Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Selectivity, Cascading and Coordination Guide www.se.

com

Selectivity table
Upstream: iC60N/H/L curve C
Downstream: iC40, iC40 N curves B, C, D

220-240/380-415 V AC
A Upstream iC60N/H/L
Curve C
In (A) 2 3 4 6 10 13 16 20 35 32 40 50 63

Downstream 1P+N
3P, 3P+N
Selectivity limit (A)
iC40 2 24 32 48 80 100 130 160 300 410 540 910 930
iC40 N 4 48 80 100 130 160 200 260 480 720 760
Curve B 6 80 100 130 160 200 260 320 400 500
10 100 130 160 200 260 320 400 500
13 200 260 320 400 500
16 200 260 320 400 500
20 260 320 400 500
25 320 400 500
32 400 500
40 500
Selectivity limit (A)
iC40 2 24 32 48 80 100 130 160 300 410 540 910 930
iC40 N 4 14 80 100 130 160 200 260 480 720 760
Curve C 6 80 100 130 160 200 260 320 400 500
10 130 160 200 260 320 400 500
13 83 260 320 400 500
16 83 260 320 400 500
20 260 320 400 500
25 124 400 500
32 163 500
40 186
Selectivity limit (A)
iC40 2 25 48 80 100 130 160 300 410 540 910 930
iC40 N 4 80 100 130 160 200 260 480 720 760
Curve D 6 100 130 160 200 260 320 400 500
10 200 260 320 400 500
13 83 165 320 400 500
16 83 165 320 400 500
20 151 400 500
25 176 500
32 255
40

4000 Selectivity limit = 4 kA.


No selectivity.

Note: if you cannot find your combination, refer to the selection table on page A-14

A-30