Interturn and Abnormal
Interturn and Abnormal
Unbalanced Loading:
If there is an unbalanced loading of the generator then the stator currents have a
negative sequence component. The stator field due to these negative sequence currents,
rotates at synchronous speed but in a direction opposite to the direction of the field
structure on the rotor. Thus, the negative sequence stator armature mmf rotates at a
speed -Ns while the rotor field speed is +Ns. Therefore, there is a relative velocity of 2Ns
between the two. This causes double frequency currents, of large amplitude, to be induced
in the rotor conductors and iron. Recall that the eddy current loss component of iron loss
in the rotor is proportional to f2(Bm,)2 while the hysteresis loss is proportional to
f (Bm)n where n = 1 6 to 2 depending upon the core material. Therefore, both the eddy
current as well as the hysteresis losses increase due to these double frequency induced
currents in the rotor.
Thus, if the stator carries unbalanced currents, then it is the rotor, which is
overheated. How long the generator can be allowed to run under unbalanced loading,
depends upon the thermal withstand capacity of the machine, which in turn depends upon
the type of cooling system adopted. The rate of heat generation is proportional to I22R
while the heat energy is proportional to I22 Rt, where t is the time and I2 is negative
sequence current. Since the capacity of a particular machine, to safely dissipate energy,
is limited to a certain value k, we can write
I22 Rt = k
I22 t = k1