User Manual: Easylogic™ Pm1130H Conzerv™ Em6438H
User Manual: Easylogic™ Pm1130H Conzerv™ Em6438H
User manual
QGH1336303-03
01/2020
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
EasyLogic™ PM1130H Conzerv™ EM6438H
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that accompany this symbol to avoid possible
injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Electrical equipment should be installed, operated, serviced and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material. A qualified person is one who
has skills and knowledge related to the construction, installation, and operation of
electrical equipment and has received safety training to recognize and avoid the
hazards involved.
QGH1336303-03 3
EasyLogic™ PM1130H Conzerv™ EM6438H
Notices
FCC
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at
his own expense.
The user is cautioned that any changes or modifications not expressly approved
by Schneider Electric could void the user’s authority to operate the equipment.
This digital apparatus complies with CAN ICES-3 (A) /NMB-3(A).
4 QGH1336303-03
EasyLogic™ PM1130H Conzerv™ EM6438H
Table of Contents
Safety precautions ......................................................................................9
Introduction ................................................................................................10
Meter overview.........................................................................................10
Meter features ..........................................................................................10
Application ...............................................................................................10
Prepaid metering ......................................................................................10
Cost management .................................................................................... 11
Network management............................................................................... 11
Main characteristics .................................................................................. 11
Feature summary .....................................................................................12
Measured parameters...............................................................................13
Energy ...............................................................................................13
Demand (PM1130H) ...........................................................................14
Instantaneous.....................................................................................14
Power quality (PM1130H) ....................................................................14
Data display and analysis tools ..................................................................14
Meter configuration ...................................................................................15
Hardware reference ..................................................................................16
Meter types ..............................................................................................16
Supplemental information..........................................................................16
Physical description ..................................................................................16
Front panel...............................................................................................16
Analog load bar ..................................................................................17
Smart keys .........................................................................................18
Panel meter .............................................................................................20
Terminal covers ........................................................................................21
Meter mounting ........................................................................................21
Meter wiring .............................................................................................21
Direct connect voltage limitsMeasuring voltage limit ....................................21
Balanced system considerations................................................................23
Serial communications ..............................................................................24
RS-485 configuration ..........................................................................24
Serial protocols...................................................................................24
RS-485 wiring.....................................................................................24
RS-485 network configuration ..............................................................24
Display and meter setup ..........................................................................26
Display overview ......................................................................................26
Energy pulsing LED ..................................................................................26
Heartbeat / serial communications LED ......................................................26
Meter screen menus .................................................................................26
Viewing parameters ............................................................................27
Display screen menu tree ....................................................................27
Button functions in viewing parameters.................................................28
Setup screen menus .................................................................................28
Setup parameters ...............................................................................29
Button functions in viewing setup parameters........................................30
Button functions in editing setup parameters .........................................31
QGH1336303-03 5
EasyLogic™ PM1130H Conzerv™ EM6438H
6 QGH1336303-03
EasyLogic™ PM1130H Conzerv™ EM6438H
THD% calculations..............................................................................54
Displaying harmonics data ........................................................................54
Maintenance and upgrades .....................................................................55
Maintenance overview ..............................................................................55
Troubleshooting LED indicators .................................................................55
Meter memory ..........................................................................................55
Firmware version, model, and serial number...............................................55
Firmware upgrades...................................................................................56
Firmware upgrade using DLF3000 .............................................................56
Technical assistance.................................................................................57
Verifying accuracy.....................................................................................58
Overview of meter accuracy ......................................................................58
Accuracy test requirements .......................................................................58
Verifying accuracy test ..............................................................................59
Required pulses calculation for accuracy verification testing ........................60
Total power calculation for accuracy verification testing ...............................61
Percentage error calculation for accuracy verification testing .......................61
Accuracy verification test points .................................................................61
Energy pulsing considerations ...................................................................62
VT and CT considerations..........................................................................62
Example calculations ................................................................................63
Typical sources of test errors .....................................................................64
Power and power factor ...........................................................................65
Power and power factor ............................................................................65
Current phase shift from voltage ................................................................65
Real, reactive and apparent power (PQS)...................................................65
Power factor (PF) .....................................................................................66
Power factor sign convention ...............................................................66
Power factor register format.................................................................67
Command interface ..................................................................................69
Command interface ..................................................................................69
Using protected command interface ...........................................................69
Specifications ............................................................................................71
Device specifications ................................................................................71
QGH1336303-03 7
Safety precautions EasyLogic™ PM1130H Conzerv™ EM6438H
Safety precautions
Installation, wiring, testing and service must be performed in accordance with all
local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E in the USA, CSA Z462 or
applicable local standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on the device or equipment.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Follow guidelines in the Wiring section of the related Installation Sheet.
• Treat communications and I/O wiring connected to multiple devices as
hazardous live until determined otherwise.
• Do not exceed the device’s ratings for maximum limits.
• Never short the secondary of a potential/voltage transformer (PT/VT).
• Never open circuit a current transformer (CT).
• Always use grounded external CTs for current inputs.
• Do not use the data from the meter to confirm power is off.
• Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED OPERATION
• Do not use this device for critical control or protection applications where
human or equipment safety relies on the operation of the control circuit.
• Do not use this device if a wrench icon appears on the top corner of the
display screen or if the value under Meter Status is not “OK”.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords/passcodes to help prevent unauthorized access
to device settings and information.
• Disable unused ports/services and default accounts, where possible, to
minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example: least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
QGH1336303-03 9
EasyLogic™ PM1130H Conzerv™ EM6438H Introduction
Introduction
Meter overview
The PM1130H / EM6438H series meters are dual source meters that offer
comprehensive 3-phase electrical instrumentation and load management facilities
in a compact and rugged package.
The PM1130H / EM6438H meters offer value for the demanding needs of your
energy monitoring and cost management applications. Meters in the series range
comply with Class 0.5 (PM1130H & EM6438H) and Class 1.0(EM6438H)
accuracy standards and feature high quality, reliability and affordability in a
compact and easy to install format.
Meter features
The PM1130H / EM6438H meter supports many features, a few of the features
are listed below:
• LED display screen: Intuitive self-guided navigation using four buttons LED
display, with three lines of concurrent values, and load bar that indicates
current loading
• Energy accounting and balancing
• Relay (PM1130H only), alternate source, and RS-485
• THD% for voltage and current, per-phase
• Active, reactive, and apparent energy readings
• Cyber security: The meter enables disabling the RS-485 port through front
panel keys against unauthorized access. This feature can also be used for
toggling between the RTU devices in case of limited availability of nodes in
software system
• Measurement of True PF
You can use the meter as a stand-alone device, but its extensive capabilities are
fully realized when used as part of an energy management system.
For applications, feature details, and the most current and complete specifications
of the PM1130H / EM6438H meters, see the technical datasheet at www.se.com.
Application
Your device can be used for dual source accounting applications that involve two
energy registers, for example Utility vs Genset, Utility vs Solar, Utility vs Wind, or a
combination of any two-power source.
Your device can also be used in installations that require split energy monitoring
for two conditions, for example, running and idle. You can form a relay to control
the load in event of abnormalities such as excessive power consumption or
electric faults.
The meters can be used for secondary billing application in large commercial
complexes or buildings as tenant meters in custom panels, switch boards, switch-
gear, Gen-set panels, non-renewable energy panels, and OEM panel boards.
Prepaid metering
A prepaid metering system enables customers to pay money to the facility
management in advance for a fixed energy value. Prepaid metering is
advantageous to both, the facility management and customers. While the facility
10 QGH1336303-03
Introduction EasyLogic™ PM1130H Conzerv™ EM6438H
management can eliminate meter readings and get advanced payments, the
customers can be freed of penalty through already stored energy consumption as
against unit consumption.
The meter supports prepaid energy metering. Customers can add on energy
credits to the balance register of the meter through communication only. The
meter starts deducting the units based on energy consumption.
The customer can set a minimum value for energy credits consumption, beyond
which the meter raises an alarm. The meter indicates the alarm through front
panel LED, by blinking the top most LED on the load bar. In situations where the
energy credits get exhausted, the meter switches on the relay. Beyond which, if
the energy consumption continues, the meter keeps accumulating negative
balance. When the customers recharge the next time, the negative accumulated
energy will get deducted and only the balance energy will get credited for use.
The facility management can configure any one of the power source, that is Utility,
Alternate Source, or Total (Utility + Alternate Source) based on the billing system.
Cost management
Your device can be used in various cost management applications.
Some of the applications are as mentioned below:
• Measurement of basic electrical parameters in control panels, power
distribution boards, OEM’s, Building management systems, and panel
instrumentation
• Aggregate energy consumption and cost allocation based on consumption
from Utility vs Genset, or between any two power sources, per area, per shift,
and per time within the same facility
Network management
Your device can be used in various network management applications.
Some of the applications are as mentioned below:
• Power quality analysis (THD %)
• Demand measurement
• Measurement of power factor
• Phase angle between the voltage and current
• % unbalance among voltage and current
• Modbus RTU protocol RS-485 port for integration with energy management
system
Main characteristics
• Easy to install: The device can be mounted on a panel using two retainer
clips. This is a compact meter with 49 mm meter depth behind the panel that
can connect up to 480 V + 10% AC L-L without voltage transformers for
installation compliant with measurement category III, and double insulated.
• Easy to operate: The device has intuitive navigation with self-guided menus
and heartbeat LED that indicate normal functioning of your device. It also
conveys the communication status when connected to an RS-485 network.
• LED display: The device has intuitive navigation with self-guided four buttons,
8 segment alpha-numeric LED, and three lines of concurrent values with Kilo
and Mega value indicator.
• Power and energy measurement: The device can measure, display, and
record power or energy from source 1 and source 2 at a time.
QGH1336303-03 11
EasyLogic™ PM1130H Conzerv™ EM6438H Introduction
• Demand measurement: The device can measure peak demand with time of
occurrence in counter and the time remaining to complete a demand cycle. It
can also measure present cycle and last cycle demand values.
• Standard compliance:
◦ Class 1.0 for active energy as per the test limits given in IEC 62053-21
◦ Class 0.5 for active energy as per the test limits given in IEC 62053-22
◦ Class 2.0 for reactive energy as per the test limits given in IEC 62053-23
◦ Tested in accordance with IEC 62052-11 for energy test requirements
◦ EMI / EMC tests as per IEC 61326-1
• CT nominal: 5 A or 1 A nominal current. CT reversal auto correction for
energy consumption.
• Password: Field configurable password to secure set up information and
prevent tampering of integrated values.
• Cyber security: The device provides an option for disabling RS–485 port
through front panel keys to prevent unauthorized access. This feature can
also be used for maintenance and troubleshooting of complex communication
network.
• Display: The device has an auto scale and auto range display capability that
provides 4 digits for Instantaneous parameters and 5+3 digits for energy
parameters.
• Analog load bar: The device’s front panel has a colour-coded analogue load
bar that indicates the percentage of load through 12 LED with the option to
select full scale based on connected load.
• Suppression current: The meter can be configured to disregard the
measurement of induced / auxiliary load current in the circuit (can be set from
5 to 99 mA).
• Favourite page: The device enables user selectable parameters to be set in
favourite page.
• Relay: Form A, 2 terminals mechanical relay for alarm, control, or
annunciation in the event of parameters exceeding or receding the set limit.
The relay can also be activated based on the amount of energy currency pre-
loaded in the concept of pre-paid metering.
• Alternate / dual source power sensor: Smart sensor detect the presence of
alternate power source. 2 pin connector supports multiple generator
paralleling and bus coupler islanding schemes.
• Tamper-resistance: Tamper cover with sealing features for protecting against
tampering with voltage and current terminals.
• Energy counter: Non-resettable energy counter to ensure integrity of energy
readings.
Feature summary
Parameter PM1130H EM6438H
Accuracy Class for Wh Class 0.5 Class 1
Class 0.5
Accuracy Class for VARh 2.0 2.0
± 0.5
Sampling rate per cycle 32 32
Current: ✔ —
• Per-phase and 3 phase average
• Calculated neutral current
Voltage: ✔ —
• V L-N - per-phase and 3 phase average
12 QGH1336303-03
Introduction EasyLogic™ PM1130H Conzerv™ EM6438H
Frequency ✔ —
Power: ✔ ✔
• Active power (kW) - Per-phase and total
• Apparent power (kVA) - Per-phase and total
• Reactive power (kVAR) - Per-phase and total
NOTE: The meter can measure and display only one power
parameter at a time based on the type of power programmed.
Voltage
THD%: ✔ —
• Voltage L-N
• Voltage L-L
• Current per phase
Meter On hours ✔ ✔
Power Interruptions
Phase angle ✔ —
• Per-phase (between Voltage and Current)
Relay ✔ —
Load percentage ✔ ✔
Measured parameters
Energy
The meter provides uni-directional, 2-quadrant, Class 1 / Class 0.5 accurate
energy metering.
The meter stores accumulated value of any one of the selected energy from
active, reactive, or apparent energy in nonvolatile memory when Source 1 = Utility
and Source 2 = Genset or DG.:
• Delivered (Utility): kWh, kVARh, kVAh
• Delivered (Alternate Source): kWh, kVARh, kVAh
• Total (Utility + Alternate Source): kWh, kVARh, kVAh
QGH1336303-03 13
EasyLogic™ PM1130H Conzerv™ EM6438H Introduction
Demand (PM1130H)
The meter provides last, present, and maximum (peak) demand values, and a
timestamp through counters when maximum (peak) demand occurred.
The meter supports standard demand calculation methods, including sliding block,
fixed block, and rolling block.
