RABEGH HYDRAULIC CALCULATION

Fire Sprinkler Reports

for

MINISTRY OF HEALTH (MOH)

RIYADH
RIYADH

Prepared By:

Eng'r. Manikandan
RED WATER
PRINCE SULTAN BIN ABDULAZIZ ROAD
AL MAATHER RIYADH

12/28/2019
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 2

General Project Data Report

General Data
Project Title: RABEGH HYDRAULIC
Project File Name: RABEGH Hydraulic Calculation..fiw
CALCULATION
Designed By: Eng'r. Manikandan Date: 12/28/2019
Code Reference: NFPA-13 & NFPA-14 Approving Agency: DAAR ENGINEERING
Client Name: MINISTRY OF HEALTH (MOH) Phone:
Address: RIYADH City, State Zip Code: RIYADH
Company Name: RED WATER Representative: AWAD
Company Address: PRINCE SULTAN BIN ABDULAZIZ
City And State: AL MAATHER RIYADH
ROAD
Phone:
Building Name: RABEGH GENERAL HOSPITAL Building Owner: MINISTRY OF HEALTH
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Light Hazard Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 200 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 50.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Model:
Size: 1/2 Temperature Rating: 156 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 353.69 gpm Calculated Inflow Residual Pressure: 84.87 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.50 psi Minimum Desired Flow Density: 0.10 gpm/ft²
Number Of Active Nodes: 29
Number Of Active Pipes: 28 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 12 Number Of Inactive Sprinklers: 0

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Non-Sprinkler ---- N/A 26.22 29.53 50.00


1
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 12.65 29.53 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 14.93 29.53 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 24.96 29.53 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 12.74 29.53 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 13.74 29.53 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 12.53 29.53 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 18.82 29.53 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 19.69 29.53 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 18.51 29.53 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 25.16 29.53 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 16.26 29.53 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 18.67 29.53 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 32.08 29.53 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.65 43.00 29.53 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 27.16 29.53 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 27.81 29.53 0.00


17
---- 0.000 0.0 ---- 0.0 0.00

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 31.20 29.53 0.00


18
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 36.96 29.53 0.00


19
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 44.70 29.53 0.00


20
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 52.32 29.53 0.00


21
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 55.00 29.53 0.00


22
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 60.67 29.53 0.00


23
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 64.80 29.53 0.00


24
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 67.12 29.53 0.00


25
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 82.95 -3.28 0.00


26
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 83.15 -3.28 0.00


27
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 83.25 -3.28 0.00


28
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 84.87 -6.56 0.00


29
---- 0.000 0.0 ---- 0.0 0.00

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 5

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 16 SCHED 40 WET STEEL 1.500 0 E 6.66 4.00 10.66 120

2 3 SCHED 40 WET STEEL 1.000 0 2E 13.32 4.00 17.32 120

3 4 SCHED 40 WET STEEL 1.000 0 ET 12.60 7.00 19.60 120

4 17 SCHED 40 WET STEEL 1.250 0 T 2.17 6.00 8.16 120

5 6 SCHED 40 WET STEEL 1.000 0 E 5.58 2.00 7.58 120

7 6 SCHED 40 WET STEEL 1.000 0 E 7.28 2.00 9.28 120

8 9 SCHED 40 WET STEEL 1.000 0 E 2.59 2.00 4.59 120

10 9 SCHED 40 WET STEEL 1.000 0 E 4.30 2.00 6.30 120

6 9 SCHED 40 WET STEEL 1.000 0 T 7.58 5.00 12.58 120

9 11 SCHED 40 WET STEEL 1.500 0 T 13.39 8.00 21.39 120

11 18 SCHED 40 WET STEEL 1.500 0 ET 2.17 12.00 14.16 120

12 13 SCHED 40 WET STEEL 1.000 0 2E 10.53 4.00 14.53 120

13 14 SCHED 40 WET STEEL 1.000 0 T 16.04 5.00 21.04 120

14 19 SCHED 40 WET STEEL 1.250 0 ET 2.17 9.00 11.16 120

15 20 SCHED 40 WET STEEL 1.000 0 E 2.17 2.00 4.16 120

16 17 SCHED 40 WET STEEL 1.500 0 E 3.38 4.00 7.38 120

17 18 SCHED 40 WET STEEL 2.000 0 T 15.68 10.00 25.68 120

18 19 SCHED 40 WET STEEL 2.500 0 T 17.39 12.00 29.39 120

19 20 SCHED 40 WET STEEL 2.500 0 T 11.19 12.00 23.19 120

20 21 SCHED 40 WET STEEL 3.000 0 T 38.55 15.00 53.55 120

21 22 SCHED 40 WET STEEL 3.000 0 E 11.84 7.00 18.84 120

22 23 SCHED 40 WET STEEL 4.000 0 T 129.95 20.00 149.95 120

23 24 SCHED 40 WET STEEL 4.000 0 E 98.88 10.00 108.89 120

24 25 SCHED 40 WET STEEL 4.000 0 TG 39.47 22.00 61.47 120

25 26 SCHED 40 WET STEEL 4.000 0 E 32.81 10.00 42.81 120

26 27 PVC, CLASS 200 6.000 0 EG 30.91 25.60 56.51 150

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 6

Fire Sprinkler Input Data

Pipe Input Data (cont'd)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

27 28 PVC, CLASS 200 6.000 0 E 6.56 21.10 27.66 150

28 29 SCHED 40 WET STEEL 6.000 0 GC 3.28 35.00 38.28 120

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 7

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 16 0 -50.00 0.00 50.00 0.00 26.22

2 3 0 -20.10 20.10 0.00 0.00 12.65 0.00074

3 2 0 20.10 21.83 0.00 0.00 14.93 0.00168


3 4 0 -41.92

4 3 0 41.92 28.23 0.00 0.00 24.96 0.00520


4 17 0 -70.14

5 6 0 -20.16 20.16 0.00 0.00 12.74 0.00116

6 5 0 20.16 0.00 0.00 0.00 13.74 -0.00044


6 7 0 20.00
6 9 0 -40.16

7 6 0 -20.00 20.00 0.00 0.00 12.53 0.00044

8 9 0 -24.51 24.51 0.00 0.00 18.82 0.00262

9 6 0 40.16 0.00 0.00 0.00 19.69 0.00000


9 8 0 24.51
9 10 0 24.31
9 11 0 -88.98

10 9 0 -24.31 24.31 0.00 0.00 18.51 0.00247

11 9 0 88.98 28.34 0.00 0.00 25.16 0.00487


11 18 0 -117.31

12 13 0 -22.78 22.78 0.00 0.00 16.26 0.00114

13 12 0 22.78 24.41 0.00 0.00 18.67 0.00209


13 14 0 -47.19

14 13 0 47.19 32.00 0.00 0.00 32.08 0.00640


14 19 0 -79.19

15 20 0 -37.04 37.05 0.00 0.00 43.00 0.00888

16 1 0 50.00 0.00 0.00 0.00 27.16 0.00000


16 17 0 -50.00

17 4 0 70.14 0.00 0.00 0.00 27.81 0.00000


17 16 0 50.00
17 18 0 -120.14

18 11 0 117.31 0.00 0.00 0.00 31.20 0.00000


18 17 0 120.14
18 19 0 -237.45

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 8

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
19 14 0 79.19 0.00 0.00 0.00 36.96 0.00000
19 18 0 237.45
19 20 0 -316.64

20 15 0 37.04 0.00 0.00 0.00 44.70 0.00000


20 19 0 316.64
20 21 0 -353.69

21 20 0 353.69 0.00 0.00 0.00 52.32 0.00000


21 22 0 -353.69

22 21 0 353.69 0.00 0.00 0.00 55.00 0.00000


22 23 0 -353.69

23 22 0 353.69 0.00 0.00 0.00 60.67 0.00000


23 24 0 -353.69

24 23 0 353.69 0.00 0.00 0.00 64.80 0.00000


24 25 0 -353.69

25 24 0 353.69 0.00 0.00 0.00 67.12 0.00000


25 26 0 -353.69

26 25 0 353.69 0.00 0.00 0.00 82.95 0.00000


26 27 0 -353.69

27 26 0 353.69 0.00 0.00 0.00 83.15 0.00000


27 28 0 -353.69

28 27 0 353.69 0.00 0.00 0.00 83.25 0.00000


28 29 0 -353.69

29 28 0 353.69 0.00 0.00 -353.69 84.87

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 9

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

2 5.65 29.53 20.10 12.65 1.00 20.10 0.13134 13.32 2.275


3 5.65 29.53 21.83 14.93 1.049 20.10 2E 4.00 0.000
SCHED 40 WET STEEL 120 7.46 0 17.32 2.275

3 5.65 29.53 21.83 14.93 1.00 21.83 0.51195 12.60 10.033


4 5.65 29.53 28.23 24.96 1.049 41.92 ET 7.00 0.000
SCHED 40 WET STEEL 120 15.56 0 19.60 10.033

5 5.65 29.53 20.16 12.74 1.00 20.16 0.13216 5.58 1.001


6 0.00 29.53 0.00 13.74 1.049 20.16 E 2.00 0.000
SCHED 40 WET STEEL 120 7.49 0 7.58 1.001

7 5.65 29.53 20.00 12.53 1.00 20.00 0.13018 7.28 1.208


6 0.00 29.53 0.00 13.74 1.049 20.00 E 2.00 0.000
SCHED 40 WET STEEL 120 7.42 0 9.28 1.208

6 0.00 29.53 0.00 13.74 1.00 0.00 0.47292 7.58 5.949


9 0.00 29.53 0.00 19.69 1.049 40.16 T 5.00 0.000
SCHED 40 WET STEEL 120 14.91 0 12.58 5.949

8 5.65 29.53 24.51 18.82 1.00 24.51 0.18960 2.59 0.871


9 0.00 29.53 0.00 19.69 1.049 24.51 E 2.00 0.000
SCHED 40 WET STEEL 120 9.10 0 4.59 0.871

10 5.65 29.53 24.31 18.51 1.00 24.31 0.18675 4.30 1.176


9 0.00 29.53 0.00 19.69 1.049 24.31 E 2.00 0.000
SCHED 40 WET STEEL 120 9.02 0 6.30 1.176

9 0.00 29.53 0.00 19.69 1.50 0.00 0.25576 13.39 5.470


11 5.65 29.53 28.34 25.16 1.610 88.98 T 8.00 0.000
SCHED 40 WET STEEL 120 14.02 0 21.39 5.470

12 5.65 29.53 22.78 16.26 1.00 22.78 0.16568 10.53 2.407


13 5.65 29.53 24.41 18.67 1.049 22.78 2E 4.00 0.000
SCHED 40 WET STEEL 120 8.46 0 14.53 2.407

13 5.65 29.53 24.41 18.67 1.00 24.41 0.63739 16.04 13.413


14 5.65 29.53 32.00 32.08 1.049 47.19 T 5.00 0.000
SCHED 40 WET STEEL 120 17.52 0 21.04 13.413

1 0.00 29.53 50.00 26.22 1.50 50.00 0.08805 6.66 0.939


16 0.00 29.53 0.00 27.16 1.610 50.00 E 4.00 0.000
SCHED 40 WET STEEL 120 7.88 0 10.66 0.939

4 5.65 29.53 28.23 24.96 1.25 28.23 0.34897 2.17 2.849


17 0.00 29.53 0.00 27.81 1.380 70.14 T 6.00 0.000
SCHED 40 WET STEEL 120 15.05 0 8.16 2.849

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 10

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

16 0.00 29.53 0.00 27.16 1.50 0.00 0.08805 3.38 0.650


17 0.00 29.53 0.00 27.81 1.610 50.00 E 4.00 0.000
SCHED 40 WET STEEL 120 7.88 0 7.38 0.650

11 5.65 29.53 28.34 25.16 1.50 28.34 0.42655 2.17 6.042


18 0.00 29.53 0.00 31.20 1.610 117.31 ET 12.00 0.000
SCHED 40 WET STEEL 120 18.49 0 14.16 6.042

17 0.00 29.53 0.00 27.81 2.00 0.00 0.13203 15.68 3.391


18 0.00 29.53 0.00 31.20 2.067 120.14 T 10.00 0.000
SCHED 40 WET STEEL 120 11.49 0 25.68 3.391

14 5.65 29.53 32.00 32.08 1.25 32.00 0.43677 2.17 4.877


19 0.00 29.53 0.00 36.96 1.380 79.19 ET 9.00 0.000
SCHED 40 WET STEEL 120 16.99 0 11.16 4.877

18 0.00 29.53 0.00 31.20 2.50 0.00 0.19599 17.39 5.760


19 0.00 29.53 0.00 36.96 2.469 237.45 T 12.00 0.000
SCHED 40 WET STEEL 120 15.91 0 29.39 5.760

15 5.65 29.53 37.05 43.00 1.00 37.05 0.40718 2.17 1.696


20 0.00 29.53 0.00 44.70 1.049 37.04 E 2.00 0.000
SCHED 40 WET STEEL 120 13.75 0 4.16 1.696

19 0.00 29.53 0.00 36.96 2.50 0.00 0.33380 11.19 7.740


20 0.00 29.53 0.00 44.70 2.469 316.64 T 12.00 0.000
SCHED 40 WET STEEL 120 21.22 0 23.19 7.740

20 0.00 29.53 0.00 44.70 3.00 0.00 0.14222 38.55 7.616


21 0.00 29.53 0.00 52.32 3.068 353.69 T 15.00 0.000
SCHED 40 WET STEEL 120 15.35 0 53.55 7.616

21 0.00 29.53 0.00 52.32 3.00 0.00 0.14222 11.84 2.680


