Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 7

Project Name: Dubai Hills Estate LLC

SR NO. DESCRIPTION SUPPLY LABOUR


1 Total Cost of Electrical Work 0 0

Total Cost of System 0 0

45, Lane 1, Gurujambeshwar Nagar A,


Gandhipath, Jaipur – 302021
91-8454931637
contact@pillarplus.com| www.pillarplus.com
Project Name: Dubai Hills Estate LLC
Electrical BOQ
Rate Amount
Sr No. Description Quantity Unit
Supply Labour Supply Labour

Eelctrical System
I Supply,Installation,Testing and Commissioning with all Accessories:
Point wiring for Light / Ceiling Fan / Exhaust Fan etc. with 600/1100 volts grade as per BS 6231
multistranded copper conductor FR PVC insulated wires in 25mm/32mm Rigid PVC conduit MMS with
Conduit System for Cable Management concealed in slab/wall or surface with suitable spacers / saddles etc.
Earthing wire 1.0 sq.mm PVC insulated shall be provided for Light Point/fan Point/5 A Plug and 1.5 sq.mm
PVC insulated shall be provided for Gyser/AC point/Power Point. Accessories e.g. Bakelite lamp holders / 3
way PVC connectors, ceiling rose, switch, sockets, MS plate & boxes etc. shall be provided. Circuit wires
for light / fan /5A Plug / Bell etc. shall be Switchboard board to point wire shall be 1.5 Sq.mm. Colour
coding to be maintain for phasing & earthing. Proper lugs and ferrueling required for any circuiting.

Primary Light Point with 1.5 Sq.mm wire complete with all accessories control from Respective Distribution
a Board With Avg Length of 14 Mtr. 489 Nos.
Secondary Light Point with 1.5 Sq.mm wire complete with all accessories control from Respective
b Distribution Board with Avg Length of 8 Mtr 1619 Nos.

II Supply,Installation,Testing and Commissioning of Switch Sockets with all Accessories:


One 5 Amp only Socket controlled by Submain/DB with 2x2.5+1x2.5 Sq.mm wires with Average Length of
14 Mtr from DB to Switch Board of 3 Module. This shall include installation of 2 mm thick PVC concealed
a box and other accessories such as bends, junction boxes, saddles, spacers, switch plates, angle holders, 28 Nos.
ceiling roses etc. as required to complete the wiring.
One 5 Amp Socket controlled by one 5 Amp Switch.(Full Points) with 2x2.5+1x2.5 Sq.mm wires with
Average Length of 15 Mtr from DB to Switch Board of 3 Module. This shall include installation of 5 Amp
b single way modular switch, 2 mm thick PVC concealed box and other accessories such as bends, junction 40 Nos.
boxes, saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

One 5 Amp Socket controlled by one 5 Amp Switch.(Half Points) with 2x2.5+1x2.5 Sq.mm wires with
Average Length of 5 Mtr from DB to Switch Board. This shall include installation of 5 Amp single way
c modular switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, 118 Nos.
saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

One 5 Amp Socket controlled by one 5 Amp Switch for AC IDU with 2x2.5+1x2.5 Sq.mm wires with
Average Length of 5 Mtr from DB to Switch Board. This shall include installation of 5 Amp single way
d modular switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, 34 Nos.
saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

One 15/5 Amp Socket controlled by one 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 15 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
e switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 39 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

Two 5/15 Amp Socket controlled by Two 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 8 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
f switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 8 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

One 5/15 Amp Socket controlled by Two 15 Amp Switch with 2x4.0+1x4.0 Sq.mm wires with Average
Length of 15 Mtr from DB to Switch Board. This shall include installation of 15 Amp single way modular
g switch, 2 mm thick PVC concealed box and other accessories such as bends, junction boxes, saddles, 9 Nos.
spacers, switch plates, angle holders, ceiling roses etc. as required to complete the wiring.

One 20A Socket controlled by one 20A Switch for Refrigerator/Oven/Kitchen Appliances with 2x4.0+1x4.0
sq.mm wires with Average Length of 15 Mtr from DB to Switch Board & Socket of 2 Module. This shall
h include installation of 20A single way modular switch, 2 mm thick PVC concealed box and other accessories 31 Nos.
such as bends, junction boxes, saddles, spacers, switch plates, angle holders, ceiling roses etc. as required to
complete the wiring.

III Distribution Board


Supply, Installation, Testing and Commissioning of the following Distribution Boards fabricated in sheet
steel with phase copper bus bars, neutral and earth bar with tapped holes, cutouts for operating the MCB
knobs in the inner cover, bakelite phase barriers, double door construction, powder coated with approved
shade and partitions to segregate phases etc. DB's shall be suitable for single phase/3 phase operation.
DB's shall be flush mounted to brick wall or surface mounted as required IP43:

Lighting DB
Incomer:
i) 40 Amp TPN Isolator
a 1 Nos.
ii) 40A 4P 100mA ELCB : 3 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB

Lighting DB
Incomer:
i) 40 Amp TPN Isolator
b 1 Nos.
ii) 40A 4P 100mA ELCB : 24 Nos
Outgoing:
i) 24# 10 Amp SP 10kA MCB

Ceiling LDB
Incomer:
i) 40 Amp TPN Isolator
c 1 Nos.
ii) 40A 4P 100mA ELCB : 4 Nos
Outgoing:
i) 36# 10 Amp SP 10kA MCB

Ceiling LDB
Incomer:
i) 40 Amp TPN Isolator
d 1 Nos.
d 1 Nos.
ii) 40A 4P 100mA ELCB : 2 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB
Power DB
Incomer:
i) 100 Amp TPN MCCB
e 2 Nos.
ii) 40A 4P 30mA ELCB : 5 Nos
Outgoing:
i) 30# 20 Amp SP 10kA MCB

AC DB
Incomer:
i) 40 Amp TPN Isolator
f 1 Nos.
ii) 40A 4P 300mA ELCB : 5 Nos
Outgoing:
i) 30# 10 Amp SP 10kA MCB

AC DB
Incomer:
i) 40 Amp TPN Isolator
g 1 Nos.
ii) 40A 4P 300mA ELCB : 4 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB

Facade LDB
Incomer:
i) 40 Amp TP Isolator
h 1 Nos.
ii) 40A 4P 100mA ELCB : 2 Nos
Outgoing:
i) 12# 10 Amp SP 10kA MCB

External DB
Incomer:
i) 40 Amp TP Isolator
i 1 Nos.
ii) 40A 4P 100mA ELCB : 3 Nos
Outgoing:
i) 18# 10 Amp SP 10kA MCB

IV Submain Wiring & Conduit


Wiring for DB to Switch Board & Switch Board to Switch Board using 2x2.5+1x2.5 Sqmm Cu FRLS Wires
a in already laid in GI /MS /HMS PVC conduits. contactor shall be consider three to four circuits in single 1585 Mtr
conduits wherever possible from DB to Submain.
Wiring for DB to Switch Board & Switch Board to Switch Board using 2x4.0+1x4.0 Sqmm Cu FRLS Wires
b in already laid in GI /MS /HMS PVC conduits. contactor shall be consider three to four circuits in single 522 Mtr
conduits wherever possible from DB to Submain. (Extra)
Supply and fixing the following sizes of RIGID PVC Medium Duty conduits complete with accessories
c such as bends, junction boxes, pull boxes etc., in recess or on surface including cutting chases in the
walls/floors and making good the same complete as required.
1 25 mm dia RIGID PVC conduits 2824 Mtr

V DG Set (Provision)
Supply, Installation, testing and commissioning of Prime power rated Diesel Generator Set complete with
Diesel Engine suitable for Generator application, developing 1500 RPM with an overloading capacity of
10% for one hour in any 12 continuous hours operation coupled at 0.85 Power factor, 415V, 3 Phase , 4
wires, 50 Hz. self excited, self regulated and brushless excitation. DG set shall be radiator type with silencer,
electronic governor, termination box, MS mounting frame, fuel piping, 990 liters diesel day tank, 24VDC
Battery Charger & batteries, Battery mounting frame, oil level indicator with gauge board, The DG Set
shall be suitable for auto-mains failure start, auto synchronization, auto load sharing and auto / manual
operations. The cost shall include fuel oil required for testing DG Set at full load. (Cost of diesel to be
included for testing, commissioning to the satisfaction of Owner. The rate shall be inclusive of providing
necessary consumables including fuel, lube oil etc. for 8 hours trials, testing and commissioning of DG sets
and required coordination with other agencies.)

320 KVA at 0.8 pf 415V 50Hz 3-Ø 1 Nos

VI CT Operated Energy Meter


Installation & commissioning of 500/5A CT Meter as per DEWA with all mounting arrangement, fastner
a and all required accessories, with MS Cover, outdoor type IP 54 protection. 1 Nos

VII ON LINE UPS SYSTEM


Supply,Installation, testing and commissioning of following type of ON LINE UPS as per drawings and
1 Nos
specifications with all other accessories
3-PHASE INPUT- 3-PHASE OUTPUT ON LINE UPS

10 KVA/---VDC True-On-Line UPS System using microchip controlled IGBT based design
maintenance free batteries for 15 minutes battery backup.
Battery Rack

VIII LT Panel
Design, fabrication, supply, testing, commissioning of medium voltage, 415 volts with IEC 61439, MS
cubicle panels, floor mounted, extensible complete with ‘C’ channels, and stand mounted @350mm/300mm
above ground level. fabricated of 14/16 CRCA sheet, treated, powder coated with Siemens gray color, cable
alleys/ cable end boxes, high electrical grade Aluminum bus bars, with color coded, heat shrinkable sleeves,
mounted on DMC / SMC supports, with following mountings , interconnection, indicating lamps, metering,
CT’s, MCCB,MCB etc. and arrangement of meters with necessary wiring etc.

Main Distribution Panel 1 Nos


Incoming:
500A FP MCCB 36kA: 2 Nos
LED Type Indicating Light 230V Red/Green/White with Smooth Lens: 2 Nos
LED Type Indicating Light 230V Yelolow/Amber with Smooth Lens: 2 Nos
LED Type Indicating Light 230V Blue with Smooth Lens: 2 Nos
CT 500/5 Amp class:1 ,15VA: 1 Nos
3 Phase LED Voltmeter: 2 Nos
3 Phase LED Ammeter: 2 Nos
a
Interlock: Incomer should be Mechanical & Electrical Interlocking Between Electrical & DG Incomer With
a Auto Changeover System
630 Amp TPN Al Busbar 36 kA

Outgoing:
400 Amp TP MCCB: 1 Nos
200 Amp TP MCCB: 1 Nos
63 Amp TP MCCB: 3 Nos
40 Amp TP MCCB: 1 Nos
16 Amp TP MCB: 1 Nos
Note: Provide 3 to 4 MCCB Provision

Sub Main Distribution Board 1 Nos


Incoming:
400A TP MCCB 36kA: 1 Nos
LED Type Indicating Light 230V Red/Green/White with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Yelolow/Amber with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Blue with Smooth Lens: 1 Nos
b 500 Amp TPN Al Busbar 25 kA

Outgoing:
200 Amp TP MCCB: 1 Nos
100 Amp TP MCCB: 2 Nos
40 Amp TP MCCB: 7 Nos
Note: Provide 3 to 4 MCCB Provision
MCC Panel 1 Nos
Incoming:
200A TP MCCB 25kA: 1 Nos
LED Type Indicating Light 230V Red/Green/White with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Yelolow/Amber with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Blue with Smooth Lens: 1 Nos
250 Amp TPN Al Busbar 25 kA
c
Outgoing:
125 Amp TP MCCB: 2 Nos
40 Amp TP MCCB: 3 Nos
25 Amp TP MCB: 1 Nos
20 Amp TP MCB: 2 Nos
16 Amp TP MCB: 4 Nos
Note: Provide 3 to 4 MCCB Provision

Capacitor Bank 1 Nos


Incoming:
200A TP MCCB 25kA: 1 Nos
LED Type Indicating Light 230V Red/Green/White with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Yelolow/Amber with Smooth Lens: 1 Nos
LED Type Indicating Light 230V Blue with Smooth Lens: 1 Nos
250 Amp TPN Al Busbar 25 kA

Outgoing:
63 Amp TP MCB: 2 Nos
50 Amp TP MCB: 2 Nos
d
32 Amp TP MCB: 2 Nos
6 Stage Low Sensitivity APFC Relay 3 Ct Sensing
30 KVAR TP Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 30 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
20 KVAR Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 20 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
10 KVAR Capacitor Duty Contactor With Damping Resistors And Early Make Poles For 10 Kvar 3ø
Capacitor 440 V ,1no+1nc Aux Contacts: 2 Nos
Capcitor Bank 30 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos
Capcitor Bank 20 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos
Capcitor Bank 10 Kvar Cylindrical Type Normal Duty Operating Losses- 0.45w/Kvar 440 V: 2 Nos

IX LT Cabling System:
Supplying, Laying, testing, commissioning of 1.1 KV grade XLPE insulated, inner sheath PVC tapped
extruded outer sheath PVC GI wire armoured, solid aluminium conductor power cable conforming to BS
6231 with latest amendments fixed on wall / column slab / in existing hume pipes / trench / shaft / GI pipes
on 5 mm. thick GI spacers / MS flat angle min. 6 mm thick with wood screws / coach screws / anchor
fastners , GI saddles min. 2 mm thick all fixing accessories or in ground at a depth of 900 mm below ground
in level with existing hume pipe ( generally at road crossings) level including excavation, sand bedding,
a
laying of baked bricks on side and top, temporary re-instartment , back filling, dewatering consolidation , if
necessary, disposal of excess earth with in the radius of 500m mtr. etc. providing brass cable number tag as
per drawing, specifications and as per the instructions of Consultants and of the following sizes :

1 4C x 185 Sq.mm CU. Arm 40 Mtr


2 4C x 150 Sq.mm CU. Arm 120 Mtr
3 4C x 120 Sq.mm CU. Arm 58 Mtr
4 4C x 95 Sq.mm CU. Arm 0 Mtr
5 4C x 70 Sq.mm CU. Arm 0 Mtr
6 4C x 50 Sq.mm CU. Arm 0 Mtr
7 4C x 35 Sq.mm CU. Arm 65 Mtr
8 4C x 25 Sq.mm CU. Arm 95 Mtr
9 4C x 16 Sq.mm CU. Arm 75 Mtr
10 4C x 10 Sq.mm CU. Arm 285 Mtr
11 4C x 6 Sq.mm CU. Arm 20 Mtr
12 1C x 95 Sq.mm CU. Arm 40 Mtr
13 1C x 70 Sq.mm CU. Arm 120 Mtr
14 1C x 50 Sq.mm CU. Arm 58 Mtr
15 1C x 35 Sq.mm CU. Arm 0 Mtr
16 1C x 25 Sq.mm CU. Arm 160 Mtr
17 1C x 16 Sq.mm CU. Arm 75 Mtr
18 1C x 10 Sq.mm CU. Arm 285 Mtr
19 1C x 6 Sq.mm CU. Arm 20 Mtr

End jointing of XLPE cable by crimping with supply of all jointing material like solder less copper socket,
insulation tape, flux duplicate earthing for cable gland with 12 SWG tinned copper wire & strip ( 3 mm thick
b minimum), Non Ferrous Gland Plate for Termination fo CU/XLPE/SWA & COpper Lugs for ECC etc. as
per drawings & specifications.
1 4C x 185 Sq.mm CU. Arm 4 Nos.
2 4C x 150 Sq.mm CU. Arm 4 Nos.
3 4C x 120 Sq.mm CU. Arm 4 Nos.
4 4C x 95 Sq.mm CU. Arm 0 Nos.
5 4C x 70 Sq.mm CU. Arm 0 Nos.
6 4C x 50 Sq.mm CU. Arm 0 Nos.
7 4C x 35 Sq.mm CU. Arm 4 Nos.
8 4C x 25 Sq.mm CU. Arm 6 Nos.
9 4C x 16 Sq.mm CU. Arm 6 Nos.
10 4C x 10 Sq.mm CU. Arm 14 Nos.
11 4C x 6 Sq.mm CU. Arm 2 Nos.
12 1C x 95 Sq.mm CU. Arm 4 Nos.
13 1C x 70 Sq.mm CU. Arm 4 Nos.
14 1C x 50 Sq.mm CU. Arm 4 Nos.
15 1C x 35 Sq.mm CU. Arm 0 Nos.
16 1C x 25 Sq.mm CU. Arm 10 Nos.
17 1C x 16 Sq.mm CU. Arm 6 Nos.
18 1C x 10 Sq.mm CU. Arm 14 Nos.
19 1C x 6 Sq.mm CU. Arm 2 Nos.
X Civil work:
Providing , laying, jointing & testing NP2 class RCC pipes with mortise - tenon, jointed with cement and
with RCC collar to cover and overlap the joints laid to correct levels below ground in trenches upto required
depth including excavation in all kind of soil (including hard rock), dewatering, refilling, watering, ramming
and removing the surplus excavated material, dumping it on site or carting away to lead of 100 meters as
directed and making good the same complete as required. Price to include 150 mm thick PCC (1:4:8)
a haunches upto centre at the joints to cover the collar and 150 mm on bothsides and 400 mm wide cradles for
intermediate supports at maximum 1 meter centre to centre in brick masonary (duly plastered 1:5 CM) on
100 mm thick PCC 1:4:8 over 230 mm rubble soling. The pipes shall be of following nominal bore (NB)
size:

