This document provides specifications for a magnetic flow transmitter and element that measures the flow of tertiary concentrate in a 4" pipe. The transmitter operates on a flow range of 0-75 cubic meters per hour and outputs a 4-20 mA signal. It is powered by 120VAC and has an accuracy of ±0.25% of reading.
This document provides specifications for a magnetic flow transmitter and element that measures the flow of tertiary concentrate in a 4" pipe. The transmitter operates on a flow range of 0-75 cubic meters per hour and outputs a 4-20 mA signal. It is powered by 120VAC and has an accuracy of ±0.25% of reading.
This document provides specifications for a magnetic flow transmitter and element that measures the flow of tertiary concentrate in a 4" pipe. The transmitter operates on a flow range of 0-75 cubic meters per hour and outputs a 4-20 mA signal. It is powered by 120VAC and has an accuracy of ±0.25% of reading.
3 Area Classification UNCLASSIFIED GENERAL 4 P&ID No. CWP No. TRP-FL-405-1-PE-236-0011 5 Ambient Temperature Max. Min. 39 °C -10 °C 6 Line No. Line Size Line Schedule 4"-405-CT-152-CSF-NI 4 in STD WT 7 Pipe Material Carbon Steel 8 Fluid Tertiary Concentrate 9 Velocity Max. Norm. Min. 2.05 m/s 1.5 m/s m/s 10 Flow Max. Norm. Min. 60 Am³/h 43 Am³/h Am³/h
PROCESS 12 Pressure Max. Norm. Min. 250 kPa-g kPa-g kPa-g
CONDITIONS 13 Fluid Conductivity 4100 microS/cm (process water) 14 Vacuum Possibility No 15 Line Design Press Line Design Temp 1034 kPa 50 °C 16 % Solids Particle Size S.G. 6.45 % N/A 1 17 18 19 Tag Number 405CT152-FE-006 20 Mag Tube Type Tube Material DC pulsed SST 21 Connection Size Connection Type 3 in. RF FLANGED FLOW 22 Connection Rating Connection Materials CLASS 150 ANSI Carbon Steel ELEMENT 23 Liner Material Casing Material PTFE COATED DIE-CAST ALUMINIUM 24 Electrode Type Electrode Material STANDARD SST 25 Element Range Power Supply 0.01 - 12 m/s FROM TRANSMITTER 26 Grounding: Type Material Via Pipe n/a 27 Enclosure Rating Certification NEMA4X FM 28 Pipe ID Tube ID 4.026 in in 29 Tag Number Function 405CT152-FIT-006 INDICATING TRANSMITTER 30 Remote / Integral Mounting REMOTE 2" PIPE MOUNT 31 Enclosure Rating Certification NEMA 4X FM TRANSMITTER 32 Signal Cable Length Electrical Connection 10 M 2 x 1/2" NPT 33 Power Supply Power Consumption 120 VAC 10 Watts 34 Calibration Range Output 0 75 m³/h 4-20 mA HART 35 Alarm Contact: No. Form N/A N/A 36 Alarm Contact: Rating Action N/A N/A 37 Weight (FE, FIT) (kg) Face to Face (mm) 15.5, 4.5 200 mm 38 Measured Error (% of Rate) ± 0.25% of reading 39 FIELDBUS 40 Power Consumption FF Bus FUNCTION 41 Resource Blk Transducer Blk 42 Analog I/P Blk PID Blk 43 Totalizer Blk 44 Manufacturer ROSEMOUNT 45 Model (FE / FIT) 8705TSA030C1W0Q4Q8DT / 8712ESR1A1M4DTQ4 PURCHASE 46 Purchase Order Number --- 47 Requisition No. Item Number --- 48 Serial Number Notes: 1. Vendor to supply 10 m of FE to FIT cable.
INSTRUMENT DATA SHEET
MAGNETIC FLOW TRANSMITTER DOC No A9PPS543-405-1-270-DS-006-1 D 10APR18 Issued for Quotation DM VT BA CLI No TRP-FL-405-1-JJ-251-0006-1 C 29MAR18 Issued for Review/Approval DM VT BA TAG No 405CT152-FIT-006 REV REV DATE DESCRIPTION BY CHK APP PRO SHEET 1 OF 1 D