Professional Documents
Culture Documents
Emerson AC DC Converter
Emerson AC DC Converter
The AC-powered cabinet uses the EPS30-4815AF power system to convert the AC input
into the DC power for power distribution.
Huawei DSLAM:MA5616
Function
The EPS30-4815AF power system converts one AC input into two DC outputs to
implement the DC power distribution. It can be connected to one set of batteries and use
its monitoring module to manage the batteries.
The EPS30-4815AF power system can also use the external sensor transfer box to
collect and report the status of sensors and standby detected parameters.
Component Configuration
The EPS30-4815AF power system can be configured with two rectifier modules, which
are connected in parallel for output.
Mapping between the quantity of rectifier modules of the EPS30-4815AF power system
and the maximum output current
1 15 A
2 30 A
RUN The green LED is on. The rectifier module works in the normal
state.
The green LED is off. This LED is off when the red LED is on or
the yellow LED is on which is not caused by
the output overcurrent.
ALM The yellow LED is on. The ALARM LED of the module is valid
when PS-off, OTP, and primary protection
are valid, or when overcurrent occurs.
The yellow LED is off. The rectifier module works in the normal
state.
FAULT The red LED is on. The FAULT LED of the module is valid when
PS-enable and Vo-OV are valid, or when fan
fault, no output, or output short circuit
occurs.
The red LED is off. The rectifier module works in the normal
state.
RUN The green LED is on for The monitoring module works in the normal
1s and off for 1s state.
repeatedly.
The green LED is blinks The monitoring unit hardware is normal but
quickly. the communication between the monitoring
unit and the upper layer device is faulty.
ALM The red LED is on. The system generates an critical alarm or
the battery is disconnected.
The red LED is off. The system does not generate any critical
alarm and the battery is already connected.
The EPS30-4815AF power system supports three output terminals. The two pins on the
left of the output terminal are the output positive pole and the two pins on the right of the
output terminal are the output negative pole.
Mapping between the fuses of the output tributaries and the load tributaries
DIP Switch
The EPS30-4815AF power system provides a DIP switch, the DIP switch is on the right
middle of the monitoring module control board, which can be seen after you remove the
monitoring module. The DIP switch has eight available electrical switches. ON indicates
1, and OFF indicates 0. Table 4-6 describes the settings of DIP switch.
The DIP switchs 1-5 are used to set the address of the environment monitoring
module, Table 4-7 shows the settings of the Dip switchs.
Parameter Specification
Rated input voltage: 220 V AC (90-300 V AC) (Note that in the range of
90-176 V AC, the output current also decreases linearly, limited within a
Input specified range.)
Output current:
Output
LOAD1: 10 A (fuse)
LOAD2: 20 A (fuse)
BATT: 20 A (fuse)
Operating -33°C to +65°C (Note that in the range of +50°C to +65°C, the output
temperature range current also decreases linearly, limited within a specified range.)
Cooling method Forced air cooling, with the built-in fan in the rectifier module
Dimensions
(excluding mounting 43.6mmx482.6mmx270mm (W x D x H)
ears)