1 250 mm. NP2 class RCC pipe. 90 Rmt


2 150 mm NP2 class RCC pipe. 160 Rmt

Constructing water tight brick masonry manhole with first class bricks in cement mortar 1:6 (1 cement :6
b coarse sand), R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size).
Foundation concrete 150 mm thick 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm
nominal size), inside plastering 12 mm thick with cement plaster 1:3 (1 cement : 3 coarse sand) finished with
a floating coat of neat cement and making channel in cement concrete 1:3:6 mix, M.S. foot rests including
fixing in 20 x 20 x 10 cm cement conc blocks neatly finished, complete as per standard design and approved
drawings. (Price shall include the cost of excavation, back filling, disposal of suplus earth dewatering and
water proofing of manholes as directed at site & other associated civil works).

1 450X450X600mm 13 Nos

Providing, fixing, jointing and testing heavy duty, PVC pipes, - 6 kg/cm2 pressure for Electrical
including jointing with rubbering / solvent / solution and airtight joints, with necessary specials, couplers,
c elbow, equal tees, tail piece, adapter (both male and female), reducer, end cap, fabricated bend, etc., and
lubricant or jointing material, including testing, cutting, making good the wall, ceiling and floor etc.
complete of the following nominal bore (NB) size:

1 50mm Corrugated pipes (Drex) 220 Rmt

XI Cable Tray
Fabricating and installing following size of Ladder MS galvanised cable trays including horizontal and
vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the
a ceiling with M.S. suspenders and including painting of suspenders etc. as required.

1 150 mm. width x 50 mm. depth x 1.6 mm. thickness 30 PMtr


2 250 mm. width x 50 mm. depth x 1.6 mm. thickness 30 PMtr

XII Earthing
Supply, Installing, Testing and Commissioning of CU earthing station with 25 x 3 mm CU strips from earth
electrode to inspection chamber, 50 mm dia CU pipe with 3 mtr long and surrounding area will be filled by
a Backfill Compund. Prices should include 4'' dia bore, back filling, masonry chamber 300 x 300 mm with 7 Nos.
concrete base, cast Iron cover, test links, disconnecting link etc.
Supplying and laying earthing conductors of Copper including necessary accessories, clamping to walls,
cables etc.as required and interconnection between lengths as per specifications and as per good installation
b practice. Prices should include all supports, accessories and hardware necessary for proper installation.

1 25 x 3 mm Cu Bare Tape 30 Mtrs.

XIII Lift System


Supply, Installation, Testing & Commissioning of Hoist way maintenance Lighting and Power for Lift-1
a including supply & intallation as Mentioned, 1 Job
1. 6/16Amp Switch Socket: 1 Nos
2. 13Amp SPN Isolator: 1 Nos
3. 40Amp TPN Isolator: 1 Nos
4. LED Hoistway Light: 4 Nos, with 2 Way Switch

b Supply, Installation, Testing & Commissioning of Cables


1 4C x 6 sqmm CU YRY CABLE 25 Mtr.
2 3C x 2.5 sqmm CU YRY CABLE 50 Mtr.

c Supply, Installation, Testing & Commissioning of Cables termination


1 4C x 6 sqmm CU YRY CABLE 2 Nos.
2 3C x 2.5 sqmm CU YRY CABLE 2 Nos.

XIV Lightning Arrestor


Supply, Installation of Lightening Arrester, 75 mm dia sphere, 6 mm. thick, tined copper with 5 nos. of
spikes of 25 mm dia 600 mm long tinned copper rod, with 300 x 300 and 6 mm thick copper plate duly
a pressed to 25 mm dia copper rod, anchoring the same over a 50 mm dia ‘B’ class GI pipe on top of a 5 Nos.
supporting MS plate of 9000sqmm with suitable nut bolts as per detailed drawing and instruction of engineer
in charge.

Supply and Installation of test link box made out of 2mm CRCA sheet , galvanized and having a GI Test
b Link of size 150 mm long , 25 x 6 mm link Cu strip mounted on suitable nut bolts , complete with hinge 5 Nos.
type covers GI clamps etc.
Supplying and laying earthing conductors of Copper / GI strips including necessary accessories, clamping to
walls, cables etc.as required and interconnection between lengths as per specifications and as per good
c installation practice. Prices should include all supports, accessories and hardware necessary for proper
installation.
1 25 x 3 mm Cu Bare Tape for Roof & Down Conductor 500 Rm