Single Line Diagram For Generator and Gen Protection Metering 660 MW

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

PRESENTATION

SINGLE LINE DIAGRAM FOR


GENERATOR
AND
GEN. PROTECTION & METERING
TIRORA COAL – FIRED POWER PLANT PROJECT
(5 X 660 MW)
BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

TO GT & UT

22 KV

IPBD TA8:25000 / 5A GPP - A


IPBD
5P40 60VA
TA9:400 / 5A
5P20 60VA GPP - A
TA7:25000 / 5A
5P40 60VA GPP - B
TA10:400 / 5A
5P20 60VA GPP - B
TA6:25000 / 5A
0.2 100VA GTP & AVR
TA11:400 / 5A GTP
0.5 30VA DC ENB TA5:25000 / 5A
0.2 100VA AVR
PT / LA
CABINET +
ET AVR GEN
-
TA4:25000 / 5A
TA12:7500 / 5A GEMP
GPP - B 0.2S 100VA
GPP – A, GEMP

5P20 60VA
GPP – B - GFR
GPP - A

GPP - A TA3:25000 / 5A
TA13:7500 / 5A GPP - B
5P40 60VA
5P20 60VA
CABLE

SPARE
TA2:25000 / 5A
TA14:7500 / 5A GPP - A
5P40 60VA
0.5 30VA
GPP – B, AC ENB TA1:25000 / 5A
5P40 60VA TO GEN. & UT PROT. PANEL USING
GTP & AVR
FOR OVERALL DIFFERENTIAL
PROTECTION
GTP
TO GEN. GPP – A
N.G.T. GPP – A, GPP – B - GFR
SHAFT GPP – B
415 V MCC
TA0: 5 / 5A GFR
0.5 30VA 2
EARTHING
BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. CT CODE CT DESCRIPTION PANEL USES QTY

GENERATOR FAULT
1 TA0 5 / 5A, 0.5, 30VA USING FOR RECORD 1
RECORDER

USING FOR OVERALL DIFFERENTIAL


2 TA1 25000 / 5A, 5P40, 60VA TO GEN. & UT PROT. PANEL 3
PROTECTION

GEN. DIFFERENTIAL (87G1 ) Id / I

THERMAL OVERLOAD (49G1) I> m=3

STARTUP / SHUTDOWN (59G1) I>


GENERATOR PROTECTION NEGATIVE PHASE SEQUENCE OVERCURRENT
3 TA2 25000 / 5A, 5P40, 60VA 3
PANEL- A (46G1) I> m≠ 3

VOLTAGE RESTRAINED OVERCURRENT


(51VG1) U<, I>

BACK-UP IMPEDANCE (21G1) Z<

GEN. DIFFERENTIAL (87G2 ) Id / I

THERMAL OVERLOAD (49G2) I> m=3

STARTUP / SHUTDOWN (59G2) I>


GENERATOR PROTECTION NEGATIVE PHASE SEQUENCE OVERCURRENT
4 TA3 25000 / 5A, 5P40, 60VA 3
PANEL- B (46G2) I> m≠ 3

VOLTAGE RESTRAINED OVERCURRENT


(51VG2) U<, I>

BACK-UP IMPEDANCE (21G2) Z<


3
BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. CT CODE CT DESCRIPTION PANEL USES QTY

USING FOR METERING (MAIN METER &


5 TA4 25000 / 5A, 0.2S, 100VA ENERGY METER PANEL 3
BACKUP METER)

EXCITATION CONTROL
6 TA5 25000 / 5A, 0.2 100VA USING FOR EXCITATION SYSTEM 3
PANEL (AVR)

GENERATOR TRANSDUCER USING FOR CONVERT 4 - 20mA FOR DCS &


7 TA6 25000 / 5A, 0.2 100VA 3
PANEL & AVR EXCITATION SYSTEM

GEN. DIFFERENTIAL (87G2 ) Id / I

LOSS OF EXCITATION (40G2) Ф<

LOSS OF STEP (68/78 G2) dz/dt>


GENERATOR PROTECTION
8 TA7 25000 / 5A, 5P40, 60VA REVERSE POWER (32G2) _P 3
PANEL- B
GENERATOR BACK - ENERGIZATION (50 / 27
G2) I> U>

LOW FORWARD POWER (37 G2) P<

GEN. DIFFERENTIAL (87G1 ) Id / I

LOSS OF EXCITATION (40G1) Ф<

LOSS OF STEP (68/78 G1) dz/dt>


GENERATOR PROTECTION
9 TA8 25000 / 5A, 5P40, 60VA REVERSE POWER (32G1) _P 3
PANEL- A
GENERATOR BACK - ENERGIZATION (50 / 27
G1) I> U>

LOW FORWARD POWER (37 G1) P< 4


BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

CT DETAILS FOR GENERATOR PROTECTION & METERING


SR.NO. CT CODE CT DESCRIPTION PANEL USES QTY

EXCITATION TRANSFORMER
INSTANTANEOUS OVERCURRENT (50SET1)
GENERATOR PROTECTION Is>
10 TA9 400 / 5A, 5P20, 60 VA 3
PANEL- A
EXCITATION TRANSFORMER
OVERCURRENT (51ET1) I>

EXCITATION TRANSFORMER
INSTANTANEOUS OVERCURRENT (50SET2)
GENERATOR PROTECTION Is>
PANEL- B
11 TA10 400 / 5A, 5P20, 60 VA EXCITATION TRANSFORMER 3
OVERCURRENT (51ET2) I>

GENERATOR FAULT
USING FOR RECORD
RECORDER

GENERATOR
USING FOR CONVERT 4 - 20mA FOR DCS &
12 TA11 400 / 5A, 0.2, 30 VA TRANSDUCER PANEL & 3
EXCITATION SYSTEM
AVR

7500 / 5A, 5P20, 60 GENERATOR PROTECTION EXCITATION TRANSFORMER THERMAL


13 TA12 3
VA PANEL- B OVERLOAD (49ET2) 3I>

7500 / 5A, 5P20, 60 GENERATOR PROTECTION EXCITATION TRANSFORMER THERMAL


14 TA13 3
VA PANEL- A OVERLOAD (49ET1) 3I>

15 TA14 7500 / 5A, 0.5, 30 VA SPARE 3

5
BTG - ELECTRICAL

DETAILS OF GENERATOR :-

PURCHASER SICHUAN MECHANICAL EQUIPMENT IMPORT –


EXPORT CO. LTD. (SCMEC)

BARGAINOR SHANGHAI ELECTRIC POWER GENERATION CO.


LTD. GENERATOR PLANT

DESIGN UNIT SOUTHWEST ELECTRIC POWER DESIGN INSTITUTE


(SWEPDI)

6
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


SPECS AND MODE
GENERATOR MODEL QFSN-660-2
RATED CAPACITY SN MVA 776
RATED POWER PN MW 660
RATED POWER FACTOR COSΦN 0.85 (LAG)
RATED VOLTAGE UN KV 22
RATED CURRENT IN A 20377
RATED FREQUENCY FN HZ 50
RATED ROTATION SPEED NN RPM 3000
RATED EXCITATION VOLTAGE UFN V 494
RATED EXCITATION CURRENT IFN/ NO-
LOAD EXCITATION CURRENT IFOZ A 4690/1497

STATOR WINDING CONNECTION MODE YY


COOLING MODE WATER, H2, H2
VENTILATION MODE TAKE GAS FROM THE AIR GAP
EXCITATION MODE STATIC EXCITATION
7
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


PARAMETER PROPERTY
-3
DC RESISTANCE FOR EACH PHASE OF THE STATOR (75℃) W 1.447×10

DC RESISTANCE FOR WINDING OF THE ROTOR (75℃) W 0.1004


GROUND CAPACITANCE FOR EACH PHASE OF THE STATOR

A ΜF 0.229
B ΜF 0.229
C ΜF 0.229
SELF INDUCTANCE OF THE ROTOR WINDING H 0.762
DIRECT AXIS SYNCHRO REACTANCE XD % 226
HORIZONTAL AXIS SYNCHRO REACTANCE XQ % 220
DIRECT AXIS TRANSIENT REACTANCE (NON-SATURATED % 31.3
VALUE) X'DU
DIRECT AXIS TRANSIENT REACTANCE (SATURATED VALUE)X'D % 27.5

HORIZONTAL AXIS TRANSIENT REACTANCE (NON-SATURATED % 46


VALUE) X'QU
HORIZONTAL AXIS TRANSIENT REACTANCE (SATURATED % 40.5
VALUE)X'Q 8
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


PARAMETER PROPERTY
DIRECT AXIS SUPER-TRANSIENT REACTANCE (NON-SATURATED % 23.2
VALUE) X"DU
DIRECT AXIS SUPER-TRANSIENT REACTANCE (SATURATED % 21.4
VALUE)X"D
HORIZONTAL AXIS SUPER-TRANSIENT REACTANCE (NON- % 22.8
SATURATED VALUE) X"QU
HORIZONTAL AXIS SUPER-TRANSIENT REACTANCE (SATURATED % 20.9
VALUE) X"Q
NEGATIVE SEQUENCE REACTANCE (NON-SATURATED VALUE) X2U % 23
NEGATIVE SEQUENCE REACTANCE (SATURATED VALUE) X2 % 21.2
ZERO SEQUENCE REACTANCE (NON-SATURATED VALUE) XOU % 10.7
ZERO SEQUENCE REACTANCE (SATURATED VALUE)X0 % 10.2
DIRECT AXIS OPEN CIRCUIT TRANSIENT TIME CONSTANT T'DO S 8.73
HORIZONTAL AXIS OPEN CIRCUIT TRANSIENT TIME CONSTANT S 0.97
T'QO
DIRECT AXIS SHORT CIRCUIT TRANSIENT TIME CONSTANT T'D S 1.065
9
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


PARAMETER PROPERTY

HORIZONTAL AXIS SHORT CIRCUIT TRANSIENT TIME S 0.179


CONSTANT T'Q
DIRECT AXIS OPEN CIRCUIT TRANSIENT TIME S 0.045
CONSTANT T"DO
HORIZONTAL AXIS OPEN CIRCUIT TRANSIENT TIME S 0.068
CONSTANT T"QO
DIRECT AXIS SHORT CIRCUIT SUPER TRANSIENT S 0.035
TIME CONSTANT T"D
HORIZONTAL AXIS SHORT CIRCUIT SUPER S 0.035
TRANSIENT TIME CONSTANT T"Q
DE-EXCITATION TIME CONSTANT TDM S 3

FLYWHEEL MOMENT GD2 T-M2 41


SHORT CIRCUIT RATIO SCR 0.518
STEADY STATUS NEGATIVE SEQUENCE CURRENT I2 % 8
TRANSIENT STATUS NEGATIVE SEQUENCE S 8
CURRENTI22T

10
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE

PARAMETER PROPERTY
ALLOWABLE FREQUENCY DEVIATION +3
±% -5
ALLOWABLE STATOR VOLTAGE DEVIATION ±% 5
DE-EXCITATION ASYNCHRONOUS RUN CAPABILITY MW
DE-EXCITATION ASYNCHRONOUS RUNTIME MIN SEE 4.2.13.4
LEADING PHASE RUN CAPABILITY MW 660
0.95PF (ADVANCE) LONG TERM
LEADING PHASE RUNTIME (H FOR RUN HOUR) H CONTINUOUS RUN

THF TELEPHONE HARMONIC FACTOR %


KU VOLTAGE WAVEFORM SINUS DISTORTION RATE KU %

THREE PHASE SHORT CIRCUIT STEADY STATUS CURRENT % 162


TRANSIENT STATUS SHORT CIRCUIT CURRENT EFFECTIVE (AC
COMPONENT)
PHASE-NEUTRAL POINT % 584
PHASE-PHASE % 407
THREE PHASE % 416
11
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


PARAMETER PROPERTY
SUB-TRANSIENT STATUS SHORT CIRCUIT CURRENT
EFFECTIVE VALUE (AC COMPONENT)
PHASE-NEUTRAL POINT % 633
PHASE-PHASE % 453
THREE PHASE % 520
THREE PHASE SHORT CIRCUIT MAXIMUM CURRENT VALUE
(INCLUDING DC COMPONENT PEAK VALUE) % 1200
PHASE-PHASE SHORT CIRCUIT MAXIMUM
ELECTROMAGNETIC TORSION T.M 2130
ROTOR AXIAL VOLTAGE V
BEARING INSULATION RESISTANCE NORMAL/MINIMUM
VALUE MW
MAXIMUM ALLOWABLE OVER-SPEED % 120
OUT OF STEP POWER MW 1260
GENERATOR STATUS RUN CAPABILITY S
ALLOWING 10000TIMES
PEAK ADJUSTMENT CAPABILITY MACHINE START/STOP.
GENERATOR SERVICE LIFE YEAR 30
NOISE DB 90
12
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


