TEST REPORT FOR

Directional PROTECTION RELAY


Date : Page no :1
Project :
Client

Panel & Relay Details


Location
Panel Name
Relay Make
Relay Name
Panel No

GENERAL CHECK
Item Description Result
1 Physical inspection of the Relay  Yes  N/A PASS
2 AC/DC Voltage Checks  Yes  N/A PASS
3 Panel Earthling Checks  Yes  N/A PASS
4 Inspect for physical damage / defects.  Yes  N/A PASS

CT/VT DETAILS:
CT RATIO 600/1 A
VT RATIO 132kV/110V

1. METERING CHECKS :
INJECTED VALUES
(Secondary Values) MEASURED VALUES
REF
(In terms of Primary Values)
A B C

PT VAB: 132KV VBC : 132 KV VCA: 132 KV


P-P
From 63.5V 63.5V 63.5V 30˚ -90˚ 150˚
MEASUREMEN 0˚ -120˚ 120˚ VAN: VBN: 76.21KV VCN: 76.21KV
T-1 P-N
76.21KV 0˚ -120˚ 120˚
CT
From 1A 1A 1A IA-1: 600 A
P-N IB-1: 600 A -120˚ IC-1:600A 120˚
MEASUREMEN 0˚ -120˚ 120˚ 0˚
T-1

For For
Name : Name :
Sign : Sign :
Date : Date :
TEST REPORT FOR
Directional PROTECTION RELAY
Date : Page no :2
Project :
Client

2. OVER CURRENT PROTECTION :


Setting :
I>1 Function IEC S INVERSE
I>1 Directional Directional FWD
I>1 Current Set 1.0 A
I>1 Time delay 0.1
I>1 tReset 0s
Characteristic Angle 45
2.I Pickup Test:
FUNCTION PICK UP CURRENT (A)
Set Current (A)
R Y B
I>1 1.0 1.004 1.004 1.005
2.II TIMING TEST:
Expected Relay operated Time(Sec)
Injected Current
FUNCTION Operation
(A) R Y B
Time(Sec)
I>1 2(2times) 1.00 1.03 1.03 1.03
I>1 2.5(2.5times) 0.757 0.76 0.76 0.76
2.III Checking Directional Feature
Relay operating Status
Expected Operating
Injected Angle
region for I>1 R-N Y-N B-N
+45˚ to 0˚ Operating Region(FWD) PASS PASS PASS
(0˚ or 360˚) to - 225.1˚ Operating Region(FWD) PASS PASS PASS
Non Operating
+45.1˚ to +225˚ PASS PASS PASS
Region(REV)

3. OVER CURRENT PROTECTION :


For For
Name : Name :
Sign : Sign :
Date : Date :
TEST REPORT FOR
Directional PROTECTION RELAY
Date : Page no :3
Project :
Client

Setting :
I>2 Function DT
I>2 Directional Directional FWD
I>2 Current Set 5.0 A
I>2 Time delay 0.1
3.I Pickup Test:

FUNCTION PICK UP CURRENT (A)


Set Current (A)
R Y B
I>2 5.0 5.005 5.005 5.005
3.II TIMING TEST:
Expected Relay operated Time(Sec)
Injected Current
FUNCTION Operation
(A) R Y B
Time(Sec)
I>2 5.5 1.00 1.03 1.03 1.03
3.III Checking Directional Feature
Relay operating Status
Expected Operating
Injected Angle
region for I>1 R-N Y-N B-N
+0˚ to +45˚ Operating Region(FWD) PASS PASS PASS
Non Operating
+45.1˚ to +225˚ PASS PASS PASS
Region(REV)
+225.1˚ to +360˚ Operating Region(FWD) PASS PASS PASS

4. Checking LED’s& Output Relays

FUNCTION Expected LED’s Operated LED Status


Dir Rph o/c Fault LED1 LED1 Verified Ok
Dir Yph o/c Fault LED-2 LED-2 Verified Ok
Dir Bph o/c Fault LED-3 LED-3 Verified Ok
o/c high fault LED-4 LED-4 Verified Ok

FUNCTION Expected Output Operated Output Status


Dir o/c Fault BO-3 BO-3 Verified Ok
o/c high fault BO-3 BO-3 Verified Ok

Result :
1. All output contacts and LED Checked OK.
2. . Relay found healthy

For For
Name : Name :
Sign : Sign :
Date : Date :