Servicemanual Samsung 020130109 1
Servicemanual Samsung 020130109 1
AR12FSFTJWQNET AR12FSFTJWQXET
Model Code AR09FSFTKWQNET AR09FSFTKWQXET
AR12FSFTKWQNZE AR12FSFTKWQXZE
AR09FSFTKWQNET AR09FSFTKWQXET
AR12FSFTKWQNZE AR12FSFTKWQXZE
CONTENTS
AR09/12FSFTKWQNET
AR09/12FSFTKWQNZE
AR09/12FSFTKWQXET
AR09/12FSFTKWQXZE
Operating Instructions and Installation
Contents
11. Precautions ........................................................................................................................................ 1-1
1-1 Installing the air conditioner .......................................................................................................... 1-1
1-2 Power supply and circuit breaker .................................................................................................. 1-1
1-3 During operation .............................................................................................................................. 1-1
1-4 Disposing of the unit ....................................................................................................................... 1-2
1-5 Others ................................................................................................................................................. 1-2
Samsung Electronics 1
Operating Instructions and Installation
Contents
9. Refrigerating Cycle Diagram ............................................................................................... 9-1
2 Samsung Electronics
1SFDBVUJPOT
*OTUBMMJOHUIFBJSDPOEJUJPOFS
O 6TFSTTIPVMEOPUJOTUBMMUIFBJSDPOEJUJPOFSCZUIFNTFMWFT
"TLUIFEFBMFSPSBVUIPSJ[FEDPNQBOZUPJOTUBMMUIFBJSDPOEJUJPOFSFYDFQUUIFXJOEPXUZQFBJSDPOEJUJPOFSJO64"BOE$BOBEB
O *GZPVEPOUJOTUBMMUIFBJSDPOEJUJPOFSQSPQFSMZ
JUNBZDBVTFBGJSF
BXBUFSMFBLBHFPSBOFMFDUSJDTIPDL
O :PVNVTUJOTUBMMUIFBJSDPOEJUJPOFSBDDPSEJOHUPUIFOBUJPOBMXJSJOHSFHVMBUJPOTBOETBGFUZSFHVMBUJPOT
O *OTUBMMUIFJOEPPSVOJUIJHIFSUIBONGSPNUIFGMPPSUPBWPJEUIFJOKVSZDBVTFECZUIFPQFSBUJPOPGUIFGBO
FYDFQUUIFXJOEPXUZQFBJSDPOEJUJPOFS
O 5IFNBOVGBDUVSFSJTOPUSFTQPOTJCMFGPSBOZBDDJEFOUTPSJOKVSZDBVTFECZBOJODPSSFDUJOTUBMMBUJPO
O 8IFOJOTUBMMJOHUIFCVJMUJOUZQFBJSDPOEJUJPOFS
LFFQBMMFMFDUSJDDBCMFTTVDIBTUIFQPXFSDBCMFBOEUIFDPOOFDUJPODPSEJOQJQFT
EVDUT
PSDBCMFDIBOOFMTUPQSPUFDUUIFNGSPNUIFEBOHFSPGJNQBDUPSBOZPUIFSJODJEFOUT
1PXFSTVQQMZBOEDJSDVJUCSFBLFS
O *GUIFQPXFSDPSEPGUIFBJSDPOEJUJPOFSJTEBNBHFE
JUNVTUCFSFQMBDFECZUIFNBOVGBDUVSFSPSBRVBMJGJFEQFSTPOJOPSEFSUPBWPJE
BIB[BSE
O 5IFBJSDPOEJUJPOFSNVTUCFQMVHHFEJOUPBOJOEFQFOEFOUDJSDVJUJGBQQMJDBCMFPSDPOOFDUUIFQPXFSDBCMFUPUIFBVYJMJBSZDJSDVJU
CSFBLFS
"OBMMQPMFEJTDPOOFDUJPOGSPNUIFQPXFSTVQQMZNVTUCFJODPSQPSBUFEJOUIFGJYFEXJSJOHXJUIBDPOUBDUPQFOJOHPGNN
O % POPUFYUFOEBOFMFDUSJDDPSEUPUIFBJSDPOEJUJPOFS
O 5IFBJSDPOEJUJPOFSNVTUCFQMVHHFEJOBGUFSZPVDPNQMFUFUIFJOTUBMMBUJPO
%VSJOHPQFSBUJPO
O % POPUSFQBJSUIFBJSDPOEJUJPOFSBUZPVSEJTDSFUJPO
*UJTSFDPNNFOEFEUPDPOUBDUBTFSWJDFDFOUFSEJSFDUMZ
O /FWFSTQJMMBOZLJOEPGMJRVJEPOUIFBJSDPOEJUJPOFS
*GUIJTIBQQFOT
UVSOPGGUIFBJSDPOEJUJPOFSBOEDPOUBDUBOBVUIPSJ[FETFSWJDFDFOUFS
O % POPUJOTFSUBOZUIJOHCFUXFFOUIFBJSGMPXCMBEFTUPQSFWFOUEBNBHFPGUIFJOOFSGBOBOEDPOTFRVFOUJOKVSZ
,FFQDIJMESFOBXBZGSPNUIFBJSDPOEJUJPOFS
O % POPUQMBDFBOZPCTUBDMFTJOGSPOUPGUIFBJSDPOEJUJPOFS
O % POPUTQSBZBOZLJOEPGMJRVJEJOUPUIFJOEPPSVOJU*GUIJTIBQQFOT
UVSOPGGUIFBJSDPOEJUJPOFSBOEDPOUBDUBTFSWJDFDFOUFS
O .BLFTVSFUIBUUIFBJSDPOEJUJPOFSJTXFMMWFOUJMBUFEBUBMMUJNFT
% POPUQMBDFBDMPUIPSPUIFSNBUFSJBMTPWFSJU
O 3FNPWFUIFCBUUFSJFTJGZPVEPOUVTFUIFSFNPUFDPOUSPMGPSBMPOHUJNF *GBQQMJDBCMF
O 6TFUIFSFNPUFDPOUSPMXJUIJONFUFSTGSPNUIFJOEPPSVOJU *GBQQMJDBCMF
4BNTVOH&MFDUSPOJDT
%JTQPTJOHPGUIFVOJU
O #FGPSFUISPXJOHPVUUIFBJSDPOEJUJPOFS
SFNPWFUIFCBUUFSJFTGSPNUIFSFNPUFDPOUSPM
O 8IFOZPVEJTQPTFPGUIFBJSDPOEJUJPOFS
DPOTVMUZPVSEFBMFS*GQJQFTBSFSFNPWFEJODPSSFDUMZ
SFGSJHFSBOUNBZCMPXPVUBOEDBVTF
BJSQPMMVUJPO8IFOJUDPOUBDUTXJUIZPVSTLJO
JUDBODBVTFTLJOJOKVSZ
O 5IFQBDLBHFPGUIFBJSDPOEJUJPOFSTIPVMECFSFDZDMFEPSEJTQPTFEPGQSPQFSMZGPSFOWJSPONFOUBMSFBTPOT
0UIFST
O /FWFSTUPSFPSMPBEUIFBJSDPOEJUJPOFSVQTJEFEPXOPSTJEFXBZTUPQSFWFOUUIFEBNBHFUPUIFDPNQSFTTPS
O :PVOHDIJMESFOPSJOGJSNQFSTPOTTIPVMECFBMXBZTTVQFSWJTFEXIFOUIFZVTFUIFBJSDPOEJUJPOFS
O .BYDVSSFOUJTNFBTVSFEBDDPSEJOHUP*&$TUBOEBSEGPSTBGFUZ
O $VSSFOUJTNFBTVSFEBDDPSEJOHUP*40TUBOEBSEGPSFOFSHZFGGJDJFODZ
4BNTVOH&MFDUSPOJDT
good’sleep Mode
good’ sleep mode can help you sleep quickly and soundly and wake up refreshed.