22 0.00 29.53 0.00 55.00 3.068 353.69 E 7.00 0.000
SCHED 40 WET STEEL 120 15.35 0 18.84 2.680

22 0.00 29.53 0.00 55.00 4.00 0.00 0.03786 129.95 5.678


23 0.00 29.53 0.00 60.67 4.026 353.69 T 20.00 0.000
SCHED 40 WET STEEL 120 8.91 0 149.95 5.678

23 0.00 29.53 0.00 60.67 4.00 0.00 0.03786 98.89 4.123


24 0.00 29.53 0.00 64.80 4.026 353.69 E 10.00 0.000
SCHED 40 WET STEEL 120 8.91 0 108.89 4.123

24 0.00 29.53 0.00 64.80 4.00 0.00 0.03786 39.47 2.327


25 0.00 29.53 0.00 67.12 4.026 353.69 TG 22.00 0.000
SCHED 40 WET STEEL 120 8.91 0 61.47 2.327

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 11

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

25 0.00 29.53 0.00 67.12 4.00 0.00 0.03786 32.81 1.621


26 0.00 -3.28 0.00 82.95 4.026 353.69 E 10.00 14.206
SCHED 40 WET STEEL 120 8.91 0 42.81 15.827

26 0.00 -3.28 0.00 82.95 6.00 0.00 0.00361 30.91 0.204


27 0.00 -3.28 0.00 83.15 5.993 353.69 EG 25.60 0.000
PVC, CLASS 200 150 4.02 0 56.51 0.204

27 0.00 -3.28 0.00 83.15 6.00 0.00 0.00361 6.56 0.100


28 0.00 -3.28 0.00 83.25 5.993 353.69 E 21.10 0.000
PVC, CLASS 200 150 4.02 0 27.66 0.100

28 0.00 -3.28 0.00 83.25 6.00 0.00 0.00515 3.28 0.197


29 0.00 -6.56 0.00 84.87 6.065 353.69 GC 35.00 1.421
SCHED 40 WET STEEL 120 3.93 0 38.28 1.618

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 12

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

2 5.65 29.53 12.65 200.00 0.100 20.10


Sub Totals For Non-Group 200.00 0.100 20.10

3 5.65 29.53 14.93 200.00 0.109 21.83


Sub Totals For Non-Group 200.00 0.109 21.83

4 5.65 29.53 24.96 200.00 0.141 28.23


Sub Totals For Non-Group 200.00 0.141 28.23

5 5.65 29.53 12.74 200.00 0.101 20.16


Sub Totals For Non-Group 200.00 0.101 20.16

7 5.65 29.53 12.53 200.00 0.100 20.00


Sub Totals For Non-Group 200.00 0.100 20.00

8 5.65 29.53 18.82 200.00 0.123 24.51


Sub Totals For Non-Group 200.00 0.123 24.51

10 5.65 29.53 18.51 200.00 0.122 24.31


Sub Totals For Non-Group 200.00 0.122 24.31

11 5.65 29.53 25.16 200.00 0.142 28.34


Sub Totals For Non-Group 200.00 0.142 28.34

12 5.65 29.53 16.26 200.00 0.114 22.78


Sub Totals For Non-Group 200.00 0.114 22.78

13 5.65 29.53 18.67 200.00 0.122 24.41


Sub Totals For Non-Group 200.00 0.122 24.41

14 5.65 29.53 32.08 200.00 0.160 32.00


Sub Totals For Non-Group 200.00 0.160 32.00

15 5.65 29.53 43.00 200.00 0.185 37.05


Sub Totals For Non-Group 200.00 0.185 37.05

Totals For All Groups 2400.00 0.127 303.72

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 13

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 7
HMD Actual Residual Pressure: 12.53 psi
HMD Actual GPM: 20.00 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.100 gpm/ft²
Application Average Density: 0.202 gpm/ft²
Application Average Area Per Sprinkler: 125.00 ft²
Sprinkler Flow: 303.72 gpm
Average Sprinkler Flow: 25.31 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 19 - 20 ) 21.22 ft/sec
Maximum Velocity Pressure ( In Pipe 19 - 20 ) 3.03 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0090 psi
Actual Average Nodal Pressure Imbalance: 0.0033 psi
Actual Maximum Nodal Flow Imbalance: 0.0089 gpm
Actual Average Nodal Flow Imbalance: 0.0013 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 28
Number Of Flowing Sprinklers: 12

Pipe System Water Volume: 294.88 gal

Sprinkler Flow: 303.72 gpm


Non-Sprinkler Flow: 50.00 gpm

Minimum Required Residual Pressure At System Inflow


84.87 psi
Node:
Demand Flow At System Inflow Node: 353.69 gpm

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem RABEGH HYDRAULIC CALCULATION
heaven Page 14

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100

90
85

80

70
Pressure psi

60

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 84.87 psi
Calculated Flow Rate: 353.69 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 15.63 psi

H:\ ...\RABEGH Hydraulic Calculation.fiw Saturday, December 28, 2019, 2:53 PM