CENTERLINE 2100 Motor Control Centers Power Fuses Specifications Technical Data
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all
changes.
Topic Page
Removed information for Bulletin Numbers 2102H, 2126, 2172. Throughout
Updated the available ampere rating for 200 A and 400 A disconnect switches. Throughout
Application
The information in this publication applies to the selection of the following fuses:
• 3-phase motor power fuses in 460V and 575V applications
• power fuses in branch circuit or non-motor applications
Power fuses for branch circuit or non-motor applications are valid for the following Bulletin 2100 NEMA products:
• Bulletin 2100D miscellaneous units with fusible disconnects
• Bulletin 2102L full-voltage lighting contactors
• Bulletin 2192F fusible disconnect feeders
• Bulletin 2192M fusible disconnect mains
• Bulletin 2196 control and lighting transformers with fusible disconnects
All power and time delay fuses are UL Class/CSA HRCI as follows:
• Class CC/HRCI-MISC
• Class J/HRCI-J
• Class RK1/HRCI-R
• Class L/HRCI-L.
IMPORTANT The HRCII-C fuses specified for use in Canada are NOT time delay fuses and also are applicable for motor loads only (must
be used in conjunction with a motor overload relay).
IMPORTANT The Class R fuse is an RK1 and DOES NOT include the RK5 type. The RK5 type can allow too much let-through energy during
a short circuit and, therefore, may not offer the best protection.
For a particular application, see the table guide (Table 2) which shows the types, manufacturer, and application.
The Allen-Bradley pre-selected motor application power fuses (Table 3…7), are based on the fuse manufacturer recommendations, Allen-Bradley
investigative testing, and requirements of the National Electrical Code/Canadian Electric Code (NEC/CEC). Supplied CC, J, and RK1 time delay fuses
specified for the Typical motor acceleration time applications are in accordance with IEC 947-4-1 test requirements and allow for Type 2 Short
Circuit Coordination.
Motor Application
Motor application power fuse selection is available in two acceleration ranges:
• Typical motor acceleration time for non-plugging or non-jogging applications. Typical motor acceleration times are 5 seconds or less.
• Long motor acceleration time for applications, where the motor acceleration times are greater than 5 seconds, for cases of light plugging or
jogging, some code letter motors, and some high efficiency motors.
Non-motor Application
Select the proper power fuse for branch circuit or non-motor applications (Table 8…13), other than transformer applications, based on load and
NEC/CEC requirements. Additionally, the power fuse rating is limited by the disconnect/fuse clip rating available for the particular application, see
Table 1.
A particular disconnect fuse clip rating allows for a particular range of fuse ratings, for example, a 60 ampere disconnect fuse clip accommodates
fuse ratings from 31…60 amperes. In addition, the fuse selection tables only allow for ‘standard ampere rating’ fuses as defined in the NEC/CEC.
The pre-selected power fuses for control and lighting transformer applications (Table 14), are based on the primary protection requirements as
found in the NEC/CEC. Additionally, the disconnect/fuse clip rating limits the maximum available power fuse rating for the particular transformer
application.
Table 1 - Fuse Clip Rating
Fuse Size (A) Fuse Clip Rating (A)
0…30 30
31…60 60
61…100 100
101…200 200
201…400 400
401…600 600
601…800 800
801…1200 1200
Tables in this publication assist in determining fuse ratings and part number correlation:
Table 2 - Reference Table
Table Type Table Page Number Fuse Manufacturer and Type Application
Table 3 5 UL Class CC / CSA HRCI-MISC. Littelfuse Type CCMR
Mersen Type AJT or Bussmann Type LPJ or Lit-
Table 4 5 UL Class J / CSA HRCI-J
telfuse Type JTD_ID
3-Phase Motor Applications (Bulletin 2106, 2112,
Table 5 6 UL Class RK1 / CSA HRCI-R Mersen Type A6D or Bussmann Type LPS-RK 2112 vacuum, 2122, 2154F, 2154G)
Table 6 6 UL Class L / CSA HRCI-L Mersen Type A4BT or Bussmann Type KLU
Table 7 7 Class C FORM II (CSA HRCII-C) Mersen Types GIA, GIS, GCP, GF, GM, and GLM
Table 8 7 UL Class CC / CSA HRCI-MISC. Littelfuse Type CCMR
Mersen Type AJT or Bussmann Type LPJ or Lit- Miscellaneous Units with Fusible Disconnects
UL Class J / CSA HRCI-J (Bulletin 2100D)
Table 9 8 telfuse Type JTD_ID
UL Class RK1 / CSA HRCI-R Mersen Type A6D or Bussmann Type LPS-RK
Fuse Ratings Table 10 8 UL Class CC / CSA HRCI-MISC. Littelfuse Type CCMR
Mersen Type AJT or Bussmann Type LPJ or Lit- Bulletin 2102L - Full Voltage Lighting Contactors
UL Class J / CSA HRCI-J
Table 11 9 telfuse Type JTD_ID
UL Class RK1 / CSA HRCI-R Mersen Type A6D or Bussmann Type LPS-RK
Table 12 9 UL Class CC / CSA HRCI-MISC. Littelfuse Type CCMR Fusible Disconnect Feeders (Bulletin 2192F)
Mersen Type AJT or Bussmann Type LPJ or Lit-
UL Class J / CSA HRCI-J
Table 13 10 telfuse Type JTD_ID
Fusible Disconnect Feeders and Mains (Bulletin
UL Class RK1 / CSA HRCI-R Mersen Type A6D or Bussmann Type LPS-RK 2192F and 2192M)
Table 14 10 UL Class L / CSA HRCI-L Mersen Type A4BT or Bussmann Type KLU
Mersen Type AJT or Bussmann Type LPJ or Lit-
UL Class J / CSA HRCI-J Control and Lighting Transformers with Fusible
Table 15 11 telfuse Type JTD_ID
Disconnects (Bulletin 2196)
UL Class RK1 / CSA HRCI-R Mersen Type A6D or Bussmann Type LPS-RK
Table 16 11 UL Class CC / CSA HRCI-MISC. Littelfuse Type CCMR
Table 17 11 UL Class J / CSA HRCI-J Mersen Type AJT
Table 18 12 UL Class J / CSA HRCI-J Bussmann Type LPJ
Table 19 12 UL Class J / CSA HRCI-J Littelfuse Type JTD_ID with Visual Blown Fuse Indication
Part No. Correlation Table 20 13 UL Class RK1 / CSA HRCI-R Mersen Type A6D
Table 21 13 UL Class L / CSA HRCI-L Mersen Type A4BT
Table 22 14 UL Class RK1 / CSA HRCI-R Bussmann Type LPS-RK
Table 23 14 UL Class L / CSA HRCI-L Bussmann Type KLU
Table 24 15 Class C FORM II (CSA HRCII-C) Mersen Types GIA, GIS, GCP, GF, GM, and GLM
Table 25 16 Valid Horsepower/Fuse Clip Rating - 460V 3-Phase Motor Applications (Bulletin 2106, 2112,
Valid HP/ Fuse Clip Ratings 2112 vacuum, 2122, 2154F, 2154G)
Table 26 17 Valid Horsepower/Fuse Clip Rating - 575V
Table 13 - Bulletin 2192F and 2192M Fusible Disconnect Feeders and Mains
UL Class J / CSA HRCI-J - Time Delay Fuse - Mersen Type AJT or Bussmann Type LPJ or Littelfuse Type JTD_ID UL Class RK1 / CSA HRCI-R - Time Delay Fuse -
Mersen Type A6D or Bussmann Type LPS-RK
480V or 600V 3-Phase
Disconnect Rating (Amperes) Supplied Fuse Ampere Rating
1
3
6
10
30
15
20
25
30
35
40
60 45
50
60
70
80
100
90
100
110
125
200 150
175
200
225
250
400 300
350
400
450
600 500
600
Table 14 - Bulletin 2192F and 2192M Fusible Disconnect Feeders and Mains
UL Class L / CSA HRCI-L - Time Delay Fuse - Mersen Type A4BT or Bussmann Type KLU
480V or 600V 3-Phase
Disconnect Rating (Amperes) Supplied Fuse Ampere Rating
601
800 700
800
1000
1200 1200
1600 1600
2000 2000
Table 15 - Bulletin 2196 Control and Lighting Transformers with Fusible Disconnects
UL Class J / CSA HRCI-J - Time Delay Fuse - Mersen AJT or Bussmann Type LPJ or Littelfuse Type JTD_ID UL Class RK1 / CSA HRCI-R - Time Delay Fuse - Mersen Type A6D or
Bussmann Type LPS-RK
480V 3-Phase 600V 3-Phase
Transformer Rating Supplied Fuse Ampere Rating Transformer Rating Supplied Fuse Ampere Rating
0.5 kVA 1Ø 2-1/2 0.5 kVA 1Ø 2
0.75 kVA 1Ø 3-1/2 0.75 kVA 1Ø 3
1 kVA 1Ø 5 1 kVA 1Ø 4
1.5 kVA 1Ø 7 1.5 kVA 1Ø 6
2 kVA 1Ø 10 2 kVA 1Ø 8
3 kVA 1Ø 15 3 kVA 1Ø 12
5 kVA 1Ø 25 5 kVA 1Ø 20
7.5 kVA 1Ø 30 7.5 kVA 1Ø 30
10 kVA 1Ø 30 10 kVA 1Ø 30
15 kVA 1Ø 60 15 kVA 1Ø 60
20 kVA 1Ø 60 20 kVA 1Ø 60
25 kVA 1Ø 60 25 kVA 1Ø 60
30 kVA 1Ø 100 30 kVA 1Ø 60
37.5 kVA 1Ø 100 37.5 kVA 1Ø 100
50 kVA 1Ø 200 50 kVA 1Ø 100
10 kVA 3Ø 30 10 kVA 3Ø 20
15 kVA 3Ø 30 15 kVA 3Ø 30
20 kVA 3Ø 30 20 kVA 3Ø 30
25 kVA 3Ø 60 25 kVA 3Ø 60
30 kVA 3Ø 60 30 kVA 3Ø 60
37.5 kVA 3Ø 60 37.5 kVA 3Ø 60
45 kVA 3Ø 100 45 kVA 3Ø 60
Table 25 - Valid Horsepower / Fuse Clip Rating When Supplying Power Fuses - 460V
Typical Acceleration Time £ 5 sec. (Hp Code Suffix _T) Long Acceleration Time > 5 sec. (Hp Code Suffix _L)
Horsepower Fuse Clip Rating Fuse Clip Rating
(Amperes) Fuse Type(1) Fuse Clip Designator
(Amperes) Fuse Type(1) Fuse Clip Designator
CC 20C CC 20C
J 20J J 20J
0.125…10 30 RK1 20R 30 RK1 20R
HRCII-C 20E HRCII-C 20E
30 J 20J J 20J
15 RK1 20R 60 RK1 20R
60 HRCII-C 20E HRCII-C 20E
J 20J J 20J
20 60 RK1 20R 60 RK1 20R
HRCII-C 20E HRCII-C 20E
60 J 20J 60 J 20J
25 RK1 20R RK1 20R
100 HRCII-C 20E 100 HRCII-C 20E
J 20J 20J
60 RK1 20R J RK1
30 100 HRCII-C 20R
100 HRCII-C 20E 20E
J 20J J 20J
40 100 RK1 20R 100 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J J 20J
50 100 RK1 20R 200 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J J 20J
60 200 RK1 20R 200 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J J 20J
75 200 RK1 20R 200 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J
100 200 RK1 20R 400 J 20J
HRCII-C 20E
J 20J J 20J
125 400 RK1 20R(2) 400 RK1 20R(2)
HRCII-C 20E(2) HRCII-C 20E(2)
J 20J J 20J
150 400 RK1 20R 400 RK1 20R(2)
HRCII-C 20E HRCII-C 20E(2)
J 20J 400 HRCII-C 20E
200 400 RK1 20R
HRCII-C 20E 600 J 20J
400 HRCII-C 20E 400 HRCII-C 20E
250 J 20J J 20J
600 600
RK1 20R(3) RK1 20R(3)
400 HRCII-C 20E
J 20J 600 HRCII-C 20E
300 600 RK
1 20R(3)
Table 26 - Valid Horsepower / Fuse Clip Rating When Supplying Power Fuses - 575V