Catech in Filter
AR09FSFTKWQ/ET AR12FSFTKWQ/ET
8.2Kg 8.2Kg
30.0Kg 30.0Kg
820*286*213 820*286*213
790*545*285 790*545*285
42/56 43/57
51/59 53/62
AR09FSFTKWQ/ZE AR12FSFTKWQ/ZE
8.2Kg 8.2Kg
30.0Kg 30.0Kg
820*286*213 820*286*213
790*545*285 790*545*285
42/51 43/53
56/59 57/62
Indoor
Unit
Manual DB68-03377A
DB67-20011A
DB73-20134A
"MJHONFOUBOE"EKVTUNFOUT
5FTU.PEF
Q)PXUP"QQSPBDI5FTU.PEF
:PVDBOBQQSPBDIUIF5FTU.PEFCZQSFTTJOHUIFPOPGGTXJUDIPG
JOEPPSVOJUGPSTFDPOET
POPGGTXJUDI
QZ5FTU.PEF0QFSBUJPO0QUJPO
"GUFSJOTUBMMJOHUIFBJSDPOEJUJPOFS
DIFDLXIFUIFSFBDITVCPSEJOBUFJTOPSNBMMZPQFSBUFEPSOPUCZPQFSBUJOHUIF5FTU.PEF
t8IFOBOFSSPSPDDVST
EJTQMBZUIF&SSPS.PEF
t0QFSBUJPO.PEF$PPMNPEF0QFSBUFUIFDPPMNPEFCZPQFSBUJOHUIFDPNQSFTTPSCZGPSDFXJUIPVUUIFDPNQSFTTPS0/0''
BDDPSEJOHUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF %POPUGPMMPXUIFBOUJGSFF[FDPOUSPM
t6QEPXOMPVWFS6QEPXOTXJOHNPEF
t*OEPPS'BO)JHI
t#FDBVTFUIF5FTU.PEFPQFSBUFUIFDPPMNPEFCZGPSDFOPUSFMBUFEUPUIFTFUUFNQFSBUVSFJOEPPSUFNQFSBUVSF
DIFDL
XIFUIFSFBDITVCPSEJOBUFJTPQFSBUFEOPSNBMMZPSOPUBGUFSDPNQMFUJOHJOTUBMMBUJPOBOENVTUUVSOPGGUIFQPXFSPGUIF
BJSDPOEJUJPOFS
4BNTVOH&MFDUSPOJDT
AR09/12FSFTKWQ/ET
AR09/12FSFTKWQ/ZE
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Caution:
The terminal is locking type.
So, when you separate terminals,
pull pressing the button.
Button
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
KCaution:
When you separate the connector,
pull pressing the locking button.
4-12
5) Loosen 2 screw(CCW) on the right side of
Cabinet Front. (Use +Screw Driver)
4-13
4-15
1) Release Nut at Fan Boss
2) Release 3 screws st Motor Bracket.
3) Detach Motor Wire from the Assy Control Out.
4-16
8 3
O perating Instructi onsand Instal lati on
7-4
7 4-3
4-4
7-3 4-6
7-3
4-2
4-5
7-2
4-8
4-7
3-3
3
3-4
3-2
3-6
3-5
3-1 3-8
3-7
10
3-7-1 3-7-2
5-2
AR09/12FSFTKWQXET
AR09/12FSFTKWQXZE
28-5
28-4
31
31-1
3
AR09/12FSFTKWQXET Exploded View sand Parts List
AR09/12FSFTKWQXZE
Parts List
9
2203-006104 C708 C-CER,CHIP 1000nF,10%,50V,X7R,TP,3225,2.5T 1
2203-006348 C502 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1
2203-006348 C510 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1
2203-006348 C512 C-CER,CHIP 1000nF,10%,25V,X5R,TP,1608 1
2203-006460 C804 C-CER,CHIP 2200nF,10%,16V,X5R,TP,1608,- 1
DB41-00975A PCB PCB MAIN-IN 11R_RAC_INV_BLDC,FR-1,1,T1.6,120*120,2 1
DB91-01114A IC04 ASSY-MIC 2011'R RAC INV POS Indoor Main Micom 1
S3F4A1H,100P,DC5V,12 MHz,TQFP,16 Bit,16
DB09-00535A IC04-1 IC MICOM 1
Bit,TQFP,QFP,16 Bit,-40~+105,512K
MICOM
DB98-31449A ASSY-LABEL MICOM QFP,64P,WHT,9*9 1
LABEL
10
OUT MAIN PCB(AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE:DB93-10952E)
0506-000175 IC701 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1
0506-000175 IC801 TR-ARRAY 2003,NPN,7,1W,SOP-16,ST,1000 1
SMD,RED,1.6 X 3.2mm,639nm,1.6 X
0601-002423 LED801 LED 1
3.2mm
SMD(REVERSE),YEL,1.6x1.5mm,588nm,
0601-002955 LED803 LED 1
3.2x1.6x1.1mm
SMD(REVERSE),GRN,1.6x1.5mm,3.2x1.
0601-002956 LED501 LED 1
6x1.1mm
SMD(REVERSE),GRN,1.6x1.5mm,3.2x1.
0601-002956 LED802 LED 1
6x1.1mm
0604-001172 IC152 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1
0604-001172 IC155 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1
0604-001172 IC351 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1
0604-001172 IC352 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1
0604-001172 IC505 PHOTO-COUPLER TR,150-300,200mW,SOP,TP 1
74HC86,OR
GATE,SOP,14P,150MIL,QUAD,ST,-
0801-000393 IC302 IC-CMOS LOGIC 1
,2.0/6.0V,0.26V,-
40to+85C,180mW,4.2V,1uA,
ISL81487LIBZ,SO,8P,4.9x3.8
1006-001325 IC301 IC-BUS TRANSCEIVER mm,SINGLE,ST,PLASTIC,5V,- 1
40to+85C,520mW,1,1,1.5/5.0V
TSSOP,TR,14P,5x4.4x1.2mm,100,5.5V
1201-002946 IC451 IC-OP AMP 1
,-40to+85C,63dB,1,1nA,1nA,1.7mV
393,SOP,8P,150MIL,DUAL,36V,CMOS,P
1202-000104 IC611 IC-VOLTAGE COMP. LASTIC,18V,780mW,0to+70C,18V,5mV, 1
250nA,50NA,30
431,TO-92,3P,-
1203-000002 IC157 IC-POSI.ADJUST REG. ,PLASTIC,2.44/2.58V,775MV,0TO+70C 1
,100MA,-,ST,-
KIA7815API,TO-
1203-002735 IC153 IC-POSI.FIXED REG. 220IS,3P,10.3x15.3mm,PLASTIC,14.4 1
/15.6V,2W,-30to+150,1A,ST
SI-8008TMX-TL,TO263-
1203-005797 IC154 IC-DC/DC CONVERTER 5,5P,6.6x6.2x2.3mm,PLASTIC,0.8/24 1
,1.65W,-
TOP253PN,DIP,7P,6.35x9.57mm,PLAST
1203-006089 IC151 IC-PWM CONTROLLER IC,-0.3V/700V,15W,- 1
40Cto+150C,1.37A,ST
1404-001274 NTC151 THERMISTOR-NTC 22ohm,1.4A,3100K,9.5mW/C,-,7.0,- 1
1404-001498 PTC020 THERMISTOR-PTC 40ohm,25%,290Vac,7A,TR 1
1405-000154 VA002 VARISTOR 460Vdc,2500A,17.5x7.5mm,TP 1
1405-000154 VA003 VARISTOR 460Vdc,2500A,17.5x7.5mm,TP 1
1405-000160 VA001 VARISTOR 680V,4500A,17.5x6.5mm,TP 1
1405-000160 VA151 VARISTOR 680V,4500A,17.5x6.5mm,TP 1
2003-000855 R151 R-METAL OXIDE(S) 47Kohm,5%,3W,AA,TP,6x16mm 1
2007-000029 R166 R-CHIP 0ohm,5%,1/8W,TP,2012 1
2007-000043 R054 R-CHIP 1Kohm,1%,1/10W,TP,1608 1
2007-000052 R156 R-CHIP 10Kohm,1%,1/10W,TP,1608 1
2007-000052 R157 R-CHIP 10Kohm,1%,1/10W,TP,1608 1
2007-000066 R155 R-CHIP 20Kohm,1%,1/10W,TP,1608 1
2007-000066 R653 R-CHIP 20Kohm,1%,1/10W,TP,1608 1
2007-000070 R309 R-CHIP 0ohm,5%,1/10W,TP,1608 1
2007-000074 R053 R-CHIP 100ohm,5%,1/10W,TP,1608 1
24
٥ New Function [ Indoor Terminal Block Safety Device ]
2. Thermal Fuse is opened when internal temperature of Terminal Block goes to a certain point
due to Tracking caused by a defective connection of indoor and outdoor units.
