Technical Particulars
S. No. Description 1C x 35 1C x 70 1C x 95 1C x 120
1.0 Make : UNISTAR UNISTAR UNISTAR UNISTAR
2.0 Type : YY YY YY YY
3.0 Applicable Standard : IS:1554/Part-1/1988 IS:1554/Part-1/1988 IS:1554/Part-1/1988 IS:1554/Part-1/1988
4.0 Voltage Grade : 1100 Volts 1100 Volts 1100 Volts 1100 Volts
5.0 Suitable for System with
a. Service Voltage : 1100 Volts 1100 Volts 1100 Volts 1100 Volts
b. Neutral Earthing : 1100 Volts 1100 Volts 1100 Volts 1100 Volts
7.0 Conductor
a. Material : Annealed Plain Copper Annealed Plain Copper Annealed Plain Copper Annealed Plain Copper
Grade/Class : Class-5 Class-5 Class-5 Class-5
Applicable Standard : IS:8130/84 IS:8130/84 IS:8130/84 IS:8130/84
8.0 Insulation
a. Material : PVC PVC PVC PVC
b. Type : Type-C Type-C Type-C Type-C
Applicable Standard : IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84
c. Thickness ... Mm (Nom.) : 1.2 1.4 1.6 1.6
Extruded (yes/no) : YES YES YES YES
568844884.xls
manish 1 of 10 Sheet4
UNIVERSAL CABLES LTD. SATNA (M.P.)
Technical Particulars
S. No. Description 1C x 35 1C x 70 1C x 95 1C x 120
10.0 Armouring
a. Material : NA NA NA NA
b. Type / Applicable Standard NA NA NA NA
c. Calculated dia. over Inner Sheath (mm) : NA NA NA NA
d. Size (...No x dia) : NA NA NA NA
e. D.C. Resistance at 20oC (Ohm/Km) : NA NA NA NA
f. Short circuit current carrying capacity for one NA NA NA NA
second (KA)
a Short Ckt Current for 1 Sec.(KA) (Conductor) : 3.6 7.3 9.9 12.5
b. Conductor Tempearature allowed for short : 160 160 160 160
circuit duty
568844884.xls
manish 2 of 10 Sheet4
UNIVERSAL CABLES LTD. SATNA (M.P.)
Technical Particulars
S. No. Description 1C x 35 1C x 70 1C x 95 1C x 120
17.0 Electrical Parameters at maximum operating
temperature
a. i) DC Resistance at 20 deg C (Max.) W/km : 0.524 0.268 0.193 0.153
ii) AC Resistance at 90 deg C (Approx.) W/km 0.661 0.338 0.244 0.194
b. Reactance at 50 Hz. W/km (Approx.) : 0.106 0.0924 0.090 0.088
c. Impedance at 50 Hz W/km (Approx.) : 0.669 0.35 0.26 0.213
d. Capacitance per phase mf/km (Approx.) 1.15 1.32 1.36 1.49
e. Volume resistivity at rated operating 1 x 1012 at 85 oC 1 x 1012 at 85 oC 1 x 1012 at 85 oC 1 x 1012 at 85 oC
temperature W cm (min.)
f. Loss Tangent NA NA NA NA
g. Partial Discharge value at KV NA NA NA NA
h. Charging current at normal operating voltage 230 260 272 298
mA/km (at 650 V)
18.0 Recommended minimum bending radius : 15 x overall diameter of cable
19.0 Derating Factor for following Ambient Temp in
Air/Ground
a. at 30oC :
b. at 35 C
o
:
c. at 45oC :
d. at 50oC :
b. Multicore Cable
i. 3 Nos. :
ii. 4 Nos. :
iii. 5 Nos. :
iv. 6 Nos. :
568844884.xls
manish 3 of 10 Sheet4
S. No. Description 2C x 1.5 12C x 1.5 24C x 1.5 3C x 2.5
1.0 Make : UNISTAR UNISTAR UNISTAR UNISTAR
2.0 Type : YWY YFY YFY YWY
3.0 Applicable Standard : IS:1554/Part-1 IS:1554/Part-1 IS:1554/Part-1 IS:1554/Part-1
4.0 Voltage Grade : 1100 volts 1100 volts 1100 volts 1100 volts
5.0 Suitable for System with
a. Service Voltage : 1100 volts 1100 volts 1100 volts 1100 volts
b. Neutral Earthing : 1100 volts 1100 volts 1100 volts 1100 volts
7.0 Conductor
a. Material : Annealed Plain Annealed Plain Annealed Plain Annealed Plain
Copper Copper Copper Copper
Grade/Class : Class-2 Class-2 Class-2 Class-2
Applicable Standard : IS:8130/84 IS:8130/84 IS:8130/84 IS:8130/84
b. Size mm2 (Nominal) : 1.5 1.5 1.5 2.5
c. No. & Diameter of wire in each conductor … : Shall be suitably selected in order to meet the max. DC resistance of the
No./mm conductor as per IS:8130/84
8.0 Insulation
a. Material : PVC PVC PVC PVC
b. Type : Type -A Type -A Type -A Type -A
Applicable Standard : IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84
c. Thickness ... Mm (Nom.) : 0.8 0.8 0.8 0.9
Extruded (yes/no) : YES YES YES YES
568844884.xls
manish 4 of 10 Sheet5
S. No. Description 2C x 1.5 12C x 1.5 24C x 1.5 3C x 2.5
b. Type / Applicable Standard IS:3975 IS:3975 IS:3975 IS:3975
c. Calculated dia. over Inner Sheath (mm) : 6.6 13.1 18.6 8.4
d. Size (...No x dia) : 17 x 1.4 9 x (4 x 0.8) 14 x (4 x 0.8) 20 x 1.4
e. D.C. Resistance at 20oC (Ohm/Km) : 6.37 5.54 3.56 5.22
f. Short circuit current carrying capacity for one 1.3 1.4 2.2 1.5
second (KA)
568844884.xls
manish 5 of 10 Sheet5
S. No. Description 2C x 1.5 12C x 1.5 24C x 1.5 3C x 2.5
e. Volume resistivity at rated operating 1 x 1010 at 70 oC 1 x 1010 at 70 oC 1 x 1010 at 70 oC 1 x 1010 at 70 oC
temperature W cm (min)
f. Loss Tangent NA NA NA NA
g. Partial Discharge value at KV NA NA NA NA
h. Charging current at normal operating voltage 24 24 24 26
mA/km (at 650 V)
18.0 Recommended minimum bending radius : 12 x overall diameter of the cable
b. Multicore Cable
i. 3 Nos. :
ii. 4 Nos. :
iii. 5 Nos. :
iv. 6 Nos. :
21.0 The Cables shall be tested as specified : IS: 1554 /I/1988 IS: 1554 /I/1988 IS: 1554 /I/1988 IS: 1554 /I/1988
568844884.xls
manish 6 of 10 Sheet5
S. No. Description 5C x 2.5 7C x 2.5 12C x 2.5 19C x 2.5 24C x 2.5
1.0 Make : UNISTAR UNISTAR UNISTAR UNISTAR UNISTAR
2.0 Type : YWY YWY YFY YFY YFY
3.0 Applicable Standard : IS:1554/Part-1 IS:1554/Part-1 IS:1554/Part-1 IS:1554/Part-1 IS:1554/Part-1
4.0 Voltage Grade : 1100 volts 1100 volts 1100 volts 1100 volts 1100 volts
5.0 Suitable for System with
a. Service Voltage : 1100 volts 1100 volts 1100 volts 1100 volts 1100 volts
b. Neutral Earthing : 1100 volts 1100 volts 1100 volts 1100 volts 1100 volts
7.0 Conductor
a. Material : Annealed Plain Annealed Plain Annealed Plain Annealed Plain Annealed Plain
Copper Copper Copper Copper Copper
