Technical Specifications of The 2 Core, 1.5 Sq. MM, Un-Armoured Cable: Sr. No Description Data

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

1) Technical Specifications of the 2 Core, 1.5 Sq.

mm, Un-Armoured Cable:

Sr. No Description DATA


1 No. of Cores 2 CORE
2 Size in Sq.mm. 1.5 Sq mm
3 Quantity Required 2000 Mtrs
4 Voltage Grade 1100 V
5 Max. rated conductor temp in Deg. C 90°C
6 Max. allowable conductor temperature during 250°C
short circuit In Deg. Centigrade
7 Conductor Properties -
(i) Material Electrolytic Grade Copper Stranded Class-2 to IS 8130 / 1984
(ii) Shape Circular
(iii) Cross Sectional area (sq.mm) 1.5 Sq mm
(iv) No. of wires 7 nos
8 Approx. Dia of each strand (mm) 0.5 mm
(Before stranding)
9 Insulation Material Properties -
(i) Material XLPE As Per IS 7098 P1
(ii) Minimum Thickness ≥ 0.4 mm
(iii) Core Color Red & Black
10 Overall Screening Aluminium backed by mylar tape of nominal thickness of 0.025 mm
with 25% Overlap and 100% coverage shall be applied over cores.
ATC Drain wire of 0.5 sq mm multi strand tinned annealed copper
conductor shall be provided under Aluminium Mylar tape in
continuous contact with Al.
11 Rip cord Non-metallic rip cord shall be provided below inner sheath
12 Inner Sheath Material Properties -
(i) Material PVC Compound ST2 As Per IS 5831
(ii) Extruded or Wrapped Extruded
(iii) Minimum Thickness (mm) ≥ 0.3 mm
13 Outer Sheath Material Properties -
(i) Material Extruded PVC Compound (FRLS) As Per IS 5831
(ii) Color Red Color (for fire alarm system)
14 Approx. Overall Dia of Cable 13.00 mm +/- 2mm

15 Minimum bending radius 12 times of Over all Diameter


16 Electrical Parameters
(i) Max. DC Resistance of conductor at 20°C ≤ 12 Ω/Km
(ohm/km)
(ii) Max. DC Resistance of Drain + Shield ≤ 30 Ω/Km
(ohm/km)
(iii) H.V. Test ( core & Screen ) 1KV for 1 min
(iv)Insulation Resistance (Megger test) ≥ 100 MΩ
17 Marking/Printing on outer sheath 1100V, 2-CORE, 1.5SQMM, FRLS, FIRE ALARM CABLE, YEAR,
METERING
18 Other Properties of Cables FR-LSH Properties
a) Oxygen Index at room temperature as Min.29%
per ASTMD 2863
b) Temperature Index. As per ASTMD- Min. 250°C at 21% Oxygen index
2863
c) Smoke density Rating as per ATSMD- Smoke density rating maximum 60% and Light transmittance 40%
2843 minimum
d) Max. HCL Emission 20% Max. (by Weight)
as per IEC 60754-1
e) Flammability Test As per IEC-60332-1/SS-424-1475/IEEE-383/IEC-60332-3
19 Standard make of the Cable Finolex/L&T/GEM/Anchor/Hawells/Polycab
(as per NFC standards for electrical items)
Note:
1. Routine Test Certificates of the quoted items should be provided along with the supplies. Items will be
accepted at NFC, Hyderabad based on those routine test certificates.
2. Supplier should indicate clearly in their offers that they are agreed for part supply (if any). If not agreed, the
offer will not be considered for technical evaluation.

