Technical features
Medium: Operating pressure: Temperature range: Materials:
Filtered, non-lubricated or dry 1 ... 10 bar (14 ... 145 psi) Up to -40 ... +80°C (-40 ... +176°F), Manifold and valve: stainless steel
compressed air, instrument air Flow: see option selector page 2 1.4404 (316 L)
nitrogen and other non-flammable Standard valves 320 ... 490 l/min Air supply must be dry enough to Seals: NBR
neutral dry fluids High flow valves 720 ... 810 l/min avoid ice formation at temperatures Internal parts: stainless steel
Operation: details see page 2 below 2°C (+35°F) 1.4404 (316 L)
3/2 Direct solenoid operated Port size:
poppet valves G 1/4, 1/4 NPT, G 1/2, 1/2 NPT Temperature solenoid: See option
Bypass: Additional filter: selector and corresponding valve
5/2 Manual operated spool valve Installation of an in-line filter is data sheets
(lockable) recommended (in the direction of
Mounting position: flow from the actuator to the RVM).
Valves vertical only
1oo2 with bypass valve 2oo2 with bypass valve 2oo3 with bypass valve *1)
exhaust guards and indicators exhaust guards and indicators exhaust guards and indicators
1 3 1 3
I2 I2
2 V1 2 V2 2
V1 W1
I3
1 3 1 3 1 3
I2
V1 2 V2 2
1 3 1 3
I1 I1 I1
4 2 4 2 4 2
B1 B1 B1
5 13 3 3 5 13 3 3 5 13 3 3
Our policy is one of continued research and development. We therefore reserve the right to amend, 11/15
without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.01
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
Port sizes Substitute Visual valve status indicators -40°C ... +80°C
in stainless steel - included in 2,5 ... 10 bar
G1/4 (Standard flow) 11 the scope of supply
1/4 NPT (Standard flow) 12 Silencers*2) Temperature
G1/2 (High flow) 23 Exhaust guard (standard) -55°C ...+80°C
1/2 NPT (High flow) 24 Manifold material Substitute
Valve type Solenoid Voltage Cable Substitute Stainless steel 2
Protection Entry
Aluminium 4
Standard flow
Bypass valve Temperature Substitute
YX13ANPH1BS Exia 24 V d.c. M 20 x 1,5 01
Stainless steel -40°C ... +60°C 2
Y013ANPH1BS Exd 24 V d.c. M 20 x 1,5 02
Stainless steel -25°C ... +80°C 4
YZ13ANPH1BS Exmbe 24 V d.c. M 20 x 1,5 03
*1) other indicators or plugs can be ordered separately,
Y013ANPH1MS Exd 230 V a.c. M 20 x 1,5 04
see page 3
YZ13ANPH1MS Exmbe 230 V a.c. M 20 x 1,5 05 *2) other silencers can be ordered separately, see page 3
YX13ANPH2BS Exia 24 V d.c. 1/2 NPT 06
Y013ANPH2BS Exd 24 V d.c. 1/2 NPT 07
YZ13ANPH2BS Exmbe 24 V d.c. 1/2 NPT 08
Y013ANPH2MS Exd 230 V a.c. 1/2 NPT 09
YZ13ANPH2MS Exmbe 230 V a.c. 1/2 NPT 10
Y013ANPH1BS-2W Exd 24V d.c. M20x1,5 22
Y013ANPV1BS-2W Exd 24V d.c. M20x1,5 24
Y013ANPH2BS-2W Exd 24V d.c. 1/2 NPT 28
Y013ANPH2ES Exd 125V d.c. 1/2 NPT 30
Y013ANPH2JS Exd 110V a.c. 1/2 NPT 31
Y013ANPH2JS Exd 110V a.c. M20x1,5 32
YZ13ANPH2ES Exmbe 125V d.c. 1/2 NPT 42
YZ13ANPH2JS Exmbe 110V a.c. 1/2 NPT 43
YZ13ANPH2TS Exmbe 120V a.c. 1/2 NPT 44
Standard flow (PBMR)
Y013PNPH1BS Exd 24V d.c. M20x1,5 21
Y013PNPH2BS Exd 24V d.c. 1/2 NPT 25
Y013PNPH2JS Exd 110V a.c. 1/2 NPT 26
Y013PNPH2BS-2W Exd 24V d.c. 1/2 NPT 29
Y013PNPH1BS-2W Exd 24V a.c. M20x1,5 33
Y013PNPH2ES Exd 125V d.c. 1/2 NPT 45
High flow
Y013AMMH1BS Exd 24 V d.c. M 20 x 1,5 12
YZ13AMMH1BS Exmbe 24 V d.c. M 20 x 1,5 13
Y013AMMH1MS Exd 230 V a.c. M 20 x 1,5 14
YZ13AMMH1MS Exmbe 230 V a.c. M 20 x 1,5 15
Y013AMMH2BS Exd 24 V d.c. 1/2 NPT 17
YZ13AMMH2BS Exmbe 24 V d.c. 1/2 NPT 18
Y013AMMH2MS Exd 230 V a.c. 1/2 NPT 19
YZ13AMMH2MS Exmbe 230 V a.c. 1/2 NPT 20
Y013AMMH1JS Exd 110V a.c. M20x1,5 39 Flow rates and valve combinations
Y013AMMH2ES Exd 125V d.c. 1/2 NPT 41 Flow direction Standard flow systems High flow systems
(port to port) Bypass mode Operation mode Bypass mode Operation mode
High flow (PBMR)
1oo2 97109 2 x Y*13ANPH*BS 97109 2 x Y*13AMMH*BS
Y013PMMH2JS Exd 110V a.c. 1/2 NPT 27
1 » 2 *1) [l/min] 950 330 1450 740
Y013PMMH1BS Exd 24V d.c. M20x1,5 46
2 » 3 *2) [l/min] — 1740 ... 2200 — 3200 ... 4600
Note; Please advise when ordering if CSA certification is required
2oo2 97109 2 x Y*13ANPH*BS 97109 2 x Y*13AMMH*BS
1 » 2 *1) [l/min] 950 490 1450 810
2 » 3 *2) [l/min] — 1640 ... 2200 — 2500 ... 4600
2oo3 97109 4 x Y*13ANPH*BS 97109 4 x Y*13AMMH*BS
1 » 2 *1) [l/min] 950 320 1450 720
2 » 3 *2) [l/min] — 1640 ... 2200 — 2500 ... 4600
*1) Flow characteristics conforms to ISO6358 from port 1 (bypass valve) to port 2 (sub-base) [6 » 5 bar],
see page 1
*2) Flow characteristics conforms to ISO6358 from port 2 (sub-base) to port 3 (sub-base or bypass valve)
[10 » 0 bar], see page 1
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.02 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
9
11
10
2
1 4
*1) For indoors use 0613679 (1/2 NPT) C/S4 (1/2 NPT) 0660835 (plastic)
*2) For outdoors use *1) For indoors use; *2) For outdoors use; *3) Must be ordered separately;
*4) Must be ordered separately for G thread only
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.03
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
194
10
10 3
2
3
45
M8
110 110
90,5
90
°
~122
9
~34
188,5
5
149
2 1 3
110
60
9
3
25
7
305 30 1
325 7,5 2
347
8 3
98 84 65,5 57,5 21
70
102
50
5
4
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.04 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
10
194
10
3
2
3
45
110 110 M8
280 110
188,5
A B
149
ø9
110
60
25
475
7,5
495
516
A B
90
°
~ 122
~34
30
2
1 7 90,5
8 3
98 84 86 84 65,5 57,5 21
70
102
50
5
4
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.05
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
207
10
10
3
2
45
3
M8
105 110
°
90
106
~131
9
~ 34
209,5
172
2
ø9
110
60
7
25
35 1
305 20 2
330
(352)
8 94,5 75 72,5 60 21 3
70
114,5
50
5
4
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.06 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
10
207
10
3
2
70
3
45
105 110 M8
255 110
A B
209,5
~172
ø9
60
110
25
455
480 20
502
A B
°
90
106
~131
~ 34
2
1
35
7
8 3
94,5 75 75 75 77,5 60 21
114,5
50
5
4
1 Valve Y*13AMMH1BS and Y*13AMMH2BS series 7 Inlet port G 1/2 or 1/2 NPT
2 Outlet port G 1/2 or 1/2 NPT 8 Visual indicator, stainless steel as standard
3 Exhaust guard (sub-base), ports G 1/2 or 1/2 NPT 9 Mounting holes
4 Bypass valve 97109 series 10 Mounting threads
5 Exhaust guard (bypass valve), ports G 1/2 or 1/2 NPT
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.07
Y*13ANPH*BS standard flow valve
Technical features
Medium: Port size: Fluid/AmbientTemperature: Materials:
Filtered, non-lubricated or dry Flanged See table below Body: stainless steel 1.4404
compressed air, instrument air Orifice: Air supply must be dry enough to (316 L)
nitrogen and other non-flammable 5 mm avoid ice formation at temperatures Coil housing: stainless steel 1.4404
neutral dry fluids Operating pressure: below 2°C (+35°F) (316 L)
Operation: 0 ... 12 bar (0 ... 174 psi) For outdoor installation please Seals: NBR
3/2 Direct solenoid operated (0 ... 10 bar (0 ... 145 psi) with CSA protect all connections against Internal parts: stainless steel
poppet valves certification) moisture ingress! 1.4404 (316 L)
Technical data
Symbol Power consumption Rated current Certifications Temperature range Electrical Model Substitute
24 V d.c. 230 V a.c. 24 V d.c. 230 V a.c. Media Ambient connection
(W) (VA) (mA) (mA) FM ATEX (°C) (°C) (conduit)
0,43 — 35 — — Ex II 1 GD, Ex ia IIC -55 … +69°C T6 (-55 … +50°C), M 20 YX13ANPH1BS 01
T4 (-55 … +69°C)
3 — 125 — Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), M 20 Y013ANPH1BS 02
Groups B, C and D T4 (-55 … +90°C)
3 — 125 — — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) M 20 YZ13ANPH1BS 03
— 3,5 — 20 Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), M 20 Y013ANPH1MS 04
3 2
Groups B, C and D T4 (-55 … +90°C)
12 — 3,5 — 20 — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) M 20 YZ13ANPH1MS 05
0,43 — 35 — — Ex II 1 GD, Ex ia IIC -55 … +69°C T6 (-55 … +50°C), 1/2 NPT YX13ANPH2BS 06
T4 (-55 … +69°C)
3 11 2 3 — 125 — Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), 1/2 NPT Y013ANPH2BS 07
Groups B, C and D T4 (-55 … +90°C)
3 — 125 — — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) 1/2 NPT YZ13ANPH2BS 08
— 3,5 — 20 Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), 1/2 NPT Y013ANPH2MS 09
Groups B, C and D T4 (-55 … +90°C)
— 3,5 — 20 — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) 1/2 NPT YZ13ANPH2MS 10
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.08 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
Y*13ANPH*BS standard flow valve
50 ø59
28
1
157
1,5
3
ø5,5
ø19,5
23
22
40
28
2
16
16
16
16
3
16 ø9 16
2 64 32
Circuit diagrams
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.09
Y*13AMMH*BS high flow valves
Technical features
Medium: Port size: Fluid/Ambient temperature: Materials:
Filtered, non-lubricated or dry Flanged See table below Body: stainless steel 1.4404
compressed air, instrument air Orifice: Depending on solenoid system (316 L)
nitrogen and other non-flammable 8 mm Air supply must be dry enough to Coil housing: stainless steel 1.4404
neutral dry fluids Operating pressure: avoid ice formation at temperatures (316 L)
Operation: 0 ... 12 bar (0 ... 174 psi) below 2°C (+35°F) Seals: NBR
3/2 Direct solenoid operated (0 ... 10 bar (0 ... 145 psi) CSA) For outdoor installation please Internal parts: stainless steel
poppet valves protect all connections against 1.4404 (316 L)
moisture ingress!
Technical data
Symbol Power consumption Rated current Certifications Temperature range Electrical Model Substitute
24 V d.c. 230 V a.c. 24 V d.c. 230 V a.c. Media Ambient connection
(W) (VA) (mA) (mA) FM ATEX (°C) (°C) (conduit)
7,8 — 325 — Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), M 20 Y013AMMH1BS 12
Groups B, C and D T4 (-55 … +90°C)
7,8 — 325 — — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) M 20 YZ13AMMH1BS 13
— 8,5 — 79 Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), M 20 Y013AMMH1MS 14
Groups B, C and D T4 (-55 … +90°C)
— 8,5 — 79 — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) M 20 YZ13AMMH1MS 15
7,8 — 325 — Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), 1/2 NPT Y013AMMH2BS 17
3 1 2 Groups B, C and D T4 (-55 … +90°C)
7,8 — 325 — — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) 1/2 NPT YZ13AMMH2BS 18
— 8,5 — 79 Class 1, Divison 1, Ex II 2 GD, Ex d IIC -55 … +90°C T6 (-55 … +50°C), 1/2 NPT Y013AMMH2MS 19
Groups B, C and D T4 (-55 … +90°C)
— 8,5 — 79 — Ex mbe II 2 GD, Ex mbe IIC -55 … +90°C T4 (-55 … +80°C) 1/2 NPT YZ13AMMH2MS 20
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.10 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
Y*13AMMH*BS high flow valves
50 ø59
27,5
1
120
137
147
1,3
5,5
3
17
24
18
75
2
22,5
14
17
1
14
10 59 22
32 44
63,5
Circuit diagrams
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.11
97109 bypass valve for standard and high flow systems
Technical features
Medium: Port size: Fluid/Ambient temperature: Materials:
Filtered, non-lubricated or dry see below, according to select -40 ... +80°C (-40 ... +176°F), Housing: stainless stainless steel
compressed air, instrument air system (standard flow or high flow) Air supply must be dry enough to 1.4404 (316 L)
nitrogen and other non-flammable Operating pressure: avoid ice formation at temperatures Seals: NBR (special perbunan)
neutral dry fluids 0 ... 10 bar below 2°C (+35°F) or HNBR
Operation: For outdoor installation please
Manual actuated spool valves protect all connections against
moisture ingress!
Technical data
Housing: Stainless steel, Seals: NBR -40 ... +65°C (-40 ... +149°F)
Symbol Port size Orifice Actuation/return Flow Operating pressure Weight Drawing Model
(mm) (l/min) (bar) (psi) (kg) (lbs) No.
NAMUR G1/4 6 Lever/spring 1300 0 ... 10 0 ... 145 1,40 3.08 5 9710907
4 2
NAMUR 1/4 NPT 6 Lever/spring 1300 0 ... 10 0 ... 145 1,40 3.08 5 9710912
NAMUR G1/2 8 Lever/spring 2600 0 ... 10 0 ... 145 3,20 7.05 6 9710909
5 13
NAMUR 1/2 NPT 8 Lever/spring 2600 0 ... 10 0 ... 145 3,20 7.05 6 9710914
Housing: Stainless steel, Seals: HNBR -25 ... +80°C (-13 ... +176°F)
Symbol Port size Orifice Actuation/return Flow Operating pressure Weight Drawing Model
(mm) (l/min) (bar) (psi) (kg) (lbs) No.
NAMUR G1/4 6 Lever/spring 1300 0 ... 10 0 ... 145 1,40 3.08 5 9710916
4 2
NAMUR 1/4 NPT 6 Lever/spring 1300 0 ... 10 0 ... 145 1,40 3.08 5 9710920
NAMUR G1/2 8 Lever/spring 2600 0 ... 10 0 ... 145 3,20 7.05 6 9710918
5 13
NAMUR 1/2 NPT 8 Lever/spring 2600 0 ... 10 0 ... 145 3,20 7.05 6 9710922
Accessories
U-lock with two keys U-lock with two keys
(brass) (stainless steel)
0613633 0613836
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.12 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
97109 bypass valve for standard and high flow systems
4 2
32
45
15,2
15
2 19,7
51 24
~148
~117
41 22 22 1
~148
34,5
20,5
5/2
7
M5
7,5
~152
2
70
45
15
31,4
2
36,3
52 40
~172
32 32 3
~121
43
~145
40
62
5/2
16
9
M6
~177
Our policy is one of continued research and development. We therefore reserve the right to amend,
11/15 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH en 5.4.930.13
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
Exhaust guard (plastic) - standard option Visual indicator (stainless steel) - standard option
C
1
G
øD1
øD
B
øD
1 isual colour
V
Red (unactuated)
Green (actuated)
G
C
C
G
B
øD
G
C
1 C
C
C
ø D1
øD
B
B
1 isual colour
V
Red (unactuated)
Green (actuated)
G
C
E
øD
B1
B
ø D1
Our policy is one of continued research and development. We therefore reserve the right to amend,
en 5.4.930.14 without notice, the specifications given in this document. (2012 - 5177d) © 2014 Norgren GmbH 11/15
V83 series Redundant valve manifold systems - Modular with bypass
1oo2 “Safety”, 2oo2 “Availability” and 2oo3 “Safety and Availability”
Warning
These products are intended for use in industrial compressed air and event of such failure.
fluid systems only. Do not use these products where pressures and System designers must provide a warning to end users in the system
temperatures can exceed those listed under »Technical features/data«. instructional manual if protection against a failure mode cannot be
Before using these products with fluids other than those specified, adequately provided.
for non-industrial applications, life-support systems, or other System designers and end users are cautioned to review specific
applications not within published specifications, consult IMI NORGREN. warnings found in instruction sheets packed and shipped with
these products.
Through misuse, age, or malfunction, components used in fluid
power systems can fail in various modes. Functional safety (SIL):
The system designer is warned to consider the failure modes of all Suitable for certain applications can only be evaluated through
component parts used in fluid power systems and to provide adequate examination of each safety-related overall system with regard to the
safeguards to prevent personal injury or damage to equipment in the requirements of IEC 61508/61511.