2021 the 4th International Conference on Energy, Electrical and Power Engineering

Research on Detection of Faulty Insulators Using


Optical Sensors
2021 4th International Conference on Energy, Electrical and Power Engineering (CEEPE) | 978-1-6654-3363-1/20/$31.00 ©2021 IEEE | DOI: 10.1109/CEEPE51765.2021.9475830

Hongfeng Ma, Youchong Duan, Zhongkai Xu, Zongyu Liu, Feng Guo
Yingkou Electric Power Company
State Grid Liaoning Electric Power Company, LTD
Yingkou, China
smwwhu@163.com

Abstract—Insulators are important parts of transmission lines. insulator. Fig. 1 is a schematic diagram of the electric field
The reliability and stability of their operation determine the safe distribution of a good insulator and a faulty insulator, the
operation of power systems. Therefore, the regular inspection of electric field around the insulator is decomposed into a
faulty insulators is one of the essential tasks in the operation and horizontal component and a vertical component. The vertical
maintenance of transmission lines. In this paper, an insulator component is parallel to the high and low voltage electrodes of
detection method based on fiber-optic electric field sensor is the insulator. Under normal conditions, the change curve along
proposed, the test results show that the deterioration of the the axis of the insulator is smooth and generally U-shaped, this
insulator at the high voltage end, the low voltage end and the is determined by the relative size of the stray capacitance
middle part can be identified by the results. It shows that the
between the insulator and the wire and the iron tower, at the
detection method proposed in this paper can be an effective
method for detecting faulty insulators on transmission lines
high voltage end close to the wire side, because the shunting
effect is greater than the confluence effect, the farther away the
Keywords-optical sensor, deteriorated insulator, detection insulator is from the high voltage end, the smaller the current
technology, electric field distribution obtained by the insulator's own capacitance, so the voltage
drop is smaller; and the grounding end close to the tower has a
smaller shunting effect than the confluence effect. Therefore,
I. INTRODUCTION the voltage drop of the insulators near the tower side will rise,
In recent years, the number of high-voltage transmission making the entire electric field distribution appear as an
lines has increased significantly, and the operating status of asymmetric "U-shaped" distribution [7-9].
insulators is closely related to the security of the power grid.
As the insulator is exposed to a more complicated external
environment for a long time, the insulation performance and
mechanical performance will be greatly reduced [1-3]. This
may cause an accident in the power transmission system, so
distinguishing the characteristics of deteriorated insulators
among strings precisely and timely is of great significance.
There are many methods for detecting faulty insulators, and
electric field method is one of the most efficient method to
defect insulators. The principle of electric field method is to
analyze the axial distribution of electric field of insulator string
and compare it with that of good string, especially the
introduction of optical fiber electric field sensor makes electric
field method more simple and more reliable [4-6].
In this paper, the principle of detecting faulty insulators
based on fiber optic electric field sensors was introduced, then
the detection method and the composition of the detection
device were introduced. Finally, the detection device was Fig. 1. Graph of relationship between insulator degradation and electric field
distribution.
tested on the 220kV transmission line to verify the feasibility
of device.
B. The Pockels Effect
II. PRINCIPLE OF ELECTRIC FIELD METHOD USING The Pockels effect means that the change in refractive
OPTICAL SENSORS index is proportional to the applied field strength. Certain
substances also produce induced birefringence in an electric
A. Electric Field Detection Method field, the magnitude of which is proportional to the intensity of
The advantages of the electric field detection method are the electric field. The Pockels effect is a linear effect and only
mainly reflected in the fact that it is less interfered by external exists in crystals without a center of symmetry [10-11]. The
factors such as weather, and it can detect the defects inside the formula for the Pockels effect is