Peak demand registers can be reset manually (password protected) or through
communication.
Demand measurements include:
• Demand (Total): W, VAR, VA
Instantaneous
The meter provides highly accurate 1-second measurements, average values,
including true RMS, per phase and total for:
• Per-phase and average voltage (line-to-line, line-to-neutral)
• Per-phase and average current, and neutral current (calculated)
• Per-phase and average power factor
• Per-phase and total power (VA, W, VAR)
• System frequency
• Revolutions per minute (RPM)
• Unbalance (voltage, current)
• Load percentage
• Phase angle, per-phase (between voltage and current)
14 QGH1336303-03
Introduction EasyLogic™ PM1130H Conzerv™ EM6438H
Meter configuration
Meter configuration can be performed through the display (if your meter is
equipped with one), the meter webpages or PowerLogic™ ION Setup.
ION Setup is a meter configuration tool that can be downloaded for free at
www.se.com.
See the ION Setup online help or in the ION Setup device configuration guide. To
download a copy, go to www.se.com and search for ION Setup device
configuration guide.
QGH1336303-03 15
EasyLogic™ PM1130H Conzerv™ EM6438H Hardware reference
Hardware reference
Meter types
The PM1130H / EM6438H series is available in one physical form factor.
METSEPM1130HCL05RS Class 0.5 panel mount meter with relay, alternate source, and RS-485, and integrated display.
METSEPM1130HCL05RD
METSEEM6438HCL05RS Class 0.5 panel mount meter with alternate source, RS-485, and integrated display.
METSEEM6438HCL10RS Class 1 panel mount meter with alternate source, RS-485, and integrated display.
METSEPM1130HCL5LVD Class 0.5 panel mount meter with low voltage DC, relay and alternate source, RS-485 and integrated
display
Supplemental information
This document is intended to be used in conjunction with the installation sheet that
ships in the box with your device and accessories.
See your device’s installation sheet for information related to installation.
See your product’s catalog pages at www.se.com for information about your
device, its options and accessories.
You can download updated documentation from www.se.com or contact your local
Schneider Electric representative for the latest information about your product.
Physical description
Front
The front panel has three rows of four digits/characters each, with auto scaling
Kilo (K), Mega (M), and minus (-) indications. The K and M indicators are lit
together to show Giga readings. The load bar graph to the right of the display
gives the indication of consumption in terms of the % ampere load with respect to
the full scale (FS) selected. Four smart keys make navigating through parameters
very quick and intuitive for viewing data and configuring the meter.
Rear
The voltage and current terminal, relay, alternate source, and RS-485
communication port are located on the back of the meter.
Front panel
The front panel contains the following indicators and controls:
• Eight-segment LED display: Three rows of alphanumeric displays, four
digits each, display three RMS parameters simultaneously or one energy
parameter. The displayed readings update every second.
• Analog load bar: Unique indication of % load with respect to the full scale
(FS).
• Indicators: Each row displays Kilo, Mega (Kilo + Mega = Giga) indicators,
and a negative (-) indicator.
• Keys: Four smart keys to scroll through the display pages.
16 QGH1336303-03
Hardware reference EasyLogic™ PM1130H Conzerv™ EM6438H
Between 50% to 80% Green LED get lit to indicate that the load is
acceptable and should not be increased further.
Above 80% Red LED get lit to indicate that the load has
exceeded the sanctioned limit and is dangerous.
Indicators
Kilo, Mega, and negative
K
Mega: When lit, indicates that the reading is in
Mega (106). 10,000 K is shown as 10.00 M and
M 1000 K as 1000 K.
K
Giga: When Kilo and Mega are lit together, the
reading is in Giga (109). 10,000 M is shown as
M 10.00 G and 1000 M as 1000 M.
K
Negative: When lit, indicates a negative
reading.
• VAR (reactive power) displays negative
indication based on quadrant of operation.
• When current is reversed: W (active
power) and PF (power factor) display
negative indication.
QGH1336303-03 17
EasyLogic™ PM1130H Conzerv™ EM6438H Hardware reference
Giga (M+K), Mega (M), Kilo (K), and decimal point scaling – RMS, Current,
Voltage and Energy (Continued)
Up to 9999 G Giga
RMS readings are four digits. Energy readings have eight digits (5+3), including
three fractional digits. The maximum number the meter handles is 9,999 G for
RMS and 99,999.999 G for energy values.
Energy readings of the power meter will overflow when either Delivered (Utility), or
Delivered (Alternate Source), or Total (Utility + Alternate Source) energy reaches
99,999.999 G. This depends on PT (VT) and CT ratios programmed in the meter.
Giga (M+K), Mega (M), Kilo (K), and decimal point scaling – Power
Up to 9999 G Giga
Smart keys
Operating the meter is easy, using the four smart keys to navigate through the
display pages. The display pages expand as you go to the right, much like the
directory or explorer tree displayed on any computer. The display shows where
you are headed.
Left key
• Going back to the main parameter pages.
• Selecting previous digit on the left, under setup.
• Exiting from editing Setup page.
Up key
• Scrolling up through display pages at the same level, within the same function.
• Increasing the value of the selected digit or navigating to the next available selection.
Down key
• Scrolling down through other display pages at the same level, through all functions.
• Decreasing the value of the selected digit or navigating to the next available selection.
18 QGH1336303-03
Hardware reference EasyLogic™ PM1130H Conzerv™ EM6438H
The following steps explain how to navigate from the RMS page to the VLN A F
page and back to RMS page.
1. From the RMS page, press right button. The display shows VLL W PF.
2. Press down button. The display shows VLN A F.
3. To return to RMS, press left bottun. The display shows RMS.
1. From the RMS page, press right button. The display shows W PF.
2. From W PF, press right button. The display shows W 123.
3. Press down button, the display shows PF 123.
4. Press down button, the display shows RPM.
NOTE: Use right button to go forward to the sub-parameter page and use left
button to go backward to the main parameter pages. Use up button and down
button to scroll up and down through the display pages.
Auto scroll
Auto-scroll allows you to monitor a group of display pages sequentially, every
eight seconds, without manual key operation. This is convenient for viewing from a
distance. The meter shows the parameter name for two seconds followed by the
value for eight seconds.
QGH1336303-03 19
EasyLogic™ PM1130H Conzerv™ EM6438H Hardware reference
NOTE: If you press any key during auto scroll, it will change to manual scroll
operation.
Panel meter
LED indicators
The LED indicators alert or inform you of meter activity or status. Refer to the
image below for the various LED indicators the meter provides.
Rear wiring
The meter provides current and voltage inputs along with other wiring options.
Refer to the image below for various wiring options the meter provides.
20 QGH1336303-03
Hardware reference EasyLogic™ PM1130H Conzerv™ EM6438H
Terminal covers
The voltage and current terminal covers help prevent tampering with the meter’s
voltage and current measurement inputs.
The terminal covers enclose the terminals, the conductor fixing screws and a
length of the external conductors and their insulation. These covers are secured
by tamper-resistant meter seals. Ensure you push the cover upwards till you hear
a click to make the cover stand.
These covers are included for meter models where sealable voltage and current
covers are required to protect against tampering of current and voltage input
signals.
Meter mounting
For mounting instructions and safety precautions, see the installation sheet that
was shipped with your device, or download a copy at www.se.com.
Meter wiring
For wiring instructions and safety precautions, see the meter installation sheet that
was shipped with your meter, or download a copy at www.se.com.
Power system Meter setting Symbol Direct connect # of VTs (if required)
description maximum (UL / IEC)
QGH1336303-03 21
EasyLogic™ PM1130H Conzerv™ EM6438H Hardware reference
Power system Meter setting Symbol Direct connect # of VTs (if required)
description maximum (UL / IEC)
Single-phase 3-wire 1P.3L 1PH 3Wire L-L with N ≤ 277 V L-N / 480 V L- 2 VT
line-to-line with L
neutral
3-phase 4-wire open 3P.4L 3PH 4Wire Center- 240 V L-N / 480 V L-L 3 VT
Delta center-tapped Tapped Open Delta
22 QGH1336303-03
Hardware reference EasyLogic™ PM1130H Conzerv™ EM6438H
Power system Meter setting Symbol Direct connect # of VTs (if required)
description maximum (UL / IEC)
3-phase 4-wire Delta 3PH 4Wire Center- 240 V L-N / 480 V L-L 3 VT
center-tapped Tapped Delta
QGH1336303-03 23
EasyLogic™ PM1130H Conzerv™ EM6438H Hardware reference
Serial communications
The meter supports serial communication through the RS-485 port.
In an RS-485 network, there is one master device, typically an Ethernet to RS-485
gateway. It provides the means for RS-485 communications with multiple slave
devices (for example, meters). For applications that require only one dedicated
computer to communicate with the slave devices, an RS-232 to RS-485 converter
can be used as the master device. In master device, recommended response
time-out setting should be minimum 1 second.
RS-485 configuration
Before connecting your device to the RS-485 bus, use the meter’s display, or ION
Setup to configure your meter’s default RS-485 settings.
Your meter has one RS-485 connection.
Your meter must have a unique unit identifier (address) and have the following
settings match the rest of the devices on the RS-485 bus:
• Protocol
• Baud rate
• Parity
You can use a communications converter (USB to RS-485 or RS-232 to RS-485)
to connect to your meter.
Serial protocols
Your meter supports the serial communication protocol on its RS-485 port.
• Modbus RTU
RS-485 wiring
Connect the devices on the RS-485 bus in a point-to-point configuration, with the
(+) and (-) terminals from one device connected to the corresponding (+) and (-)
terminals on the next device.
RS-485 cable
Use a shielded 2 wire or 1 twisted pair RS-485 cable to wire the devices. Use
either shielded 2 wire or 1 twisted pair to connect the (+) and (-) terminals.
The total distance for devices connected on an RS-485 bus should not exceed
900 m (2953 ft).
NOTE: You can connect a maximum of 32 devices to a single RS-485 bus.
RS-485 terminals
- Data minus. This transmits/receives the inverting data signals.
24 QGH1336303-03
Hardware reference EasyLogic™ PM1130H Conzerv™ EM6438H
NOTE: To communicate with the meter using ION Setup, you must set the
serial site and all connected devices in the RS-485 network to the same parity
setting.
For meters that do not have a display, you must first wire and configure each one
separately before connecting these meters to the same RS-485 bus.
QGH1336303-03 25
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
B Retainer clip
D LED indicators
E Menu selection buttons
26 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
With the meter front panel, you can view parameter values; configure parameters;
perform demand resets; perform LED checks; and view meter information. Each
of these functions can be accomplished by pressing the Up, Down, and OK
buttons on the front panel.
These button actions achieve different results according to the mode that the
meter is in:
• Display mode (default): view parameter measurements
• Setup mode: configure a parameter
• Diagnostics mode: verify that the front panel display LEDs are operational,
and view meter information (e.g. meter model, firmware version, etc.)
• Clear mode: reset measurements
• Lock mode: lock or unlock a screen
Viewing parameters
The meter’s display screen and buttons allow you to view the required
parameters.
To view display parameters:
1. Press the Up or Down button to navigate to RMS menu.
2. Press OK.
3. Press the Up or Down button to navigate to the previous or next parameter
page.
QGH1336303-03 27
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
Display mode Down key: To navigate down To view the next parameter
NOTE: Display mode is value.
view-only and displays the
parameter values.
Up key: To navigate up To view the previous parameter
value.
28 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
Setup parameters
QGH1336303-03 29
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
LABL LABL: Phase labeling [123, Abc, rst, pqr, ryb] 123
BAUD BAUD: BPS (Baud rate per [4800, 9600, 19200, 38400] 19200
second)
30 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
QGH1336303-03 31
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
Demand setup
Demand is a measure of average consumption (power) over a fixed programmed
time interval.
You can view the demand values provided in Demand page by navigating through
display parameters. The meter supports editing power demand through Setup
mode.
To view demand setup values, follow these steps:
1. From the Home page, use Up or Down button to navigate to Maintain.
2. Press OK.
3. Use Up or Down button to navigate to Set.
4. Press OK.
5. Enter password. Default password is 0000.
6. Press OK.
7. Select the parameter from the list. Press the Down button to select Pd (power
demand method), Pd.Cy (demand period), Pd.ut (demand update time), or
Pd.P (demand parameter).
8. Press OK.
9. Press the Down button to select required values from the list.
10. Press OK.
11. Press Left button.
12. Select Yes (Press OK button) to save your settings.
Communications setup
After wiring the meter’s serial communications ports, you can configure these
ports so you can connect to the meter remotely and use device configuration
software such as ION Setup to configure the meter.
The setup screen allows you to configure the meter’s RS-485 communications
port so you can use software to access the meter’s data or configure the meter
remotely.
To turn on communication in setup screen, follow these steps:
1. From the Home page, use Up or Down button to navigate to Maintain.
2. Press OK.
3. Use Up or Down button to navigate to Set.
4. Press OK.
5. Enter password. Default password is 0000.
6. Press OK.
7. Use UP or Down button to select Comm (communication).
8. Press OK.
9. Press the Down button to select ON from the list.
10. Press OK.
11. Press Left button.
12. Select Yes (press OK button) to save your settings.
32 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
Baud Rate 4800, 9600, 19200, 38400 Select the speed for data
transmission. The baud rate
must be the same for all
devices in a communications
loop.
Password setup
The meter password can only be configured through the front panel. The factory-
default setting for all passwords is “0000” (zero). Changing the default password
for screens that are password protected prevents unauthorized personnel from
accessing certain screens such as the Setup and Clear screens.
To change the meter password using Setup, follow these steps:
1. From the Home page, use Up or Down button to navigate to Maintain.
2. Press OK.
3. Use Up or Down button to navigate to Set.
4. Press OK.
5. Enter password. Default password is 0000.
6. Press OK.
7. Press the Up button to select PASS (password) parameter.
8. Press OK.
9. Press the Down or Up button to change the digits.
NOTE: Use the Left button to move the cursor to the next digit.
10. Press OK.
11. Press Left button.
12. Select Yes (press OK button) to save your settings.
Password settings
QGH1336303-03 33
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
Lost password
Visit www.se.com for support and assistance with lost passwords or other
technical problems with the meter. Make sure you include your meter’s model,
serial number, and firmware version in your email or have it readily available if
calling Technical Support.
34 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
M
K ! ! ! !
M
K ! ! !
M
K ! ! !
All LEDs on Last edit time
!
! !
!
OS version on Hours
! ! K !
Diag parameters
Screens Description
Diagnostics error code Displays the error codes of the meter for
diagnostics. For example: 0041 is the error code
for Over-Running energy pulse output.
QGH1336303-03 35
EasyLogic™ PM1130H Conzerv™ EM6438H Display and meter setup
Screens Description
ID, BAUD, Parity Displays the unit ID, baud rate, and parity values
of the meter.
Meter On hours Displays the meter on (auxiliary / control power
ON) duration.
Last edit time 1 Displays the last edit time of setup edit.
The meter allows you to clear the values only through communication.
Clear parameters
Parameters Description
Lock / unlock
Lock enables you to set the meter screen to default screen. You can scroll to other
display screens while a screen is locked. Once the manual scrolling is stopped,
the meter displays the default (lock) screen after 4 minutes.
36 QGH1336303-03
Display and meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
NOTE:
You can only lock the display parameters. You cannot enter the Setup or
Reset when a meter screen is locked.
You cannot enter the Setup or Clear when a meter screen is locked.
QGH1336303-03 37
EasyLogic™ PM1130H Conzerv™ EM6438H Security
Security
Security overview
Your Schneider Electric product is equipped with security-enabling features.
These features arrive in a default state and can be configured for your installation
needs. Please note that disabling or modifying settings within the scope of these
individual features can impact the overall security robustness of the device and
ultimately the security posture of your network in either positive or negative ways.
Review the security intent and recommendations for the optimal use of your
device’s security features.
Products are hardened to increase security robustness. This is an ongoing
process consisting of secure development practices, inclusion of security features
and testing at our security test facilities. Following system hardening best
practices is also necessary to help ensure your overall system security.
See the Cybersecurity Hardening Best Practices white paper for suggested best
practices.
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
38 QGH1336303-03
Remote meter setup EasyLogic™ PM1130H Conzerv™ EM6438H
ION setup
Go to www.se.com and search for ION Setup to download a copy of the
installation file.
If you already have an existing installation of ION Setup, it is recommended that
you upgrade to the latest version in order to access new features or
enhancements and properly configure features available on your device.
Refer to the online help to learn how to use ION Setup.
QGH1336303-03 39
EasyLogic™ PM1130H Conzerv™ EM6438H Remote meter setup
Address 1 to 247 Set the address for this device. The address
must be unique for each device in a
communications loop.
Baud rate 4800, 9600, 19200, 38400 Select the speed for data transmission. The
baud rate must be the same for all devices in a
communications loop.
Parity Even, Odd, None Select None if the parity bit is not used. The
parity setting must be the same for all devices in
a communications loop.
40 QGH1336303-03
Viewing meter data EasyLogic™ PM1130H Conzerv™ EM6438H
RMS page
To view RMS parameters:
1. From the Home (RMS) page, use Up or Down button to navigate to RMS.
2. Press OK.
3. Press the Up or Down button to navigate to the next RMS parameter.
4. Press Left button to exit.
PM1130H
EM6438H
QGH1336303-03 41
EasyLogic™ PM1130H Conzerv™ EM6438H Viewing meter data
INTG page
To view INTG parameters:
1. From the Home page, use Up or Down button to navigate to INTG.
2. Press OK.
3. Press the Up or Down button to navigate to the next INTG parameter.
4. Press Left button to exit.
42 QGH1336303-03
Viewing meter data EasyLogic™ PM1130H Conzerv™ EM6438H
NOTE: Based on the selected power type under Demand setup, the DM page
displays either DM W, DM VA, or DM VAR.
QGH1336303-03 43
EasyLogic™ PM1130H Conzerv™ EM6438H Viewing meter data
V% 12, 23, 31 Voltage THD% for Voltage lines 12, 23, and 31
respectively
44 QGH1336303-03
Viewing meter data EasyLogic™ PM1130H Conzerv™ EM6438H
Diag page
To view Diag parameter:
1. From the Home page, use Up or Down button to navigate to Diag.
2. Press OK.
3. Press the Up or Down button to navigate to the next Diag parameter.
4. Press Left button to exit.
M
K ! ! ! !
M
K ! ! !
M
K ! ! !
All LEDs on Last edit time
!
! !
!
OS version on Hours
! ! K !
Tot INTG
Applicable for METSEPM1130HCL5LVD
To view tot INTG parameters:
1. From the Home page, use Up or Down button to navigate to Tot INTG.
2. Press OK.
3. Press the Up or Down button to navigate to the next Tot INTG parameter.
4. Press Left button to exit.
QGH1336303-03 45
EasyLogic™ PM1130H Conzerv™ EM6438H Viewing meter data
46 QGH1336303-03
Viewing meter data EasyLogic™ PM1130H Conzerv™ EM6438H
QGH1336303-03 47
EasyLogic™ PM1130H Conzerv™ EM6438H Relay and Alternate source sense
Relay
Relay is used to trigger an alarm or a secondary system based on a preset
condition in the meter.
The relay is Normally Open (NO) when not triggered. When triggered (operated) it
changes to Normally Closed (NC).
A relay can be triggered depending on source of operation. The supplied source
can be utility, alternate source, or both.
The following parameters are associated to trigger a relay. The relay gets trigger if
the mentioned conditions are met.
Relay parameters
48 QGH1336303-03
Relay and Alternate source sense EasyLogic™ PM1130H Conzerv™ EM6438H
Two different parameters can be set simultaneously for the relay trigger
functionality with separate upper and lower limits for each parameter.
• Parameter associated with Source 1 (or 2)
• Parameter associated with Source 2 (or 1) or both (1 and 2)
For a relay to operate, the power or demand parameter must be same as
configured in the meter. The meter does not allow users to configure any other
parameter apart from the configured power or demand parameters.
NOTE: Configuration is not allowed if both parameters are same.
Only one parameter can be configured, associating it with the source (as per the
system connected). The other parameter must be set to zero (with zero as UL and
zero as LL).
To trigger or restore a relay status, you can manually program a time delay. The
delay can be set between 1-60 seconds. The set time enables the triggering or
restoration of the associated relay during a fault occurrences.
QGH1336303-03 49
EasyLogic™ PM1130H Conzerv™ EM6438H Measurements and calculations
Real-time readings
The meter measures currents and voltages, and reports in real time the RMS
(Root Mean Squared) values for all three phases and neutral.
The voltage and current inputs are continuously monitored at a sampling rate of
64 samples per cycle. This amount of resolution helps enable the meter to provide
reliable measurements and calculated electrical values for various commercial,
buildings and industrial applications.
Energy
The meter provides uni-directional, 2-quadrant, Class 1 / Class 0.5 accurate
energy metering.
The meter stores accumulated value of any one of the selected energy from
active, reactive, or apparent energy in nonvolatile memory when Source 1 = Utility
and Source 2 = Genset or DG.:
• Delivered (Utility): kWh, kVARh, kVAh
• Delivered (Alternate Source): kWh, kVARh, kVAh
• Total (Utility + Alternate Source): kWh, kVARh, kVAh
50 QGH1336303-03
Measurements and calculations EasyLogic™ PM1130H Conzerv™ EM6438H
Power demand
Power demand is a measure of average power consumption over a fixed time
interval.
Only one demand parameter can be set at a given time. You can set it using the
meter’s display, through communication using ION setup, or by using any Modbus
tool that supports FC16.
The list of demand parameters that can be configured are :
• VA demand
• VAR demand
• W demand
Last demand: This demand updates in the NVRAM of the meter at the end of a
demand interval. The present value at the end of the demand interval updates to
last demand.
Present demand: The demand calculated by dividing energy accumulated during
a specified period by length of that period.
Peak demand: Peak Demand is the highest recorded demand value in NVRAM. It
is not dependent on any interval or cycle. Unless there is no value recorded higher
than the current value of the peak demand, the peak demand value will not
update. The meter displays the peak demand occurrence time. The meter takes a
snapshot of meter On hours at which the peak demand occurred.
NOTE: This value gets cleared or reset when demand configuration is
changed to other configuration parameter or when the demand parameter is
reset in the meter.
The meter measures instantaneous consumption and can calculate demand using
various methods.
QGH1336303-03 51
EasyLogic™ PM1130H Conzerv™ EM6438H Measurements and calculations
Type Description
Timed Sliding Block Select an interval from 1 to 60 minutes (in 1-minute increments). If
the interval is between 1 and 15 minutes, the demand calculation
updates every 15 seconds. If the interval is between 16 and 60
minutes, the demand calculation updates every 60 seconds. The
meter displays the demand value for the last completed interval.
Timed Block Select an interval from 1 to 60 minutes (in 1-minute increments). The
meter calculates and updates the demand at the end of each
interval.
Timed Rolling Block Select an interval and a subinterval. The subinterval must divide
evenly into the interval (for example, three 5-minute subintervals for
a 15-minute interval). Demand is updated at the end of each
subinterval. The meter displays the demand value for the last
completed interval.
Demand value is
Calculation updates the average for the
every 15 seconds last completed interval
15-minute interval
Time (sec)
15 30 45 60 . . .
Timed Block
Demand value is
the average for the
Calculation updates at
last completed
the end of the interval
interval
Time
(min)
15 30 45
Time
(min)
15 20 25 30 35 40 45
Peak demand
The meter records the peak (or maximum) values for kWD, kVARD, or kVAD
power (or peak demand).
52 QGH1336303-03
Measurements and calculations EasyLogic™ PM1130H Conzerv™ EM6438H
The peak for each value is the highest average reading since the meter was last
reset. These values are maintained in the meter’s non-volatile memory.
The meter also stores the date and time when the peak demand occurred.
Timer
The meter supports meter on hours and load run hours (only Utility, Alternate
source and Total).
The timer data can be read through register map.
Meter on hours
Meter on hours show how long the meter has been powered up.
QGH1336303-03 53
EasyLogic™ PM1130H Conzerv™ EM6438H Power quality
Power quality
Harmonics overview
This section describes the meter’s power quality features and how to access
power quality data. The meter measures voltage and current harmonics up to the
15th harmonic to calculate Total Harmonic Distortion (THD%).
Harmonics are integer multiples of the fundamental frequency of the power
system. Harmonics information is required for compliance to system power quality
standards such as EN50160 and meter power quality standards such as IEC
61000-4-30.
The meter measures fundamental and higher harmonics relative to the
fundamental frequency. The meter’s power system setting defines which phases
are present and determines how line-to-line or line-to-neutral voltage harmonics
and current harmonics are calculated.
Harmonics are used to identify whether the supplied system power meets required
power quality standards, or if non-linear loads are affecting your power system.
Power system harmonics can cause current flow on the neutral conductor, and
damage to equipment such as increased heating in electric motors. Power
conditioners or harmonic filters can be used to minimize unwanted harmonics.
THD% calculations
THD% is a quick measure of the total distortion present in a waveform and is the
ratio of harmonic content (HC) to the fundamental harmonic (H1).
By default, the meter uses the following equation to calculate THD%:
HC
THD = -------
- x 100%
H1
NOTE:
The LED rows display V1THD%, V2THD%, and V3THD% for VTHD% values, and
V12THD%, V23THD%, V31THD%, and A1THD%, A2THD%, and A3THD% for ITHD%
values.
54 QGH1336303-03
Maintenance and upgrades EasyLogic™ PM1130H Conzerv™ EM6438H
NOTICE
METER DAMAGE
• Do not open the meter case.
• Do not attempt to repair any components of the meter.
Failure to follow these instructions can result in equipment damage.
Do not open the meter. Opening the meter voids the warranty.
Heartbeat / serial Internal hardware problem Perform a hard reset: turn off
communications LED remains control power to the meter,
lit and does not flash ON and then re-apply power. If the
OFF problem persists, contact
Technical Support.
If the problem is not fixed after troubleshooting, contact Technical Support for help
and ensure you have your meter’s firmware version, model and serial number
information available.
Meter memory
The meter stores configuration and logging information in non-volatile memory
and a long-life memory chip.
The meter uses its non-volatile memory (NVRAM) to retain all data and metering
configuration values.
QGH1336303-03 55
EasyLogic™ PM1130H Conzerv™ EM6438H Maintenance and upgrades
Firmware upgrades
There are a number of reasons why you may want to upgrade your meter’s
firmware.
Some of the reasons are mentioned below. It is suggested to keep your meter
firmware upgraded for optimum performance.
• Improve meter performance (e.g., optimize processing speed)
• Enhance existing meter features and functions
• Add new functionality to the meter
• Achieve compliance to new industry standards
56 QGH1336303-03
Maintenance and upgrades EasyLogic™ PM1130H Conzerv™ EM6438H
11. Make sure the connection name, i.e., the one you defined in the previous
step, is still selected. Enter the device address.
12. Select the protocol (e.g., Modbus).
13. Click OK.
14. Click Next.
15. Select the device name from the Download Candidate Devices pane, then
click the right arrow button to move the selection to the Download Target
Devices pane.
16. Select the meter firmware in the Firmware to field.
17. Click Next.
18. Click Health Check to confirm the meter is communicating. The Health
Status shows Passed to indicate successful communications.
19. Click Next.
20. The Firmware Update Group shows the connection name, the firmware
version and status (should be “Queued”). The Group Device List shows the
device or devices being upgraded. Click Download.
NOTE: A warning message displays, “Warning: Relays on PowerLogic™
Metering Devices will be de-energized if selected for download and will
remain in this mode until a successful download is completed. Press OK
to start the download.”
21. Click OK.
• The Firmware Upgrade Group status changes to Active, then updates to
show the current upgrade progress (in percent complete).
• The Group Device List status shows “Entering Download Mode”, then
changes to “Downloading” when the firmware is being downloaded to the
meter. “Estimated Time Remaining” shows the firmware download
progress.
• You can also check the progress on meters display panel. The meter
display shows “Download in progress” and a shows a dynamically
increasing number for “Percent Complete” (up to 100%).
22. When the firmware upgrade is complete, the Firmware Update Group status
shows Complete (Passed). The Group Device List status shows Successful
Download. Click Finished.
23. To exit the download firmware program, click Yes when prompted to quit DLF.
NOTE: A maximum of 6 devices can be upgraded in parallel through DLF.
Technical assistance
Visit www.se.com for support and assistance with lost passwords or other
technical problems with the meter.
Make sure you include your meter’s model, serial number and firmware version in
your email or have it readily available if calling Technical Support.
QGH1336303-03 57
EasyLogic™ PM1130H Conzerv™ EM6438H Verifying accuracy
Verifying accuracy
Overview of meter accuracy
All meters are tested and verified at the factory in accordance with International
Electrotechnical Commission (IEC) and Institute of Electrical and Electronics
Engineers (IEEE) standards.
Your meter typically does not require re-calibration. However, in some installations
a final accuracy verification of the meters is required, especially if the meters will
be used for revenue or billing applications.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Verify the device’s power source meets the specifications for your device’s
power supply.
Failure to follow these instructions will result in death or serious injury.
Control equipment
Control equipment is required for counting and timing the pulse outputs from an
energy pulsing LED.
• Most standard test benches have an arm equipped with optical sensors to
detect LED pulses (the photodiode circuitry converts detected light into a
voltage signal).
• The reference device or energy standard typically has digital inputs that can
detect and count pulses coming from an external source (i.e., the meter’s
pulse output).
NOTE: The optical sensors on the test bench can be disrupted by strong
sources of ambient light (such as camera flashes, florescent tubes, sunlight
reflections, floodlights, etc.). This can cause test errors. Use a hood, if
necessary, to block out ambient light.
Environment
The meter should be tested at the same temperature as the testing equipment.
The ideal temperature is about 23 ºC (73 ºF). Make sure the meter is warmed up
sufficiently before testing.
58 QGH1336303-03
Verifying accuracy EasyLogic™ PM1130H Conzerv™ EM6438H
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E in the USA, CSA Z462 or
applicable local standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on the device or equipment.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Do not exceed the device’s ratings for maximum limits.
• Verify the device’s power source meets the specifications for your device’s
power supply.
Failure to follow these instructions will result in death or serious injury.
1. Turn off all power supplying this device and the equipment in which it is
installed before working on the device or equipment.
2. Use a properly rated voltage sensing device to confirm that all power is off.
QGH1336303-03 59
EasyLogic™ PM1130H Conzerv™ EM6438H Verifying accuracy
3. Connect the test voltage and current source to the reference device or energy
standard. Ensure all voltage inputs to the meter under test are connected in
parallel and all current inputs are connected in series.
A1 A2 A3
V1 V2 V3 VN
+ - + - + -
A1 A2 A3
V1 V2 V3 VN
+ - + - + -
A1 A2 A3
+ - + - + -
V1 V2 V3 VN
4. Connect the control equipment used for counting the standard output pulses
using one of these methods:
Option Description
Energy pulsing LED Align the red light sensor on the standard test bench armature over
the energy pulsing LED.
Pulse output Connect the meter’s pulse output to the standard test bench pulse
counting connections.
60 QGH1336303-03
Verifying accuracy EasyLogic™ PM1130H Conzerv™ EM6438H
QGH1336303-03 61
EasyLogic™ PM1130H Conzerv™ EM6438H Verifying accuracy
Full load 100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at unity power factor or one (1).
Light load 10% of the nominal current, 100% of the nominal voltage and nominal
frequency at unity power factor or one (1).
Inductive load (lagging 100% of the nominal current, 100% of the nominal voltage and nominal
power factor) frequency at 0.50 lagging power factor (current lagging voltage by 60°
phase angle).
Full load 100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at zero power factor (current lagging voltage by 90°
phase angle).
Light load 10% of the nominal current, 100% of the nominal voltage and nominal
frequency at zero power factor (current lagging voltage by 90° phase
angle).
Inductive load (lagging 100% of the nominal current, 100% of the nominal voltage and nominal
power factor) frequency at 0.87 lagging power factor (current lagging voltage by 30°
phase angle).
The pulse rate depends on the voltage, current and PF of the input signal source,
the number of phases, and the VT and CT ratios.
If Ptot is the instantaneous power (in kW) and K is the pulse constant (in pulses
per kWh), then the pulse period is:
3600 1
Pulse period (in seconds) = =
K x Ptot Pulse frequency (Hz)
VT and CT considerations
Total power (Ptot) is derived from the values of the voltage and current inputs at
the secondary side, and takes into account the VT and CT ratios.
The test points are always taken at the secondary side, regardless of whether VTs
or CTs are used.
If VTs and CTs are used, you must include their primary and secondary ratings in
the equation. For example, in a balanced 3-phase Wye system with VTs and CTs:
VTp CTp 1 kW
Ptot = 3 x VLN x xIx x PF x
VTs CTs 1000 W
where Ptot = total power, VTp = VT primary, VTs = VT secondary, CTp = CT
primary, CTs = CT secondary and PF = power factor.
62 QGH1336303-03
Verifying accuracy EasyLogic™ PM1130H Conzerv™ EM6438H
Example calculations
This example calculation shows how to calculate power, pulse constants and
maximum pulse frequency, and how to determine a pulse constant that reduces
the maximum pulse frequency.
A balanced 3-phase Wye system uses 480:120 volt VTs and 120:5 amp CTs. The
signals at the secondary side are 119 volts line-to-neutral and 5.31 amps, with a
power factor of 0.85. The desired pulse output frequency is 20 Hz (20 pulses per
second).