- When Thermal Fuse is opened, Main PBA (DC12V) is turned off and the indoor unit does
not operate. (There is no problem with Main PBA in this case)
- In the above case, the change of all-in-one Terminal Block will make Main PBA operate again.
ۆھۊۇڝ ۏۄېھۍۄڞ
ۍۄڼڡ ۀۑۄۏھۀہۀڟ
̰ Wire connecting the indoor unit terminal blocks
1. Terminal press of Ring terminal shall be set facing up before connecting wire.
2. There shall be no empty space between Ring terminal and Screw after Clamp.
If not, there exists a possibility of fire which can be caused by electric heat in the
connecting part.
ྙ ྚ ྛ ྜ ྜྷ ྞ
ྙ,ྚ : Good
ྛ Bad : Ring terminal is connected reversely
ྜ Bad : Not clamped Screw
ྜྷ Bad : In the gap between Ring terminal & Screw
ྞ Bad : Unused Ring Terminal
AR09/12FSFTKWQNET
AR09/12FSFTKWQNZE
AR09/12FSFTKWQXET
AR09/12FSFTKWQXZE
AR09/12FSFTKWQ/ET AR09/12FSFTKWQ/ZE
AR09/12FSFTKWQXET AR09/12FSFTKWQXZE
1
AR09/12FSFTKWQNET
AR09/12FSFTKWQNZE
AR09/12FSFTKWQXET
AR09/12FSFTKWQXZE
Main parts
Room
temperature
sensor
Air intake
indicator
Operation indicator
Power button
Smart Saver
Mode
Less energy usage makes your space
Set one of the 5 operating modes
cool between the temperature range
(see pages 10-11 for instructions).
of 24°C~30°C.
Auto Clean
Turbo Auto clean function – Dry inside of the indoor
Operate in auto fan speed to unit to get rid of odor.
cool quickly.
Quiet Air swing
Reduce noise generated from an indoor
unit during operation. automatically up and down.
Fan
h
h
Temp + -
Increase/Decrease the temperature by 1˚C.
such as Auto/Low/Medium/High.
Set the mode on.
Set
On Timer
Set the timer/ mode.
Set the On Timer on.
Cancel
Cancel the timer/ mode.
Time Up/Time Down
Adjust the time for timer/
mode.
This button doesn't have any function.
5SPVCMFTIPPUJOH
*UFNTUPCFDIFDLFEGJSTU
5IFJOQVUWPMUBHFTIPVMECFSBUJOHWPMUBHFSBOHF
5IFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZJGUIFWPMUBHFJTPVUPGUIJTSBOHF
*TUIFMJOLDBCMFMJOLJOHUIFJOEPPSVOJUBOEUIFPVUEPPSVOJUMJOLFEQSPQFSMZ
5IFJOEPPSVOJUBOEUIFPVUEPPSVOJUTIBMMCFMJOLFECZDBCMFT
$IFDLUIFUFSNJOBMTJGUIFJOEPPSVOJUBOEPVUEPPSVOJUBSFQSPQFSMZMJOLFECZUIFTBNFOVNCFSPGDBCMFT
0UIFSXJTFUIFBJSDPOEJUJPOFSNBZOPUPQFSBUFQSPQFSMZ
8IFOBQSPCMFNPDDVSTEVFUPUIFDPOUFOUTJMMVTUSBUFEJOUIFUBCMFCFMPXJUJTBTZNQUPNOPUSFMBUFEUPUIFNBMGVODUJPOPGUIF
BJSDPOEJUJPOFS
/P 0QFSBUJPOPGBJSDPOEJUJPOFS &YQMBOBUJPO
5IF01&3"5*0/JOEJDBUJPO-&% #-6&
CMJOLTXIFOBQPXFS *UJOEJDBUFTQPXFSJTPO5IF-&%TUPQTCMJOLJOHJGUIFPQFSBUJPO
QMVHPGUIFJOEPPSVOJUJTQMVHHFEJOGPSUIFGJSTUUJNF 0/0''CVUUPOPOUIFSFNPUFDPOUSPMVOJUJTQVTIFE
'BOTQFFETFUUJOHJTOPUBMMPXFEJO%3:
NPEF 5IFTQFFEPGUIFJOEPPSGBOJTTFUUP--JO%3:NPEF
'BOTQFFEJTTFMFDUFEBVUPNBUJDBMMZJO"650NPEF
$PNQSFTTPSTUPQTPQFSBUJPOJOUFSNJUUFOUMZJO%3:
$PNQSFTTPSPQFSBUJPOJTDPOUSPMMFEBVUPNBUJDBMMZJO%3:NPEF
NPEF EFQFOEJOHPOUIFSPPNUFNQFSBUVSFBOEIVNJEJUZ
5JNFS-&% 03"/(&
PGUIFJOEPPSVOJUMJHIUTVQBOEUIF 5JNFSJTCFJOHBDUJWBUFEBOEUIFVOJUJTJOSFBEZNPEF
BJSDPOEJUJPOFSEPFTOPUPQFSBUF 5IFVOJUPQFSBUFTOPSNBMMZJGUIFUJNFSPQFSBUJPOJTDBODFMMFE
5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZJOB$00-NPEFPS 5IFDPNQSFTTPSTUPQTJOUFSNJUUFOUMZPSUIFGBOTQFFEPGUIF
%3:NPEF
BOEGBOTQFFEPGUIFJOEPPSVOJUEFDSFBTFT JOEPPSVOJUEFDSFBTFTUPQSFWFOUJOTJEFPVUTJEFBJSGSP[FO
EFQFOEJOHPOUIFJOTJEFPVUTJEFBJSUFNQFSBUVSF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJGSPPN
5IFDPNQSFTTPSBOEJOEPPSGBOTUPQJOUFSNJUUFOUMZJO)&"5 UFNQFSBUVSFFYDFFETBTFUUJOHUFNQFSBUVSFJOPSEFSUPQSPUFDU
NPEF UIFDPNQSFTTPSGSPNPWFSIFBUFEBJSJOB)&"5NPEF
<*ODBTFPGIFBUQVNQNPEFM> 5IFDPNQSFTTPSPQFSBUFTJOBSFWFSTFDZDMFUPSFNPWF
*OEPPSGBOBOEPVUEPPSGBOTUPQPQFSBUJPOJOUFSNJUUFOUMZ FYUFSJPSJDFJOB)&"5NPEF
BOEJOEPPSGBOBOEPVUEPPS
JOB)&"5NPEF GBOEPOPUPQFSBUFJOUFSNJUUFOUMZGPSXJUIJOPGUIFUPUBM
IFBUFSPQFSBUJPO
4BNTVOH&MFDUSPOJDT
Communicationerror
1.Checklist :
1) Is the cable between the indoor unit and outdoor unit connected correctly?
