NOVEC System - Commissioning and Testing
NOVEC System - Commissioning and Testing
WARNING
PROCEDURES
*Pressure ( )
*Weight of NOVEC ( )
* Containers Bracketing ( )
* Containers Supports ( )
Pipes Normal ( )
(If found with corrosion, the pipes must be
changed).
* Auto Mode
Zone 1, Detectors ( )
Alarm Bells activate ( )
A/C & Dampers ( )
Shutdown
Zone 2, Detectors ( )
Siren Strobe activate ( )
Actuators activate ( )
after 30 seconds time
delay.
*Manual Mode
Zone 1 or Zone 2 not ( )
activate the actuators,
Activate S/S Fire ( )
Alarm.
Dual Action Manual ( )
Release, not activate
the actuators.
c). Operate Dual Action Manual Release to simulate
agent release. The actuating controls must move to
DISCHARGE position.
*Alarm Bells ( )
*Siren/Strobe Light ( )
*Siren/Strobe Light ( )
*HVAC & Dampers shutdown ( )
*Actuator must be in ( )
Discharge Position.
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
_____________________________________________________________________
Approval Status:
Accepted