978-1-6654-3363-1/21/$31.00 ©2021 IEEE 49

Authorized licensed use limited to: Kirikkale Univ. Downloaded on December 19,2021 at 13:19:56 UTC from IEEE Xplore. Restrictions apply.
G kE (1) polarized light, and then passes through a 1/4 glass plate to
become circularly polarized light [12-13]. When passing
In the equation, G is a refractive index, k is the coefficient through the optical crystal, it undergoes birefringence under the
action of an external electric field. The phase of the light has
for the Pockels effect, E is an applied electric field.
changed, and finally the phase change of the light is converted
The principle of the Pockels effect is shown in Fig. 2, into the change of light intensity using the analyzer, which can
When the incident light enters along the optical axis of the reflect the electric field intensity [14-16].
crystal, it first passes through a polarizer to become linearly

Fig. 2. Schematic diagram of the Pockels effect.

220kV composite insulator string, a total of 19 to 23 pieces,


III. EXPERIMENTAL STUDY suspended on single-phase wire, and the loading voltage is
123.7kV. The humidity is 35% and the temperature is 3~6ć.
A. Device for Detecting Faulty Insulator
The schematic diagram of the online monitoring structure 1) Electric field measurement test of composite insulators
of the device for detecting faulty insulator is shown in Fig. 3. running at reduced voltage under different measuring
Passive electric field probe 5 is a rectangular passive optical distances.
electric field sensor that does not contain any conductive Sample: without defect, the loading voltage is 110kV.
materials and is encapsulated by a shell, the signal is led out by
The measured electric field distribution curve is shown in
two optical cables with a sheath diameter of 3mm. The electric
Fig. 4.
field measuring device 1 sends out a measured light signal with
stable power, which is input into the passive electric field
probe and passes through the electro-optic crystal. The output
terminal receives the optical signal modulated by the external
electric field, and the measured value of the electric field
intensity can be obtained by the signal conditioning circuit
after photoelectric conversion.

Fig. 4. Electric field distribution curve at different measuring distances.

It can be seen from the Fig. 4 that the sensor is 10cm or less
Fig. 3. Chematic diagram of detection system structure. from the insulator, the measured electric field distribution
curve is close to the theoretical U-shaped distribution, and is
relatively smooth. The farther the distance is, the less the
B. Experiment Results surface electric field distribution is affected by the insulator
The experiments for detecting faulty insulators are carried itself. Therefore, the measuring distance is selected as 10cm in
out in the high-voltage test hall. The specific test conditions are: the following experiment.

50

Authorized licensed use limited to: Kirikkale Univ. Downloaded on December 19,2021 at 13:19:56 UTC from IEEE Xplore. Restrictions apply.
2) Electric field measurement test of good composite The measured electric field distribution curve is shown in
insulator under rated voltage Figure 6-8.
Sample: without defect, the loading voltage is 220kV. It can be seen from the Fig. 6-8 that the internal defect
The measured electric field distribution curve is shown in made of tin foil in the composite insulator significantly affects
Fig. 5. the distribution of the electric field on the surface of the
insulator. The position of the defect directly corresponds to the
partial depression of the electric field shape. Through the
electric field distribution curve, the degree and location of this
type of continuity defect can be directly judged.

Fig. 5. Electric field distribution of good composite insulator under rated


voltage.

It can be seen from the Fig. 5 that the electric field


distribution curve of a good composite insulator under the rated
voltage level has the same shape as under the step-down
operating condition, and only the numerical value changes Fig. 7. Electric field distribution of the deterioration of the sixth and seventh
proportionally, which is a smooth U-shaped distribution insulator.
without obvious distortion.
3) Electric field measurement test of composite insulator
with internal defect under rated voltage
The core rod sheath of the composite insulator is wrapped
in tin foil to simulate the internal defects of the composite
insulator. There are three types of samples:
(1) Sample: the position of the sixth umbrella skirt of the
composite insulator is defective, the loading voltage is 220kV.
(2) Sample: the position of the sixth and seventh umbrella
skirt of the composite insulator is defective, the loading voltage
is 220kV.
(3) Sample: the position of the nineteenth umbrella skirt of
the composite insulator is defective, the loading voltage is
220kV.
Fig. 8. Electric field distribution of the deterioration of the nineteenth
insulator.