Typical Acceleration Time £ 5 sec. (Hp Code Suffix _T) Long Acceleration Time > 5 sec. (Hp Code Suffix _L)
Horsepower Fuse Clip Rating Fuse Clip Rating
(Amperes) Fuse Type(1) Fuse Clip Designator
(Amperes) Fuse Type(1) Fuse Clip Designator
CC 20C CC 20C
J 20J J 20J
0.125…10 30 RK1 20R 30 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J 30 J 20J
15 30 RK1 20R RK1 20R
HRCII-C(1) 20E 60 HRCII-C 20E
J 20J J 20J
20…25 60 RK1 20R 60 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J 60 J 20J
30 60 RK1 20R RK1 20R
HRCII-C 20E 100 HRCII-C 20E
J 20J J 20J
60 RK1 20R
40 100 RK1 20R
100 HRCII-C 20E HRCII-C 20E
J 20J J 20J
50 100 RK1 20R 100 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J J 20J
60 100 RK1 20R 200 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J J 20J
75…100 200 RK1 20R 200 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J 200 HRCII-C 20E
125 200 RK1 20R J 20J
HRCII-C 20E 400
RK1 20R(2)
200 HRCII-C 20E J 20J
150 J 20J 400 RK1 20R (2) (3)
400 HRCII-C
RK1 20R(2) 20E (2)
J 20J J 20J
200 400 RK1 20R 400 RK1 20R
HRCII-C 20E HRCII-C 20E
J 20J 400 HRCII-C 20E
250 400 RK1 20R
HRCII-C 20E 600 J 20J(3)
400 HRCII-C 20E 400 HRCII-C 20E
300 J 20J J 20J
600 600
RK1 20R RK1 20R (3)
400 HRCII-C 20E
J 20J 600 HRCII-C 20E
350 600
RK1 20R(4)
800 L 20L(4) 800 L 20L(4)
600 HRCII-C 20E 600 HRCII-C 20E
400…500
800 L 20L(4) 800 L 20(4)
(1) HRCII-C fuses are available in Canada only and are NOT UL Listed.
(2) Option NOT valid on 2112 vacuum applications. Catalog number, second position (2L).
(3) Option NOT valid on 2112 vacuum applications. Catalog number, second position (2N).
(4) Option NOT valid 2112 vacuum applications. Catalog number, second position (2P).
Notes:
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
CENTERLINE® 2100 Motor Control Centers Bulletin 1494U Disconnect Switch/Fuse Provides information to install a 30 A, 60 A, or 100 A Bulletin 1494U Disconnect Switch in a
Block Installation Instructions, publication 2100-IN095 CENTERLINE 2100 motor control center unit.
CENTERLINE 2100 Motor Control Centers Bulletin 1494U Disconnect Switch/Fuse Provides information to install a 200 A or 400 A Bulletin 1494U Disconnect Switch in a
Block Installation Instructions, publication 2100-IN099 CENTERLINE 2100 motor control center unit.
CENTERLINE 2100 Disconnect Switch Specifications Technical Data, Provides specification and dimension information for 1494U disconnect switch in a CENTERLINE
publication 2100-TD035 2100 motor control center unit.
CENTERLINE 2100 Motor Control Centers Program Guide, publication 2100-CA004 Provides guidelines for the configuration of CENTERLINE 2100 motor control centers.
American Standards, Configurations, and Ratings: Introduction to Provides an overview of American motor circuit design based on methods that are outlined
Motor Circuit Design, publication IC-AT001 in the NEC.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
Allen-Bradley, CENTERLINE, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur