Professional Documents
Culture Documents
Total Cost of System 0 0
Total Cost of System 0 0
Eelctrical System
I Supply,Installation,Testing and Commissioning with all Accessories:
Point wiring for Light / Ceiling Fan / Exhaust Fan etc. with 600/1100 volts grade as per BS 6231
multistranded copper conductor FR PVC insulated wires in 25mm/32mm Rigid PVC conduit MMS with
Conduit System for Cable Management concealed in slab/wall or surface with suitable spacers / saddles etc.
Earthing wire 1.0 sq.mm PVC insulated shall be provided for Light Point/fan Point/5 A Plug and 1.5 sq.mm
PVC insulated shall be provided for Gyser/AC point/Power Point. Accessories e.g. Bakelite lamp holders / 3
way PVC connectors, ceiling rose, switch, sockets, MS plate & boxes etc. shall be provided. Circuit wires
for light / fan /5A Plug / Bell etc. shall be Switchboard board to point wire shall be 1.5 Sq.mm. Colour
coding to be maintain for phasing & earthing. Proper lugs and ferrueling required for any circuiting.
Primary Light Point with 1.5 Sq.mm wire complete with all accessories control from Respective Distribution
a Board With Avg Length of 14 Mtr. 489 Nos.
Secondary Light Point with 1.5 Sq.mm wire complete with all accessories control from Respective
b Distribution Board with Avg Length of 8 Mtr 1619 Nos.
One 5 Amp Socket controlled by one 5 Amp Switch.(Half Points) with 2x2.5+1x2.5 Sq.mm wires with
Average Length of 5 Mtr from DB to Switch Board. This shall include installation of 5 Amp single way
c modular switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, 118 Nos.
saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.
One 5 Amp Socket controlled by one 5 Amp Switch for AC IDU with 2x2.5+1x2.5 Sq.mm wires with
Average Length of 5 Mtr from DB to Switch Board. This shall include installation of 5 Amp single way
d modular switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, 34 Nos.
saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.
One 15/5 Amp Socket controlled by one 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 15 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
e switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 39 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.
Two 5/15 Amp Socket controlled by Two 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 8 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
f switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 8 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.
One 5/15 Amp Socket controlled by Two 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 15 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
g switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 9 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.
One 20A Socket controlled by one 20A Switch for Refrigerator/Oven/Kitchen Appliances with 2x4.0+1x4.0
sq.mm wires with Average Length of 15 Mtr from DB to Switch Board & Socket of 2 Module. This shall
h include installation of 20A single way modular switch, 2 mm thick PVC concealed box and other accessories 31 Nos.
such as bends, junction boxes, saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to
complete the wiring.
Lighting DB
Incomer:
i) 40 Amp TPN Isolator
a 1 Nos.
ii) 40A 4P 100mA ELCB : 3 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB
Lighting DB
Incomer:
i) 40 Amp TPN Isolator
b 1 Nos.
ii) 40A 4P 100mA ELCB : 24 Nos
Outgoing:
i) 24# 10 Amp SP 10kA MCB
Ceiling LDB
Incomer:
i) 40 Amp TPN Isolator
c 1 Nos.
ii) 40A 4P 100mA ELCB : 4 Nos
Outgoing:
i) 36# 10 Amp SP 10kA MCB
Ceiling LDB
Incomer:
i) 40 Amp TPN Isolator
d 1 Nos.
d 1 Nos.
ii) 40A 4P 100mA ELCB : 2 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB
Power DB
Incomer:
i) 100 Amp TPN MCCB
e 2 Nos.
ii) 40A 4P 30mA ELCB : 5 Nos
Outgoing:
i) 30# 20 Amp SP 10kA MCB
AC DB
Incomer:
i) 40 Amp TPN Isolator
f 1 Nos.
ii) 40A 4P 300mA ELCB : 5 Nos
Outgoing:
i) 30# 10 Amp SP 10kA MCB
AC DB
Incomer:
i) 40 Amp TPN Isolator
g 1 Nos.
ii) 40A 4P 300mA ELCB : 4 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB
Facade LDB
Incomer:
i) 40 Amp TP Isolator
h 1 Nos.
ii) 40A 4P 100mA ELCB : 2 Nos
Outgoing:
i) 12# 10 Amp SP 10kA MCB
External DB
Incomer:
i) 40 Amp TP Isolator
i 1 Nos.
ii) 40A 4P 100mA ELCB : 3 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB
V DG Set (Provision)
Supply, Installation, testing and commissioning of Prime power rated Diesel Generator Set complete with
Diesel Engine suitable for Generator application, developing 1500 RPM with an overloading capacity of
10% for one hour in any 12 continuous hours operation coupled at 0.85 Power factor, 415V, 3 Phase , 4
wires, 50 Hz. self excited, self regulated and brushless excitation. DG set shall be radiator type with silencer,
electronic governor, termination box, MS mounting frame, fuel piping, 990 liters diesel day tank, 24VDC
Battery Charger & batteries, Battery mounting frame, oil level indicator with gauge board, The DG Set
shall be suitable for auto-mains failure start, auto synchronization, auto load sharing and auto / manual
operations. The cost shall include fuel oil required for testing DG Set at full load. (Cost of diesel to be
included for testing, commissioning to the satisfaction of Owner. The rate shall be inclusive of providing
necessary consumables including fuel, lube oil etc. for 8 hours trials, testing and commissioning of DG sets
and required coordination with other agencies.)
10 KVA/---VDC True-On-Line UPS System using microchip controlled IGBT based design
maintenance free batteries for 15 minutes battery backup.
Battery Rack
VIII LT Panel
Design, fabrication, supply, testing, commissioning of medium voltage, 415 volts with IEC 61439, MS
cubicle panels, floor mounted, extensible complete with ‘C’ channels, and stand mounted @350mm/300mm
above ground level. fabricated of 14/16 CRCA sheet, treated, powder coated with Siemens gray color, cable
alleys/ cable end boxes, high electrical grade Aluminum bus bars, with color coded, heat shrinkable sleeves,
mounted on DMC / SMC supports, with following mountings , interconnection, indicating lamps, metering,
CT’s, MCCB,MCB etc. and arrangement of meters with necessary wiring etc.
Outgoing:
400 Amp TP MCCB: 1 Nos
200 Amp TP MCCB: 1 Nos
63 Amp TP MCCB: 3 Nos
40 Amp TP MCCB: 1 Nos
16 Amp TP MCB: 1 Nos
Note: Provide 3 to 4 MCCB Provision
Outgoing:
200 Amp TP MCCB: 1 Nos
100 Amp TP MCCB: 2 Nos
40 Amp TP MCCB: 7 Nos
Note: Provide 3 to 4 MCCB Provision
MCC Panel 1 Nos
Incoming:
200A TP MCCB 25kA: 1 Nos
LED Type Indicating Light 230V Red/Green/White with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Yelolow/Amber with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Blue with Smooth Lens: 1 Nos
250 Amp TPN Al Busbar 25 kA
c
Outgoing:
125 Amp TP MCCB: 2 Nos
40 Amp TP MCCB: 3 Nos
25 Amp TP MCB: 1 Nos
20 Amp TP MCB: 2 Nos
16 Amp TP MCB: 4 Nos
Note: Provide 3 to 4 MCCB Provision
Outgoing:
63 Amp TP MCB: 2 Nos
50 Amp TP MCB: 2 Nos
d
32 Amp TP MCB: 2 Nos
6 Stage Low Sensitivity APFC Relay 3 Ct Sensing
30 KVAR TP Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 30 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
20 KVAR Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 20 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
10 KVAR Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 10 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
Capcitor Bank 30 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos
Capcitor Bank 20 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos
Capcitor Bank 10 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos
IX LT Cabling System:
Supplying, Laying, testing, commissioning of 1.1 KV grade XLPE insulated, inner sheath PVC tapped
extruded outer sheath PVC GI wire armoured, solid aluminium conductor power cable conforming to BS
6231 with latest amendments fixed on wall / column slab / in existing hume pipes / trench / shaft / GI pipes
on 5 mm. thick GI spacers / MS flat angle min. 6 mm thick with wood screws / coach screws / anchor
fastners , GI saddles min. 2 mm thick all fixing accessories or in ground at a depth of 900 mm below ground
in level with existing hume pipe ( generally at road crossings) level including excavation, sand bedding,
a
laying of baked bricks on side and top, temporary re-instartment , back filling, dewatering consolidation , if
necessary, disposal of excess earth with in the radius of 500m mtr. etc. providing brass cable number tag as
per drawing, specifications and as per the instructions of Consultants and of the following sizes :
End jointing of XLPE cable by crimping with supply of all jointing material like solder less copper socket,
insulation tape, flux duplicate earthing for cable gland with 12 SWG tinned copper wire & strip ( 3 mm thick
b minimum), Non Ferrous Gland Plate for Termination fo CU/XLPE/SWA & COpper Lugs for ECC etc. as
per drawings & specifications.
1 4C x 185 Sq.mm CU. Arm 4 Nos.
2 4C x 150 Sq.mm CU. Arm 4 Nos.
3 4C x 120 Sq.mm CU. Arm 4 Nos.
4 4C x 95 Sq.mm CU. Arm 0 Nos.
5 4C x 70 Sq.mm CU. Arm 0 Nos.
6 4C x 50 Sq.mm CU. Arm 0 Nos.
7 4C x 35 Sq.mm CU. Arm 4 Nos.
8 4C x 25 Sq.mm CU. Arm 6 Nos.
9 4C x 16 Sq.mm CU. Arm 6 Nos.
10 4C x 10 Sq.mm CU. Arm 14 Nos.
11 4C x 6 Sq.mm CU. Arm 2 Nos.
12 1C x 95 Sq.mm CU. Arm 4 Nos.
13 1C x 70 Sq.mm CU. Arm 4 Nos.
14 1C x 50 Sq.mm CU. Arm 4 Nos.
15 1C x 35 Sq.mm CU. Arm 0 Nos.
16 1C x 25 Sq.mm CU. Arm 10 Nos.
17 1C x 16 Sq.mm CU. Arm 6 Nos.
18 1C x 10 Sq.mm CU. Arm 14 Nos.
19 1C x 6 Sq.mm CU. Arm 2 Nos.
X Civil work:
Providing , laying, jointing & testing NP2 class RCC pipes with mortise - tenon, jointed with cement and
with RCC collar to cover and overlap the joints laid to correct levels below ground in trenches upto required
depth including excavation in all kind of soil (including hard rock), dewatering, refilling, watering, ramming
and removing the surplus excavated material, dumping it on site or carting away to lead of 100 meters as
directed and making good the same complete as required. Price to include 150 mm thick PCC (1:4:8)
a haunches upto centre at the joints to cover the collar and 150 mm on bothsides and 400 mm wide cradles for
intermediate supports at maximum 1 meter centre to centre in brick masonary (duly plastered 1:5 CM) on
100 mm thick PCC 1:4:8 over 230 mm rubble soling. The pipes shall be of following nominal bore (NB)
size:
Constructing water tight brick masonry manhole with first class bricks in cement mortar 1:6 (1 cement :6
b coarse sand), R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size).
Foundation concrete 150 mm thick 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm
nominal size), inside plastering 12 mm thick with cement plaster 1:3 (1 cement : 3 coarse sand) finished with
a floating coat of neat cement and making channel in cement concrete 1:3:6 mix, M.S. foot rests including
fixing in 20 x 20 x 10 cm cement conc blocks neatly finished, complete as per standard design and approved
drawings. (Price shall include the cost of excavation, back filling, disposal of suplus earth dewatering and
water proofing of manholes as directed at site & other associated civil works).
1 450X450X600mm 13 Nos
Providing, fixing, jointing and testing heavy duty, PVC pipes, - 6 kg/cm2 pressure for Electrical
including jointing with rubbering / solvent / solution and airtight joints, with necessary specials, couplers,
c elbow, equal tees, tail piece, adapter (both male and female), reducer, end cap, fabricated bend, etc., and
lubricant or jointing material, including testing, cutting, making good the wall, ceiling and floor etc.
complete of the following nominal bore (NB) size:
XI Cable Tray
Fabricating and installing following size of Ladder MS galvanised cable trays including horizontal and
vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the
a ceiling with M.S. suspenders and including painting of suspenders etc. as required.
XII Earthing
Supply, Installing, Testing and Commissioning of CU earthing station with 25 x 3 mm CU strips from earth
electrode to inspection chamber, 50 mm dia CU pipe with 3 mtr long and surrounding area will be filled by
a Backfill Compund. Prices should include 4'' dia bore, back filling, masonry chamber 300 x 300 mm with 7 Nos.
concrete base, cast Iron cover, test links, disconnecting link etc.
Supplying and laying earthing conductors of Copper including necessary accessories, clamping to walls,
cables etc.as required and interconnection between lengths as per specifications and as per good installation
b practice. Prices should include all supports, accessories and hardware necessary for proper installation.
Supply and Installation of test link box made out of 2mm CRCA sheet , galvanized and having a GI Test
b Link of size 150 mm long , 25 x 6 mm link Cu strip mounted on suitable nut bolts , complete with hinge 5 Nos.
type covers GI clamps etc.
Supplying and laying earthing conductors of Copper / GI strips including necessary accessories, clamping to
walls, cables etc.as required and interconnection between lengths as per specifications and as per good
c installation practice. Prices should include all supports, accessories and hardware necessary for proper
installation.
1 25 x 3 mm Cu Bare Tape for Roof & Down Conductor 500 Rm