4) Electric field measurement test of composite insulators


affected by salt water immersion
Sample: The fourteenth umbrella skirt impregnated in salt
water, the loading voltage is 220kV.
The measured electric field distribution curve is shown in
Fig. 9.
It can be seen from Fig. 9 that the composite insulator
defect caused by salt water immersion can cause the electric
field distribution distortion, but the influence is weaker than the
defect made by tin foil. The position of the electric field
Fig. 6. The electric field distribution when the position of the sixth umbrella depression and the defect position of the salt water can still be
skirt of the composite insulator is defective. well matched.

51

Authorized licensed use limited to: Kirikkale Univ. Downloaded on December 19,2021 at 13:19:56 UTC from IEEE Xplore. Restrictions apply.
(1) In this experiment, the insulating rod extends from the
side to the insulator, but in the actual transmission line, the
insulating rod and the insulator are placed in parallel, so the
influence of the insulating rod on the electric field distribution
will be different.
(2) Theoretically speaking, to find the lowest point of the
electric field intensity near the faulty insulator, it is necessary
to take continuous and gapless points. The method adopted in
the experiment is to take one measurement point for each
insulator instead of continuous sampling.

IV. CONCLUSION
In this paper, a new detection method for faulty insulators
with an optical sensor as the main component was proposed.
Fig. 9. Electric field distribution of the deterioration of the forteenth insulator. and a detection experiment was conducted. Comparing the
experiment results with the theory, the feasibility of this
5) Electric field measurement test of composite insulator detection method was verified. The experiment results show
without corona ring that the deterioration of the insulators at the high-voltage side,
Sample: without defect, remove the corona ring on both the low-voltage side end and the middle can be reflected by the
high voltage side and the low voltage side, the loading voltage electric field measurement results, this shows that the method
is 220kV. of detecting faulty insulators described in this paper is
promising for practical applications on transmission lines.
The measured electric field distribution curve is shown in
Fig. 10.
ACKNOWLEDGMENT
It can be seen from the figure that the presence or absence This work is supported by project: Research on axial
of the corona ring has little effect on the electric field electric field detection and deterioration analysis technology of
distribution curve. Compared with the corona ring, the electric transmission line insulator(2020YF-54), which is sponsored by
field distribution curve without the corona ring is smoother, State Grid Corporation of China.
still showing a U-shaped distribution, and there is no obvious
local depression.
REFERENCES
[1] Wang Linong,Jian Siliang,Song Bin,Guo Zhenping,Li Enwen,Zhang
Qiushi. Research on the Detection of Faulty Insulator in Transmission
Line Based on Electric Field Distribution Measurement[J]. Insulators
and Surge Arresters, 2019(04):199-205+212
[2] Z. Yang et al., "Simulation of electric field around insulators in high
voltage line," 2015 5th International Conference on Electric Utility
Deregulation and Restructuring and Power Technologies (DRPT),
Changsha, 2015, pp. 1478-1482.
[3] Wang Linong,,Li Xiaochun,Song Bin,Hu Xin,Guo Zhenping,Liu
Xiaowei. Researches of Simulation and Detection for Electric Field
Distribution Along Faulty Insulator on Transmission Line[J].High
Voltage Apparatus, 2018,54(10):49-55+62
[4] Shu, Lichun; Liu, Yanqing; Jiang, Xingliang; Hu, Qin; He, Gaohui; Yu,
Zhou; Xiao, Longfang: 'Three-dimensional electric field simulation and
flashover path analysis of ice-covered suspension insulators', High
Voltage, 2020, 5, (3), p. 327-333.
[5] Wang Ping,Li Kang,Geng Jianghai,Jia Boyan,Zhang Zhimeng,Liu Jie.
Study on space electric field of 110 kV faulty porcelain suspension
Fig. 10. Electric field distribution of insulators without the influence of corona insulator[J]. Electrical Measurement & Instrumentation,2020,57(14):93-
ring. 98.
[6] J. Wang, Y. Chen, J. Liao and Z. Peng, "Voltage and E-field distribution
of UHV composite insulator with connection of porcelain insulators,"
C. Difference between Experiment Results and Theory 2015 IEEE 11th International Conference on the Properties and
Comparing the experiment results with the theoretical Applications of Dielectric Materials (ICPADM), Sydney, NSW, 2015,
pp. 628-631,
research results, it can be seen from the results that the theory
[7] X. Changfu, H. Chengbo, X. Jiayuan, L. Yunpeng, Z. Kaiyuan and P.
and test results are in good agreement with each other. Shaotong, "Influence of deteriorated porcelain insulator on electric field
Although there are some slight differences, these small and potential distribution of insulators strings in 110kV transmission
differences have no effect on judging the deterioration of lines," 2017 IEEE International Conference on Smart Grid and Smart
insulators, especially the more serious internal defects. There Cities (ICSGSC), Singapore, 2017, pp. 162-166,
may be two reasons for these small differences: [8] Chen Yao,Zhou Dehua,Niu Jie,Luo Richeng,Tang Xiangsheng. The
Impact of Zero and Low Resistance Insulator on Potential and Electric