1. Calculate the typical total output power (Ptot):
3. At full load (120% of nominal current = 6 A) and power factor (PF = 1),
calculate the maximum total output power (Pmax):
QGH1336303-03 63
EasyLogic™ PM1130H Conzerv™ EM6438H Verifying accuracy
2. Check the new maximum pulse frequency against the limits for the LED and
pulse outputs:
• 17.1 Hz ≤ LED maximum pulse frequency (35 Hz)
• 17.1 Hz ≤ pulse output maximum frequency (20 Hz)
As expected, changing K to a value below Kmax allows you to use the pulse
output for energy pulsing.
3. Set the new pulse constant (K) on your meter.
64 QGH1336303-03
Power and power factor EasyLogic™ PM1130H Conzerv™ EM6438H
Current and voltage in phase (resistive) Current leads voltage (capacitive) Current lags voltage (inductive)
QGH1336303-03 65
EasyLogic™ PM1130H Conzerv™ EM6438H Power and power factor
+Q
(+kVAR, +kVARh)
Imported/delivered
)
Ap
VA
pa
(
er
re
w
nt
po
po
nt
w
re
er
pa
(V
Ap
A)
Active power (W) Active power (W)
Exported/received Imported/delivered
-P +P
(-kW, -kWh) 180° 0° (+kW, +kWh)
Active power (W) Active power (W)
Exported/received
Exported/received
A)
Ap
(V
p
ar
er
en
w
po
tp
ow
nt
re
er
pa
(V
Ap
A)
Quadrant 3 Quadrant 4
PF lagging PF leading
Power factor sign convention: Power factor sign convention:
IEEE = − IEEE = +
IEC = − IEC = +
270°
-Q
(-kVAR, -kVARh)
Power flow
Positive real power P(+) flows from the power source to the load. Negative real
power P(-) flows from the load to the power source.
An ideal, purely resistive load has no reactive components, so its power factor is
one (PF = 1, or unity power factor). Inductive or capacitive loads introduce a
reactive power (Q) component to the circuit which causes the PF to become
closer to zero.
True PF
The meter supports true power factor values:
• True power factor includes harmonic content.
66 QGH1336303-03
Power and power factor EasyLogic™ PM1130H Conzerv™ EM6438H
• Quadrant 2 and 3: Negative real power (-kW), the PF sign is negative (-).
IEC -1 to +1 format
Quadrant PF Range HMI Representation PF in RS-485 Comm
with sign
(Reg IEC format)
Sample screen
QGH1336303-03 67
EasyLogic™ PM1130H Conzerv™ EM6438H Power and power factor
-0.5 +0.5
Quadrant 2 Quadrant 1
-1 ≤ PF ≤ 0 0 ≤ PF ≤ 1
-1 +1
Quadrant 3 Quadrant 4
-1 ≤ PF ≤ 0 0 ≤ PF ≤ 1
-0.5 +0.5
PF Value 0 to -1 -1 to 0 0 to +1 +1 to 0
0 -1 0 +1 0
Quadrant 3 Quadrant 2 Quadrant 1 Quadrant 4
-2 -1 0 +1 +2
PF register -2 to -1 -1 to 0 0 to +1 +1 to +2
0 0
-0.5 +0.5
Quadrant 2 Quadrant 1
-1 ≤ PF register ≤ 0 0 ≤ PF register ≤ 1
-1 +1
Quadrant 3 Quadrant 4
-2 ≤ PF register ≤ -1 2 ≤ PF register ≤ 1
-1.5 +1.5
-2 +2
The PF value is calculated from the PF register value using the following formulae:
68 QGH1336303-03
Command interface EasyLogic™ PM1130H Conzerv™ EM6438H
Command interface
Command interface
The command interface allows you to configure the power meter by sending
specific commands using Modbus protocol. Reference the online Modbus register
list for meter commands, results, and data types.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection applications where human
or equipment safety relies on the operation of the control circuit.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
QGH1336303-03 69
EasyLogic™ PM1130H Conzerv™ EM6438H Command interface
• If the meter shows a nonzero number, you own the semaphore. Semaphore is
provided once until it is released or has been inactive for approximately 4
minutes. Once you have the semaphore, subsequent reads of the semaphore
register will return zero until you release the semaphore or it times out.
To send a meter command using the protected command interface:
1. Read the semaphore register and record the meter response. This is your
semaphore.
2. Build the packet to be written to the command block.
3. Write the packet as a Modbus block write (enter the command number,
semaphore, and parameters at the same time).
Command 2039
Semaphore 5
Parameters 1
Status 2039
Result 0
Data 1
5. Write the semaphore back to the semaphore register to release it for another
master to use.
70 QGH1336303-03
Specifications EasyLogic™ PM1130H Conzerv™ EM6438H
Specifications
Device specifications
The specifications contained in this section are subject to change without notice.
For installation and wiring information, refer to the meter installation sheet.
Mechanical characteristics
IP degree of protection (IEC 60529-1) Front Display: IP51
Display type 8 segment alpha-numeric LED, 3 rows with 4 digits per row, 1 column of 12 LEDs to indicate
percentage of load connected in system. 4 digits for instantaneous parameters and 5+3 digits for
energy parameters with auto scrolling and auto range
Keypad 4 button
Electrical characteristics
Measurement accuracy: PM1130H
QGH1336303-03 71
EasyLogic™ PM1130H Conzerv™ EM6438H Specifications
Class 0.5*
Voltage inputs
VT primary 100 V L-L to 999 kV L-L maximum, starting voltage depends on the VT ratio
V nominal Up to 277 V L-N / 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy 80-480 V L-L ± 10%, Category III
Impedance ≥ 5 MΩ
Frequency 50 / 60 Hz nominal ± 2 Hz
Current inputs
CT secondary 1 A or 5 A
Impedance 0.3 mΩ
Frequency range 50 / 60 Hz ± 2 Hz
VA burden ≤ 0.1 VA at 5 A, 50 Hz
72 QGH1336303-03
Specifications EasyLogic™ PM1130H Conzerv™ EM6438H
Displays update
Environmental characteristics
Operating temperature -10º to +60º C (+14º ... +140º F)
Pollution degree 2
QGH1336303-03 73
EasyLogic™ PM1130H Conzerv™ EM6438H Specifications
Safety
Communications
RS-485 port Modbus RTU: 2-Wire, 4800, 9600,19200 or 38400 baud
Other specifications
24 V DC at 2A
OFF: 0 to 30 V L-N
DC:
ON: 18 - 60 V DC ± 10%
OFF: 0 to 4 V DC
Protection features Password protected for set-up parameters, energy clearing, and other integrated data
74 QGH1336303-03
Specifications EasyLogic™ PM1130H Conzerv™ EM6438H
Technical publication Printed multi-lingual installation sheet (IS / QSG) supplied with meter (EN, ES, FR, DE, PT, RU,
TR, ZH)
QGH1336303-03 75
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com