Professional Documents
Culture Documents
Datasheet For Cable: 1 Pair Overall Shielded Armoured Cable, Type F (Single Pair Cable Shall Have Only Overall Shielding)
Datasheet For Cable: 1 Pair Overall Shielded Armoured Cable, Type F (Single Pair Cable Shall Have Only Overall Shielding)
6 Insulation
a) Reference standard VDE-0207 Part 4
b) Material Extruded PVC Type YI3
c) Thickness (mm) 0.25 / 0.3 / 0.35 (Min/Nom/Max)
d) Minimum volume resistivity ( in ohm
cm)
(i) at 20 deg C 1 X 1014
(ii) at 70 deg C 1 X 1011
7 Pair & Twisting
a) Whether pairs are twisted Yes
b) Single layer of binder tape on each pair Yes
provided
c) Max. lay of twist (mm) 50
d) Pair identification. As per manufacturer’s standard.
e) Unit formation of four pairs with Yes
numbered polyester binder tape for
cables more than 4P is provided.
8 Shield
a) Material Al-Mylar Tape
b) Min. Thickness of individual shield (in 0.028
mm)
c) Min. Thickness of overall shield (in 0.055
mm)
d) Overlap / Coverage (minimum) 20% / 100%
DATASHEET FOR CABLE
9 Drain wire
a) Reference standard IS-8130
b) Material Annealed Tinned Copper (ATC)
c) Size ( sq mm) / No. of strands / 0.5 / Seven (7) / 0.3 (nom) (Approx.)
Diameter of strands (mm) (before
stranding)
c) Separate drain wires for individual as Yes
well as overall shield provided