Professional Documents
Culture Documents
Transformer Vector Group
Transformer Vector Group
Transformer Vector Group
Winding Connections: Now, what will you call the connection shown in Fig.
(1)? DELTA? Then what will you call the connection shown in Fig. (2)?
Same DELTA? Is there not a difference between Fig. (1) & Fig. (2)? There, in
fact, is a difference in end connections of the windings and hence, in the
direction of current flow in each winding. In Fig. (1), for example, in ‘U’
winding, current would flow from A1 to A2, whereas in Fig. (2), it will be from
A2 to A1. Isn’t it? Then, how can we give the same name to both
connections? So, one can be given the name “NORMAL DELTA” and the
other, as the current direction is reverse when compared to the first, can be
given the name, “REVERSE DELTA”.
Now, which one is normal delta and which one is reverse delta? One would
believe that Fig. (1) is normal delta and Fig. (2) is reverse delta.
R C1 R
C2 A1 A2
W U W U
A2 A1
C1 Y C2 Y
B2 V B1 B1 V B2
B B
But, surprisingly, the connection shown in Fig. (2) is called Normal Delta
and that in Fig. (1) is called Reverse Delta. Similar nomenclature is given
for Star Connection too. Fig. (3) is Reverse Star and Fig. (4) is Normal Star.
R R
A1 A2
U U
C2 A2 C1 A1
W B2
V W B1
V
C1 B1 C2 B2
Y Y
B B
Table (1)
******
Let us analyse one type of connection for example, say, Normal Star/
Normal Star. For this vector group representation, the winding connections
would be as shown in Fig. (5):
A1 B1 C1 a1 b1 c1
U V W u v w
A2 B2 C2 a2 b2 c2
1U 1V 1W 1N 2u 2v 2w 2n
s
Fig. (5)
VU
V1U-1V
vu
vw v2u-2v
VW vv VV
Fig. (6)
As can be seen from the vector diagram, when one applies a voltage
across the primary terminals 1U-1V, he gets a voltage across the
secondary terminals 2u-2v and the phase displacement is 0o. That is, there
is no phase displacement between the primary voltage and the secondary
voltage. This is called as the 0o phase displacement group.
Going by the above and assuming that the above transformer is a step-
down transformer, the clock hour representation would be that of 12 O’
Clock or 0 O’ Clock. Isn’t it? So, the above connection can simply be
represented as ‘Yy0’. The first ‘Y’ for the HV winding connection, which is
Star and the small ‘y’ for the LV winding connection, which, too, is star. The
phase displacement, which, as per the above vector diagram is 0o, is
represented by the following ‘0’, which is the relevant clock hour number.
Also, it is to be noted that if the neutrals are brought out in star windings, it
has to be denoted by a ‘N’ subscripting the ‘Y’, in case of HV winding
neutral and by a ‘n’ subscripting the ‘y’ in case of LV winding. In the above
vector group, if both the HV & the LV neutrals are brought out, then the
vector group notation would be YNyn0.
Now, we can re-construct Table (1) into Vector Group Notations as below
(Table-2):
Table (2)
******
Now, we will do similar analysis for another vector group, which is the
most popular in the industry, (i.e.) Dyn11. Going by the above definitions,
Vector Group Dyn11 signifies that the HV winding is connected is Normal
Delta and the LV winding is connected in Normal Star, with the LV neutral
brought out, and the LV Voltage is leading the HV Voltage by 30o.
A1 B1 C1 a1 b1 c1
U V W u v w
A2 B2 C2 a2 b2 c2
1U 1V 1W 2u 2v 2w 2n
s
Fig. (7)
In the above connection, if supply voltage is given across terminals 1U-1V,
then the ‘U’ winding will have the line voltage impressed on it. When the
primary ‘U’ winding is impressed upon a voltage, it will induce an EMF, in
proportion to the turns ratio, in its secondary winding ‘u’. This secondary
induced voltage will be in phase with the primary applied voltage. Now, if
we build a vector diagram for the above connection, at this stage, it will be
as per Fig. (8):
VU = V1U-1V
vu = v2u-2n
vw = v2w-2n
Fig. (8)
VU = V1U-1V
30o
v2u2v
vu = v2u-2n
v2n2v
vv = v2v-2n
Fig. (9)
As can be seen from the above re-drawn vector diagram for vector group
Dyn11, the secondary (LV) voltage vector 2u-2v, leads the primary (HV)
voltage vector by 30o.
Similar analysis can be made for all the other vector groups too.
Note: Please note that it is not possible to have Reverse ….. / Normal ……
Whatever may be the connection, the HV winding is taken as reference or
normal and the connection of the LV winding is verified if it is normal or
reverse with respect to the HV winding.
***********
References: