Model ESFR-17
Early Suppression Fast Response Pendent Sprinklers
16.8 K-factor
of 14.0. In particular, the Model ESFR-
General 17 has been designed to operate at
substantially lower end head pres-
Description sures, as compared to ESFR sprin-
klers having a nominal K-Factor of
The Model ESFR-17 Pendent Sprin- 14.0. This feature offers flexibility when
klers (Ref. Figure 1) are “Early Sup- sizing the system piping, as well as
pression Fast Response Sprinklers” possibly reducing or eliminating the
having a nominal K-factor of 16.8. They need for a system fire pump.
are suppression mode sprinklers that
are especially advantageous as a WARNINGS
means of eliminating in-rack sprin- The Model ESFR-17 Sprinklers de-
klers, when protecting rack storage. scribed herein must be installed and
The Model ESFR-17 is primarily de- maintained in compliance with this
signed for use in ceiling only sprinkler document, as well as with the applica-
systems (i.e. no in-rack sprinklers) for ble standards of the National Fire Pro-
the protection of storage heights of tection Association, in addition to the
most encapsulated or non-encapsu- standards of any other authorities hav-
lated common materials including car- ing jurisdiction (e.g., FM Global). Fail-
toned unexpanded plastics of up to 35 ure to do so may impair the perform-
ft. (10,7 m) with ceiling heights to 40 ft. ance of these devices.
(12,2 m), as well as cartoned ex- The owner is responsible for maintain-
panded plastics up to 25 ft. (7,6 m) with ing their fire protection system and de-
ceiling heights to 30 ft.(9,1 m). In addi- vices in proper operating condition.
tion, the protection of some storage The installing contractor or sprinkler
arrangements of rubber tires, roll pa- manufacturer should be contacted
per, and aerosols can be considered. with any questions.
In some cases, the Model ESFR-17
can be used to protect storage heights
up to 40 ft. (12,2 m) with ceiling heights
to 45 ft. (13,7 m) in combination with Sprinkler
one level of in-rack sprinklers.
The ESFR-17 provides the system de- Identification
signer with hydraulic options not pres-
ently available to traditional ESFR Numbers
sprinklers having a nominal K-Factor SIN TY7226 - (Pendent K=16.8)
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
3/4" NPT
7
1-13/16"
8 1/2" (46,0 mm)
1-Frame (12,7 mm)
2-Deflector 9 NOMINAL
3-Compression Screw MAKE-IN
4-Hook
5-Strut 6
6-Link Assembly 3-9/16" THERMAL
7-Button (90,5 mm) SENSING
8-Sealing Assembly 5 ELEMENT
9-Ejection Spring
WRENCH
4 FLATS
2 TEMPERATURE
RATING
1-7/8" (47,6 mm)
Data NOTE
GENERAL GUIDELINES
The National Fire Protection Associa- System Type: Wet pipe system.
Approvals tion (NFPA) and FM Global (FM) pro-
UL and C-UL Listed. FM and VdS Ap- Roof Construction: Unobstructed or
vide installation standards that must
proved. LPCB Approved (094b/01 & obstructed construction. For example:
be used to properly design an auto-
007l/01). NYC under MEA 356-01-E. smooth ceiling, bar joists, beam and
matic sprinkler system utilizing Early
girder, etc.
Maximum Working Pressure Suppression Fast Response (ESFR)
175 psi (12,1 bar) Sprinklers. The guidelines provided by
NOTE
NFPA and FM may differ; conse-
Pipe Thread Connection Where the depths of the solid struc-
quently, the appropriate standard must
3/4 inch NPT or ISO 7-R3/4 tural members (beams, stem, etc.) ex-
be used for a given installation.
ceed 12 inches (302 mm), ESFR
Discharge Coefficient The following data sheets describe the Sprinklers shall be installed in each
K = 16.8 GPM/psi1/2 ESFR Sprinklers offered by Tyco Fire channel formed by the structural mem-
(241,9 LPM/bar1/2) Products: bers.
Temperature Ratings TFP312 — Model ESFR-25 (TY9226), Ceiling Slope: Maximum 2 inch rise
165°F/74°C or 214°F/101°C K=25.2 Pendent Sprinkler for 12 inch run (16.7%).
Finish TFP315 — Model ESFR-17 (TY7226), Building Heights, Storage Heights,
Natural Brass K=16.8 Pendent Sprinkler and Commodity: Refer to Table A.
Physical Characteristics TFP316 — Model ESFR-17 (TY7126), Maximum Coverage Area:
Frame . . . . . . . . . . . . . . Brass K=16.8 Upright Sprinkler 100 ft2 (9,3 m2). In some cases, the
Deflector . . . . . . . . . . . Bronze installation standards permit a greater
Compression Screw . . . . . . . . . TFP318 — Model ESFR-1 (TY6226),
coverage area.
