Calculations For Septic Tank and Soakage Pit-Compliance
Calculations For Septic Tank and Soakage Pit-Compliance
Sl
Client Comments WABAG reply
No
Inside of the WTP all septic tanks
should be sealed type and not
accepted soakage pits where there is
In all locations percolation rate remains at
1. high water table and percolation
75mm/hr.
rate below 75mm/hr. for those
areas you have to propose
alternative solutions
The considered population of the
Maximum population is 80% of capacity.
2. administration building should be at
Because of that 60 persons is sufficient
least 80 persons
Separate treatment system should
be provided for wash room waste As per the contract document, it is not
3. water and kitchen waste water with required
grease trap.