2) Isn't the power cable and communication cable cross?
2. Troubleshooting procedure
Restart aŌer power oī.
YES
NO
Is the connecƟon of power cable
Correct the wrong cable.
and communicaƟon cable normal?
YES
NO
Is the power is normal?
Exchange the PBA of no power unit
(check the LED Lamp)
YES
NO
Is the communicaƟon error Terminate the service.
occurred again?
YES
12-3
Indoor temperature sensor error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is the sensor Sensor resistance value : 20ć - 12.09kohm
NO
resistance value#1-#2 10kohm±3% at the room
30ć - 8.31kohm
temperature
35ć - 6.94kohm
of 25ć
40ć - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
1.Remove the temprature sensor and check the resistace VHWSRZHURQDQGFKHFNWKHYROWDJHRIWKH&13,13,1
sensor resistance value as follow: WKHYROWDJHLVEHWZHHQ9DQG9
20ćkohm
30ćkohm
35ćkohm
40ćkohm
12-4
Indoor Eva-in temperature sensor error
1.Checklist :
1) Is the indoor units temperature sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
Sensor Replace
Is sensor resistance NO Sensor resistance value : 20ć - 12.09kohm
the value #3-#4 10kohm±3% at the room 30ć - 8.31kohm
temperature
35ć - 6.94kohm
of 25ć
40ć - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the indoor PBA
NO
YES
1.Remove the temprature sensor and check the resistace 6HWSRZHURQDQGFKHFNWKHYROWDJHRIWKH&13,13,1
12-5
When the Up/Down louver motor does not operate (Initial Diagnosis) (Not displayed)
1.Checklist :
1) Is the input power voltage normal?
2) Is the Up/Down louver motor properly connected with the connector? (CN61)
2. Troubleshooting procedure
Unplug the power cord and plug it aŌer 30seconds
later.
YES
NO
Is the connected louver wire? Connect the wire PBA to louver motor
YES
NO
YES
12-6
When the remote control is not receiving
1.Checklist :
1) Check if the connector was normally assembled.
2) Check the battery in remote control
3) All the lights out and check again : Change electronic typed to a fluorescent
4) Put the set in operation and check the voltage of display PBA
5) Replace the display PBA
12-7
Indoor fan motor speed detecting error (AC fan)
1.Checklist :
1) Is the indoor units fan motor properly connected with the connector(CN72)?
2) Is the AC voltage correct?
3) Is the HALL IC(feedback sensing) in indoor fan motor properly connected with the connector(CN44)?
4) Is the running capacitor(CR71) properly connected with PBA?
2. Troubleshooting procedure
AŌer unplugging out the power cord should be
reconnected with in 5 seconds
YES
YES
YES
NO
Is the supply
+ voltage of- the fanvoltage PBA should be
PBA is out of order
motor suĸcient? replaced
1.Set power on,check the voltage of SS71 and 2.Set power on,and check the voltage of the CN72(PIN1,PIN5)
12-8
Outdoor temperature sensor error
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
connected correctly in accordance ReconnecƩ he sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Is the sensor Sensor resistance value : 20 - 12.09kohm
NO
resistance value #1-#2 10kohm±3% aƩ he room 30 - 8.31kohm
temperature
35 - 6.94kohm
of 25
40 - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
YES
Sensor Replace
Is the sensor resistance NO Sensor resistance value : 20 - 12.09kohm
value #1-#2 10kohm±3% aƩ he room 30 - 8.31kohm
temperature of 25 35 - 6.94kohm
40 - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
12-8
Outdoor Coil temperature sensor error
YES
Sensor Replace
Is the sensor Sensor resistance value : 20 - 12.09kohm
resistance value #5-#6 10kohm±3% aƩ he room NO
30 - 8.31kohm
temperature
35 - 6.94kohm
of 25
40 - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
YES
Sensor Replace
Is the sensor resistance NO Sensor resistance value : 20 - 12.09kohm
value #3-#4 (CN501) 10kohm±3% aƩ he room 30 - 8.31kohm
temperature of 25 35 - 6.94kohm
40 - 5.83kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
1.Is the sensor resistance value #5-#6 Below 0.5V or Over 4.5V?
12-9
Outdoor Discharge temperature sensor error
1.Checklist :
1) Is the sensor connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull-up correct?
Is the sensor connector(CN251) NO
connected correctly in accordance ReconnecƩ he sensor connector.
with a color(BLU,6PIN)?
YES
Sensor Replace
Is the sensor Sensor resistance value : 20 - 242kohm
NO
resistance value #3-#4 200kohm±3% aƩ he room 30 - 166ohm
temperature
35 - 138ohm
of 25
40 - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO
YES
YES
Sensor Replace
Is the sensor Sensor resistance value : 20 - 242kohm
NO
resistance value #3-#4 200kohm±3% aƩ he room
30 - 166ohm
temperature
35 - 138ohm
of 25
40 - 115kohm
YES
YES
Below 0.5V or Over 4.5V? Exchange the Outdoor PBA
NO 1.Is the sensor resistance value #5-#6 Below 0.5V or Over 4.5V?
10kohm±3% at the room temperature of 25
YES
12-10
Outdoor Discharge over temperature error
1.Checklist :
1) Check the discharge temperature in the outdoor unit
2) Check the compressor locking or gas leak
3) Download the EEPROM data
2. Troubleshooting procedure
Restart a er power o .
a er 30min ~ 1Hr
YES
NO
Is the discharge over temperature
sensor error appeared again? Terminate the service
YES
NO
Is the discharge over temperature
Terminate the service
sensor error appeared again?
YES
12-11
Outdoor Fan motor error
1.Checklist :
1) Are the input power voltage and the power connection correct?
2) Is the motor wire connected to the outdoor PBA correctly?
3) Is there no assembly error or none-assembly in the terminal of motor wire connector?
4) Is there no obstacle at the surrounding of motor and propeller?
2. Troubleshooting procedure
Restart a er power o .
YES
Reassemble the fan wire and inpuƩ he power again Is there short among each pin YES Exchange the Fan
#1~#6 motor
NO Terminate the NO
Is the fan error appeared again?
service
YES
NO
Is the voltage of CN901 #1-#3 over Follow the check procedure of outdoor unit power
250Vdc supply error check
YES
YES
250Vdc?
12-12
Compressor starting error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart aŌer power oī.
NO
Is the restart error occurred again? Terminate the service
YES
NO
Is the connecƟon of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-13
Compressor wire missing error/rotation error
1.Checklist :
1) Is the connection of cable for the compressor?
2) Is the compressor wire is connected clockwise? U(RED)-V(BLU)-W(YEL)
3) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart aŌer power oī.
NO
Is the restart error occurred again? Terminate the service
YES
YES
NO
Is the restart error occurred again? Terminate the service
YES
YES
Is the compressor body and
Exchange the Outdoor PBA
interphase resistance insulated?
NO
12-14
O.C(Over Current) error
1.Checklist :
1) Is the IPM Shunt(A*V18***:R451,R452,R453,A*V24***:R413,R414,R415) resistance value correct? Check the resistor is opened
2) Is the condition of surrounding temperature abnormal overload?
3) Is there any problem as like the temperature sensor separation or measurement value error?
4) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart aŌer power oī.
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connecƟon of compressor
wire is normal? Connect the comp wire normally
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
YES
NO
12-15
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE )
YES
Restart a er power o .
on (cooling mode or hea ng mode)
YES
YES
NO
Is the reactor insula on damaged? Exchange the Outdoor PBA
YES
1.Is the DC_link voltage (CE101 or CE001) is normal in operation mode? 2.Is the DC_link sensing voltage(R104 or R004) is normal in operation mode?
12-1
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE
YES
Restart a er power o .
YES
YES
Restart a er power o .
on (cooling mode or hea ng mode)
YES
Is the DC_link NO
sensing voltage(R104or R004) is normal in opera on mode? Exchange the Outdoor PBA
Normal range (0.2Vdc~2.8Vdc)
YES
NO
Is the reactor insula on damaged? Exchange the Outdoor PBA
YES 2.Is the DC_link voltage (CE101 or 3.Is the DC_link sensing voltage(R104
1.Is the the input voltage is nomal?
Normal range(180Vac ~ 270Vac) CE001) is normal in operation mode?
Exchange the Reactor Normal range(280Vdc~320Vdc) Normal range(280Vdc~320Vdc)
,BWULS HUURU 3)& RYHU FXUUHQW
&KHFNOLVW
,V WKH 3)& 6KXQWUHVLVWDQFH YDOXH FRUUHFW" &KHFN WKH UHVLVWRU LV RSHQHG˛
,V WKH FRQGLWLRQ RI VXUURXQGLQJ WHPSHUDWXUH DEQRUPDO RYHUORDG"
,V WKHUH DQ\ SUREOHP DV OLNH WKH WHPSHUDWXUH VHQVRU VHSDUDWLRQ RU PHDVXUHPHQW YDOXH HUURU"
,V WKH LQWHUSKDVH UHVLVWDQFH RI FRPSUHVVRU QRUPDO"
7URXEOHVKRRWLQJ SURFHGXUH
Restart a er power o .
YES
Is the I_trip error NO Terminate the
YES occurred again? service
YES
YES
12-1
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE value
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE)?
Restart a er power o .
Is the PFC shunt and IPM shunt NO Exchange the Outdoor PBA
resistance value correct?
YES
YES
12-
Heatsink sensor error/Heatsink over heat
1.Checklist :
1) Are there screws assembly in PBA-heatsink?
2) Is the gap PBA-heatsink
3) Is the fan operation normal?
4) Is the cover assembly in conrol-box normal?
2. Troubleshooting procedure
Restart aŌer power oī.
NO
Are there screws in PBA-heatsink?
Fastening the screw
(4 screws)
YES
NO
Check the fan connecƟon
Is the fan operaƟon normal?
Change the Fan motor
YES
12-20
AR09/12FSFTKWQ*ET,AR09/12FSFTKWQ*ZE
Restart a er power o .
NO
Is the O.C error occurred? Terminate the service
YES
NO
Is the connec on of compressor
wire is normal?
YES
NO
Is the O.C error occurred again? Terminate the service
YES
YES
YES Is the O.C error NO Terminate the
occurred again? service
Is the posi NO
on or exchange the sensor
sensor and sensing value normal?
YES
NO
12-2
AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE)?
YES
12-2
AC zero cross signal error
1.Checklist :
1) Check the power condition at customer's house (Is there any power noise?)
2) Have been there power failure?
2. Troubleshooting procedure
Restart aŌer power oī
YES
12-23
Operation condition secession error
1.Checklist :
1) Check the temperature around the outdoor unit.
2. Troubleshooting procedure
YES
YES
12-24
&DSDFLW\ PLVV PDWFK HUURU
&KHFNOLVW
&KHFN WKH %WX EHWZHHQ LQGRRU DQG RXWGRRU XQLW
&KHFN WKH LQGRRU XQLW RSWLRQ DQG RXWGRRU XQLW ((3520 GDWD
7URXEOHVKRRWLQJ SURFHGXUH
Is the rated Btu between indoor NO Exchange the one o hem according to the exact
unit and outdoor unit? model spec
YES
YES
YES
12-2
*DV OHDN HUURU
YES
Restart a er power o
a er 20minutes later
YES
YES
YES
YES
YES
Restart a er power o .
YES
YES
YES
1.Is the the input voltage is nomal? 2.Is the DC_link voltage (CE101 or 3.Is the DC_link sensing voltage(R104
YES
Normal range(180Vac ~ 270Vac) CE001) is normal in operation mode? or R004) is normal in operaon mode?