Page 1 of 4
(2) Technical Specifications of the 2 Core, 1.5 Sq. mm, Armoured Cable:
Sr No Description DATA
1 No of Cores 2 CORE
2 Size in Sq.mm. 1.5 Sq mm
3 Quantity Required 3000 Mtrs
4 Voltage Grade 1100 V
5 Max. rated conductor temp in Deg. C 90°C
6 Conductor Properties -
(i) Material Electrolytic Grade Copper Stranded Class-2 to IS 8130 / 1984
(ii) Shape Circular
(iii) Cross Sectional area (sq.mm) 1.5 Sq mm
(iv) No. of wires 7 nos
7 Approx. Dia. of each strand (mm) 0.5 mm
(Before stranding)
8 Insulation Material Properties -
(i) Material XLPE As Per IS 7098 P1
(ii) Minimum Thickness ≥ 0.4 mm
(iii) Core Color Red & Black
9 Overall Screening Aluminium backed by mylar tape of nominal thickness of 0.025 mm
with 25% Overlap and 100% coverage shall be applied over cores.
ATC Drain wire of 0.5 sq mm multi strand tinned annealed copper
conductor shall be provided under Aluminium Mylar tape in
continuous contact with Al.
10 Inner Sheath Material Properties -
(i) Material Extruded PVC Compound (FRLS) As Per IS 5831
(ii) Color Black Color
11 Rip cord Non-metallic rip cord shall be provided below inner sheath
12 Armoured material properties -
(i) Material Single GS round wire as per IS 3975
(ii) Type of Armour Round wire
(iii) Nominal Dimensions (mm) ≥ 0.9 mm
13 Outer Sheath Material Properties -
(i) Material Extruded PVC Compound (FR-LSH) As Per IS 5831
(ii) Min. for Armoured (mm) ≥ 1.2 mm
(iii) Colour Red color for fire alarm system
14 Approx. Overall Dia of Cable 13.00 mm +/- 2mm
15 Minimum bending radius 12 times of Over all Diameter
16 Electrical Parameters
(i) Max. DC Resistance of conductor at 20°C ≤ 12.1 Ω/Km
(ohm/km)
(ii) Max. DC Resistance of Drain+Shield ≤ 30 Ω/Km
(ohm/km)
(iii) H.V. Test ( core & Screen ) 1KV for 1 min
(iv)Insulation Resistance (Megger test) ≥ 100 MΩ
17 Marking/printing on outer sheath 1100V, 2-CORE, 1.5SQMM, FRLS, FIRE ALARM CABLE, YEAR,
METERING
18 Other Properties of Cables FRLS Properties
a) Oxygen Index at room temperature as Min.29%
per ASTMD-2863
b) Temperature Index. As per Min. 250°C at 21% Oxygen index
ASTMD-2863
c) Smoke density Rating as per ATSMD- Smoke density rating maximum 60% and Light transmittance 40%
2843 minimum
d) Max. HCL Emission as per 20% Max. (by Weight)
IEC 60754-1
e) Flammability Test As per IEC-60332-1/SS-424-1475/IEEE-383/IEC-60332-3
19 Standard make of the Cable CC/Universal/Polycab/RPG/Finecab/GEM
(as per NFC standards for electrical items)
Note:
1. Routine Test Certificates of the quoted items should be provided along with the supplies. Items will be
accepted at NFC, Hyderabad based on those routine test certificates.
2. Supplier should indicate clearly in their offers that they are agreed for part supply (if any). If not agreed, the
offer will not be considered for technical evaluation.

Page 2 of 4
(3) Technical Specifications of the 1 Pair, 1 Sq. mm, Armoured Cable:
Sr No Description DATA
1 No .of Pairs 1 Pair
2 Size in Sq.mm. 1 Sq. mm
3 Quantity Required 1000 Mtrs
4 Voltage Grade 1100 V
5 Max. rated conductor temp in Deg. C 90°C
6 Conductor Properties -
(i) Material Electrolytic Grade Copper Stranded Class-2 to IS 8130 / 1984
(ii) Shape Circular
(iii) Cross Sectional area (sq.mm) 1 Sq. mm
(iv) No. of wires 7 nos
7 Approx. Dia. of each strand (mm) 0.5 mm
(Before stranding)
8 Insulation Material Properties -
(i) Material XLPE As Per IS 7098 P1
(ii) Minimum Thickness ≥ 0.4 mm
(iii) Pair Color Red & Black
9 Overall Screening Aluminium backed by mylar tape of nominal thickness of 0.025 mm
with 25% Overlap and 100% coverage shall be applied over cores.
ATC Drain wire of 0.5 sq mm multi strand tinned annealed copper
conductor shall be provided under Aluminium Mylar tape in
continuous contact with Al.
10 Rip cord Non-metallic rip cord shall be provided below inner sheath
11 Inner Sheath Material Properties -
(i) Material Extruded PVC Compound (FRLS) As Per IS 5831
(ii) Color Black Color
12 Armoured material properties -
(i) Material Single GS round wire as per IS 3975
(ii) Type of Armour Round wire
(iii) Nominal Dimensions (mm) ≥ 0.9 mm
13 Outer Sheath Material Properties -
(i) Material Extruded PVC Compound (FR-LSH) As Per IS 5831
(ii) Min. for Armoured (mm) ≥ 1.2 mm
(iii) Colour Black
14 Approx.Overall Dia.of Cable 13.00 mm +/- 2mm
15 Minimum bending radius 12 times of Over all Diameter
16 Electrical Parameters
(i) Max. DC Resistance of conductor at 20°C ≤ 12.1 Ω/Km
(ohm/km)
(ii) Max. DC Resistance of Drain+Shield ≤ 30 Ω/Km
(ohm/km)
(iii) H.V. Test ( core & Screen ) 1KV for 1 min
(iv)Insulation Resistance (Megger test) ≥ 100 MΩ
17 Marking/printing on outer sheath 1100V, 2-CORE, 1.5SQMM, FRLS, YEAR, METERING
18 Other Properties of Cables FRLS Properties
a) Oxygen Index at room temperature as Min.29%
per ASTMD 2863
b) Temperature Index. Min. 250°C at 21% Oxygen index
as per ASTMD-2863
c) Smoke density Rating Smoke density rating maximum 60% and Light transmittance 40%
as per ATSMD-2843 minimum
d) Max. HCL Emission as per IEC 60754-1 20% Max. (by Weight)
e) Flammability Test As per IEC-60332-1/SS-424-1475/IEEE-383/IEC-60332-3
19 Standard make of the Cable CC/Universal/Polycab/RPG/Finecab/GEM
(as per NFC standards for electrical items)
Note:
1. Routine Test Certificates of the quoted items should be provided along with the supplies. Items will be
accepted at NFC, Hyderabad based on those routine test certificates.
2. Supplier should indicate clearly in their offers that they are agreed for part supply (if any). If not agreed, the
offer will not be considered for technical evaluation.

