 mm
500 mm 400 mm 500 mm 500 mm
Footing size Fb= 2200 mm Fd= 2200 mm Footing Depth from NGL = 2.00 m
Net Soil Bearing Capacity SBC = 125 kN/m² Density of Soil = 18.00 kN/m3
Gross Soil Bearing Capacity SBC = 161 kN/m²
Self-weight of footing = 60.50 kN Wt. of Soil above FTG.= 130.68 kN
Total Load P = 171 kN
p max x
The unfactored stresses are : 1 Fb 2
P/A = 35.37 kN/m² B Pb
Mx/Zx = 7.22 kN/m² Pd

My/Zy = 34.25 kN/m² Fd


X
Pressure at 1 = P/A + Mx/Zx + My/Zy = 76.83 kN/m²
Pressure at 2 = P/A + Mx/Zx - My/Zy = 8.34 kN/m² Y
3 A 4 p min x
Pressure at 3 = P/A - Mx/Zx + My/Zy = 62.40 kN/m²

p min y
p max y

Pressure at 4 = P/A - Mx/Zx - My/Zy = -6.10 kN/m²


Max pressure < SBC hence, Footing Size is OK!
There is a tension, hence increase the size of Footing??
in X-direction in Y-direction
Offset A & B = 850.00 mm 900.00 mm
p maximum (P without soil weight & selfwt.) = 37.33 kN/m² 37.33 kN/m²
p minimum (P without soil weight & selfwt.) = 22.90 kN/m² 22.90 kN/m²
Facored Moment @ yy & Moment @ xx 44.51 kN.m 49.90 kN.m
d effective required 164 mm 155 mm
Cross section area at face 1.100 m² 1.100 m²
Reinforcement required 232 mm² 260 mm²
Minimum 0.12% reinf. 1320 mm² 1320 mm²
Reinf. Bar Dia 12 mm 12 mm
Spacing of bars 193 mm 193 mm
Nos. of bars required 12 nos. 12 nos.
Provided reinf. % 0.123 % 0.123 %

Page 1 of 2
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS A
REV NO
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
Check for One Way Shear at d distance from face of column/pedestal
Effective depth at d distance 440.00 mm 440.00 mm
Top width of ftg at d distance 1300.00 mm 1400.00 mm
Cross section area at d distance 770000 mm² 792000 mm²
Shear Force at d distance 49.28 kN 55.44 kN
Shear stress at d distance tv 0.064 N/mm² 0.070 N/mm²
Provided reinf. % at d distance 0.176 % 0.171 %
Permissible Shear Stress tc 0.316 N/mm² 0.312 N/mm²
tv<tc, OK ! tv<tc, OK !
Check for two way (Punching) Shear at d/2 distance from face of col./pedestal
Perimeter at crictical section = 3600.00 mm Area resisting shear = 1800000 mm²
Effective depth at critical section = 500.00 mm Design shear = 213.93 kN
tc = 1.37 N/mm² ks = 1 tc' = 1.37 N/mm²
tv = 0.12 N/mm² tv < tc, hence, O.K.
Check for bearing pressure at column base
Actual bearing stress = Pu / (axb) = -0.150 N/mm²
A1 (= Fb x Fd ) = 4840000 mm² A2 (= Pb x Pd ) = 200000 mm²
Perm. Bearing Stress=0.45 x Fck x sqrt(A1/A2) = 66.4 N/mm² Safe O.K.

