w Fully integrated and tested switch EnergyLine’s M Series Switch Operators charging voltages. The Switch Operator
operator are fully integrated, microprocessor-based tests the battery at regular intervals and
controls that let you automate almost any will flag low or bad battery conditions. If
w Works with most distribution- distribution-class switch. By combining the battery voltage drops below a
class switches and testing the electromechanical certain value, the Switch Operator is
w Automates retrofitted or new components, RTU, control, and communi- automatically disabled to prevent
installations cations as a single package, we also improper operation or deep discharge of
added intelligence, increased reliability, the battery.
w Provides torsional or and reduced costs.
reciprocating operation
And the M Series Switch Operator has REMOTE OPERATION
w Protects switches from partial unique intelligence to go with its power. EnergyLine’s completely integrated
open or close operations By monitoring the switching cycle, it can design lets you monitor and control the
automatically take corrective action in the Switch Operator from a SCADA master
w Uses microprocessor control for event of stuck, frozen, or welded con-
all functions station. EnergyLine offers factory- or
tacts. This protects your equipment from field-installed communications devices
w Field-proven single power supply/ partial operations. for the system of your choice, as well as
battery system With the fault sensing option, the Switch an array of communications protocols.
Operator can also isolate faults without
w Fast, easy, and precise setup the need for expensive line post current SOFTWARE CONTROL
w Full range of safety features sensors. Sectionalizing is based on ARCHITECTURE
voltage loss (with or without prior fault).
w Emergency override commands All of EnergyLine’s utility products run
POWER SUPPLY/BATTERY SYSTEM under the supervision of a state-of-the-
w Loss of voltage operation art operating system for increased
EnergyLine uses a single power source reliability and maintainability. The menu-
w Fault sensing option for the entire package, thereby reducing driven Setup software lets you select
w Dependable, cost-effective failure rates inherent in non-integrated setpoint values and reduce the setup
systems with multiple power supplies and time. A standard DB9 serial data port on
solution for remote switching
batteries. This highly efficient, field- the faceplate (or optional optical port)
proven switching power supply delivers provides easy access to the Switch
FLEXIBLE both 12 and 24 VDC to the entire system, Operator using a PC. The Switch
INTELLIGENT as well as a trickle charge to the batteries
AUTOMATION
Operator’s integrated package also
for maximum battery life. It also provides includes data logging and troubleshoot-
accurate, temperature-compensated ing information.
EnergyLine Systems, Inc.
1135 Atlantic Avenue
Alameda, CA 94501 A U T O M A T I O N B Y E N E R G Y L I N E
AUTOMATION BY ENERGYLINE

Mild carbon steel enclosure


(stainless steel optional)

Three-point latching

Faceplate with CLOSE/OPEN


and REMOTE/LOCAL switches

Padlockable handle

Safety interlock
operating handle
(storage position shown)

Door pocket for User’s Manual

Door retainer

Lockout point

Decoupler

ALIGN switch
(for setting travel limits)

Power Supply/Battery Charger


and I/O board
DC circuit breaker

AC fuse

Universal Communications
Mounting Plate

Batteries Grounded Motor Gearbox


AC outlet

© 1998 by EnergyLine Systems, Inc. All rights reserved. Printed in the USA.
E N E R G Y L I N E
5"
1.5"

5" 3.795"

ENERGYLINE ENERGYLINE
9.5"

42" 30.5"
24" 12" 24"

12.83" 12.545"
12.83" 24" 20.827" 24"

Torsional Switch Operator Reciprocating Switch Operator


(side and front views) (side and front views)

HOW TO ORDER For more information or other options, contact EnergyLine.

• ‚ ƒ „ … † ‡ ˆ
M T S - D RK 0 - 0 FH SA
Operation Operating Rod Shroud
Enclosure Radio Faulted Circuit Indicator
Protocol Antenna
Remote Communications Communications Installation
Hardware

• Operation … Communications Installation


T = Torsional 0 = No communications installation
R = Reciprocating E = Installation; equipment provided by EnergyLine*
‚ Enclosure C = Installation; equipment provided by customer
*Plus price of the equipment. Prices will be indicated on EnergyLine quotations.
M = Painted steel
S = Stainless steel † Antenna
ƒ Protocol 0 = None
D = DNP 3.0 E = Antenna ready
P = PG&E SCADA (Cooper 2179) ‡ Fault Detection
T = Landis & Gyr Telegyr 8979 00 = None
Z = Other (contact EnergyLine for options) Fx = Radio faulted circuit indicator
„ Remote Communications Hardware (contact EnergyLine for options)
00 = None ˆ Operating Rod Shroud
Rx = Radio (contact EnergyLine for options) 00 = None
Mx = Modem (contact EnergyLine for options) Sx = Shrouded (contact EnergyLine for options)
Fx = Fiber (contact EnergyLine for options)

EnergyLine and the EnergyLine logo are registered trademarks of EnergyLine Systems, Inc. All other trademarks are the property of their respective holders.
M Series

S P E C I F I C A T I O N S

Torsional Switch Operator Performance


w 90° rotation (in 0.5 sec)
w Control rod travel: 0 to 180°
w Accuracy: ±2°
Reciprocating Switch Operator Performance
w 14" vertical movement (in 0.5 sec)
w Control rod travel: 0 to 15"
w Accuracy: ±0.2"
Travel Limits
w One-step travel limits setup with microprocessor control
Motor
w 3.6 HP DC motor
Operating Environmental Characteristics
w Temperature: -40°C to +70°C
w Microprocessor-controlled heater (to minimize condensation problems)
Control Power
w 120 VAC
w Grounded AC convenience outlet
Enclosure
w 24" x 24" x 13" (plus mounting bracket)
w Mild carbon steel, with RAL 7035 light grey paint; optional stainless steel enclosure
w Bracket mount, with lifting hole
w Weight (nominal): 175 lbs. (plus battery)
Power Supply/Battery Charger
w Battery: 33 amp-hour, gel cell
w Charger: 50 W – regulated 24 VDC
w Expected battery carryover 1: 16 hours
w Supports communications equipment
w Automatic, remote, and local battery testing
Communications Ports
w Two RS232 DB9 connectors, 300 to 9600 baud
w Optional optical port
Communications Hardware2
w CellNet®
w Metricom®
w MDS
w Modems
w Fiber optic transceivers
Protocols2
w DNP 3.0
w PG&E SCADA (Cooper 2179)
w Landis & Gyr Telegyr 8979

1
Battery carryover varies with battery type, age, ambient temperature, communications option installed, and number of
operations.
2
Consult EnergyLine for current list of communications hardware and protocols supported.