T 2.

4/6/EN/1

Active Chilled Beams


Type DID-E
Air discharge in one direction








Gebrüder Trox GmbH Telephone +49 / 28 45 / 2 02-0


Telefax +49 / 28 45 / 2 02-2 65
Heinrich-Trox-Platz e-mail trox@trox.de
D-47504 Neukirchen-Vluyn www.troxtechnik.com
Construction · Material · Dimensions

Description 2
Construction · Material 3
Dimensions 3
Assembly 4
Nomenclature 5
Performance overview – cooling / heating 6
Aerodynamic data 7
Order details 8








Description Caution!
Trox active chilled beams type DID-E discharge the air in one The chilled water flow temperature must be selected such
direction and use a combination of air and water systems for that it never falls below room dewpoint.
fresh air supply as well as room heating and cooling. They are
particularly suitable for use in hotel bedrooms, individual Max. operating pressures:
hospital wards and cellular offices. for 2-pipe and 4-pipe system
They combine the air flow characteristics of sidewall supply 6 bar at 90°
grilles with the energy benefits of load dissipation using water. 7 bar at 20°

The required primary volume flow for fresh air is supplied through Other operating pressures available on request!
a duct into which nozzles are fitted. As a result secondary air is
induced through a horizontal water coil for heating or cooling, or
heating and cooling.

In the mixing section of the type DID-E the induced air is mixed
with the primary air and the total discharged into the room via a
Trox sidewall grille.

2
Construction · Material · Dimensions

Construction Dimensions in mm
Active chilled beams type DID-E consist of the casing with
LN L1 Z
primary air duct and integrated discharge nozzles which can
have different free areas. The primary air connection on site is 900 940 922
via a rear mounted side entry circular spigot. 1200 1240 1222
1500 1540 1522
A coil is fitted inside the casing which can be used either for
heating or cooling (2-pipe system) or for heating and cooling Required ventilation grille dimensions
(4-pipe system).
L x H (mm)
The unit is provided with suspension holes for mounting on site. 925* x 125
Induction and discharge spigots can be supplied as accessories. Discharge grille 1225
1525*
Materials 925* x 225
Casing made of galvanized sheet steel, discharge nozzles made Induction grille 1225
of plastic, coil is made of copper tubes with formed aluminium 1525*
fins. Finish of casing and spigots, if required, powder or dip (* = Intermediate dimensions)
coated black (RAL 9005).
The grilles must be ordered separately,
see leaflet no. T 1.1/1/D/... (free area: min. 50 %).

C View A-A

L1 ~46   
A
75
ø123

122xZ
R1/2”
200

123
B
44

 max.
or 3535
13,5 13,5 
A
50  222xZ
700
726

View C

View B



Water connections right (R)
Water connections left (L)

110 35 105 70


 Discharge nozzles
 Coil (connections R1/2” outside according
to DIN 2999)
 IS – Induction spigot
 AS – Discharge spigot
 Casing
 Primary air connection spigot
 Air vent valve
 Coil heating
Coil cooling

3
Assembly

Active chilled beams type DID-E are ideal for installation into a
formed plaster board bulkhead, as in the vestibule areas of hotel
bedrooms, individual hospital wards and cellular offices.
The assembly is hung from the ceiling slab using metal hangers
or screwed rods locating in the suspension holes in the unit.
All hanging systems must have a Building Authority certificate
of approval.

The plaster bulkhead must have an opening in its base for the
induced air. The induction aperture cover must have at least
50 % free area e.g. perforated plate. Trox can supply an
induction spigot and return air grille as accessories, these are
recommended to be used. The vertical face of the bulkhead
must have a discharge opening. For optimum air supply into the
space Trox discharge spigot and supply air grille should be
used.

View C
ceiling not shown
C Z
L1
A

R1/2”
B
44

600
A
50

View B
4-pipe connection dimensions
(for the 2 pipe-system there are only the two outer connections)

Detail Z
Suspension holes
63

110 35 105 70 Ø 12

18

View A-A

Ceiling
Suspension
~11

of the unit with


threaded rods,
carried out by
122

the customer. Width of the


discharge
Suspended opening
ceiling
Discharge
spigot
Induction spigot
~85 222
Width of the
induction opening

4
Nomenclature
‡WH tWRH
WK tWRK
WH tWVH

Example (for diagrams and tables, see page 6 +7)


‡WK tWVK Hotel double bedroom, 16 m2 (4 x 4 m),
X room height H = 2.7 m, spec. cooling load: 30 W/m2
Requirements:
‡Pr ‡Pr = 65 m3/h tR max = 24°C
Pr
tPr LWA = 25 dB(A) tWVK = 16°C
ges ges = 16 m2 x 30 W/m2 = 480 W tPr = 16°C
‡Zul
H1 selected LN = 900/C nozzle from table
‡Pr = 65 m3/h
H S = 377 : 10 x 8 = 302 W (∆tRWV = -8K instead of -10 K)
Pr = 217 : 10 x 8 = 174 W (∆tPR = -8K instead of -10K)
ƒL; ∆tL ges = S + Pr = 476 W ➔ rather too low
Increase of the water volume from 110 l/h to 140 l/h
S NEW = S OLD x 1.05 (Correction value from table) = 302 x 1.05
1,7
1.7 m S NEW = 317 W ges = 317 + 174 = 491 W ➔ OK, so >480 W
from diagram 1: ∆tW ~2K
from diagram 2: ∆pW = 2.4 kPa
L = X + H1 = 4 m + 2.7 m – 1.7 m = 5 m
from diagram 7: ƒL = 0.24 m/s,
∆tL /∆tZ = 0.2, ∆tL = 0.2 x ∆tZ = 1.6 K

∆tL in K: Temp. diff. between room air tR and core tL at distance L


∆tPr in K: Temp. diff. between room air and primary air
∆tZ in K: Temp. diff. between room air and supply air into space
∆tW in K: Water temperature difference
∆tRWV in K: Temp. diff. between room air and water flow temperature
∆pt in Pa: Primary air pressure drop
∆pW in kPa: Water pressure drop
tR in °C: Room temperature
tWVK in °C: Water flow temperature – cooling
tWRK in °C: Water return temperature – cooling
tWVH in °C: Water flow temperature – heating
tWRH in °C: Water return temperature – heating
tPr in °C: Primary air temperature
WK in W: Water cooling capacity
WH in W: Water heating capacity
ges in W: Total cooling capacity Pr + S
Pr in W: Primary air cooling/heating capacity
S in W: Water side thermal capacity (for cooling S = WK, for heating S = WH)
ªZul in W/m2: Specific cooling capacity
‡WK in l/h: Water volume flow rate – cooling
‡WH in l/h: Water volume flow rate – heating
‡Zul in l/s: Supply air volume flow rate
‡Pr in l/s: Primary air volume flow rate
ƒL in m/s: Time average air velocity at distance L
LWA in dB(A): A-weighted sound power level
L in m: Horizontal plus vertical distance from diffuser, discharge down the wall L = X + H1
X in m: Horizontal distance from diffuser to the wall
H1 in m: Distance ceiling – occupied zone
H in m: Room height or height of installation
LN in m: Nominal length

5
Performance overview – cooling/heating
with 2-pipe and 4-pipe system

Cooling - Correction factors 1 Cooling 2 Cooling


50 l/h 70 90 11
. 8 110
VWK in l/h 50 70 90 140 200 250
10 1500
900 0.59 0.82 0.93 1.05 1.10 1.13 7 9
140 1200
LN 1200 0.59 0.82 0.93 1.05 1.10 1.13 6 8
7

∆pW in kPa
1800 0.59 0.82 0.93 1.05 1.10 1.13 5 900

∆tW in K
200 6
4
LN
250 5
Heating - Correction factors 3 4
‡WK
. 2
3
VWH in l/h 50 70 90 140 200 250
2
900 0.47 0.77 0.91 1.07 1.14 1.17 1
1

LN 1200 0.47 0.77 0.91 1.07 1.14 1.17 0 0


200 300 400 500 600 700 800 900 1000 1100 40 60 80 100 120 140 160 180 200 220 240 260
1800 0.47 0.77 0.91 1.07 1.14 1.17 WK in W ‡WK in l/h

3 Heating 4 Heating
Reference values – Cooling 16
50 l/h 70 90
tWVK = tPr = 16°C 14
110
4 1500
‡WK = 110 l/h
∆tPr = tPr – tR = –10 K 12
140
1200

∆tRWV = tWVK – tR = –10 K 3 900


10

∆pW in kPa
LN
∆tW in K

8 200
Reference values – Heating 2
250
tR = tPr = 22°C (isothermal) 6

‡WH = 110 l/h ‡WH


4
∆tRWV = tWVH – tR = 10 K 1

0 0
200 400 600 800 1000 1200 1400 1600 1800 2000 40 60 80 100 120 140 160 180 200 220 240 260
WH in W ‡WH in l/h

COOLING HEATING
. . . . . .
LN Nozzles V Pr ∆Pt LWA Q Pr QS Q ges ∆tW ∆PW Q S = Q ges ∆tW ∆PW
l/s m3/h Pa dB(A) W W W K kPa W K kPa
6 22 32 <20 72 269 341 2.1 205 1.6
A 12 43 126 <20 145 393 538 3.1 303 2.4
18 65 284 24.8 217 485 702 3.8 378 3.0
12 43 45 <20 145 349 493 2.7 268 2.1
900 B 18 65 102 <20 217 433 650 3.4 1.6 335 2.6 0.7
24 86 181 29.8 289 501 791 3.9 391 3.1
18 65 46 <20 217 377 594 2.9 291 2.3
C 24 86 82 25.8 289 439 728 3.4 341 2.7
30 108 127 33.7 362 492 854 3.8 385 3.0
8 29 34 <20 96 347 443 2.7 266 2.1
A 14 50 103 <20 169 466 634 3.6 362 2.8
20 72 210 26.0 241 557 798 4.4 437 3.4
14 50 37 <20 169 415 584 3.2 321 2.5
1200 B 20 72 75 20.7 241 498 740 3.9 1.9 389 3.0 0.8
26 94 127 30.1 314 568 881 4.4 447 3.5
20 72 34 <20 241 437 678 3.4 339 2.7
C 26 94 57 26.0 314 499 813 3.9 390 3.1
32 115 87 33.4 386 554 940 4.3 435 3.4
10 36 35 <20 121 419 540 3.3 324 2.5
A 16 58 90 <20 193 533 726 4.2 417 3.3
22 79 171 27.3 265 622 887 4.9 491 3.8
16 58 32 <20 193 476 669 3.7 371 2.9
1500 B 22 79 61 22.1 265 558 824 4.4 2.3 439 3.4 1.0
28 101 99 30.7 338 627 965 4.9 496 3.9
22 79 28 <20 265 491 756 3.8 383 3.0
C 28 101 45 26.6 338 554 891 4.3 435 3.4
34 122 66 33.5 410 608 1018 4.8 481 3.8

6
Aerodynamic data

5 LN = 900 mm, Nozzle type A 6 LN = 900 mm, Nozzle type B 7 LN = 900 mm, Nozzle type C

1.00 1.00 1.00

0.70 0.70 0.70

0.50 0.50 ‡P 0.50


r= ‡P
10 r=
ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ
0.40 0.40 0 0.40 12
‡P 80 m 3 0
r= /h 10 m 3
0 /h
0.30 60 0.30 60 0.30 80
m3 50 7
/h 60 0
40 40
0.20 0.20 0.20
30
0.15 20 0.15 0.15
∆tL/∆tZ ∆tL/∆tZ

0.10 0.10 0.10


∆tL/∆tZ

0.05 0.05 0.05


2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16

Distance L in m Distance L in m Distance L in m

8 LN = 1200 mm, Nozzle type A 9 LN = 1200 mm, Nozzle type B 10 LN = 1200 mm, Nozzle type C

1.00 1.00 1.00

0.70 0.70 0.70


‡P
0.50 ‡P 0.50 0.50 r=
r= ‡P 16
ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ

0.40 90 0.40 r= 0.40 0


12 m3
m3 0 12 /h
70
0.30
/h 10 m3
/h 0.30 10 0
50
0.30 0 0
70 80
40 6
0.20 30 0.20 50 0 0.20

0.15 0.15 0.15 ∆tL/∆tZ


∆tL/∆tZ
∆tL/∆tZ
0.10 0.10 0.10

0.05 0.05 0.05


2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16

Distance L in m Distance L in m Distance L in m

11 LN = 1500 mm, Nozzle type A 12 LN = 1500 mm, Nozzle type B 13 LN = 1500 mm, Nozzle type C

1.00 1.00 1.00

0.70 0.70 0.70


‡P ‡P
0.50 0.50 0.50 r=
r= ‡P 18
10
ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ

ƒL in m/s or ∆tL/∆tZ

0.40 0 0.40 r=
0.40 0m
12 1 3
80 m3
/h 0 1460 /h
60
10 m3 12 0
0.30 0.30 0 /h 0.30 10 0
50 8 0
70 0
40 60
0.20 0.20 0.20
∆tL/∆tZ
0.15 0.15 0.15
∆tL/∆tZ

0.10 ∆tL/∆tZ 0.10 0.10

0.05 0.05 0.05


2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16 2 3 4 5 6 8 10 12 14 16

Distance L in m Distance L in m Distance L in m

7
Order details

Specification text
Trox active chilled beams type DID-E discharge air in one Materials
direction and are particularly suitable for use in hotel Casing made of galvanized sheet steel, discharge nozzles
bedrooms, individual hospital wards and cellular offices. made of plastic, coil is made of copper tubes with formed
They consist of the casing with primary air duct and integrated aluminium fins.
discharge nozzles which can have different free areas. The induction and discharge spigots (available as accessories)
The primary air connection on site is via a side entry circular are made of galvanized sheet steel.
spigot. Finish of casing and spigots, if required, powder or dip coated
The coil inside the casing can be used either for heating or black (RAL 9005).
cooling (2-pipe system) or for heating and cooling (4-pipe
system).
The unit is provided with suspension holes for site fixing.

Order code

These codes do not need to be completed for standard products

DID - E - 2 - A - R / 1200 / 0 / 0 / G1

Not used
Coil: 900
Two-pipe 2 IEE 1200
OE TE
Four-pipe 4 P 1500
EE 0 Standard
LN1) EE galvanized
(mm) EE
Nozzle options: A IE EE G1 Casing and
EEO EE
B EE 1) Nominal length of the coil Coil
C EP EZE black
EE RAL 9005
EE
EE
Water connections
IEE EE G2 Casing
right R OE EE black
left L P U RAL 9005
Design changes reserved · All rights reserved © Gebrüder Trox GmbH (3/2005)

Accessories:
DID-E-IS = Induction spigot
DID-E-AS = Discharge spigot
DID-E-IA = Induction and discharge spigots
Ventilation grilles to be ordered separately
see leaflet no. T 1.1/1/D/...

Order example
Make: TROX
Type: DID - E - 2 - A - R / 1200 / G1
Accessory: DID - E-IA / RAL 9005* (Induction and discharge spigots,
powder-coated black)

* without this information, delivery in standard galvanized construction