Page 2 of 2
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS REV NO A
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. VV
BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. TGB
BY
Design of Isolated Footing :- F3 Compression +Bending TR2B - C Concrete Grade = M30
Unfactored col. load without selfwt. of footing = 92 kN Fy= 500 N/mm²
Unfactored Moment @ x axis = 2.85 kN.m
Unfactored Moment @ y axis = 33.54 kN.m
Pedestal / Column Size Footing depth effe. Cover to reinf Effe. depth
Pb Pd At face D At edge d 50 mm 450 mm
500 mm 400 mm 500 mm 500 mm
Footing size Fb= 1500 mm Fd= 1500 mm Footing Depth from NGL = 2.00 m
Net Soil Bearing Capacity SBC = 125 kN/m² Density of Soil = 18.00 kN/m3
Gross Soil Bearing Capacity SBC = 161 kN/m²
Self-weight of footing = 28.13 kN Wt. of Soil above FTG.= 60.75 kN
Total Load P = 180 kN
p max x
The unfactored stresses are : 1 Fb 2
P/A = 80.17 kN/m² B Pb
Mx/Zx = 5.07 kN/m² Pd

My/Zy = 59.63 kN/m² Fd


X
Pressure at 1 = P/A + Mx/Zx + My/Zy = 144.86 kN/m²
Pressure at 2 = P/A + Mx/Zx - My/Zy = 25.61 kN/m² Y
3 A 4 p min x
Pressure at 3 = P/A - Mx/Zx + My/Zy = 134.73 kN/m²

p min y
p max y

Pressure at 4 = P/A - Mx/Zx - My/Zy = 15.48 kN/m²


Max pressure < SBC hence, Footing Size is OK!
There is no tension hence, Footing Size is OK!
in X-direction in Y-direction
Offset A & B = 500.00 mm 550.00 mm
p maximum (P without soil weight & selfwt.) = 105.36 kN/m² 105.36 kN/m²
p minimum (P without soil weight & selfwt.) = 95.23 kN/m² 95.23 kN/m²
Facored Moment @ yy & Moment @ xx 29.63 kN.m 35.86 kN.m
d effective required 134 mm 132 mm
Cross section area at face 0.750 m² 0.750 m²
Reinforcement required 154 mm² 186 mm²
Minimum 0.12% reinf. 900 mm² 900 mm²
Reinf. Bar Dia 12 mm 12 mm
Spacing of bars 203 mm 203 mm
Nos. of bars required 8 nos. 8 nos.
Provided reinf. % 0.121 % 0.121 %
DATE 04-10-21
DESIGN CALCULATION REPORT FOR CONVEYOR
BC2 TRESTLE FOUNDATIONS REV NO A
MECHANIZATION AT KRISHNAPATNAM PORT, ANDRA HOWE DOC B3027-450-E-
PROJECT : PRADESH NO: CV-DC-006
PREPARED
CLIENT : ADANI KRISHNAPATNAM PORT Ltd. PSR
BY
CHECKED
CLIENT'S CONSULTANT : HOWE ENGINEERING PROJECTS (I) Pvt. Ltd. VV
BY
APPROVED
CONSULTANT : KALI-FL CONSULTING ENGINEERS Pvt. Ltd. TGB
BY
Check for One Way Shear at d distance from face of column/pedestal
Effective depth at d distance 440.00 mm 440.00 mm
Top width of ftg at d distance 1300.00 mm 1400.00 mm
Cross section area at d distance 616000 mm² 638000 mm²
Shear Force at d distance 11.85 kN 23.71 kN
Shear stress at d distance tv 0.019 N/mm² 0.037 N/mm²
Provided reinf. % at d distance 0.147 % 0.142 %
Permissible Shear Stress tc 0.291 N/mm² 0.286 N/mm²
tv<tc, OK ! tv<tc, OK !
Check for two way (Punching) Shear at d/2 distance from face of col./pedestal
Perimeter at crictical section = 3600.00 mm Area resisting shear = 1800000 mm²
Effective depth at critical section = 500.00 mm Design shear = 173.47 kN
tc = 1.37 N/mm² ks = 1 tc' = 1.37 N/mm²
tv = 0.10 N/mm² tv < tc, hence, O.K.
Check for bearing pressure at column base
Actual bearing stress = Pu / (axb) = 0.686 N/mm²
A1 (= Fb x Fd ) = 2250000 mm² A2 (= Pb x Pd ) = 200000 mm²
Perm. Bearing Stress=0.45 x Fck x sqrt(A1/A2) = 45.3 N/mm² Safe O.K.