Grade/Class : Class-2 Class-2 Class-2 Class-2 Class-2
Applicable Standard : IS:8130/84 IS:8130/84 IS:8130/84 IS:8130/84 IS:8130/84
b. Size mm2 (Nominal) : 2.5 2.5 2.5 2.5 2.5
c. No. & Diameter of wire in each conductor … : Shall be suitably selected in order to meet the max. DC resistance of the conductor as per
No./mm IS:8130/84
8.0 Insulation
a. Material : PVC PVC PVC PVC PVC
b. Type : Type -A Type -A Type -A Type -A Type -A
Applicable Standard : IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84 IS:5831/84
c. Thickness ... Mm (Nom.) : 0.9 0.9 0.9 0.9 0.9
Extruded (yes/no) : YES YES YES YES YES
568844884.xls
manish 7 of 10 Sheet5
S. No. Description 5C x 2.5 7C x 2.5 12C x 2.5 19C x 2.5 24C x 2.5
b. Type / Applicable Standard IS:3975 IS:3975 IS:3975 IS:3975 IS:3975
c. Calculated dia. over Inner Sheath (mm) : 10.3 11.4 15.6 18.6 22.2
d. Size (...No x dia) : 24 x 1.4 26 x 1.4 11 x (4 x 0.8) 14 x (4 x 0.8) 16 x (4 x 0.8)
e. D.C. Resistance at 20oC (Ohm/Km) : 4.32 4.0 4.53 3.56 3.12
f. Short circuit current carrying capacity for one 1.8 2.0 1.8 2.2 2.5
second (KA)
12.0 Approximate overall diameter (mm) : 18.0 19.0 23.0 26.0 30.0
13.0 Standard drum length with tolerance (mtrs), furnish : 1000 + 5% 1000 + 5% 1000 + 5% 1000 + 5% 1000 + 5%
14.0 Net Weight of Cable (Kg/Km)
15.0 Continuous Current Rating for Standard IS
Condition laid Direct
a. In Ground at 30 deg.C : 23 20 17 14 13
b. In Duct at 30 deg.C : 19 17 14 12 11
c. In Air (open air) at 40 deg. C : 19 17 14 12 11
16.0 :
a Short Ckt Current for 1 Sec.(KA) (Conductor) : 0.29 0.29 0.29 0.29 0.29
b. Conductor Tempearature allowed for short : 160 160 160 160 160
circuit duty
17.0 Electrical Parameters at maximum operating
temperature
a. i) DC Resistance at 20 deg C (Max.) W/km : 7.41 7.41 7.41 7.41 7.41
ii) AC Resistance at 90 deg C (Approx.) W/km 8.89 8.89 8.89 8.89 8.89
b. Reactance at 50 Hz. W/km (Approx) : 0.106 0.106 0.106 0.106 0.106
c. Impedance at 50 Hz W/km (Approx) : 8.89 8.89 8.89 8.89 8.89
d. Capacitance per phase mf/km (Approx) 0.13 0.13 0.13 0.13 0.13
568844884.xls
manish 8 of 10 Sheet5
S. No. Description 5C x 2.5 7C x 2.5 12C x 2.5 19C x 2.5 24C x 2.5
e. Volume resistivity at rated operating 1 x 1010 at 70 oC 1 x 1010 at 70 oC 1 x 1010 at 70 oC 1 x 1010 at 70 oC 1 x 1010 at 70 oC
temperature W cm (min)
f. Loss Tangent NA NA NA NA NA
g. Partial Discharge value at KV NA NA NA NA NA
h. Charging current at normal operating voltage 26 26 26 26 26
mA/km (at 650 V)
18.0 Recommended minimum bending radius : 12 x overall diameter of the cable
b. Multicore Cable
i. 3 Nos. :
ii. 4 Nos. :
iii. 5 Nos. :
iv. 6 Nos. :
21.0 The Cables shall be tested as specified : IS: 1554 /I/1988 IS: 1554 /I/1988 IS: 1554 /I/1988 IS: 1554 /I/1988 IS: 1554 /I/1988
568844884.xls
manish 9 of 10 Sheet5
FRLS CHARACTERISTICS
a) Oxygen index test on FRLS sheath as per ASTM D-2863 and min. oxygen index
shall be 29 at room temp.
b) Temp.index test on FRLS sheath as per ASTM D-2863 ( by extrapolation method) and
min. temperature index shall be 250 degC at oxygen index of 21.
c) Acid gas generation test on FRLS sheath as per IEC-60754(I) and max. acid gas
generation shall be 20% by weight.
d) Smoke generation test on FRLS sheath as per ASTM D-2843 and max. smoke density
rating shall be 60%