. . . . . . . . . . . . Stainless Steel K=14.0 Pendent Sprinkler
Hook . . . . . . . . . . . . . . Monel Minimum Coverage Area:
The following general guidelines pro-
Strut . . . . . . . . . . . . . . Monel 80 ft2 (7,4 m2) per NFPA 13, and
vided for ESFR Sprinklers offered by
Link Assembly . . . . Solder, Nickel 64 ft2 (5,8 m2) per FM 2-2
Tyco Fire Products may be used for a
Button . . . . . . . . . . . . . . Brass quick reference to help select the ap- Maximum Spacing: 12 feet (3,7 m) for
Sealing Assembly . . . . . . . . . . propriate Tyco Fire Products’ ESFR building heights up to 30 feet (9,1 m),
. . . . . Beryllium Nickel w/Teflon* Sprinkler: and 10 feet (3,1 m) for building heights
Ejection Spring . . . . . . . . Inconel greater than 30 feet (9,1 m).
*Registered trademark of Dupont. Minimum Spacing:
NOTE 8 feet (2,4 m).
Patents In all cases, the appropriate NFPA or
Minimum Clearance To Commodity:
U.S.A. Patent Numbers: FM installation standard must be refer-
36 inches (914 mm).
4,580,729 5,829,532 enced to assure applicability and to
6,059,044 6,336,509 obtain complete installation guide-
6,502,643 lines, since the following general
Patents pending.
TFP315 Page 3 of 8
TABLE A
BUILDING HEIGHTS, STORAGE HEIGHTS, AND COMMODITY
(See Design Criteria Section)
Open frame (i.e. no solid shelves) single,
double, multiple-row, or portable rack See Table A-1
storage of Class I - IV and Group A or B (Refer to NFPA 13 or FM 8-9 and 2-2
plastics for details)
NFPA 13 — Deflector To Ceiling FM 2-2 — Deflector To Ceiling FM 2-2 — Thermal Sensing Element
Distance: Distance: To Ceiling Distance:
ESFR-17 (K=16.8) Pendent: ESFR-17 (K=16.8) Pendent: ESFR-17 (K=16.8) Pendent:
6 to 14 inches (152 to 356 mm). 5 to 14 inches (121 to 356 mm). 4 to 13 inches (102 to 330 mm).
ESFR-1 (K=14.0) Pendent: ESFR-1 (K=14.0) Pendent: ESFR-1 (K=14.0) Pendent:
6 to 14 inches (152 to 356 mm). 5 to 14 inches (121 to 356 mm). 4 to 13 inches (102 to 330 mm).
ESFR-25 (K=25.2) Pendent: ESFR-17 (K=16.8) Upright: ESFR-17 (K=16.8) Upright:
6 to 18 inches (152 to 457 mm). 5 to 14 inches (121 to 356 mm). 4 to 13 inches (102 to 330 mm).
ESFR-25 (K=25.2) Pendent:
4 to 18 inches (102 to 457 mm).
Page 4 of 8 TFP315
TABLE A-1
RACK STORAGE
(See Design Criteria Section)
Commodity Maximum Maximum Minimum Flow Pressure, PSI (BAR)
Building Storage
Height, Height, Comparison to Other TFP ESFR Sprinklers
Feet Feet ESFR-1 ESFR-17 ESFR-25
ESFR-17
(m) (m) PENDENT UPRIGHT PENDENT
PENDENT
K = 16.8 K = 14.0 K = 16.8 K = 25.2
See Data Sheet See Data Sheet See Data Sheet
TFP318 TFP316 TFP312
NFPA FM NFPA FM NFPA FM NFPA FM
Class I, 45 40 63 * 63 * 90 * 90 * 40 50
Class II, (13,7) (12,2) (4,3) (4,3) (6,2) (6,2) (2,8) (3,4)
Class III, and 40 35 52 52 75 75 25 40
Class IV (12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (1,7) (2,8)
Encapsulated or 35 30 52 52 75 75 52 20 30
Unencapsulated (10,7) (9,1) (3,6) (3,6) (5,2) (5,2) (3,6) (1,4) (2,1)
-and- 32 25 42 42 60 60 42 20 30
Cartoned (9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (2,9) (1,4) (2,1)
Unexpanded
Plastics 30 25 35 35 50 50 35 15 20
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (2,4) (1,0) (1,4)
Uncartoned 45 40 63 * 63 * 90 * 90 *
(Exposed) (13,7) (12,2) (4,3) (4,3) (6,2) (6,2)
Unexpanded 40 35 52 52 75 75 50
Plastics (12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (3,4)
32 25 42 42 60 60 50
(9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (3,4)
30 25 35 35 50 50 50
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (3,4)
Cartoned 32 25 42 42 60 60 42
Expanded Plastics (9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (2,9)
30 25 35 35 50 50 35
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (2,4)
Uncartoned 30 25 100
(Exposed) (9,1) (7,6) (6,8)
Expanded Plastics 25 20 75
(7,6) (6,1) (5,2)
* One level of in-rack sprinklers is required.
TFP315 Page 5 of 8
TABLE A-2
PALLETIZED AND SOLID PILED STORAGE
(See Design Criteria Section)
Commodity Maximum Maximum Minimum Flow Pressure, PSI (BAR)
Building Storage
Height, Height, Comparison to Other TFP ESFR Sprinklers
Feet Feet ESFR-1 ESFR-17 ESFR-25
ESFR-17
(m) (m) PENDENT UPRIGHT PENDENT
PENDENT
K = 16.8 K = 14.0 K = 16.8 K = 25.2
See Data Sheet See Data Sheet See Data Sheet
TFP318 TFP316 TFP312
NFPA FM NFPA FM NFPA FM NFPA FM
Class I, 45 40 40 50
Class II, (13,7) (12,2) (2,8) (3,4)
Class III, and 45 35 90 40 50
Class IV (13,7) (10,7) (6,2) (2,8) (3,4)
Encapsulated or 40 35 52 52 75 75 25 40
Unencapsulated (12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (1,7) (2,8)
-and- 35 30 52 52 75 75 52 20 30
(10,7) (9,1) (3,6) (3,6) (5,2) (5,2) (3,6) (1,4) (2,1)
Cartoned 32 25 42 42 60 60 42 20 30
Unexpanded (9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (2,9) (1,4) (2,1)
Plastics 30 25 35 35 50 50 35 15 20
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (2,4) (1,0) (1,4)
Uncartoned 45 35 90
(Exposed) (13,7) (10,7) (6,2)
Unexpanded 40 35 52 52 75 75 50
Plastics (12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (3,4)
32 25 42 42 60 60 50
(9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (3,4)
30 25 35 35 50 50 50
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (3,4)
Cartoned 32 25 42 42 60 60 42
Expanded Plastics (9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (2,9)
30 25 35 35 50 50 35
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (2,4)
Uncartoned 40 25 60
(Exposed) (12,2) (7,6) (4,1)
Expanded Plastics 30 25 100 60
(9,1) (7,6) (6,8) (4,1)
25 20 75 60
(7,6) (6,1) (5,2) (4,1)
Page 6 of 8 TFP315
TABLE A-3
IDLE PALLET STORAGE
(See Design Criteria Section)
Type and Maximum Maximum Minimum Flow Pressure, PSI (BAR)
Arrangement Building Storage
Height, Height, Comparison to Other TFP ESFR Sprinklers
Feet Feet ESFR-1 ESFR-17 ESFR-25
ESFR-17
(m) (m) PENDENT UPRIGHT PENDENT
PENDENT
K = 16.8 K = 14.0 K = 16.8 K = 25.2
See Data Sheet See Data Sheet See Data Sheet
TFP318 TFP316 TFP312
NFPA FM NFPA FM NFPA FM NFPA FM
Wood or Plastic 40 35 52 52 75 75 50
In-rack (12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (3,4)
32 25 42 42 60 60 50
-and- (9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (3,4)
Plastic on Floor 30 25 35 35 50 50 50
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (3,4)
Wood on Floor 40 35 52 52 75 75 50
(12,2) (10,7) (3,6) (3,6) (5,2) (5,2) (3,4)
35 20 52 52 75 75 52 50
(10,7) (6,1) (3,6) (3,6) (5,2) (5,2) (3,6) (3,4)
32 25 42 42 60 60 50
(9,7) (7,6) (2,9) (2,9) (4,1) (4,1) (3,4)
32 20 42 42 60 60 42 50
(9,7) (6,1) (2,9) (2,9) (4,1) (4,1) (2,9) (3,4)
30 25 35 35 50 50 50
(9,1) (7,6) (2,4) (2,4) (3,4) (3,4) (3,4)
30 20 35 35 50 50 35 50
(9,1) (6,1) (2,4) (2,4) (3,4) (3,4) (2,4) (3,4)
TFP315 Page 7 of 8
TABLE A-4
RUBBER TIRE STORAGE
(See Design Criteria Section)
Piling Method Maximum Maximum Minimum Flow Pressure, PSI (BAR)
Building Storage
Height, Height, Comparison to Other TFP ESFR Sprinklers
Feet Feet ESFR-1 ESFR-17 ESFR-25
ESFR-17
(m) (m) PENDENT UPRIGHT PENDENT
PENDENT
K = 16.8 K = 14.0 K = 16.8 K = 25.2
See Data Sheet See Data Sheet See Data Sheet
TFP318 TFP316 TFP312
NFPA * FM NFPA FM NFPA FM NFPA FM
On-Side or On-Tread
in Palletized Portable
30 25 35 35 50 50 35 15 20
Racks, Open Portable
(9,1) (7,6) (2,4) (2,4) (3,5) (3,5) (2,4) (1,0) (1,4)
Racks, or Fixed Racks
without Solid Shelves
On-Side in Palletized
Portable Racks, Open
35 25 52 75 25
Portable Racks, or
(10,7) (7,6) (3,6) (5,2) (1,7)
Fixed Racks without
Solid Shelves
Laced Tires in Open 30 25 52 75
Portable Steel Racks (9,1) (7,6) (3,6) (5,2)
On-Side in Palletized 40 25 52 75
Portable Racks (12,2) (7,6) (3,6) (5,2)
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446