Normal range(280Vdc~320Vdc) Normal range(280Vdc~320Vdc)
Exchange the PBA
3UHLQVSHFWLRQ1RWLFHV
&KHFNLI\RXSXOOHGRXWWKH$&SRZHUSOXJZKHQ\RXHOLPLQDWHWKH3&%RUIURQWSDQHO
'RQ
WKROGWKH3&%VLGHQRWLPSRVHH[FHVVLYHIRUFHRQLWWRHOLPLQDWHWKH3&%
'RQÿWSXOOWKHOHDGZLUHEXWKROGWKHZKROHKRXVLQJWRFRQQHFWRUGLVFRQQHFWDFRQQHFWRUWRWKH3&%
,QFDVHRIRXWGRRU3&%GLVDVVHPEO\FKHFNILUVWWKHFRPSOHWHGLVFKDUJHRIFRQGHQVHUDIWHUPLQXWHSRZHURII
,QVSHFWLRQSURFHGXUH
&KHFNFRQQHFWRUFRQQHFWLRQDQGSHHOLQJRI3&%RUEURQ]HFRDWLQJSDWWHUQZKHQ\RXWKLQNWKH3&%LVEURNHQ
7KH3&%LVFRPSRVHGRISDUWV
ƽ,QGRRU0DLQSDUW0,&20DQGVXUURXQGLQJFLUFXLWUHOD\IDQPRWRUVHQVLQJDQGGULYLQJFLUFXLWWHPSHUDWXUHVHQVLQJFLUFXLW
SRZHUFLUFXLWRI6036EX]]HUFLUFXLW&RPPXQLFDWLRQFLUFXLW
ƽ'LVSOD\SDUW/('ODPS6ZLWFK5HPRWHFRQWUROPRGXOH
ƽ2XWGRRU0DLQSDUW0,&20DQGVXUURXQGFLUFXLWIDQPRWRUVHQVLQJDQGGULYLQJFLUFXLWFRPSUHVVRUGULYLQJFLUFXLW
SRZHUFLUFXLWRI60363)&FRQWUROFLUFXLWZD\FLUFXLWFRPPXQLFDWLRQFLUFXLW
237,21((9FRQWUROFLUFXLWWHPSHUDWXUHVHQVLQJFLUFXLW
,QGRRUGHWDLOHGLQVSHFWLRQSURFHGXUH
1R SURFHGXUH ,QVSHFWLRQ0HWKRG &DXVH
3OXJRXWDQGSXOOWKH
2YHUFXUUHQW
3&%RXWRIWKHFRQWURO ,VVWIXVHGLVFRQQHFWHG"
,QGRRU)DQPRWRUVKRUW
ER[ ,VQGIXVHGLVFRQQHFWHG"
$&SDUWDQGSDWWHUQVKRUWRI,QGRRU3%$
&KHFNWKH3&%IXVH
&KHFNWKHSRZHUYROWDJH
6XSSO\SRZHU ,VWKH%'LQSXWYROWDJH 3RZHUFRUGLVIDXOW)XVHRSHQ:URQJ3RZHU
,IWKHRSHUDWLQJODPS 9DFa9DF" FDEOH:LULQJ$&SDUWLVIDXOW\
WZLQNOHVDWWKLVWLPH ,VWKHYROWDJHEHWZHHQERWK
6ZLWFKLQJ7UDQVRI3RZHUFLUFXLWLVIDXOW\
WKHDERYHaKDYHQR WHUPLQDORI,&SLQ9GF"
UHODWLRQ ,VWKHYROWDJHEHWZHHQERWK
3RZHUFLUFXLWLVIDXOW\/RDGVKRUW
WHUPLQDORI,&SLQ9GF"
,VWKHYROWDJHRYHU$&9EHLQJ
LPSRVHGRQWHUPLQDORIIDQPRWRU )DQPRWRURIWKHLQGRRULVIDXOW\
3UHVVWKH212))EXWWRQ FRQQHFWRU&1"
)DQVSHHGKLJK 7KHIDQPRWRURIWKHLQGRRUXQLW
&RQWLQXRXV2SHUDWLRQ GRHVQ
WUXQ )DQPRWRUFRQQHFWRU&1LVIDXOW\
7KHSRZHUYROWDJHEHWZHHQWHUPLQDO
3%$LVIDXOW\
RIWKHFRQQHFWRU&1LV9
12-33
(AR09/12FSFTKWQXET,AR09/12FSFTKWQXZE)
12-33
4
01230
AR09/12FSFTKWQXET
AR09/12FSFTKWQXZE
VW QG UG WK WK WK WK WK WK WK WK WK WK WK
SURMHFW &DSDFLW\ 6HOO<HDU )HDWXUH 6HULHV &RORU 8QLW ([SRUW
$ 5 ) + $ ' $ : . 1; ( 8
<HDU )
0LOG%OXH 'HFR 8 4
0$/',9(6 8523()0&$ 3+
<HDU *
%25$&$< 6702'(/ 7$
<HDU -
%25$&$< ,QGLD67)67 7'
; 2XWGRRUXQLW
%25$&$< ,QGLD63,67 7(
)HDWXUH %25$&$< &,6)0&5D 7*
$UHD
%25$&$< &,6)0&5 7+
(8 81,7('.,1*'20
,19(57(5+3 6 (( 6:('(1
%25$&$< 8523($ 7-
,19(57(5&2 9 %25$&$< 8523()0&$ 7/ (7 ,7$/<
0$; 6702'(/ 8$ =( &=(&+2
+35D 4
0$; ,QGRQHVLD/2::$7767 8%
121,19(57(5&25D 5 0$; 60$5767 8&
9 HUVLRQ
121,19(57(5+35 3 0$; &,6)0&5 8'
$ . 66(&
0$; 8523($ 8(
121,19(57(5&25 & /6 76(
0$; 8523()0&$ 8*
+($7(5+3 : )0&67' 6702'(/63,,1&/8'( 6$
)0&67' 63,(;&(37 6%
+($7(5&2 7
9,9$&( 6702'(/ 9$
-81*)5$8350 6702'(/ <$
)HDWXUH
zwp z
uGzwp m
14-2 Low Refrigerant Pressure Distribution
Note : Please measure the refrigerant pressure after the air conditioner operates on testing cooling mode during more than
10 minutes.
Outdoor Temperature[ ]
Q1PXFS)FBU
8 DBMT LDBMI #UVI )1 LH NT *C NT
4BNTVOH&MFDUSPOJDT
2"GPS/POUSPVCMF
2 5IFDPPMJOHJTXFBL
" 8
IFOJUJTIPUPVUTJEF
JUTDPPMJOHDBQBDJUZEFDSFBTFTEVFUPUIFJODSFBTFPGUIFBNCJFOUUFNQFSBUVSF8IFO
UIFEVTUGJMUFSHFUTCMPDLFEPSXBSNPVUTJEFBJSHFUTJO
UIFDPPMJOHDBQBDJUZXJMMEFDSFBTF4P
NBLFTVSFUP
DMFBOUIFEVTUGJMUFSGSFRVFOUMZ
QSFWFOUIFBUMPTTCZDMPTJOHUIFEPPSTBOEJOTVMBUFUIFDPPMJOHBSFBCZVTJOH
DVSUBJOT
CMJOET
TIBEFTPSXJOEPXUJOUJOH
2 5IFDPPMJOHJTHPPEHFOFSBMMZ#VU JUHFUTXFBLXIFOJUJTDPOTJEFSBCMZIPU
2 *UGBJMTUPEPDPPMJOH
" 8
IFOUIFBJSDPOEJUJPOFSJTTFUUP7FOUJMBUJPOPSUIFEFTJSFEUFNQFSBUVSFJTTFUIJHIFSUIBOUIF
DVSSFOUUFNQFSBUVSF
JUGBJMTUPEPDPPMJOH*OUIJTDBTF
TFMFDU$PPMJOHPSTFUUIFEFTJSFEUFNQFSBUVSFMPXFS
2 *UGMPPETUIFGMPPS
2 8BUFSESJQTBUUIFESBJODPOOFDUJPO TFSWJDFWBMWF
PGUIFPVUEPPSVOJU
" 8
IFOBHMBTTCPUUMFJTUBLFOPVUPGUIFSFGSJHFSBUPS
NPJTUVSFHFUTDPOEFOTFEPOJUTTVSGBDFEVFUPUIF
UFNQFSBUVSFEJGGFSFODFT5IFTBNFQSJODJQMFBQQMJFTUPUIFBJSDPOEJUJPOFS8IFODPMESFGSJHFSBOUHPFT
UISPVHIUIFDPQQFSUVCF
NPJTUVSFHFUTDPOEFOTFEPOUIFTVSGBDFPGUIFUVCFBOEUIFDPOOFDUJPOBSFBT
-FBLBHF 5PQSFWFOUUIFXBUFSDPOEFOTBUJPO
UIFQJQFTBSFJOTVMBUFE#VU
UIFDPOOFDUJPOBSFBTPGUIFPVUEPPSVOJUBSF
OPUJOTVMBUFEGPSUIFQVSQPTFPGNBJOUFOBODFPSSFQBJS
BOEXBUFSHFUTDPOEFOTFEEVFUPUIFUFNQFSBUVSF
EJGGFSFODFTBOEESJQTEPXO(FOFSBMMZ
JUFWBQPSBUFTSJHIUBXBZ#VU
XIFOJUESJQTNVDIEVSJOHNVHHZEBZT
QVUBXBUFSQBOPOUIFGMPPS
2 *UMFBLTFWFOUIPVHIBESBJOQVNQJTVTFE
" * UPDDVSTXIFOUIFESBJOQVNQJTQMVHHFEPVUPSJUJTPVUPGPSEFS$IFDLUIFQPXFSPGUIFESBJOQVNQBOE
UIFQPTJUJPOPGUIFESBJOIPTF
BOEXIFOUIFQVNQJTGBVMUZ
DPOUBDUUIFESBJOQVNQNBOVGBDUVSFS4BNTVOH
&MFDUSPOJDTEPOPUNBOVGBDUVSFESBJOQVNQT4P
XFBSFOPUBCMFUPDPSSFDUUIFESBJOQVNQQSPCMFNT
2 8IFOFWFSUIFBJSDPOEJUJPOFSJTUVSOFEPO JUJSSJUBUFTNZFZFTBOEHJWFTNFBIFBEBDIF
" 5 IFSFBSFOPDPNQPOFOUTJOUIFBJSDPOEJUJPOFSJSSJUBUJOHUIFFZFTBOETFOEJOHPVUDIFNJDBMTNFMMT
#VU
XIFOUIFBJSDPOEJUJPOFSJTUVSOFEPO
PUIFSTNFMMTPVSDFTBSFTVDLFEJOUPUIFBJSDPOEJUJPOFSBOE
4NFMMT HFUPVUPGJU4P
GJOEBOESPPUPVUUIFTNFMMTPVSDFT(FOFSBMMZ
JUPDDVSTBUBJOUFSJPSSFOPWBUFEQMBDF
B
QIBSNBDZ
BHBTPMJOFIBOEMJOHQMBDF
BUJSFTIPQ
BTFDPOEIBOECPPLTIPQPSBOFMFDUSPOJDDPNQPOFOU
IBOEMJOHQMBDFXIFOJUTDIFNJDBMPSNVTUZTNFMMTBSFTVDLFEJOBOETFOUPVU
JUDBOCFNJTMFEUIBUUIFBJS
DPOEJUJPOFSHFOFSBUFTUIFN4P
GJOEBOESPPUPVUUIFQSPCMFNPSSFGSFTIUIFSPPNGSFRVFOUMZ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
2 8IPJOTUBMMTUIFBJSDPOEJUJPOFS 3FMPDBUJPO3FJOTUBMMBUJPO
" 8
IFOSFMPDBUJOHPSSFJOTUBMMJOHUIFBJSDPOEJUJPOFS
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF
$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUBOEIBWFUIFNUPEPUIFKPC *GOPU
JUDPVMEDBVTFQFSTPOBMJOKVSZPS
QSPEVDUEBNBHF
5IFDPTUGPSUIFSFMPDBUJPOSFJOTUBMMBUJPOPGUIFBJSDPOEJUJPOFSJTTVCKFDUUPUIFDVTUPNFShTFYQFOTF
5IFSFJTBDPTUUBCMF#VU
PVSTFSWJDFFOHJOFFSOFFETUPWJTJUUPUPUBMVQUIFDPTUDPSSFDUMZ
8IFOZPVNPWFJO
NBLFTVSFUPDPOUBDU4BNTVOH&MFDUSPOJDT4FSWJDF$FOUFSPS"VUIPSJ[FE4FSWJDF"HFOUJO
BEWBODFUPTUSFBNMJOFUIFQSPDFTT
2 *TJUQPTTJCMFUPJOTUBMMUIFPVUEPPSVOJUPVUTJEF
" * UJTQPTTJCMFUPJOTUBMMJUBUBEFTJHOBUFEQMBDFJOUIFBQBSUNFOUPSPOUIFSPPGUPQOFBSCZ
#VU
JUhTJMMFHBMIBOHJOHBOBOHMFJSPODBTFXJUIUIFPVUEPPSVOJUJOJUPVUTJEFUIFBQBSUNFOU
*OTUBMMBUJPO "MTP
JUJTJMMFHBMPCTUSVDUJOHQBTTFSTCZXJUIUIFPVUEPPSVOJUJOTUBMMFEPVUTJEF
2 8IBUDBOCFEPOFUPJOTUBMMUIFPVUEPPSVOJUGBDJOHUIFSPBECFDBVTFJUJTBDPNNFSDJBMCVJMEJOH
" 5 IFGPMMPXJOHJTBOFYDFSQUGSPN#VJMEJOH$PEFHPJOHJOUPFGGFDUGSPN+6/&TU5IFFYIBVTUQJQFPGB
DPPMJOHPSWFOUJMBUJPOGBDJMJUZJOTUBMMFEJOBCVJMEJOHBEKBDFOUUPUIFTUSFFUTPGDPNNFSDJBMPSSFTJEFOUJBMBSFBT
TIBMMCFJOTUBMMFEIJHIFSUIBONUPQSFWFOUUIFFYIBVTUBJSGSPNCMPXJOHEJSFDUMZUPQBTTFSTCZBOEUIF
DVSSFOUGBDJMJUJFTTIBMMCFDPSSFDUFECZ.":TU4P
QMFBTFJOTUBMMJUIJHIFSUIBONPSOPUUPCMPXUIF
IPUFYIBVTUJOHBJSEJSFDUMZUPQBTTFSTCZ
2 8IBUBCPVUJOTUBMMJOHBXJOETDSFFOEVSJOHJOTUBMMBUJPOOPUUPCMPXIPUBJSEJSFDUMZUPQBTTFSTCZ
4BNTVOH&MFDUSPOJDT
Opening the panel
Tightly grab top of the front panel and pull it down to open.
Then slightly lift the panel up.
Open the panel and put the Air filter out. Clean the Air filter with a vacuum cleaner or soft brush.
If dust is too heavy, rinse it with running water.
Insert the Air filter back in its original position Dry the Air filter in a ventilated area.
and close the front panel.
on the usage and environmental conditions. In dusty area, clean it once a week.
Power
well-ventilated area.