Page 3 of 4
(4) Technical Specifications of the 4 Core, 1.5 Sq. mm, Armoured Cable:
Sr No Description DATA
1 No.of Cores 4 CORE
2 Size in Sq.mm. 1.5 Sq. mm
3 Quantity Required 1000 Mtrs
4 Voltage Grade 1100 V
5 Max. rated conductor temp in Deg. C 90°C
6 Conductor Properties -
(i) Material Electrolytic Grade Copper Stranded Class-2 to IS 8130 / 1984
(ii) Shape Circular
(iii) Cross Sectional area (sq.mm) 1.5 Sq. mm
(iv) No. of wires 7 nos
7 Approx. Dia. of each strand (mm) 0.5 mm
(Before stranding)
8 Insulation Material Properties -
(i) Material XLPE As Per IS 7098 P1
(ii) Minimum Thickness ≥ 0.4 mm
(iii) Core Color Red, Yellow, Blue & Black
9 Overall Screening Aluminium backed by mylar tape of nominal thickness of 0.025 mm
with 25% Overlap and 100% coverage shall be applied over cores.
ATC Drain wire of 0.5 sq mm multi strand tinned annealed copper
conductor shall be provided under Aluminium Mylar tape in
continuous contact with Al.
10 Rip cord Non-metallic rip cord shall be provided below inner sheath
11 Inner Sheath Material Properties -
(i) Material Extruded PVC Compound (FR-LSH) As Per IS 5831
(ii) Color Black Color
12 Armoured material properties -
(i) Material Single GS round wire as per IS 3975
(ii) Type of Armour Round wire
(iii) Nominal Dimensions (mm) ≥ 0.9 mm
13 Outer Sheath Material Properties -
(i) Material Extruded PVC Compound (FR-LSH) As Per IS 5831
(ii) Min. for Armoured (mm) ≥ 1.2 mm
(iii) Colour Black
14 Approx.Overall Dia.of Cable 13.00 +/- 2mm
15 Minimum bending radius 12 times of Over all Diameter
16 Electrical Parameters
(i) Max. DC Resistance of conductor at 20°C ≤ 12.1 Ω/Km
(ohm/km)
(ii) Max. DC Resistance of Drain+Shield ≤ 30 Ω/Km
(ohm/km)
(iii) H.V. Test ( core & Screen ) 1KV for 1 min
(iv)Insulation Resistance (Megger test) ≥ 100 MΩ
17 Marking/printing on outer sheath 1100V, 2-CORE, 1.5SQMM, FRLS, YEAR, METERING
18 Other Properties of Cables FRLS Properties
a) Oxygen Index at room temperature as Min.29%
per ASTMD 2863
b) Temperature Index. Min. 250°C at 21% Oxygen index
as per ASTMD-2863
c) Smoke density Rating Smoke density rating maximum 60% and Light transmittance 40%
as per ATSMD-2843 minimum
d) Max. HCL Emission as per IEC 60754-1 20% Max. (by Weight)
e) Flammability Test As per IEC-60332-1/SS-424-1475/IEEE-383/IEC-60332-3
19 Standard make of the Cable CC/Universal/Polycab/RPG/Finecab/GEM
(as per NFC standards for electrical items)
Note:
1. Routine Test Certificates of the quoted items should be provided along with the supplies. Items will be
accepted at NFC, Hyderabad based on those routine test certificates.
2. Supplier should indicate clearly in their offers that they are agreed for part supply (if any). If not agreed, the
offer will not be considered for technical evaluation.

Page 4 of 4