52

Authorized licensed use limited to: Kirikkale Univ. Downloaded on December 19,2021 at 13:19:56 UTC from IEEE Xplore. Restrictions apply.
Field Distribution of Long Insulator Strings in the 500kV Transmisson [13] Liu Xiaowei,Wang Linong,Wang Junhua,Li Xiaochun. Research on
Line[J]. Insulators and Surge Arresters,2015(03):29-34 automatic detection technology for faulty porcelain insulators on AC
[9] Bai Huan,Chen Hongbo,Huang Daochun. Analysis and Research on transmission lines[J]. Electrical Measurement & Instrumentation,
Electric Field Simulation of 110 kV Zero-value Insulator[J]. Sichuan 2016,53(11):110-115.
Electric Power Technology,2014,37(02):62-67. [14] Y. ZHANG et al., "Study on the Formation of the Electric Field around
[10] Wang Shenghui,Liu Peng,Xie Tangwen,Wang Zhaoqi,Dai Hui. Study Three-phase Insulators in 110kV Transmission Tower and Its Influence
on the characteristic of surface pollution distribution of insulators[J]. on Flashover Voltage," 2018 International Conference on Power System
Electrical Measurement & Instrumentation,2017,54(08):21-27. Technology (POWERCON), Guangzhou, 2018, pp. 3521-3527,
[11] D. Huang, Z. Zheng, Z. Huang, W. Guoli, J. Ruan and P. Li, [15] P. Taklaja, I. Kiitam, J. Niitsoo, J. Klüss and P. Hyvönen, "Electric field
"Calculation model simplification study for porcelain insulator string distribution in glass and porcelain pin insulators," 2015 IEEE 15th
potential and grading ring surface electric field distribution of UHV AC International Conference on Environment and Electrical Engineering
transmission line," 2013 Annual Report Conference on Electrical (EEEIC), Rome, 2015, pp. 267-271.
Insulation and Dielectric Phenomena, Shenzhen, 2013, pp. 634-637. [16] Yu Zhuoqi,Gao jinwen,Wang Kesheng,Zhang Huijun,Duan Xinghui,Pan
[12] R. Sardast, F. Faghihi and M. Vakilian, "Study on Different Dimensions Longyu. Research on crack defect detection method for GIS basin-type
of C-type Corona Rings in 400 kV Insulator Strings Based on FEM insulators based on modal analysis[J]. Electrical Measurement &
Analysis of Electric Field Distribution," 2019 27th Iranian Conference Instrumentation, 2020,57(16):23-27.
on Electrical Engineering (ICEE), Yazd, Iran, 2019, pp. 673-678.