Professional Documents
Culture Documents
Earth Resistance Tester Lab 3
Earth Resistance Tester Lab 3
Earth Resistance Tester Lab 3
The Resistance of a conductor depends on the atomic structure of the material or its
Resistivity (measured in Ohm-m or Ω-m), which is that property of a material that measures
its ability to conduct electricity. A material with a low resistivity will behave as a “good
conductor” and one with a high resistivity will behave as a “bad conductor”. The commonly
used symbol for resistivity is ρ (Greek symbol rho).
The resistance (R) of a conductor can be derived from the resistivity as:
Resistivity is also sometimes referred to as “Specific Resistance” because, from the above
formula. Soil resistivity is the measure of the resistance between the opposite sides of the
cube of soil of 1 meter side dimension each.
The term “earth resistivity” expressed in ohm-centimetres (abbreviated ohm-cm) is one basic
variable affecting resistance to earth of an electrode system. But the actual value of earth
resistivity need not be measured to check the electrode earth resistance. Consider other fields
where the value of resistivity is measured; also some of the factors affecting it that are of
Workshop Lab 3
interest in earth testing. Earth resistivity measurements can be used conveniently for
geophysical prospecting — to locate ore bodies, clays, and water-bearing gravel beneath the
earth’s surface. The measurement can also be used to determine depth to bed rock and
thickness of glacial drift. Measurements of earth resistivity are useful also for finding the best
location and depth for low resistance electrodes. Such studies are made, for example, when a
new electrical unit is being constructed; a generating station, substation, transmission tower,
or telephone central office.
A four-terminal instrument is used to measure earth resistivity. Now, however, you use four
small-sized electrodes driven down to the same depth and equal distances apart in a straight
line (Fig. 1). Four separate lead wires connect the electrodes to the four terminals on the
instrument, as shown. Hence, the name of this test: the four-terminal method. Dr. Frank
Wenner of the U.S. Bureau of Standards (now NIST) developed the theory behind this test in
1915 (see reference pg. 76). He showed that, if the electrode depth (B) is kept small
compared to the distance between the electrodes (A), the following formula applies:
ρ = 2π AR
Where ρ is the average soil resistivity to depth A in ohm-cm, π is the constant 3.1416, A is
the distance between the electrodes in cm, and R is the Megger earth tester reading in ohms.
In other words, if the distance A between the electrodes is 4 ft. you obtain the average earth
resistivity to a depth of 4 ft as follows:
4 x 12 x 2.54 cm = 122 cm
Workshop Lab 3
2. Multiply 2 π A to obtain a constant for a given test setup:
Now, for example, if your instrument reading is 60 Ω, the earth resistivity would be 60 x 766,
or 45,960 ohm-cm.
----------------------------------------------------------------------------------------------------------------
V
Rx ¿ I ohm
The value of Rx depends on the placing of the auxiliary electrode. A curve showing the Rx
for different distances of Y from X as shown in figure 1 , the correct value of Rx is that in
section A to B on the curve. By means of Earth resistance tester Model PE-331 the resistance
Rx can be measured directly. In this experiment we used two earthing plates.
Workshop Lab 3
Figure 3. Earth resistance Testing Connection Diagram
----------------------------------------------------------------------------------------------------------------
3.5 Procedure
2. Connect the earth wire to the X and auxiliary earth Y and electrode Z to the corresponding
terminals of the tester.
4. Power ON the tester now after complete wires connection to tester terminals.
5. For each distance between Y and X, press the push button control. Read the displayed
resistance of earth.
7. Tabulate the resistance values each time and evaluate average resistance by summing up
all resistances at different distances divided by total number of experiment repeated.
R 1+ R 2+ R3+ …
R=
n
Workshop Lab 3
Spike 1 Distance Spike 2 Distance Resistance in Ohm AC-Voltage
S.No in Meters (m) in Meters measured
3.7 Calculations
3.8 Conclusion:
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………………
…………………………………………………………………………………………
Assessment Sheet:
Workshop Lab 3
Name: ----------------------------------------------------
Date: -----------------------------------------------------
Task
Lab Viva
Instructor verification
Workshop Lab 3