*OTUBMMBUJPO
#FGPSF*OTUBMMBUJPO
,FFQUIFBJSDPOEJUJPOFSPVUMFUBOEJOMFUGSFFGSPNJUTTVSSPVOEJOHT
*ODBTFPGJOTUBMMBUJPO
LFFQUIFTZNNFUSZBOEGJYJUUPQSFWFOUWJCSBUJPO
5IFQJQFMFOHUITIBMMNFFUUIFTUBOEBSEBTGBSBTQPTTJCMF
*OTUBMMBUJPO1SPDFEVSF
Q -PDBUJPO
*OTUBMMUIFQSPEVDUJOBOBSFBUPHVBSBOUFFUIFCFTUDPPMJOHFGGFDU
DPOWFOJFODFPGQJQJOHBOEFMFDUSJDXPSL
BOEJOFYJTUFODFPG
WJCSBUJPOPSXJOE
Q 8BMM%SJMMJOH
%SJMMUIFXBMMEPXOXBSEJOBEJBNFUFSPGUPNN
Q 'JYJOH*OEPPS6OJU0VUEPPS6OJU
'JYUIFBJSDPOEJUJPOFSJOEPPSVOJUTFDVSFMZUPUIFXBMM4FDVSFUIFPVUEPPSVOJUJOBTVJUBCMFQPTJUJPO
Q 1JQF4QPPMJOH$POOFDUJOH
:PVTIBMMDVUUIFQJQFXJUIBQJQFDVUUFSBOEHSJOEBMMUIFCVSSTPGUIFDVUTVSGBDF
1JQFFYQBOTJPONBZDPOUJOVFVOUJMUIFQJQFTVSGBDFCFDPNFTVOFWFOPSUPSOBQBSU
#FTVSFUPVTFBUPSRVFXSFODIUPUJHIUFOQJQFTPSGMBSFOVUT
5PSRVF%FQUI
0VUFS%JBNFUFS %
5PSRVF LHGrDN
%FQUI "
NN
_ NN
NN
_ NN
NN
_ NN
NN
_ NN
NN
_
NN
Q -FBL5FTU
1 VUBOJOFSUHBTMJLFOJUSPHFOJOUIFPVUEPPSVOJUQJQFBOEQVUTPBQCVCCMFTPSPUIFSUFTUMJRVJETPOUIFQJQFTVSGBDFGPSUIF
MFBLUFTU
Q %SBJO)PTF$POOFDUJOH
*OTUBMMUIFESBJOIPTFEPXOXBSEUPESBJOXBUFSOBUVSBMMZ#FTVSFUPQPVSXBUFSJOUPUIFIPTFUPDIFDLJGJUESBJOTXFMM
Q &MFDUSJD&BSUI8PSL
& MFDUSJDBOEFBSUIXPSLTIBMMNFFUUIF&MFDUSJD'BDJMJUZ5FDIOPMPHZ4UBOEBSEBOEUIF*OUFSOBM8JSF3FHVMBUJPOPGUIF&MFDUSJD
#VTJOFTT-BXT
Q *OTQFDUJPO5SJBM3VO
QPODPNQMFUJPOPGUIFUFTUT
ZPVTIBMMNBLFBUSJBMSVOXIJMFZPVFYQMBJOUIFNBJOGVODUJPOTPGUIFBJSDPOEJUJPOFSUPGJOJTIUIF
6
JOTUBMMBUJPO
4BNTVOH&MFDUSPOJDT
*OTUBMMBUJPO%JBHSBNPG*OEPPS6OJUBOE0VUEPPS6OJU
"JS1VSHF1SPDFEVSF
0VUEPPSVOJU *OEPPSVOJU
$POOFDUFBDIBTTFNCMZQJQFUPUIFBQQSPQSJBUFWBMWF
POUIFPVUEPPSVOJUBOEUJHIUFOUIFGMBSFOVU (BTQJQFTJEF
-JRVJEQJQFTJEF
$POOFDUUIFDIBSHJOHIPTFPGMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFUPUIFQBDLFEWBMWFIBWJOHBTFSWJDF
QPSUBTTIPXOBUUIFGJHVSF
0QFOUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDPVOUFSDMPDLXJTF
1VSHFUIFBJSGSPNUIFTZTUFNVTJOHWBDVVNQVNQ
GPSBCPVUNJOVUFT
o.BLFTVSFUIBUQSFTTVSFHBVHFTIPX
.1B DN)H
BGUFSBCPVUNJOVUFT
o5IJTQSPDFEVSFJTWFSZJNQPSUBOUJOPSEFSUPBWPJE
HBTMFBL
o5VSOPGGUIFWBDVVNQVNQ
o$MPTFUIFWBMWFPGUIFMPXQSFTTVSFTJEFPG
NBOJGPMEHBVHFDMPDLXJTF
o3FNPWFUIFIPTFPGUIFMPXQSFTTVSFTJEF
PGNBOJGPMEHBVHF
7BDVVN1VNQ
4FUWBMWFDPSLPGCPUIMJRVJETJEFBOEHBTTJEFPG
QBDLFEWBMWFUPUIFPQFOQPTJUJPO
7BMWFTUFN
.PVOUUIFWBMWFTUFNOVUTBOEUIFTFSWJDFQPSUDBQ
4UFNDBQ
UPUIFWBMWF
BOEUJHIUFOUIFNBUUIFUPSRVFPG
LHGtDNXJUIBUPSRVFXSFODI "
HBT
#
MJRVJE
$IFDLGPSHBTMFBLBHF
"UUIJTUJNF
FTQFDJBMMZDIFDLGPSHBTMFBLBHFGSPN
UIFXBZWBMWFTTUFNOVUT
BOEGSPNUIFTFSWJDF
QPSUDBQ
4BNTVOH&MFDUSPOJDT
3FGFSFODF4IFFU
i1VNQEPXOw1SPDFEVSF
1VNQEPXOXJMMCFDBSSJFEPVUXIFOBOFWBQPSBUPSJTSFQMBDFEPSXIFOUIFVOJUJTSFMPDBUFEJOBOPUIFSBSFB
3FNPWFUIFDBQTGSPNUIFXBZWBMWFBOEUIF
8BZWBMWF
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTFBOE
DPOOFDUBQSFTTVSFHBVHF MPXQSFTTVSFTJEF
XBZ7BMWF
UPUIFTFSWJDFWBMWF
BOEPQFOUIFXBZWBMWF
BHBJO
XBZ7BMWF
4FUUIFVOJUUPDPPMPQFSBUJPONPEF
$IFDLJGUIFDPNQSFTTPSJTPQFSBUJOH
5VSOUIF8BZWBMWFDMPDLXJTFUPDMPTF
8IFOUIFQSFTTVSFHBVHFJOEJDBUFTUVSOUIF
8BZWBMWFDMPDLXJTFUPDMPTF
4UPQPQFSBUJPOPGUIFBJSDPOEJUJPOFS
$MPTFUIFDBQPGFBDIWBMWF
3FMPDBUJPOPGUIFBJSDPOEJUJPOFS
t3FGFSUPUIJTQSPDFEVSFXIFOUIFVOJUJTSFMPDBUFE
t$BSSZPVUUIFQVNQEPXOQSPDFEVSF SFGFSUPUIFEFUBJMTPGhQVNQEPXOh
t3FNPWFUIFQPXFSDPSE
t%JTDPOOFDUUIFBTTFNCMZDBCMFGSPNUIFJOEPPSBOEPVUEPPSVOJUT
t3FNPWFUIFGMBSFOVUDPOOFDUJOHUIFJOEPPSVOJUBOEUIFQJQF
t"UUIJTUJNF
DPWFSUIFQJQFPGUIFJOEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHO
NBUFSJBMFOUFSJOH
t%JTDPOOFDUUIFQJQFDPOOFDUFEUPUIFPVUEPPSVOJU
"UUIJTUJNF
DPWFSUIFWBMWFPGUIFPVUEPPSVOJUBOEUIFPUIFSQJQFVTJOHBDBQPSWJOZMQMVHUPBWPJEGPSFJHONBUFSJBM
FOUFSJOH
t.BLFTVSFZPVEPOPUCFOEUIFDPOOFDUJPOQJQFTJOUIFNJEEMFBOETUPSFUPHFUIFSXJUIUIFDBCMFT
t.PWFUIFJOEPPSBOEPVUEPPSVOJUTUPBOFXMPDBUJPO
t3FNPWFUIFNPVOUJOHQMBUFGPSUIFJOEPPSVOJUBOENPWFJUUPBOFXMPDBUJPO
4BNTVOH&MFDUSPOJDT
15-1. POWER SUPPLY
Working Voltage 176V ~ 264V
Within a 3% Deviation from Each Voltage at the Main Terminal of
Voltage Imbalance
Outdoor Unit
Starting Voltage Higher than 80% of the Rated Voltage
Cooling Heating
working range min (oC) max (oC) rated (oC) working range min (oC) max (oC) rated (oC)
outdoor -10 46 35 outdoor -15 24 7
indoor 16 32 27 indoor __ 27 20
30 30
20 20
10 10
0 0
-10 -10
-20 -20
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Indoor temperature Indoor temperature