Havells End to End Solution
Table 1 - Voltage distortion limits Table 2 - Current distortion limits for systems
Bus Voltage V at PCC Individual Total harmonic rated 120 V through 69 kV
harmonic (%) distortion THD (%) Maximum harmonic current distortion in percent of IL
V < 1.0 kV 5.0 8.0 Individual harmoninc order (odd harmonics)a, b
1 kV < V ≤ 69 kV 3.0 5.0 Isc/IL 3≤h<11 11≤h< 17 17≤h<23 23≤h<35 35≤h≤50 TDD
69 kV < V ≤ 161 kV 1.5 2.5 <20 4.0 2.0 1.5 0.6 0.3 5.0
161 kV < V 1.0 1.5* 20<50 7.0 3.5 2.5 1.0 0.5 8.0
* High- voltage systems can have up to 2.0% THD where the cause is an HVDC terminal whose effects 50<100 10.0 4.5 4.0 1.5 0.7 12.0
will have attenuated at points in the network where future users may be connected.
100<1000 12.0 5.5 5.0 2.0 1.0 15.0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
3
Havells Active Harmonic Filter
I ntroduction
As we move towards the Industry 4.0 revolution, the rapid change in loads and introduction of critical application etc. makes the traditional
Reactive Power Solution system less effective. Introduction of PLC, Robotics, IT Infrastructure, UPS, CNC, AC & DC Drive for precision
equipment's in industry generates high level of harmonics in the system. In addition to above, these harmonics are playing major role in
deration of DG Set and failure of system. The continuous & critical operations increase the failure rates of electronics & sensitive
equipment's which makes expensive down time and also loss of production. High harmonics also generates, the high neutral current in
system which leads to generate the high neutral voltage which is also a concern of system failures these days.
AHF Factures
The Havells make AHF is a unique innovation solution for Power Quality that address all power quality issues effectively. Major features are:
l Ultra- fast response
l No deration up-to 50℃ ambient temperature
l Havells unique Quad Pro feature- These features enables user to program AHF as per its priority for following compensation :
m Current harmonics
m Reactive compensation
m Load balancing
m Neutral compensation
l Priority selection feature for maximum capacity utilization as per the system requirement.
AHF Advantage
l Harmonics mitigation
l Reactive power compensation
l Load balancing
l Neutral compensation
l Programmable and customer friendly
l Ultra- fast algorithm
l DG deration compensation
l Reduce down time by protection of failure of electronics cards from transients, resonance voltage fluctuation etc
l Flexibility for future expansion
l Modular design with flexibility of Top & Bottom cable entry.
4
Technical Specifications
System Connection 3 P / 4 W or 4 P / 4 W
Input Voltage 415 V (+/-10%) and 50 Hz (+/-)5% other rating on request
Phase compensation current range 15 A - 1000 A (other ratings on request)
Neutral Current Compensation Available
Technology Two Level Topology / Three Level Topology
Harmonic filtration range 2nd to 51st order
Individual harmonic selection Available
Harmonic Attenuation Ratio in % >96% at rated load
Power factor compensation 100% (Lead / Lag)
Load Balancing Negative Sequence Compensation (Zero Sequence compensation in 4 P / 4 W range)
Reaction time <0.3 ms
Function Selection Quad Pro (Harmonic filtering, Power Factor correction, Load Balancing, Neutral current compensation)
Overload (peak value) Upto 160% of rated peak (instantaneous)
Current Transformer: Secondary o/p 5A/1A
CT Class and VA (recommended) Class: 0.5 or better, Power: 15 VA or more
Interface (Communication) GSM, MODBUS RTU, USB, Ethernet, Profibus
IP Protection Class IP-41 and higher on request
System Cooling Forced air colling
Overheating Protection Yes
Cable entry Top / Bottom & Front / Back
Panel Mounting Wall / Floor
Ambient Temperature No deration upto 500C
Relative Humidity 96% (Non condensing)
Maximum operating altitude 1000 m
Acoustic noise at 1m < 60 dB
Man Machine Interface 17.78 cm (7) LCD touch screen MMI with easy and customer friendly navigation pages
Protections Hardware & Software Protections
5
Havells Hybrid Current
Conditioners (HCC)
CLASSIFICATION | PUBLIC Havells is always working towards the best and the reliable, cost effective solutions for various applications. In this
category Havells has designed Hybrid Current Conditioner for Harmonic mitigation. HCC is combination of most advanced Active Harmonic Filter
and Detuned LC circuit which are controlled by centralized most advanced Microprocessor based intelligent controller. The Detuned LC circuit
improve the Power factor and avoid the chances of resonance and AHF controls does the Harmonic mitigation on micro level.
This makes Havells HCC as most cost effective solution with advance technology to cater the requirement of Power Factor and Harmonic related
issues.
Thanks to Quad- Pro Technology of Havells HCC, which allows HCC solution to be programmed centrally to correct Harmonic distortions and to
decide the Priority for Harmonics mitigation, Power Factor correction, Current unbalance and neutral correction as well.
Most Innovative modular design, stepless operation makes Havells - HCC most rugged, efficient & virtually maintenance free solution.
Sensing CTs
Load
3j Electrical
Grid
m p-based
Intelligent master
controller
mp-Controller
k1 k2 kn
IGBT Based
AHF
De-tuned LCs
Under-compensation Under-compensation
AHF Over-compensation
AHF LC
LC LC
AHF
6
“Copyright Subsists. Imitation of trade dress, graphics and color scheme of this document is a punishable offence."