4.1) Design PVT Heat Pump System For Residential Building
4.1) Design PVT Heat Pump System For Residential Building
4.1) Design PVT Heat Pump System For Residential Building
Site data:
Climate data
Climate data record: Amman (Shafa Badran)
Annual sum of global irradiation: 2,077,720 Wh/m²
Longitude: -35.98 ° E
Latitude: 31.98 ° N
Domestic Hot Water
Average daily usage: 160 l
Target temperature: 54 °C
Cold water temperature in February: 15.5 °C
Cold water temperature in August: 20.5 °C
One-way length of piping system: 10 m
Temperature spread supply/return: 5.0 K
Specific losses: 0.30 W/(m*K).
Space Heating
Heated useable area: 172 m²
Indoor temperature: 23.0 °C
Heating limit temperature: 10 °C
Feed/Return of low temperature loop: 35.0/28.0 °C.
Heat pump system with combination tank and Pvt panel support (water to water).
Figure 2:Heat pump system with combination tank and Pvt panel support (water to water).
System components:
Heat pump
Manufacturer: Standard
Construction type: Water/water
Nominal heating power: 19.0 kW
Electrical nominal output: 3.1 kW
Power of heating element: 9.0 kW
Mode of operation: mono energetic / parallel
Heating element out of service above: -5.0 °C
Groundwater
Minimum groundwater temperature: 8.0 °C on 03/01
Maximum groundwater temperature: 12.0 °C on 09/01
Power input of the groundwater pump for continuous operation after start-up: 150 W
Groundwater pump volume flow: 4,480 l/h
Combination tank
Manufacturer: Standard
Model: Standard Speicher
Volume: 750 L
Tank losses: 2.40 kWh/d
Solar Loop
Manufacturer: GASOKOL GmbH
Construction type: Flat-plate collector
Number: 12
Gross surface area (total): 20.16 m 2
Inclination (tilt angle): 30 °
Orientation (north=0°, east=90°): 180 °
Azimuth (south=0°, west=90°): 0 °
Losses / Year
Tank losses: 797 kWh
Fraction of solar tank losses: 317 kWh
Solar loop piping indoors: 545 kWh
Solar loop piping outdoors: 102 kWh
Primary energy savings and CO2 prevention
Primary energy savings: 19,404 kWh
CO2 emissions avoided: 4,802 kg
Heat pump system with combination tank and Pvt panel support (Brine to water) ground.
Figure 4:Heat pump system with combination tank and Pvt panel support (Air to water) ground.
System components:
Heat pump
Manufacturer: Standard
Construction type: Brine/Water
Nominal heating power: 18.0 kW
Electrical nominal output: 4.2 kW
Power of heating element: 9.0 kW
Mode of operation: mono energetic / parallel
Heating element out of service above: -5.0 °C.
Geothermal collector
Area: 200.0 m²
Laying depth: 1.5 m
Groundwater depth: 10 m
Nominal output of brine pump: 264 W
Brine pump volume flow: 4,230 L/h
Spec. heat capacity: 1.5 MJ/(m³*K)
Conductivity: 0.4 W/(m*K)
Combination tank
Manufacturer: Standard
Model: Standard Speicher
Volume: 750 L
Tank losses: 2.40 kWh/d
Solar Loop
Manufacturer: GASOKOL GmbH
Construction type: Flat-plate collector
Number: 12
Gross surface area (total): 20.16 m 2
Inclination (tilt angle): 30 °
Orientation (north=0°, east=90°): 180 °
Azimuth (south=0°, west=90°): 0 °
Losses / Year
Tank losses: 789 kWh
Fraction of solar tank losses: 315 kWh
Solar loop piping indoors: 540 kWh
Solar loop piping outdoors: 101 kWh
Consumption:
Total consumption: 7200 KWh.
Number of panels: 20
PV Surface: 22.3 m^2
Thermal System:
Thermal demand: 2354KWh
Combination tank
Manufacturer: Standard
Model: Standard Speicher
Volume:160 L
Tank losses: 2.40 kWh/d
Heat pump:
Type: 10KW
COP: 3.8
Results of the annual simulation
PV System:
PV Generator Output. 4.50 kWp
Appliances:
Appliances. 7200 kWh/Year
Standby Consumption (Inverter). 63 kWh/Year
Heat pump 610 kWh/Year
total Consumption. 7873 kWh/Year
covered by PV power. 2967 kWh/Year
covered by grid. 4907 kWh/Year
Solar Fraction. 37.7%
Thermal system:
Heating demand. 2354 kWh/Year
Thermal losses. 418 kWh/Year
Total heat demand. 2772 kWh/Year
covered by boiler. 17 kWh/Year
covered by heat pump. 2755 kWh/Year
Electrical energy consumption of the heat pump. 610 kWh/Year
of which is solar. 65 kWh/Year
Solar Fraction (Thermal system): 10.5%
co2 Emissions avoided: 377 kg/Year
Use of PV Energy: