Table of Contents
1. GENERAL OPERATING INSTRUCTIONS FOR PARAMETERIZATION .................................................. 3
2 ҏ EFAFLEX GmbH
EFACON
Door-Controller
1. General operating instructions for parameterization
Operating
Function / remarks Reaction LC display
element
Press
4. × STOP+OPEN
keys at same
Software-controlled switching
into parameter mode
„Service“ is shown in
the top line of the display
P: Service
B Parameter selection
P: Service
1. STOP short Value of the parameter
The cursor jumps to the right onto
the parameter value xxx= 10
If the current parameter value is P: Service
Press OPEN key to increase
× OPEN
parameter value
increased, a little star flashes
behind the value. xxx= 11
2.
If the current parameter value is P: Service
Press CLOSE key to reduce the
Ø CLOSE
parameter value
decreased, a little star flashes
behind the value. xxx= 09
Abortion, P: Service
or STOP short Reject selected parameter value the original parameter value is
shown again xxx= 10
P: Service
4. STOP short End of parameter setting
The cursor jumps to the left onto
the parameter number xxx 10
EFAFLEX GmbH 3
Operating
Function / remarks Reaction LC display
element
Press STOP key Parameter mode is left, automatic Automatic operation, procedure
1. Sync-Start
3s mode active depending on the door type set.
S200
ON OFF
S200
X26
1
83
82
80 81
X25
1 2 1 2 3 4 5
60 61 70 71 72 73 74
X 23 X24
1. After switching on, change to the synchronization mode by briefly pressing the STOP key
2. Close door using the CLOSE key and save position by pressing the STOP key (for approx 3 seconds).
3. Press foil keypad OPEN key door OPEN position is automatically moved to in slow motion and stored.
By the subsequent first travels of the door in automatic operation, the acceleration and braking ramps are
automatically set.
The teaching of end positions can be again requested. Set parameter P.210 = New teaching of all end positions
at value „5“.
4 ҏ EFAFLEX GmbH
EFACON
Door-Controller
2 Parameter overview
P.002 [Cycles] Total number of cycles Indicates the total number of counted door cycles
This counter can be reset via P.998 = 2 (password-protected)
P.005 [Cycles] Maintenance instruction Indicates the number of cycles remaining until maintenance is due
) Setting -1 means that the counter has not yet been activated.
P.010 [s] Keep open time 1 Indicates the time value, after which the door is automatically
0 ... 200 closed (is active after complete door opening)
P.011 [s] Keep open time 2 Indicates the time value, after which the door is automatically
0 ... 200 closed (is active on travel to intermediate hold)
P.015 [s] Minimum keep-open Indicates the minimum time value, after which the door is
0 ... 200 time automatically closed
P.016 [s] Minimum display time Stipulates the direction release for the air locks
0 ... 60 for green signal
P.017 [s] Saving of opening 0: Saving of opening pulses is switched off
0 ... 60 pulses > 0: Saving period for opening pulses (is only active when the door
is closed)
P.018 [min] Compulsory opening 0: Compulsory opening time is switched off
0 ... 255 time > 0: Door opens after the time set and closes after the pre-set keep
open time 1 (P.010)
P.019 [s] Saving of closing 0: Saving of closing commands is switched off.
0 ... 60 commands > 0: Closing command is saved for this time with active counter-
locking
P.020 [10ms] Pre-warming time before The opening of the door is delayed after the receipt of the OPEN
0 ... 1000 opening command by the time set in this parameter.
P.025 [s] Pre-warming time before The closing of the door is delayed after the receipt of the CLOSE
0 ... 20 closing command or after expiry of the keep open time (compulsory
closing) by the time set in this parameter.
P.026 0 .. 1 Clearing / Pre-warning 0: Clearing time is only active in the end positions.
time 1: Counts down always, not only in the end positions.
P.030 [sec] Vehicle - over-length
0 ... 60 detection after x sec
2.2 Drive
P.100 [HZ] Motor rated frequency The motor-rated frequency indicated on the nameplate of the motor
30 ... 200 is entered here.
P.101 [A] Motor rated current The motor-rated current indicated on the nameplate of the motor is
0 ... 9,9 entered here.
IMPORTANT
Note Y/∆ switching of the motor!
(see Figure 1: Typical star /delta wiring
P.102 [%] Power factor cos ϕ The time factor indicated on the nameplate of the motor is entered
40 ... 100 here.
EFAFLEX GmbH 5
P. [Unit] Function Description / note
Operating
range
IMPORTANT
The entry is made without the leading „0“,
63 thus means cos ϕ 0.63.
P.103 [V] Motor rated voltage The motor-rated voltage indicated on the nameplate of the motor is
100 ... 500 entered here.
IMPORTANT
Note Y/∆ switching of the motor!
L1 L2 L3 L1 L2 L3
U1 V1 W1 U1 V1 W1
W2 U2 V2
W2 U2 V2
Stern-Schaltunng Dreieck-Schaltung
IMPORTANT
Switching of the motor windings to 400V operation does not make
sense with the efacon door controller, as it can output a maximum
of 230V!
U
Unenn
P103
f nenn
P100
Input of the voltage frequency curve on the basis
of the motor nameplate
P.110 Drive profile This profile is used to set the motor rating of a known motor.
) The exact settings which the profile involves can be found in the
„drive profile appendix“.
6 ҏ EFAFLEX GmbH
EFACON
Door-Controller
P. [Unit] Function Description / note
Operating
range
3.8 kW 100 2.2 kW at 100
100 Hz 230 / 400 V 2.2 kW 100 Hz 230 V 400 V
at 173 Hz Hz Hz
100 1.9 kW
100 Hz 133 / 230 V 1.1 kW 100 Hz 133 V not useful 230 V
Hz at 173 Hz
P.111 0 ... 1 Motor cut-out The motor cut-out activates the monitoring of the motor current
(error message F515).
2.3 Converter
P.130 0 ... 1 Motor rotary field This parameter specifies the rotary field of the motor for OPEN
move.
0: Right rotating
1: Left rotating
P.140 [%] Boost for OPEN move The boost increases the output voltage and thus the power in the
0 ... 30 lower speed range until the cutoff frequency (P.100) is reached.
U
UMAX
Boost
curve
normal
P.140/ curve
145
Fcutoff
f
EFAFLEX GmbH 7
P. [Unit] Function Description / note
Operating
range
2x
motor
rated
current
P101
t
The frequency stop function enables the moving of heavy doors.
f
fmax
P310
fRampstop
P141/146
t
Figure 5: Frequency ramp stop characteristic curve
P.142 [Hz] IxR compensation for In this parameter you specify the frequency up to which IxR
0 ... 15 OPEN compensation is in effect.
The voltage is held at the same value below this frequency.
The voltage value is derived from the voltage which is normally
output for the frequency set here.
U
UMAX
UIXR
fIxR fECK
f
Figure 6: IxR compensation characteristic curve
8 ҏ EFAFLEX GmbH
EFACON
Door-Controller
P. [Unit] Function Description / note
Operating
range
The IxR compensation increases the voltage and thus the output of
the motor exclusively in the lower speed range.
P.143 [% Voltage reduction for The indicated value specifies what percent of the output voltage is.
35 ... 100 OPEN move
U
U MAX
% U NENN
P.143/
148
f ECK
f
Figure 7: Voltage reduction characteristic curve
P.161 [Hz] Max. frequency for open The maximum permissible travel speed is limited by the value
Mcp2 15 ... 200 entered in this parameter.
P.103
) This parameter can only be changed by someone having a
password for the plant level.
EFAFLEX GmbH 9
P. [Unit] Function Description / note
Operating
range
ATTENTION
If the mains input voltage is too high, this may damage the
controller.
0: Function deactivated
1: Warning F.425 is issued for overvoltage
2: Fault F.525 is issued for overvoltage and the door can only be
operated in deadman mode
3: Fault F.525 is issued for overvoltage and no operation is
possible
) The exact settings which the profile involves can be found in the
„drive profile appendix“.
2.4 Brake
P.180 [Hz] Activating the brake The brake is activated when the travel frequency specified in the
0 ... 20 parameter falls short while the door is slowing down.
P.181 [10ms] Activating the brake The brake is activated after reaching the limit switch bands after the
0 ... 6000 time set in the parameter
P.185 [Hz] Deactivating the brake The brake is deactivated when the travel frequency specified in the
0 ... 20 parameter is exceeded while the door is accelerating.
P.186 [10ms] Deactivating the brake The brake is deactivated after the time specified in the parameter
0 ... 6000 during acceleration of the door.
P.187 0 ... 1 Switching brake contact Switching of the rest state of the brake contact
0: Brake contact declined in rest state
1: Brake contact increased in rest state
P.18F Brake profile This profile is used to set the behaviour of the brake.
) The exact settings which the profile involves can be found in the
„drive profile" appendix.
P.189 [%] Brake for lifting anchor Lifting anchor motors require a voltage in order to lift the rotor.
0 ... 50 motors Only then is the motor able to turn.
Since frequency converters increase the voltage at the beginning of
travel only slowly, this does not result in releasing of the brake or
raising of the rotor. Therefore this parameter is used to set a
voltage increase similar to IxR compensation
P.201 0 ... 1 Baud rate This parameter determines the baud rate of the limit switch
connected.
P.202 0 ... 20 Translation factor This parameter is used to set the translation factor of the encoder.
The quicker the drive shaft, the higher the translation factor set.
Is only effective in connection with the absolute encoder EFA-PD.
P.205 Positioning system This profile sets the limit switch system used.
profile
IMPORTANT
In addition, the standard functions of the controller inputs are
adjusted to the limit switch type used.
) The exact settings which the profile involves can be found in the
„positioning system profile" appendix.
2.6 Positioning
P.210 0 ... 5 New teaching of end This parameter is used to start a new teaching of the end positions.
positions: The corresponding end positions are moved to in deadman mode
after activating the procedure and saved by holding down the stop
key.
The following setting options are possible:
EFAFLEX GmbH 11
P. [Unit] Function Description / note
Operating
range
setting in Parameter P.244
P.215 0 ... 1 Requesting correction of If automatic calculation of the pre-limit switch and limit switch bands
the pre-limit switch and (P.216) is activated, this parameter can be used to start a new
limit switch bands teaching of the pre-limit switch and limit switch bands.
0: Make no correction.
1: Start correction of the pre-limit switch and limit switch bands
P.216 0 ... 2 Selecting the ramp There are two basic ways to set the steepness of a ramp. The ramp
setting mode time can be set in milliseconds, or the ramp acceleration can be set
in Hz per second.
In addition, the limit switch bands are automatically set when
Automatic is activated.
P.217 [%] Tolerance band for An offset value is added to the end position ascertained by the
0 ... 250 automatic limit switch automatic limit switch correction.
correction This prevents the door from crossing the end position during the
first travel and being damaged.
The end position is shifted by the percentage set.
P.218 0 ... 2 Independent This parameter is used to determine the start conditions for the
implementation of independent implementation of the automatic end limit switch
automatic limit switch correction. If the start condition is fulfilled, the controller starts with
correction an automatic operation, whereby in the LOWER end position and in
the UPPER end position a keep open time expires, which can be
set by P.219. Then, the door moves again into the other end
position. If the message I.510 is issued, the automatic limit switch
correction is completed and the door remains in the LOWER end
position. Independent implementation is deactivated.
0: Independent implementation is started by request OPEN or
CLOSE command
1: Independent implementation is started after the expiry of the
time set in parameter P.219.
P.219 [s] Time for the This parameter is used to set the keep open time in the LOWER
2 ... 60 independent and UPPER end position during the independent implementation of
implementation of the limit switch correction. In addition, this time can be used as a
automatic limit switch start condition, if P.218 = 2 is set.
correction
P.221 [Increments] Correction value end This parameter is used to shift the entire lower end position, i.e. the
± 125 position door CLOSE end position is shifted together with the relevant pre-limit switch.
P.222 [Increments] Position pre-limit switch The parameter value specifies the distance to the absolute limit
Mcp2 0 ... 2100 door CLOSE switch door CLOSE in increments.
P.223
The pre-limit switch is used to initiate the brake ramp “r6”. The
steepness of the ramp is set with Parameter P.361 or P.362.
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
P.222
Break ramp r6
P.361 / P.362
Frequency
P.223 [Increments] Limit switch band The limit switch band specifies the range by detecting the position
Mcp2 0 ... 200 door CLOSE as end position for door CLOSE. This is comparable with the range
P.222 in which a mechanical cam limit switch is tripped. When the limit
switch band is reached, the stop ramp “ru” is run. The steepness of
the ramp is set with Parameter P.381 or P.383
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
P.223
Stop ramp ru
P.381 / P.383
Frequency
P.225 [Increments] Position of second pre- This pre-limit switch is used to achieve an additional acceleration
0 ... 4200 limit switch ramp during the beginning of the door travel.
door CLOSE The incremental value entered in the parameter specifies the
distance of the pre-limit switch 2 to the end position down.
At the beginning of the travel, the start ramp „r3“ is run. After
activation of the pre-limit switch 2, the start ramp „r1“ begins.
EFAFLEX GmbH 13
P. [Unit] Function Description / note
Operating
range
start ramp „r1“.
The steepness of the start ramp "r1" is set with parameter P.311 or
P.312, the steepness of the start ramp "r3" is set with parameter
P.316 or P.317.
Frequency
Start ramp r1
P.311 / P.312
Start ramp r1
P.311 / P.312
P.226 [Increments] Position of third pre-limit With this pre-limit switch an additional brake ramp for braking the
0 ... 2100 switch door is activated.
end position door
CLOSE 0 switches off the additional brake ramp.
The entered value specifies the distance of the pre-limit switch to
the end position door CLOSE in increments.
The pre-limit switch 3 is used to initiate the brake ramp “r8”. The
steepness of this ramp is set with Parameter P.366 or P.367.
After reaching the pre-limit switch door CLOSE, the ramp “r6” is
run.
Limit switch
Door CLOSE
Pre limit Pre limit switch 3 CLOSE
switch Door CLOSE
Door
Way CLOSE
Break ramp r6
P.361 / P.362
Break ramp r8
P.366 / P.367
Frequency
P.229 [Increments] Emergency limit switch The emergency limit switch band lies behind the limit switch band
0 ... 100 band door CLOSE (P.223). If the limit switch band is passed and the emergency limit
switch band reached, the frequency converter runs a fast stop
ramp. At the same time the information message I.150 (End
position door CLOSE reached at excessively high speed) is issued.
Way
Frequency
P.230 [Increments] End position door OPEN This parameter displays the number of increments that were taught
50 ... 9999 during calibration or synchronization of the door
IMPORTANT
A maximum of 3700 increments are possible when using absolute
encoders for position sensing.
P.231 [Increments] Correction value end This parameter is used to shift the entire door OPEN end position,
± 60 position door OPEN i.e., the end position is shifted together with the associated pre-limit
switches.
A change in the parameter value in the negative direction causes
the end position to shift up.
A change in the parameter value in the negative direction causes
the end position to shift down.
P.232 [Increments] Position pre-limit switch The parameter value specifies the distance to the absolute limit
Mcp2 0 ... 2100 door OPEN switch door OPEN in increments.
P.233 The pre-limit switch is used to initiate the brake ramp “r2”. The
steepness of the ramp is set with Parameter P.321 or P.322
Frequency
Break ramp r2
P.321 / P.322
P.232
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.233 [Increments] Limit switch band The limit switch band specifies the range by detecting the position
Mcp2 0 ... 200 door OPEN as upper end position. This is comparable with the range in which a
P.232 mechanical cam switch is tripped.
When the limit switch band is reached, the stop ramp “ro” is run.
EFAFLEX GmbH 15
P. [Unit] Function Description / note
Operating
range
The steepness of the ramp is set with Parameter P.341 or P.343
Frequency
Stop ramp ro
P.341 / P.343
P.233
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.235 [Increments] Position of second pre- This pre-limit switch is used to achieve an additional acceleration
0 ... 4200 limit switch ramp during the beginning of the door travel.
End position door OPEN The incremental value entered in the parameter specifies the
distance of the pre-limit switch 2 to the end position door OPEN.
At the beginning of the travel, the start ramp „r/“ is run. After
activation of the pre-limit switch 2, the start ramp „r5“ begins.
The steepness of the start ramp "r5" is set with parameter P.351 or
P.352, the steepness of the start ramp "r7" is set with parameter
P.356 or P.357.
P.235
Way
Start ramp r7
P.356 / P.357
Start ramp r5
P.351 / P.352
Frequency
P.236 [Increments] Position of third pre-limit With this pre-limit switch an additional brake ramp when braking the
0 ... 2100 switch door is activated.
door OPEN The entered value specifies the distance from the pre-limit switch to
the end position door CLOSE in increments.
The pre-limit switch 3 is used to initiate the brake ramp “r4”. The
steepness of this ramp is set with Parameter P.326 or P.327.
After reaching the pre-limit switch door OPEN, the ramp “r2” is run.
Break ramp r4
P.326 / P.327
Break ramp r2
P.321 / P.322
Pre limit
switch Way
Pre limit switch 3 Door Limit switch
OPEN Door OPEN OPEN Door OPEN
P.239 [Increments] Emergency switch band The emergency limit switch band lies behind the limit switch band
0 ... 100 door OPEN (P.223). If the limit switch band is passed and the emergency limit
switch band reached, the frequency converter runs a fast stop
ramp. At the same time the information message I.100 (End
position door OPEN reached at excessively high speed) is issued.
) This function is comparable with a mechanical cam-operated
limit switch, which generates an E-STOP when the end position is
crossed.
Frequency
Way
P.233
P.239
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.240 [Increments] Intermediate stop The entered value specifies the distance of the intermediate stop
25 ... 9999 position E1 position to the end position door CLOSE in increments.
P.242 [Increments] Position of middle pre- The parameter value specifies the distance to the middle limit
Mcp2 0 ... 2100 limit switch switch in increments.
P.243 The pre-limit switch is used to initiate the brake ramp “r2”. The
steepness of the ramp is set with Parameter P.321 or P.322.
EFAFLEX GmbH 17
P. [Unit] Function Description / note
Operating
range
Frequency
Break ramp r2
P.321 / P.322
P.242
Way
Middle pre Limit switch
OPEN limit switch middle
P.244 0 ... 3 Selection of intermediate The position of the intermediate stop can be set directly to typical
stop position values using this parameter.
P.245 [Increments] Intermediate stop The entered value specifies the distance of the intermediate stop
25 ... 9999 position E2 position to the end position door CLOSE in increments.
2.7 Synchronization
P.250 0 ... 1 Incremental counting The pulses of the incremental encoder can be processed in two
different ways.
Either the edges (rising and falling edge) of the signal or the states
(High or Low level) are evaluated.
By counting edges, four increments per signal pair result.
Counting states results in one increment per signal pair.
0. Quadrature method (edges are processed)
1. Single method (states are processed)
P.251 0 ... 5 Mode for automatic The door position is lost after turning off the controller when using
synchronization after incremental encoders. To find a valid position again, the door must
power-up be resynchronized (homed) to a reference point.
This parameter specifies how the door controller is to behave after
power-up.
IMPORTANT
Automatic opening is only possible if P.280 1.
P.253 0 ... 4 Automatic first If this parameter is activated, an automatic first synchronization is
Mcp2 synchronization carried out, without manually teaching the end positions before.
P.252 0: Manual deadman move to door CLOSE end position, then
deadman move to the door OPEN end position. Then save
position with STOP
1: Manual deadman move to door CLOSE end position, then
save position with STOP, then automatic OPEN travel to
reference in the door OPEN end position.
2: Manual deadman move to the door OPEN end position, then
save position with STOP, then automatic CLOSE travel to
reference in the door CLOSE end position.
3: Automatic CLOSE move to reference point in the door CLOSE
end position, then automatic OPEN move to reference point in
the door OPEN end position
4: Automatic OPEN move to reference point in the door OPEN
end position, then automatic CLOSE move to reference point
in the door CLOSE end position
P.25F Synchronization profile This profile is used to set the references switches and the mode of
Mcp2 the automatic synchronization.
P.290
) The exact settings which the profile involves can be found in the
„positioning system profile" appendix.
P.270 0 ... 3 Select reference in the Here you specify the type of reference which is activated in the
door CLOSE end door CLOSE end position.
position
0: No reference
1: Reference switch
2: Mech. stop
3: Safety edge
IMPORTANT
Automatic synchronization to reference switches only functions if
the switch was previously detected during an automatic move. In
this case, message I.200 is issued
P.271 0 ... 3 Start conditions for Automatic synchronization to the door CLOSE end position starts
Mcp2 automatic under the following conditions:
P.254 synchronization
0: After briefly pressing the foil key À CLOSE
EFAFLEX GmbH 19
P. [Unit] Function Description / note
Operating
range
1: Automatically after the synchronization time entered in
Parameter P.273 has elapsed.
P.272 0 ... 1 Cyclical synchronization: When cyclical synchronization is enabled, the reference position is
checked each time a close move is made.
If this deviates too significantly from the learned position, a fault is
generated.
P.273 [s] Waiting time before the After expiry of this time, the automatic synchronization of the door
0 ... 200 beginning of the CLOSE end position begins if Parameter P.273 was entered as a
automatic start condition in Parameter P.271.
synchronization
P.275 [Increments] Correct increments after The value entered in this parameter is used to shift the switching off
±500 completion of position of the door.
synchronization If, for example, synchronization to a mech. stop is made, the door
should not travel against this stop with each travel. To prevent this,
the stop position is corrected using this parameter.
P.280 0 ... 2 Select reference in the Here you specify the type of reference which is activated in the
door OPEN end position door OPEN end position.
0: No reference
1: Reference switch
2: Mech. stop
IMPORTANT
Automatic synchronization to reference switches only functions if
the switch was previously detected during an automatic move. In
this case, message I.200 is issued.
P.281 0 ... 1 Start conditions for Automatic synchronization to the door OPEN end position starts
Mcp2 automatic under the following conditions:
P.254 synchronization
0: After briefly pressing the foil key ¿ OPEN
1: Automatically after the synchronization time entered in
Parameter P.283 has elapsed.
P.282 0 ... 1 Cyclical synchronization: When cyclical synchronization is enabled, the reference position is
checked each time an open move takes place.
If this deviates too significantly from the learned position, a fault is
generated.
P.283 [s] Waiting time before the After expiry of this time, the automatic synchronization of the door
0 ... 200 beginning of the OPEN end position begins if the value 1 was entered as a start
automatic condition in Parameter P.281.
synchronization
P.285 [Increments] Correct increments after By value entered in this parameter the switching off position of the
±1250 completion of door is shifted.
synchronization If, for example, synchronization to a mech. stop is made, the door
should not travel against this stop with each travel. To prevent this,
the stop position is corrected using this parameter.
2.8 Speeds
P.310 [Hz] Travel frequency for Here you specify the maximum opening speed in Hz.
Mcp2 6 ... 200 rapid open Start ramp “r1” is used to accelerate to this speed.
P.315 The steepness of the ramp is set with Parameter P.311 or P.312.
Frequency
P.310
Start ramp r1
P.311 / P.312
Way
P.311 [10ms] Duration of start ramp Time of start ramp „r1“ in milliseconds.
Mcp2 15 ... 500 „r1“ The door is accelerated within the specified time from 0Hz to the
P.316 maximum opening speed (P.310).
P.312 [Hz/s] Acceleration of start Acceleration during start ramp "r1" in Hertz per second.
5 ... 300 ramp „r1“
Smaller values result in diminished acceleration of the door.
Larger values result in greater acceleration of the door.
P.315 [Hz] Average opening speed If Parameter P.225 was used to activate the additional acceleration
Mcp2 6 ... 200 during acceleration ramp “r3”, this parameter is used to determine the average opening
P.310 phase speed.
Frequency
Start ramp r1
P.311 / P.312
P.315
Start ramp r3
P.316 / P.317
P.225
Door OPEN Way
position
Pre limit
CLOSE
switch 2
P.316 [10ms] Duration of start ramp Time of start ramp „r3“ in milliseconds.
Mcp2 20 ... 500 „r3“ The door is accelerated within the specified time from 0Hz to the
P.311 average opening speed (P.315).
After reaching the pre-limit switch 2, the door is accelerated up to
the maximum opening speed (P.310).
EFAFLEX GmbH 21
P. [Unit] Function Description / note
Operating
range
P.320 [Hz] Creep speed frequency Brake ramp “r2” is used to slow to creep speed frequency, and is
Mcp2 6 ... 200 for open initiated after activation of the pre-limit switch door OPEN. Brake
P.325 ramp “r2” is used to slow to creep speed frequency, and is initiated
after activation of the pre-limit switch door OPEN.
The steepness of the brake ramp “r2” is set with Parameter P.321
or P.322.
Frequency
P.310
Break ramp r2
P.321 / P.322
P.320
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.321 [10ms] Duration of brake ramp This parameter specifies the time of brake ramp “r2” in
Mcp2 15 ... 500 „r2“ milliseconds.
P.326 The door is decelerated from maximum opening frequency (P.310)
to creep frequency (P.320) within this time.
P.322 [Hz/s] Acceleration of brake This parameter specifies the acceleration of the door during brake
5 ... 300 ramp „r2“ ramp “r2 in Hertz per second.
Frequency
P.310
Break ramp r4
P.326 / P.327
Break ramp r2
P.325 P.321 / P.322
P.320
Pre limit
switch
Way
Pre limit switch 3 Door Limit switch
OPEN Door OPEN OPEN Door OPEN
P.326 [10ms] Duration of brake ramp Time of brake ramp „r4“ in milliseconds
Mcp2 15 ... 500 „r4“ The door is decelerated within the specified time from maximum
P.321 opening speed (P.310) to the second opening speed (P.325).
P.327 [Hz/s] Acceleration of start Acceleration during start ramp "r4" in Hertz per second.
5 ... 300 ramp „r4“ After reaching the pre-limit switch 3, the door is decelerated to the
second opening speed (P.325).
P.331 [10ms] Duration of stop ramp Time of stop ramp „rSi-A“ in milliseconds
0 ... 250 “rSi-A” after safety edge is The door is decelerated within the specified time from maximum
tripped opening speed to 0 Hz after tripping of the safety edge.
EFAFLEX GmbH 23
P. [Unit] Function Description / note
Operating
range
Frequency
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.332 [Hz/s] Acceleration of stop Acceleration during stop ramp "rSi-A" in Hertz per second.
50 ... 600 ramp “rSi-A” after safety The door is decelerated from maximum opening speed to 0 Hz
edge is tripped after tripping of the safety edge.
P.333 [10ms] Duration of stop ramp Time of stop ramp „rZSi-A“ in milliseconds.
0 ... 250 “rZSi-A” after an additional The door is decelerated within the specified time from maximum
safety is tripped opening speed to 0 Hz after tripping of an additional safety.
Frequency
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.334 [Hz/s] Acceleration of stop Acceleration during stop ramp „rZSi-A“ in Hertz per second.
50 ... 600 ramp “rZSi-A” after an The door is decelerated from maximum opening speed to 0 Hz
P.335 [10ms] Duration of start ramp Acceleration ramp after reversal request by tripping an (additional)
0 ... 500 after safety reversal safety or an open command during closing.
/reversal
) This parameter is only visible if parameter P.216 is set at 0.
P336 [Hz/s] Acceleration of start Acceleration of start ramp after safety reversal
5 ... 300 ramp after safety
reversal Smaller values result in diminished acceleration of the door.
Larger values result in greater acceleration of the door.
P.340 [10ms] Duration of stop ramp Time of stop ramp „rSTOP-A“ in milliseconds
Mcp2 3 ... 250 “rSTOP-A” after stop is The door is decelerated in the specified time from maximum
P.342 tripped opening speed to 0 Hz after tripping of a stop command.
Frequency
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.341 [10ms] Duration of stop ramp Time of stop ramp „ro“ in milliseconds.
3 ... 250 „ro“ The door is decelerated in the specified time from creep speed to 0
Hz after reaching the limit switch.
EFAFLEX GmbH 25
P. [Unit] Function Description / note
Operating
range
Frequency
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.342 [Hz/s] Acceleration of stop Acceleration during stop ramp „rSTOP-A“ in Hertz per second.
5 ... 300 ramp “rSTOP-A” after stop The door is decelerated from maximum opening speed to 0 Hz
is tripped after tripping of a stop command.
P.343 [Hz/s] Acceleration of stop Acceleration during stop ramp "ro" in Hertz per second.
5 ... 300 ramp „ro“ The door is decelerated from creep speed to 0 Hz after reaching
the limit switch
P.348 [Hz/s] Acceleration of stop Acceleration during stop ramp in Hertz per second.
50 ... 600 ramp after Emergency The door is decelerated from maximum opening speed to 0 Hz
STOP is tripped after tripping of an emergency stop.
Frequency
Way
Pre limit switch Limit switch
OPEN Door OPEN Door OPEN
P.350 [Hz] Travel frequency for Here you specify the maximum closing speed in Hz.
Mcp2 6 ... 200 rapid close Start ramp “r5” is used to accelerate to this speed.
P.355 The steepness of the ramp is set with Parameter P.351 or P.352.
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
Start ramp r5
P.351 / P.352
P.350
Frequency
P.351 [10ms] Duration of start ramp Time of start ramp „r5“ in milliseconds
Mcp2 15 ... 500 „r5“ The door is accelerated within the specified time from 0Hz to the
P.356 maximum closing speed (P.350).
P.352 [Hz/s] Acceleration of start Acceleration during start ramp "r5" in Hertz per second.
20 ... 300 ramp „r5“
Smaller values result in diminished acceleration of the door.
Larger values result in greater acceleration of the door.
EFAFLEX GmbH 27
P. [Unit] Function Description / note
Operating
range
P.355 [Hz] Average closing speed If Parameter P.235 was used to activate the additional acceleration
Mcp2 6 ... 200 during acceleration ramp “r7”, this parameter is used to determine the average closing
P.350 phase speed.
P.235
Way
Start ramp r7
P.356 / P.357
P.355
Start ramp r5
P.351 / P.352
Frequency
P.356 [10ms] Duration of start ramp Time of start ramp „r7“ in milliseconds
Mcp2 20 ... 500 „r7“ The door is accelerated within the specified time from 0Hz to the
P.351 average closing speed (P.355).
After reaching the pre-limit switch 2, the door is accelerated up to
the maximum closing speed (P.350).
P.357 [Hz/s] Acceleration of start Acceleration during start ramp "r7" in Hertz per second.
5 ... 300 ramp „r7“ After reaching the pre-limit switch 2, the door is accelerated up to
the maximum closing speed (P.350).
P.360 [Hz] Creep speed frequency Brake ramp “r6” is used to slow to creep speed frequency, and is
Mcp2 6 ... 200 for close move initiated after activation of the pre-limit switch door CLOSE.
P.365 The steepness of the brake ramp “r6” is set with Parameter P.361
or P.362.
P.360
Start ramp r6
P.351 / P.352
Frequency
P.361 [10ms] Duration of brake ramp This parameter specifies the time of brake ramp “r6” in
Mcp2 15 ... 500 „r6“ milliseconds.
P.366 The door is decelerated from maximum closing frequency (P.350)
to creep frequency (P.360) within this time.
P.362 [Hz/s] Acceleration of brake This parameter specifies the acceleration of the door during brake
5 ... 300 ramp „r6“ ramp “r6" in Hertz per second.
P.365 [Hz] Specify frequency for If Parameter P.226 was used to activate the additional brake ramp
Mcp2 6 ... 200 second closing speed “r8”, this parameter is used to determine the second opening
P.360 during braking phase speed.
After reaching pre-limit switch 3, ramp “r9” is used to decelerate to
this speed.
The steepness of the ramp is set with Parameter P.366 or P.367.
Limit switch
Door CLOSE
Pre limit
switch
Pre limit switch 3 CLOSE
Door CLOSE
Door
Way CLOSE
P.360
Break ramp r6
P.365
P.361 / P.362
Break ramp r8
P.366 / P.367
P.350
Frequency
EFAFLEX GmbH 29
P. [Unit] Function Description / note
Operating
range
P.366 [10ms] Duration of brake ramp Time of brake ramp „r8“ in milliseconds
Mcp2 15 ... 500 „r8“ The door is decelerated from maximum closing speed (P.350) to
P.361 the second closing speed (P.365) after reaching pre-limit switch 3
in the specified time.
P.367 [Hz/s] Acceleration of brake Acceleration during start ramp "r8" in Hertz per second.
5 ... 300 ramp „r8“ After reaching pre-limit switch 3, the door is decelerated from
nd
maximum closing speed (P.350) down to the 2 closing speed
(P.365).
P.371 [10ms] Duration of stop ramp Time of stop ramp „rn“ in milliseconds
3 ... 250 „rn“ after safety edge is The door is decelerated within the specified time from maximum
tripped closing speed to 0 Hz after tripping of the safety edge.
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
Stop ramp rn
P.371 / P.372
Frequency
P.372 [Hz/s] Acceleration of stop Acceleration during stop ramp „rn“ in Hertz per second.
50 ... 600 ramp „rn“ after safety The door is decelerated from maximum closing speed to 0 Hz after
edge is tripped tripping of the safety edge.
P.373 [10ms] Duration of stop ramp Time of stop ramp „rZSi-Z“ in milliseconds
Mcp2 3 ... 250 „rZSi-Z“ after an additional The door is decelerated within the specified time from maximum
P.372 safety is tripped closing speed to 0 Hz after tripping of an additional safety device.
Frequency
P.374 [Hz/s] Aceleration of stop ramp Acceleration during stop ramp „rZSi-Z“ in Hertz per second.
50 ... 600 „rZSi-Z“ after an additional The door is decelerated from maximum closing speed to 0 Hz after
safety device is tripped tripping of an additional safety device.
P.380 [10ms] Duration of stop ramp Time of stop ramp „rSTOP-Z“ in milliseconds.
Mcp2 3 ... 250 “rSTOP-Z” after stop is The door is decelerated in the specified time from maximum closing
P.382 tppried speed to 0 Hz after tripping of a stop command.
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
Frequency
) This ramp also takes effect after the light barrier is tripped.
P.381 [10ms] Duration of stop ramp Time of stop ramp „ru“ in milliseconds
3 ... 250 „ru“ The door is decelerated in the specified time from creep speed to 0
Hz after reaching the limit switch.
EFAFLEX GmbH 31
P. [Unit] Function Description / note
Operating
range
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
Frequency
P.382 [Hz/s] Acceleration of stop Acceleration during stop ramp „rSTOP-Z“ in Hertz per second.
5 ... 300 ramp “rSTOP-Z” after stop The door is decelerated from maximum closing speed to 0 Hz after
is tripped tripping of a stop command.
) This ramp also takes effect after the light barrier is tripped.
P.383 [Hz/s] Acceleration of stop Acceleration during stop ramp „ru“ in Hertz per second.
5 ... 300 ramp „ru“ The door is decelerated from creep speed to 0 Hz after reaching
the limit switch
Limit switch
Door CLOSE
Pre limit switch
Door CLOSE
CLOSE
Way
Stop ramp
Emergency-STOP
P.388 / P.389
Frequency
P.390 [Hz] Travel frequency for This parameter specifies the travel speed in Hertz for opening in
6 ... 100 deadman open move deadman mode.
P.391 [10ms] Duration of start ramp Time of start ramp for deadman open move in milliseconds
10 ... 500 for deadman The door is accelerated within the specified time from 0Hz to the
Open move deadman speed (P.390).
P.392 [Hz/s] Acceleration of start Acceleration during start ramp for opening in deadman mode in
5 ... 300 ramp for deadman Hertz per second.
opening The door is accelerated with the maximum permissible specified
acceleration from 0Hz to the deadman speed (P.390).
EFAFLEX GmbH 33
P. [Unit] Function Description / note
Operating
range
P.395 [Hz] Travel frequency for This parameter specifies the travel speed in Hertz for closing in
6 ... 100 deadman close deadman mode.
P.396 [10ms] Duration of start ramp Time of start ramp for closing in deadman mode in milliseconds
10 ... 500 for close in deadman The door is accelerated within the specified time from 0Hz to the
mode deadman speed (P.395).
P.397 [Hz/s] Acceleration of start Acceleration during start ramp for close in deadman mode in Hertz
5 ... 300 ramp for close in per second.
deadman mode The door is accelerated with the maximum permissible specified
acceleration from 0Hz to the deadman speed (P.395).
P.398 [Hz/s] Acceleration of stop Acceleration during stop ramp for deadman travel in Hertz per
5 ... 300 ramp after deadman second.
mode The door is decelerated with the maximum permissible specified
acceleration from deadman speed to 0 Hz (P.395 or P.390).
P.399 [10ms] Duration of stop ramp Time of stop ramp for deadman move in milliseconds
3 ... 100 after deadman move The door is decelerated within the specified time to 0Hz from the
deadman speed (P.395 or P.390).
P.39F Speed profile With this profile, the acceleration of the door is set.
Mcp2
P.992
) The exact settings which the profile involves can be found in the
„speed profile" appendix.
P.408 0 ... 3 Acknowledgement The controller allows you to require an acknowledgement after
certain controller events, i.e., the operator must intervene. Without
this acknowledgement the door can no longer be operated.
The STOP key is used for acknowledgement.
0: no acknowledgement
1: Acknowledgement necessary after turning on the controller
2: Acknowledgement necessary after turning on the controller
and tripping of the EMERGENCY OFF.
3: Acknowledgement necessary after turning on the controller,
tripping of the EMERGENCY OFF and after error messages.
P.410 [s] Run time monitoring The time set here is the max. permissible door runtime for the
Mcp2 0 ... 9900 open move OPEN direction.
P.400 If the move takes longer than specified, this results in fault F.020.
P.415 [s] Runtime monitoring The time set here is the max. permissible door runtime for the
Mcp2 0 ... 9900 close move CLOSE direction.
P.401 If the move takes longer than specified, this results in fault F.020.
P.417 0 ... 1 Stop at new tripping of a Switching off of the stop at new tripping of a safety in deadman
safety in deadman mode mode (e.g. at P.980=2, in close move at P.980=1, on switching off
automatic per receipt and similar)
P.418 0 ... 2 Deadman mode in Function of deadman mode by tripped securities in automatic mode
automatic mode (e.g. at P.980 = 0 or at P.980=1 in open move)
P.419 [s] Runtime monitoring The time set here is the max. permissible door runtime for the
Mcp2 0 ... 9900 deadman mode OPEN and CLOSE direction in deadman mode.
P.402 If the move takes longer than specified, this results in fault F.020.
P.420 [10ms] Reversing time when If the safety edge is tripped during moving, the door is stopped and
Mcp2 3 ... 200 safety edge is tripped after a short pause moved into the opposite direction again.
P.425 during closing The time of the pause between stop and resume is set by this
parameter.
P.421 [10ms] Reversing time when If the safety edge is tripped during moving, the door is stopped and
Mcp2 0: 3 ... 200 external safety edge is after a short pause moved into the opposite direction again.
P.435 tripped The time of the pause between stop and resume is set by this
parameter.
EFAFLEX GmbH 35
P. [Unit] Function Description / note
Operating
range
If this parameter is 0, the value of P.420 is used.
P.422 [10ms] Reversing time during If an open command is tripped during closing, the door is stopped
0; 5 ... 200 close and after a short pause opened again.
The time of the pause between stop and resumed opening is set by
this parameter.
IMPORTANT
The reversal times on tripping of the safety edges are separately
set by the parameters P.420 and P.421.
P.424 [10ms] Reversing time during If an additional safety device (e.g. a light barrier) which has a
0; 5 ... 200 close on tripping of an reversing effect when tripped is tripped during closing, the door is
additional safety device stopped and after a short pause opened again.
The time of the pause between stop and resume is set by this
parameter.
P.430 [s] Lag error when using If after initiating a move command the limit switch is not left within a
Mcp2 0 ... 5.0 mechanical limit time specified by this parameter, it is assumed that the door is not
P.405 switches moving.
This results in fault F.030 and the door will be stopped
P.431 1..190 Number of permissible This parameter is only available when the TLG is activated!
self-test errors until In the case of a missing self-test, the info message I 927 is issued
error message and the missing self-text is counted. The further automatic
operation is still possible.
On reaching the set number, the controller goes into error and only
closing in deadman mode is possible. Error F.927 is shown.
After the successful test, the error counter is set to 0 and the error
is cancelled. The test is also carried out at closing in deadman
mode
0 = deactivated
1-190: Number of permissible self-test errors
P.433 0…2 Activate TLG This parameter determines among others the self-test logics for the
the TLG.
0: Deactivation of TLG
1: Activation of TLG
2:
P.438 [ms] Direction of rotation This function monitors constantly whether the door moves intot he
10 ... 500 errors with electronic expected direction.
limit switches If the door moves into the wrong direction by the time set in this
parameter, then error F.031 is issued.
P.440 [Increments] Safety edge pre-limit This parameter specifies the distance of the safety-edge pre-limit
Mcp2 -60 ... 999 switch position switch to the end position door CLOSE in increments. With active
P.426 TLG, this position is maintained without regard to P.221 (correction
value of door CLOSE), otherwise it will be shifted.
WARNING
The max. permissible distance of the safety edge pre-limit switch to
the ground is 50mm at the worst point.
max. 50 mm
P.450 [10ms] Lag error when using With electronic limit switches a change in distance is constantly
Mcp2 10 ... 300 electronic limit switches monitored during active moving.
P.406 If there is no change, after the time specified here fault F.030 is
issued and the door is stopped.
P.452 [%] Dynamics at obstacle The smaller the later the response to the obstacle takes place.
35 ... 100 detection Short-term faults, for example when starting or reversing can be
filtered out
P.453 [Increments] Tolerance band The tolerance band set here must be exceeded at the beginning of
0 ... 99 the travel or at reversal, before the monitoring of the obstacle
starts.
P.460 -1 ... 5 Type of safety edge This parameter is used to specify which safety edge type is
Mcp2 connected.
P.420
0: Safety edge inactive
IMPORTANT
This setting is only possible if no safety edge is connected.
1: Electrical safety edge, redundantly processed, functioning as
closing system, i.e., short circuit indicates tripping.
2: Electrical safety edge, redundantly processed, functioning as
opening system, i.e., interruption indicates tripping.
3: Safety edge with testing in the door CLOSE end position,
functioning as closing system, i.e. there must be a tripping of
the safety edge for checking its proper function in the door
CLOSE end position
4: Safety edge with testing in the door CLOSE end position,
functioning as opening system, i.e. there must be a tripping of
the safety edge for checking its proper function in the door
EFAFLEX GmbH 37
P. [Unit] Function Description / note
Operating
range
CLOSE end position
5: Dynamic optical system
P.461 0 ... 5 Max. number of In case of an obstacle in the door area the safety edge is used to
Mcp2 permissible reversals reverse the movement.
P.421 If the obstacle is still present and automatic closing is activated, the
door would continuously open and close.
To prevent this the door remains stopped at the door OPEN end
position after the number of reversals set here is reached
This also causes fault F.361 to be issued.
IMPORTANT
To acknowledge this fault, the door must be moved once in
deadman mode to the door CLOSE end position.
P.462 0 ... 2 Safety edge functions This parameter specifies how the safety edge processing responds
Mcp2 to the safety edge pre-limit switch.
P.422
0: After the safety edge pre-limit switch is tripped, the safety edge
is tripped only to stop the door.
1: After the safety edge pre-limit switch is tripped, the safety edge
function is ignored.
2: The safety edge function is ignored after the door CLOSE end
position regardless of the safety edge pre-limit switch.
P.463 0 ... 1 End positions after This parameter specifies which are moved to after reversal.
Mcp2 reversals to be moved to
P.423 0: End position door OPEN
1: End position as before e.g. intermediate hold / partial opening
P.467 [Ink] Increments to be moved This parameter specifies whether and which keep open times /
Mcp2 0 ... 9999 to after reversals forced closing time runs after the reversal until end position top.
P.427
0: Reversing until end position
>0: Reversing by number of increments
P.468 0 ... 1 Deactivation during Deactivates the safety edge during automatic synchronization
Mcp2 automatic
P.428 synchronization 0: Evaluate safety edge also during automatic synchronization
1: Ignores safety edge during automatic synchronization
P.469 0 ... 27 LCD message for safety For each input a message can be selected from a list, which is
edge tripping shown when tripping the corresponding input in the LCD display.
P.46B 0 ... 3 Keep open time This parameter specifies whether and which keep open times /
Mcp2 forced closing time runs after the reversal until end position top.
P.424
0: Without keep open time
1: With keep open time (P.010 or P.011)
2: With minimum keep open (P.015)
3: No keep open time, closing only after activation of a CLOSE
command. Keep open time cannot be started by another
OPEN command.
4: As before
5: Stop upper time in end position, on reversal only minimum
keep open time.
6: With priority 1 (highest prio: pulse OPEN)
7: With priority 2 (second highest prio: as one channel (=current
impulse))
P.471 0 ... 5 Max. number of In case of an obstacle in the door area the safety edge is used to
Mcp2 reversals reverse the movement.
P.431 If the obstacle is still present and automatic closing is activated, the
door would continuously open and close.
To prevent this the door remains stopped at the door OPEN end
position after the number of reversals set here is reached
This also causes fault F.361 to be issued.
EFAFLEX GmbH 39
P. [Unit] Function Description / note
Operating
range
P.472 0 ... 2 Safety edge function for This parameter specifies how the safety edge processing responds
Mcp2 close move to the safety edge pre-limit switch.
P.432
0: After the safety edge pre-limit switch is tripped, the safety edge
is tripped only to stop the door.
1: After the safety edge pre-limit switch is tripped, the safety edge
function is ignored.
2: The safety edge function is ignored after the door CLOSE end
position regardless of the safety edge pre-limit switch.
P.473 0 ... 1 End positions after This parameter specifies which are moved to after reversal.
Mcp2 reversals to be moved to
P.433 0: End position door OPEN
1: End position as before e.g. intermediate hold / partial opening
P.475 0 ... 1 Safety edge functions Specifies the response to a safety edge trip during the OPEN move
for starting at door OPEN limit switch.
OPEN move
0: The door is stopped.
1: The safety edge tripping is ignored and the door continues to
door OPEN end position
P.476 0 ... 1 Response after tripping Specifies the behavior of the door after the safety edge is tripped
during OPEN move during the OPEN move.
P.477 [Inc] Leaving increments after This parameter specifies whether and which keep open times /
Mcp2 0 ... 9999 reversals forced closing time runs after the reversal until end position top.
P.437
0: Reversing until end position
>0: Reversing by number of increments
P.478 0 ... 1 Deactivation during Deactivates the safety edge during automatic synchronization
Mcp2 automatic
P.438 synchronization 0: Evaluate safety edge also during automatic synchronization
1: Ignores safety edge during automatic synchronization
P.479 0 ... 27 LCD message for safety For each receipt a message can be selected from a list, which is
Mcp2 edge tripping shown when tripping the corresponding input in the LCD display.
P.439
The list of messages can be found in the LCD selection messages.
P.47A 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
Mcp2
P.43A 0: Without clearing time
1: With clearing time (P.025)
P.47B 0 ... 3 Keep open time This parameter specifies whether and which keep open times /
Mcp2 forced closing time runs after the reversal until end position top.
P.483 0 ... 5 max. number of Max. number of obstacles during OPEN move, on excess F320,
obstacles when reaching the top end position the move is considered to be
completed and counting starts from the beginning
P.485 0 ... 2 Reaction to obstacle in
CLOSE move 0: None
1: Stop
2: Reversal:
P.486 [10ms] Reversal time after At present only used when P485 = 2, corresponds to the waiting
10 ... 250 obstacle in CLOSE time after an obstacle before the reversal is made
move
P.487 0 ... 10 Max. number of
obstacles 0: F.325 is not set, always reversing
>0: Max. number of obstacles during CLOSE move, on excess
F0.325, when reaching the lower end position the move is
considered to be completed and counting starts from the
beginning
P.4A1 0 ... 3 Switching off of Selection of different conditions for the switching off of additional
additional safety A Close securities in CLOSE move
move
0: No switching off
1: Switching off after reaching the lower end position
2: Switching off after reaching the lower pre-limit switch
3: Switching off after reaching the lower pre-limit switch for
additional safety A (P.4A3 / P.5x0=11, P.5x1=1)
EFAFLEX GmbH 41
P. [Unit] Function Description / note
Operating
range
P.4A2 0 ... 9999 Position of additional Position for switching off of additional safety A Open move
safety A Open move
P.4A3 0 ... 9999 Position of switching off Position for switching off of additional safety A close move
of additional safety A
Close move
P.4A7 0 ... 2 Closing command on 0: No close command
release of additional 1: Close command after additional safety becomes free
safeties A 2: Close command after release of additional safety and the close
command is also saved during the OPEN move.
P.4A9 0 ... 1 Additional safety A Selection of additional safety during automatic synchronization
Mcp2 active during automatic 0: Input is processed
P.468 synchronization 1: Input is ignored during synchronization.
Mcp2
P.478
P.4B0 0 ... 3 Switching off of Selection of different conditions for the switching off of additional
additional safety B Open securities in OPEN move
move 0: No switching off
1: Switching off after reaching the top end position
2: Switching off after reaching the pre-limit switch TOP
3: Switching off after reaching the pre-limit switch TOP for
additional safety B (only for electronic limit switch P.4B2)
P.4B1 0 ... 3 Switching off of Selection of different conditions for the switching off of additional
Mcp2 additional safety B Close securities in CLOSE move
P.440 move
0: No switching off
1: Switching off after reaching the lower end position
2: Switching off after reaching the lower pre-limit switch
3: Switching off after reaching the lower pre-limit switch for
additional safety B (P.4B3 / P.5x0=11, P.5x1=1)
P.4B2 0 ... 9999 Position of switching off Position for switching off of additional safety B Open move
of additional safety B
Open move
P.4B3 0 ... 9999 Position of switching off Position for switching off of additional safeties B close move
Mcp2 of additional safety B
P.446 Close move
P.4B7 0 ... 2 Closing command on 0: No close command
release of additional 1: Close command after additional safety becomes free
safeties B 2: Close command after release of additional safety and the close
command is also saved during the OPEN move.
P.4B9 0 ... 1 Additional safety B Selection of additional safety during automatic synchronization
Mcp2 active during automatic 0: Input is processed
P.448 synchronization 1: Input is ignored during synchronization.
Mcp2
P.468
P.4C0 0 ... 3 Switching off of Selection of different conditions for the switching off of additional
additional safety C Open securities in OPEN move
move
0: No switching off
1: Switching off after reaching the top end position
2: Switching off after reaching the pre-limit switch TOP
3: Switching off after reaching the pre-limit switch TOP for
additional safety C (only for electronic limit switch P.4C2)
P.4C1 0 ... 3 Switching off of Selection of different conditions for the switching off of additional
P.4C2 0 ... 9999 Position of switching off Position for switching off of additional safety C in Open move
of additional safety C
Open move
P.4C3 0 ... 9999 Position of switching off Position for switching off of additional safeties C in close move
Mcp2 of additional safety C
P.456 Close move
P.4C7 0 ... 2 Closing command on 0: No close command
release of additional 1: Close command after additional safety becomes free
safeties C 2: Close command after release of additional safety and the close
command is also saved during the OPEN move.
P.4C9 0 ... 1 Additional safety C Selection of additional safety during automatic synchronization
Mcp2 active during automatic 0: Input is processed
P.458 synchronization 1: Input is ignored during synchronization.
Mcp2
P.468
2.12 Inputs
P.501 Input profiles Through this profile, the input function can be defined.
All parameters necessary for the input function are reset in one
Input 1 step.
The profiles are divided into function groups which are allocated
as follows:
EFAFLEX GmbH 43
P. [Unit] Function Description / note
Operating
range
P.508 Input 8 see P.501
P.509 Input 9 see P.501
P.50A Input 10 see P.501
Parameter P.5x0 must be set to 1 to activate the basic faction OPEN command for this input.
X = Number of the input you wish to configure.
P.5x1 0 ... 6 Mode This parameter specifies the mode of the OPEN command.
0: OPEN 1, lockable
1: OPEN 2, lockable
2: OPEN 3, not lockable
3: OPEN 4, not lockable
4: OPEN 5, not lockable and deadman move possible
) Deadman opening using external command switches is only
possible using this setting.
5: OPEN air lock move, not lockable
)This OPEN command can only be used with an active
airlock system
6: Reserved
7: Reserved
8: Reserved
9: Reserved
10: In the case of a crash with key switch after end position OPEN
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 3 End position to move to This parameter specifies which end position is traveled to after
activating the input.
P.5x4 0 ... 4 Keep open time / priority This parameter specifies if and which hold-open time / forced
closing time runs after activating the input and/or which priority a
command has.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 0 ... 3 Direction Specifies which logical direction the input has.
Specifying the direction is necessary for opposing traffic controllers.
The controller uses this information to decide which direction is
clear, which traffic light is switched or which airlock gate is opened.
0: No direction specified
1: From outside to inside
2: From inside to outside
3: Both directions are cleared
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 2 to activate the basic function single channel / pull switch for this input.
X = Number of the input you wish to configure
EFAFLEX GmbH 45
P. [Unit] Function Description / note
Operating
range
P.5x1 0 ... 7 Mode This parameter specifies the mode of the current impulse
command.
By repeatedly activating the input the various commands are run in
the sequence shown below.
0: OPENÆSTOPÆOPENÆend position
1: OPENÆSTOPÆOPENÆend positionÆCLOSEÆOPEN
2: OPENÆend positionÆCLOSEÆOPEN
3: OPENÆSTOPÆCLOSEÆOPEN
4: OPENÆSTOPÆCLOSEÆSTOP
5: OPENÆend position
6: CLOSE
7: OPEN only from end position door CLOSE
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 3 End position to move to This parameter specifies which end position is traveled to after
activating the input.
P.5x4 0 ... 3 Keep open time / priority This parameter specifies if and which hold-open time / forced
closing time runs after activating the input and/or which priority a
command has.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 0 ... 3 Direction Specifies which logical direction the input has.
Specifying the direction is necessary for opposing traffic controllers.
The controller uses this information to decide which direction is
clear, which traffic light is switched or which airlock gate is opened.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 3 to activate the basic function pulse OPEN for this input.
X = Number of the input you wish to configure
P.5x1 Mode This parameter is not evaluated when using this function.
0: Pulse Open (no close move until the next external close
command, i.e. keep open times are switched off, priorities can
be allocated with 5x0 = 6.7)
1: Summer mode for airlock (open commands from door 1 (open)
are sent to door 2 (functional like contact opening)
2: Contact opening (with rising edge, open move takes place, on
falling edge, Close move from upper end position)
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 3 End position to move to This parameter specifies which end position is traveled to after
activating the input.
EFAFLEX GmbH 47
P. [Unit] Function Description / note
Operating
range
P.5x4 Keep open time / priority 0: Without keep open time
1-5: Without function
6: With priority 1 (highest prio: pulse OPEN)
7: With priority 2 (second highest prio: as one channel (=current
impulse))
8: With priority 3 (third highest prio: like contact opening)
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 0 ... 3 Direction Specifies which logical direction the input has.
Specifying the direction is necessary for opposing traffic controllers.
The controller uses this information to decide which direction is
clear, which traffic light is switched or which airlock gate is opened.
0: No direction specified
1: From outside to inside
2: From inside to outside
3: Both directions are cleared
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 4 to activate the basic function STOP for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 1 Mode This parameter specifies the mode of the stop command.
0: Stop function
1: Stop function and additional acknowledgement function, i.e.
with this input an acknowledgement takes place.
An acknowledgement must be performed under the conditions
stated under P.408.
2: (Crash impulse, deadman travel permitted, acknowledgement
only in end position TOP (debouncing with additional 170 ms)
3: (Crash impulse, deadman's open/close travel not permitted,
acknowledgement automatically in upper end position
(debouncing with additional 170 ms)
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 5 to activate the basic function additional safeties for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 7 Mode This parameter specifies the reaction to an activated additional
safety input and/or which function is performed.
EFAFLEX GmbH 49
P. [Unit] Function Description / note
Operating
range
tripping in open move until input is free again, then stop
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 1 End position to move to This parameter specifies which end position is traveled to after
activating the input.
P.5x4 0 ... 3 Keep open time This parameter specifies whether and which keep open times /
forced closing time runs after activation of the input.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
Parameter P.5x0 must be set to 6 to activate the basic function manual / automatic toggling for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 1 Mode This parameter specifies the mode of the hand / automatic toggle.
When activated, the controller switches to manual operation.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
EFAFLEX GmbH 51
P. [Unit] Function Description / note
Operating
range
Parameter P.5x0 must be set to 7 to activate the basic function CLOSE command for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 1 Mode This parameter specifies the mode of the close command.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 8 to activate the basic function door locking in end position for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 2 Mode This parameter specifies the behaviour of the door when the
locking is activated.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 3 Locking position This specifies in which position the controller is to change in the
locked condition.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
EFAFLEX GmbH 53
P. [Unit] Function Description / note
Operating
range
2: Testing on reaching the end position door CLOSE and after
switching on
P.5x1 0 ... 7 Mode This parameter specifies the mode of the cross traffic input.
If this input is activated, the following commands are locked or
suppressed for the time set under Parameters P.810, P.811 and
P.820, p.821.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 10 to activate the basic function switching off / deactivation for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 5 Mode This parameter specifies which function or input is deactivated.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
EFAFLEX GmbH 55
P. [Unit] Function Description / note
Operating
range
switching on
Parameter P.5x0 must be set to 11 to activate the limit switch basic functions for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 7 Mode Specifies which limit switch type is connected to the input.
max. 50 mm
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
P.5x4 Keep open time This parameter is not evaluated when using this function.
P.5x5 Clearing time This parameter is not evaluated when using this function.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 14 to activate the basic function additional safeties for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 7 Mode This parameter specifies the reaction to an activated additional
safety input and/or which function is performed.
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 3 End position to move to This parameter specifies which end position is traveled to after
activating the input.
P.5x4 0 ... 3 Keep open time This parameter specifies whether and which keep open times /
EFAFLEX GmbH 57
P. [Unit] Function Description / note
Operating
range
forced closing time runs after activation of the input.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 15 to activate the simulation of the foil keypad basic function for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 2 Mode This parameter specifies which keys of the foil keypad are
simulated.
IMPORTANT
The external foil keypad cannot be used for parametrizing the
controller.
The functionality of the inputs depends on the parametrizing of the
foil keypad inputs (see Parameter P.631 to P.659)
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 End position to move to This parameter is not evaluated when using this function.
The settings which have been made for the respective key of the
foil pad, are taken over (see P.631 to P.659)
P.5x4 Keep open time This parameter is not evaluated when using this function.
The settings which have been made for the respective key of the
foil pad, are taken over (see P.631 to P.659)
P.5x5 Clearing time This parameter is not evaluated when using this function.
The settings which have been made for the respective key of the
foil pad, are taken over (see P.631 to P.659)
P.5x6 Direction This parameter is not evaluated when using this function.
The settings which have been made for the respective key of the
foil pad, are taken over (see P.631 to P.659)
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text This parameter is not evaluated when using this function.
The settings which have been made for the respective key of the
foil pad, are taken over (see P.631 to P.659)
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
Parameter P.5x0 must be set to 16 to activate the basic function additional safeties for this input.
X = Number of the input you wish to configure
P.5x1 0 ... 7 Mode This parameter specifies the reaction to an activated additional
safety input and/or which function is performed.
EFAFLEX GmbH 59
P. [Unit] Function Description / note
Operating
range
2: Reversing during close move and stop during open move
3: Stop during OPEN move
4: Entrapment protection
5: Stop during OPEN travel with continuation after end position
door OPEN after the input has become free.
6: Stop during open and close travel
7: Stop during OPEN and CLOSE travel with continuation after
end position door close after the CLOSE move has become
free.
8: Monitoring of close move with stop, continuation to lower end
position after CLOSE move has become free.
9: Monitoring of open move, reversing after close move on
tripping in open move
10: Monitoring of open move, reversing after close move on
tripping in open move until input is free again, then stop
P.5x2 0 ... 1 Contact type Specifies the contact type of the switch which is connected to the
input.
0: Normally closed
1: Normally open
P.5x3 0 ... 1 End position to move to This parameter specifies which end position is traveled to after
activating the input.
P.5x4 0 ... 3 Keep open time This parameter specifies whether and which keep open times /
forced closing time runs after activation of the input.
P.5x5 0 ... 1 Clearing time Activates the clearing time which elapses before the next closing.
P.5x6 Direction This parameter is not evaluated when using this function.
P.5x7 [s] Switching on delay of The evaluation of the input is delayed by the time set in this
P.5x8 [s] Switching off delay of The decrease of the input is delayed by the time set in this
0 ... 999,9 input parameter.
P.5x9 0 ... 27 LCD text For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.5xA 0 ... 2 Testing Each input can be tested. This parameter specifies in which end
position testing is made.
0: No testing
1: Testing on reaching the end position door OPEN and after
switching on
2: Testing on reaching the end position door CLOSE and after
switching on
P.610 0 ... 27 LCD message for For each receipt a message can be selected from a list, which is
Mcp2 internal EMERGENCY shown when tripping the corresponding input in the LCD display.
P.6C9 OFF
The list of messages can be found in the LCD selection messages.
P.611 0 ... 27 LCD message for For each receipt a message can be selected from a list, which is
Mcp2 external EMERGENCY shown when tripping the corresponding input in the LCD display.
P.6D9 OFF 1
The list of messages can be found in the LCD selection messages.
P.612 0 ... 27 LCD message for For each receipt a message can be selected from a list, which is
Mcp2 external EMERGENCY shown when tripping the corresponding input in the LCD display.
P.6E9 OFF 2
The list of messages can be found in the LCD selection messages.
P.633 0 ... 3 End position to move to Specifies which end position is traveled to after pressing the OPEN
key.
EFAFLEX GmbH 61
P. [Unit] Function Description / note
Operating
range
2: To intermediate stop / to door OPEN end position from
intermediate stop
3: Like 2, but when key is pressed twice the door moves to the
door OPEN end position.
P.634 0 ... 4 Keep open time This parameter specifies whether and which keep open time /
forced closing time elapses after arriving at the end position.
P.635 0 ... 1 Clearing time Activates the clearing time / pre-warning time before closing the
door if it was previously opened by pressing the OPEN key.
P.636 0 ... 3 Direction The direction of the OPEN command is used mainly for direction-
dependent controlling of traffic lights.
The parameter specifies for which direction the OPEN command
works.
0: No direction enabled
1: From outside to inside enabled
2: From inside to outside enabled
3: Both directions are cleared
P.639 0 ... 27 LCD message For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.641 0 ... 1 Function foil keypad - Specifies the function (mode) of the STOP key.
STOP
0: After pressing the STOP key the door is stopped and waits for
any command.
1: After pressing the STOP key the door is stopped and waits for
a keypad command.
2: After pressing the STOP key the door is stopped, open move
is possible with any command, close move only by keypad
CLOSE command.
P.649 0 ... 27 LCD message For each receipt a message can be selected from a list, which is
P.651 0 ... 2 Function foil keypad - Specifies the function (mode) of the CLOSE key.
CLOSE
0: No door function
1: Only deadman travel during deadman mode
2: Deadman and automatic mode
P.654 0-7 Keep open time / priority 0: Without keep open time
1: 5: Without function
6: with priority 1 (highest prio: like pulse CLOSE)
7: with priority 2 (second highest prio: as one channel (=current
impulse))
P.655 0 ... 1 Clearing time Changing this parameter specifies whether the clearing time before
closing is cancelled or not.
P.659 0 ... 27 LCD message For each receipt a message can be selected from a list, which is
shown when tripping the corresponding input in the LCD display.
P.661 [s] Switching on delay Loop delay above lower end position (when door is not CLOSE)
Mcp2 0 ... 65 detector Channel 1 (response delay) e.g. opening intermediate hold position →upper
P.66B above lower end end position
position not effective for safety loop or during closing
P.662 [s] Falling delay detector Continuous post running time for loop
EFAFLEX GmbH 63
P. [Unit] Function Description / note
Operating
range
Mcp2 0 ... 65 Channel 1 (off delay)
P.66C above lower end also effective for safety loop or during closing
position
P.663 0 ... 3 End position to move to Specifies which end position is traveled to after Detector Channel 1
is activated.
P.664 0 ... 3 Keep open time This parameter specifies whether and which keep open time /
forced closing time elapses after arriving at the end position.
P.665 0 ... 1 Clearing time Activates the clearing time / pre-warning time before closing the
door if it was previously opened by detector Channel 1
P.666 0 ... 3 Direction The direction is used mainly for direction-dependent controlling of
traffic lights.
The parameter specifies for which direction the detector Channel 1
works.
0: No direction enabled
1: From outside to inside enabled
2: From inside to outside enabled
3: Both directions are cleared
P.667 20 ... 25 Locking detector To prevent false triggering, the detector Channel 1 can be locked
Mcp2 Channel 1 out for the time specified in P.678.
P.66E
Channel 1 is locked:
20: Deactivated
21: Detector Channel 2
22: Detector Channel 2 and OPEN 2 commands
23: Detector Channel 3
24: Detector Channel 3 and OPEN 1 commands
25: Reserved
P.668 [s] Locking time Detector Channel 1 is locked out for the time specified in this
Mcp2 0 ... 120 parameter (see also P.667)
P.66D
P.66A [s] Switching on delay The parameterized function of detector Channel 1 is only executed
0 ... 65 detector Channel 1 after the time specified in this parameter.
P.66D 0 ... 1 Deactivation detector Deactivation detector Channel 1 during automatic synchronization
Mcp2 Channel 1 during
P.668 automatic 0: Evaluate detector also during automatic synchronization
synchronization 1: Ignores detector during automatic synchronization
P.671 [s] Switching on delay Loop delay above lower end position (when door is not CLOSED)
Mcp2 0 ... 65 detector Channel 2 (response delay) e.g. opening intermediate hold position →upper
P.67B above lower end end position
position not effective for safety loop or during closing
P.672 [s] Falling delay detector Continuous post running time for loop
Mcp2 0 ... 65 Channel 2 (off delay)
P.67C above lower end also effective for safety loop or during closing
position
EFAFLEX GmbH 65
P. [Unit] Function Description / note
Operating
range
P.673 0 ... 5 End position to move to Specifies which end position is traveled to after detector Channel 2
is activated.
P.674 0 ... 3 Keep open time This parameter specifies whether and which keep open time /
forced closing time elapses after arriving at the end position.
P.675 0 ... 1 Clearing time Activates the clearing time / pre-warning time before closing the
door if it was previously opened by detector Channel 2
P.676 0 ... 3 Direction The direction is used mainly for direction-dependent controlling of
traffic lights.
The parameter specifies for which direction the detector Channel 2
works.
0: No direction enabled
1: From outside to inside enabled
2: From inside to outside enabled
3: Both directions are cleared
P.677 20 ... 25 Locking detector To prevent false triggering, the detector Channel 2 can be locked
Mcp2 Channel 2 out for the time specified in P.668.
P.67E
Channel 2 is locked:
20: Deactivated
21: Detector Channel 2
22: Detector Channel 2 and OPEN 2 commands
23: Detector Channel 3
24: Detector Channel 3 and OPEN 1 commands
25: Reserved
P.678 [s] Locking time Detector Channel 2 is locked out for the time specified in this
Mcp2 0 ... 120 parameter (see also P.677)
P.67D
P.67A [s] Switching on delay The parameterized function of detector Channel 2 is only executed
0 ... 65 detector Channel 2 in after the time specified in this parameter.
lower end position
P.67C 0 ... 3 Closing command on 0: No close command
Mcp2 leaving the loop Channel 1: Close command after the loop becomes free
P.671 2 2: Close command after release of loop and the close command
is also saved during the OPEN move.
3: Reserved
4: Close command after release of loop only in the TOP end
position. During closing, the detector is ignored.
P.67D 0 ... 1 Deactivation detector Deactivation detector Channel 2 during automatic synchronization
Mcp2 Channel 2 during
P.678 automatic 0: Evaluate detector also during automatic synchronization
synchronization 1: Ignores detector during automatic synchronization
P.608 Radio Channel 1 profile This parameter specifies all parameters for radio Channel 1
Mcp2
P.6A0 See attached profile table
P.680 0 ... 16 Basic function radio Defines the basic function of the radio input. The functions are
Channel 1 profile similar to the basic functions of the inputs 1 to 10 and 21 to 26. The
function of the P.68x parameter depends on the basic function set
here. These are described in "" section.
EFAFLEX GmbH 67
P. [Unit] Function Description / note
Operating
range
P.609 Radio Channel 2 profile This parameter specifies all parameters for radio Channel 2
Mcp2
P.6A0 See attached profile table
P.690 0 ... 16 Basic function radio Defines the basic function of the radio input. The functions are
Channel 2 profile similar to the basic functions of the inputs 1 to 10 and 21 to 26. The
function of the P.68x parameter depends on the basic function set
here. These are described in "" section.
The detector Channel 3 can only be used in connection with the extension circuit board EFACON.
Extension circuit board (must be activated after plug in by P800)
P.60C Profile of detector See attached profile table
Mcp2 Channel 3
P.680
P.6C1 [s] Switching on delay Loop delay above lower end position (when door is not CLOSED)
Mcp2 0 ... 65 detector Channel 3 (response delay) e.g. opening intermediate hold position →upper
P.68B above lower end end position
position not effective for safety loop or during closing
P.6C2 [s] Falling delay detector Continuous post running time for loop
Mcp2 0 ... 65 Channel 3 (off delay)
P.68C above lower end also effective for safety loop or during closing
position
P.6C3 0 ... 3 End position to move to Specifies which end position is traveled to after detector Channel 3
Mcp2 is activated.
P.683
0: To door open end position
1: To intermediate stop / to partial opening (input switching off
allowed for)
2: Reserved
3: Reserved
4: To intermediate stop / to partial opening (input switching off not
allowed for)
P.6C4 0 ... 3 Keep open time This parameter specifies whether and which keep open time /
Mcp2 forced closing time elapses after arriving at the end position.
P.684
0: Without keep open time
1: Without keep open time
2: With minimum keep open time
3: No keep open time, closing only after activation of a CLOSE
command. Keep open time cannot be started by another
OPEN command.
P.6C5 0 ... 1 Clearing time Activates the clearing time / pre-warning time before closing the
Mcp2 door if it was previously opened by detector Channel 3
P.685
0: Without clearing time
1: With clearing time
EFAFLEX GmbH 69
P. [Unit] Function Description / note
Operating
range
Parameter P.025.
P.6C6 0 ... 3 Direction The direction is used mainly for direction-dependent controlling of
Mcp2 traffic lights.
P.686 The parameter specifies for which direction the detector Channel 3
works.
0: No direction enabled
1: From outside to inside enabled
2: From inside to outside enabled
3: Both directions are cleared
P.6C7 20 ... 25 Locking detector To prevent false triggering, the detector Channel 3 can be locked
Mcp2 Channel 3 out for the time specified in P.678.
P.68E
Channel 3 is locked:
20: Deactivated
21: Detector Channel 2
22: Detector Channel 2 and OPEN 2 commands
23: Detector Channel 3
24: Detector Channel 3 and OPEN 1 commands
Reserved
P.6C8 [s] Locking time Detector Channel 3 is locked out for the time specified in this
Mcp2 0 ... 120 parameter (see also P.667)
P.68D
P.6C9 0 ... 27 LCD message For each receipt a message can be selected from a list, which is
Mcp2 shown when tripping the corresponding input in the LCD display.
P.689
The list of messages can be found in the LCD selection messages.
P.6CA [s] Switching on delay The parameterized function of detector Channel 3 is only executed
Mcp2 0 ... 65 detector Channel 3 after the time specified in this parameter.
P.68A
P.6CC 0 ... 3 Closing command on 0: No close command
Mcp2 leaving the loop Channel 1: Close command after the loop becomes free
P.681 3 2: Close command after release of loop and the close command
is also saved during the OPEN move.
3: Reserved
4: Close command after release of loop only in the UPPER end
position. During closing, the detector is ignored.
P.6CD 0 ... 1 Activation of detector Deactivation detector Channel 3 during automatic synchronization
Mcp2 Channel 3 during
P.688 synchronization 1. Evaluate detector also during automatic synchronization
2. Ignores detector during automatic synchronization
P.B61 0 ... 1 Deactivating Loop 3 Here the scanning of Loop 2 can be deactivated.
0: Deactivate scanning
1: Scanning performed
P.B62 1 ... 5 Frequency range of This parameter specifies the frequency range of Loop 3.
Loop 3 1: Range 30-40 kHz
P.B6D 0 ... 1 Scanning filter This parameter specifies whether scanning signals are filtered.
0: No filter (high sensitivity)
1: With filter (high interference immunity)
P.B6E 0 ... 1 Request new After setting the parameter to 1, a new synchronization of all loops
synchronization is performed.
The detector Channel 4 can only be used in connection with the extension circuit board EFACON.
Extension circuit board(must be activated after plug in by P800)
P.60D Profile of detector See attached profile table
Mcp2 Channel 4
P.690
P.6D0 20... 25 Function detector The response of the door controller to triggering of detector
Mcp2 Channel 4 Channel 4 is specified in this parameter.
P.691
The detector responses as:
P.6D1 [s] Switching on delay Loop delay above lower end position (when door is not CLOSED)
Mcp2 0 ... 65 detector Channel 4 (response delay) e.g. open travel intermediate hold position
P.69B above lower end →upper end position
position not effective for safety loop or during closing
P.6D2 [s] Falling delay detector Continuous post running time for loop
EFAFLEX GmbH 71
P. [Unit] Function Description / note
Operating
range
Mcp2 0 ... 65 Channel 4 (off delay)
P.69C above lower end also effective for safety loop or during closing
position
P.6D3 0 ... 3 End position to move to Specifies which end position is traveled to after detector Channel 4
Mcp2P. is activated.
693
0: To door open end position
1: To intermediate stop / to partial opening (input switching off
allowed for)
2: Reserved
3: Reserved
4: To intermediate stop / to partial opening (input switching off not
allowed for)
P.6D4 0 ... 3 Keep open time This parameter specifies whether and which keep open time /
Mcp2 forced closing time elapses after arriving at the end position.
P.694
0: Without keep open time
1: Without keep open time
2: With minimum keep open time
3: No keep open time, closing only after activation of a CLOSE
command. Keep open time cannot be started by another
OPEN command.
P.6D5 0 ... 1 Clearing time Activates the clearing time / pre-warning time before closing the
Mcp2 door if it was previously opened by Detector Channel 4
P.695
0: Without clearing time
1: With clearing time
P.6D6 0 ... 3 Direction The direction is used mainly for direction-dependent controlling of
Mcp2 traffic lights.
P.696 The parameter specifies for which direction the detector Channel 4
works.
0: No direction enabled
1: From outside to inside enabled
2: From inside to outside enabled
3: Both directions are cleared
P.6D7 20 ... 25 Locking detector To prevent false triggering, the detector Channel 4 can be locked
Mcp2 Channel 4 out for the time specified in P.678.
P.69E
Channel 4 is locked:
20: Deactivated
21: Detector Channel 2
22: Detector Channel 2 and OPEN 2 commands
23: Detector Channel 3
24: Detector Channel 3 and OPEN 1 commands
25: Reserved
P.6D8 [s] Locking time Detector Channel 4 is locked out for the time specified in this
Mcp2 0 ... 120 parameter (see also P.667)
P.69D
P.6DA [s] Switching on delay The parameterized function of detector Channel 4 is only executed
Mcp2 0 ... 65 detector Channel 4 after the time specified in this parameter.
P.69A
P.6DC 0 ... 3 Closing command on 0: No close command
Mcp2 leaving the loop Channel 1: Close command after the loop becomes free
P.691 4 2: Close command after release of loop and the close command
is also saved during the OPEN move.
3: Reserved
4: Close command after release of loop only in the UPPER end
position. During closing, the detector is ignored.
P.6DD 0 ... 1 Activation of detector Deactivation detector Channel 4 during automatic synchronization
Mcp2 Channel 4 during
P.698 synchronization 1. Evaluate detector also during automatic synchronization
2. Ignores detector during automatic synchronization
P.B71 0 ... 1 Deactivating Loop 4 Here the scanning of Loop 4 can be deactivated.
0: Deactivate scanning
1: Scanning performed
P.B72 1 ... 5 Frequency range of This parameter specifies the frequency range of Loop 4.
Loop 4
See P.xxx
P.B73 1 ... 255 Threshold value of Loop Threshold value from which Loop 4 is considered to be occupied.
4
See P.xxx
P.B75 [min] Holding time of Loop 4 This parameter specifies the smallest time of occupation on which
0 ... 255 the detector starts a new synchronization for Loop 4.
0: infinite holding time (no new synchronization)
1-255: Holding time in minutes
2.33 Outputs
P.701- Output profiles Through this profile, the output function can be defined.
All parameters necessary for the output function are reset in one
step.
EFAFLEX GmbH 73
P. [Unit] Function Description / note
Operating
range
Extension circuit board
Extension circuit board (must be activated after plug in by P800)
P.704 Profile output 4 see P.701
P.705 Profile output 5 see P.701
P.706 Profile output 6 see P.701
P.707 Profile output 7 see P.701
P.708 Profile output 8 see P.701
P.709 Profile output 9 see P.701
P.70A Profile output 10 see P.701
P.7x1 [s] Switching behaviour of The switching behaviour of the relay is determined by this
0 ... 1000.0 the relay parameter after activation.
0: flashes at 1Hz
1-1000,0: Turn-on time of the relay in seconds
1000,0: Relay continuously switched on
) For courtyard function 10 seconds
Turn off delay P.7x0 = 5
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
P.7x8 0 ... 4 Behaviour during closing This parameter specifies the switching behaviour of the relay during
closing.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
P.7x9 0 ... 7 Behaviour in the door This parameter specifies the switching behaviour of the relay in the
OPEN end position door OPEN end position.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
5: Traffic light off, when condition of P.7xF is fulfilled.
6: Traffic light off, when condition of P.7xF is fulfilled.
EFAFLEX GmbH 75
P. [Unit] Function Description / note
Operating
range
7: Traffic light flashes at 1 Hz, when condition of P.7xF is fulfilled.
P.7xA 0 ... 4 Behaviour during This parameter specifies the switching behaviour of the relay during
clearing clearing / pre-warning time.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
5: Traffic light off, when condition of P.7xF is fulfilled.
6: Traffic light off, when condition of P.7xF is fulfilled.
7: Traffic light flashes at 1 Hz, when condition of P.7xF is fulfilled.
P.7xb 0 ... 4 Behaviour during close This parameter specifies the switching behaviour of the relay during
travel closing.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
P.7xc 0 ... 4 Behaviour during stop This parameter specifies the switching behaviour of the relay at
stop between the end positions.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
P.7xd 0 ... 4 Behaviour if no This parameter specifies the switching behaviour of the relay when
automatic there is no automatic function.
0: Continuously off
1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
P.7x9 0 ... 4 Traffic light behaviour 0: Continuously off
during MinOH 1: Continuously on
2: Flashes at 0.5Hz
3: Flashes at 1Hz
4: Flashes at 2Hz
0: Function deactivated
1 – 10: Input 1 to 10
11 – 12: Reserved
13: internal EMERGENCY OFF
14: External EMERGENCY OFF 1
15: External EMERGENCY OFF 2
16: Foil keypad OPEN
17: Foil keypad STOP
18: Foil keypad CLOSE
19: Detector Channel 1
20: Detector Channel 2
21: Radio Channel 1
22: Radio Channel 2
P.811 [s] Block time for input Block time when locking a lockable OPEN 1 command by one of
Mcp2 0 ... 30 OPEN 1 at cross traffic the detector Channels 2 and 3.
P.821 0: Deactivated
>0: Locking time of the input OPEN 1 at cross traffic
P.820 [s] Block time detector Detector Channel 2 and OPEN 2 commands are locked out for the
Mcp2 0 ... 30 Channel 2 and OPEN 2 time specified in this parameter after activating a cross-traffic input.
P.812
P.821 [s] Block time for input Block time when locking a lockable OPEN 2 command by one of
Mcp2 0 ... 30 OPEN 1 at cross traffic the detector Channels 1 and 4.
P.822 0: Deactivated
>0: Locking time of the input OPEN 2 at cross traffic
EFAFLEX GmbH 77
P. [Unit] Function Description / note
Operating
range
2.39 Airlock
P.830 0 ... 2 Airlock mode This parameter specifies the mode of the airlock system.
2.40 Crash
P.870 0 ... 4 CRASH 0: Deactivated (does not apply for crash impulse)
1: Reserved
2: Reserved
3: Crash position is travelled to after expiry of a holding time
4: Reserved
5: Open move with key switch (P.5x0 = 1, P.5x1 = 10)
P.871 0...65535 Crash counter Shows the number of counted crashes
P.873 0...300 [Ink] Crash band Crash position above top end position
P.874 5...15 ”crash”) Shows the time the door rests in the crash position, before the door
[s] Waiting time after is closed again.
tripping of crash In addition, this parameter shows the waiting time after a crash
tripping, before it is automatically moved into the crash position.
P.879 0...1 Reset crash counter Resets the number of counted crashes to 0
1: Reset P.871 to 0.
2.41 Diagnosis
P.910 0 ... 22 Selection of display With the aid of this parameter you can show the variables listed
mode below in the display of the door controller.
P.920 Error memory The controller stores the last eight errors in the error memory.
P.925 Software version This parameter is shows the version of the currently used software.
Mcp2
P.900
Mcp2
P.971
P.930 [s] Runtime of the motor In this parameter the time required for the last door operation is
0 ... 120,0 saved.
P.940 [V] Input voltage In this parameter the amount of the currently present input voltage
is displayed.
) This and the next four parameters are not available if P.800 is
configured at 4 (extension circuit board activated).
P.946 [Hz] Current frequency: This parameter indicates the current frequency of the oscillator
0 ... 200000 circuit of the detector channel selected via P.945.
EFAFLEX GmbH 79
P. [Unit] Function Description / note
Operating
range
P.947 -32767 ... Current detuning This parameter indicates the current detuning of the detector
32768 channel selected via P.945.
P.948 -32768 ... Maximum detuning This parameter indicates the maximum detuning caused by the last
32767 metallic object, which occupied the loop of the detector channel
selected via P.945.
P.949 [Cnt] Presence counter This parameter indicates the presence counter of the detector
0 ... 65535 channel selected via P.945.
P.950 [Increments] Current position In this parameter indicates the current position of the door related
-999 ... 9999 to the CLOSE door end position
P.951 [Dig] Raw data of the This parameter indicates, independent on the type of the connected
0 ... 0xFFFF connected encoder encoder (e.g. incremental coder (e.g. absolute encoder, absolute
system encoder EFA-PD) the raw data. Display is in hex format and
consists of maximally 8-digit.
P.970 0 ... 3 Response to due There are various ways to respond to a due maintenance.
maintenance. Messages or errors will be output:
P.971 [1000 cycl.] Number of door cycles This parameter specifies the number of door cycles that are
1 ... 9999 after acknowledgement possible after resetting the maintenance counter until the next is
issued.
P.972 [Cycles] Warning before This parameter specifies the number of door cycles before the
0 ... 9999 expiration of the maintenance counter expires during which the warning I.080 is
maintenance counter issued.
P.973 0 ... 1 Resetting of the By setting the parameter to 1, the maintenance counter is
maintenance counter acknowledged.
P.980 0 ... 5 Operating mode This parameter is used to set the operating mode of the controller.
WARNING
All safety systems and limit switches are ignored.
4: Endurance tests with safeties
Automatic opening and closing motion Before each new
operation, the holding time P.010 is in effect.
5: Endurance test without safeties
WARNING
All safety systems are ignored.
P.981 0 ... 3 Mode of the door cycle Depending on the setting, the cycle counter counts using various
counter conditions.
0: Each time the door CLOSE end position is reached, the count is
incremented by 1.
1: Each time one of the upper end positions (end position door
OPEN or intermediate stop / partial open), the count is
incremented by 1.
2: With each full door cycle the count is incremented by 1, i.e., the
door must from the end position door CLOSE reach the end
position door OPEN and then again move to the end position
door CLOSE.
3: With each travel command, the count is incremented by 1
independent of the end positions.
0. English texts
1. German texts
2. Spanish texts
3. French texts
4. Dutch texts
P.986 0 ... 7 Selection of door name Selection of the door name indicated on the LCD
0. Display of „Efacon“
1. Display of „Efacon“
2. Display of „Eco Tor“
3. Display of „EL/EC Tor“
4. Display of „Efaflex HHS“
5. Display of „SRT“
6. Display of „SST“
7. Display of „STT“
8. Display of „STR“
EFAFLEX GmbH 81
P. [Unit] Function Description / note
Operating
range
9. Display of „SST-ECO“
P.990 0 ... 1 Factory setting By setting and saving this parameter to 1 all parameter values are
restored to their original value.
P.991 Door profile This profile is used to make settings for in- and outputs as well as
Mcp2 typical settings for the door.
P.991 ) The exact settings which the profile involves can be found in the
„drive profile appendix“.
P.998 0 ... 2 Reset the door cycle After setting this parameter to 1 the current door cycle counter is
Mcp2 counter cleared.
P997
Mcp2 0: Cancel
P998
1: Resets only P.000
2: Resets P.000 and P.002 (is only selectable from password level
4 onwards)
P.999 0 ... FFFF Password The password provides access to the various parameter levels.
1: Start-up level
2: Extended start-up level
xxxx: Manufacturer level
IMPORTANT
Through the different levels of passwords, access to a different
number of parameters is granted.
A changing of parameters without knowing their function is not
permitted.
To avoid errors and dangers by unauthorized access, passwords
must only be issued to trained staff.
3 In-/output parametrisation
For each input of the door controller, any function can be set.
This function can be set through the selection of an input profile (P.501 to P.50A and P.A01 to P.A06) or with the
parameters P.5x0 to P.5x9 and/or P.Ax0 to P.Ax9 individually.
IMPORTANT
The setting under P.5x0 involves different settings of parameters P.5x1 to P.5x9.
EFAFLEX GmbH 83
4 Overview of Messages
F.043 Fault in pre-limit switch for the The pre-limit switch for the optosensor remains engaged even in the
optosensor middle end position or the upper end position.
F.051 Reference switch position deviates Reference switch is in the limit switch band
from the permissible range. Reference switch is more than 15 % of upper end position
Reference switch is defective
F.052 Reference switch not detected The reference switch is not detected within 20% of upper end position
during automatic synchronization after power-up
The reference switch is not detected in the associated end position.
Crash errors
F.060 Crash detected The power circuit for the detection of crash tripping is open. (opener
principle)
F.064 Synchronization of loop 4 • Check and if necessary adapt sensitivity and frequency setting
F.211 External E-stop 1 tripped E-stop chain was interrupted starting at E-stop input 1
F.212 External E-stop 2 tripped E-stop chain was interrupted starting at E-stop input 2
F.362 Redundancy error for short circuit One of the processing channels for short circuit detection is not
detection responding identically to the second channel.
Æ control board defective
Dynamic optical system connected but not set in Parameter P.460.
F.363 Open circuit on safety edge input Cable defective or not connected
Termination resistor defective or missing
Jumper incorrectly set
F.364 Safety edge test failed • Safety edge was not activated as expected when test was
requested.
• The time between request for test and the actual test are
incompatible.
• The dynamic optical system is defective.´
F.365 Redundancy error at open circuit • One of the processing channels for open circuit detection is not
responding identically to the second channel.
Æ control board defective
• Dynamic optical system connected but not set in Parameter
P.460.
F.366 Too high a pulse frequency for Faulty optical safety edge
optical safety edge • Defective input for internal safety edge.
EFAFLEX GmbH 85
Safety chain faults
F.369 Internal safety edge incorrectly • An internal safety edge is connected, but not deactivated.
parametrized
F.373 Fault in safety edge (message Cable break to safety edge, no edge connected, edge termination
comes from module) resistor incorrect or defectiveJumper for termination resistor definition
in wrong position
• Safety edge processing selected with Parameter P.470, but
module not plugged in or wrong module.
F.374 Safety edge test failed • Pre-limit switch for safety edge incorrectly set or defective
• Processor module defective
• Safety edge defective
F.379 Safety edge detection defective • No module plugged in, but was reported as present by a
(coding pin or parameter setting) parameter
The controller was started up with another module than the one
currently plugged in.
F.385 Fault in pre-limit switch for the The pre-limit switch turning off the safety edge or reversing after the
safety edge edge is tripped remains engaged even in the upper end position.
EFAFLEX GmbH 87
Internal system faults
F.920 Internal 2.5 reference voltage Defective hardware
faulty
F.921 Internal 15 V supply faulty • Defective hardware
F.922 E-stop chain not complete • Not all E-STOP inputs are separately jumpered although the entire
E-Stop chain is jumpered
• Redundant checking tripped E-stop chain
F.927 TLG test error • TLG defective (formerly message I.927)
Number in P.431 exceeded • Door does not reach sync beam in lower end position of the door
(formerly message I.928)
F.930 external watchdog faulty • Faulty hardware or significantly disturbed environment
General messages
STOP Stop / reset state, wait for the next arriving command.
Endlage ZU Lower end position
CLOSE end position
Zu, verriegelt Locked lower end position → no opening move possible (e.g. airlock)
Close locked
Zufahrt Active closing
Closing
Endlage AUF Upper end position
Open end position
Dauerauf Upper end position locked → no closing possible (e.g. safety loop)
Permanent open
Auffahrt Active opening
Opening
Zwischenhalt Middle end position E1 (intermediate stop position)
Intermediate hold
Störung/ Fehler Middle end position locked → no closing possible (e.g. safety loop)
Error/fault
STOP Fault → only deadman mode possible, if applicable automatic opening
Eichen Calibration → Setting of end positions in deadman travel
Calibration (for absolute encoders) → start procedure by STOP key
Not-Aus Emergency off → no travel possible, hardware safety chain interrupted
E-Off
Notfahrt Fault → only deadman moves ignoring safeties etc.
E-travel
EFAFLEX GmbH 89
I.500 Correction of upper limit switch in progress
I.501 Upper pre-limit switch corrected
I.502 Upper limit switch band corrected
I.505 Correction of lower limit switch in progress
I.506 Lower pre-limit switch corrected
I.507 Lower limit switch band corrected
I.510 Correction of the end position
I.515 Control prepares the automatic teaching of the limit switch.
I.520 Speed error (set speed is not reached)
I.555 Correction of the limit switch is in progress
I.927 TLG test failed (no test impulse by TLG)
I.928 TLG test failed (sync beam was not reached)