VIBRATION VALUE
CRITICAL SPEED (FIRST ORDER) R/MIN 690
CRITICAL SPEED (SECOND ORDER) R/MIN 1935
CRITICAL SPEED BEARING VIBRATION VALUE
VERTICAL MM
HORIZONTAL MM
BEARING VIBRATION VALUE IN CASE OF OVER-SPEED
VERTICAL MM
HORIZONTAL MM
BEARING VIBRATION VALUE IN CASE OF RATED
ROTATION SPEED
VERTICAL MM
HORIZONTAL MM
CRITICAL SPEED AXIS VIBRATION VALUE
VERTICAL MM
13
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


VIBRATION VALUE
HORIZONTAL MM
AXIS VIBRATION VALUE IN CASE OF
OVER-SPEED
VERTICAL MM
HORIZONTAL MM
AXIS VIBRATION VALUE IN CASE OF
RATED ROTATION SPEED
VERTICAL MM
HORIZONTAL MM
FV STATOR WINDING TERMINAL
VIBRATION FREQUENCY HZ
STATOR WINDING TERMINAL ≤0.1(1.0 UN NO-LOAD OR 1.0 I N SHORT
VIBRATION AMPLITUDE VALUE MM CIRCUIT. )
AXIAL TORSIONAL FREQUENCY HZ

14
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE

LOSS AND EFFICIENCY ( UNDER RATED CONDITIONS)

STATOR WINDING COPPER LOSS QCU1 KW 1803

STATOR IRON LOSS QFE KW 637

EXCITATION LOSS QCU2 KW 2208


SHORT CIRCUIT ADDITIONAL LOSS
QKD KW 1055

MECHANICAL LOSS QM KW 1607


EXCITATION MACHINE AND
EQUIPMENT LOSS KW

TOTAL LOSS ΣQ KW 7310

FULL LOAD EFFICIENCY Η % 98.9

15
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESCRIPTION UNIT DESIGN VALUE


INSULATION GRADE AND TEMPERATURE
STATOR WINDING INSULATION GRADE F
WINDING OUTLET WATER TEMPERATURE UNDER
STATOR WINDING THA WORK CONDITIONS ℃ 74
WINDING OUTLET WATER TEMPERATURE UNDER
STATOR WINDING T-MCR WORK CONDITIONS ℃
WINDING OUTLET WATER TEMPERATURE UNDER
STATOR WINDING VWO WORK CONDITIONS ℃
INTERLAYER TEMPERATURE UNDER STATOR WINDING
THA WORK CONDITIONS ℃ 79
INTERLAYER TEMPERATURE UNDER STATOR WINDING
T-MCR WORK CONDITIONS ℃
INTERLAYER TEMPERATURE UNDER STATOR WINDING
VWO WORK CONDITIONS ℃
STATOR IRON CORE INSULATION GRADE F

16
BTG - ELECTRICAL
DETAILS OF GENERATOR :-

DESIGN
DESCRIPTION UNIT VALUE

INSULATION GRADE AND TEMPERATURE


HOTTEST POINT TEMPERATURE UNDER STATOR IRON
CORE THA WORK CONDITIONS ℃ 88
HOTTEST POINT TEMPERATURE UNDER STATOR IRON
CORE T-MCR WORK CONDITIONS ℃
TEMPERATURE UNDER STATOR TERMINAL STRUCTURE
PART THA WORK CONDITIONS ℃
TEMPERATURE UNDER STATOR TERMINAL STRUCTURE
PART T-MCR WORK CONDITIONS ℃
TEMPERATURE UNDER STATOR TERMINAL STRUCTURE
PART VWO WORK CONDITIONS ℃
ROTOR WINDING INSULATION GRADE F
TEMPERATURE UNDER ROTOR WINDING THA WORK
CONDITIONS (RESISTANCE METHOD) ℃ 92
TEMPERATURE UNDER ROTOR WINDING T-MCR WORK
CONDITIONS (RESISTANCE METHOD) ℃

17
BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION UNIT DESIGN VALUE


EXCITAION TRANSFORMER
TYPE SINGLE PHASE DRY TYPE
MODEL
CAPACITY KVA 3×2950
MANUFACTURER JINPAN/SHUNTE
RATED VOLTAGE RATED VOLTAGE
PRIMARY KV 22
PRIMARY V
1060
FREQUENCY HZ 50

PHASE NO. 3

CONNECTION GROUP CATEGORY Y/△-11

TERMINAL LEAD-OUT AND


GROUNDING MODE
INSULATION GRADE F
18
BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION UNIT DESIGN VALUE


EXCITAION TRANSFORMER
INSULATION WITHSTAND VOLTAGE KV
IMPACT VOLTAGE KV
HIGH SIDE 125
LOW SIDE
HIGH SIDE KV
LOW SIDE 50
PROTECTION GRADE IP23
COOLING MODE AN/AF
LOSS
COPPER LOSS KW 26
IRON LOSS KW 14
LOSS ADDITIONAL LOSS KW 9
LOSS TOTAL LOSS KW 49
EFFICIENCY % 99.8

19
BTG - ELECTRICAL
DETAILS OF EXCITATION TRANSFORMER :-

DESCRIPTION UNIT DESIGN VALUE


EXCITAION TRANSFORMER
VOLTAGE REGULATION % ±5
IMPEDANCE VOLTAGE % 8
POSITIVE SEQUENCE IMPEDANCE % 8
ZERO SEQUENCE IMPEDANCE % 7.2
HIGH VOLTAGE WINDING RESISTANCE Ω 3×0.1138
EXCITATION CURRENT A 0.9
NOISE LEVEL DBA 70
OVERLOAD CAPACITY OVERLOAD CAPACITY KVA 1.1 LONG TERM
TRANSFORMER TEMPERATURE SIGNAL I SECTION OVER TEMPERATURE
ALARM
II SECTION OVER TEMPERATURE
TRIPPING
TRANSFORMER MAXIMUM ALLOWABLE 100K
TEMPERATURE RISE
EXTERNAL SIZE (L×W×H) MM 3400×1520×2950
TRANSPORT SIZE (L×W×H) MM 4100×2600×2950
20
WEIGHT T 19.6
BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION UNIT DESIGN VALUE


EXCITATION POWER CABINET

TYPE
THYRISTOR POWER ELEMENT
RATED VOLTAGE V
RATED CURRENT A 2075
REVERSE PEAK VOLTAGE V 4200
RATED CURRENT A 1700
COOLING MODE FORCE WIND COOLING
ELEMENT NO. SERIES CONNECTIONS FOR EACH PCS 1
CABINET AND EACH BRIDGE ARM
PARALLEL CONNECTION BRANCH NO. FOR EACH PCS 6
CABINET AND EACH BRIDGE ARM
RECTIFICATION CABINET NOISE DB ≤65DB
BLOWER FAN AVERAGE NO-FAULT TIME H 45000
POWER CABINET NO. 5
CURRENT SHARING FACTOR 0.95
Voltage sharing factor 21
BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION UNIT DESIGN VALUE

MAGNETIC FIELD BREAKER

RATED VOLTAGE V 2000


RATED CURRENT RATED CURRENT A 6000

BREAKING CURRENT A 75000

CONTROL VOLTAGE (DC) VD.C 220

MAX. ARC VOLTAGE(ABOVE 2000V) V 2800

MANUFACTURER ABB

MODEL HPB60M-82S

22
BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION UNIT DESIGN VALUE


AVR PROPRTY
VOLTAGE REGULATION % 30%~110% UG0
MANUAL REGULATION SCOPE % 10%IF0~110% IFN
STATIC DIFFERENCE RATE % ±1
TRANSITION STATUS RESOLUTION MS
SINGLE TIME RECORD LENGTH S
TOTAL RECORD LENGTH S 1000
RISE TIME S ≤0.04
CONTROL PERIOD MS
SAMPLING MODE AC
PHASE FREQUENCY MARGIN ° ≥40°
AMPLITUDE FREQUENCY MARGIN DB ≥6DB
CONTROL RULE PID
MANUFACTURER

23
BTG - ELECTRICAL
DETAILS OF EXCITATION POWER CABINET :-

DESCRIPTION UNIT DESIGN VALUE

EXCITATION INITIATING CIRCUIT


PARAMETER
EXCITATION INITIATING VOLTAGE V/AC 415

EXCITATION INITIATING CURRENT A 150

EXCITATION INITIATING POWER KVA 65


WASTE
ROTOR OVER VOLTAGE PROTECTION

OVER VOLTAGE NON LINEAR MJ 5


RESISTANCE CAPACITY
OVER VOLTAGE PROTECTION ACTION 4UFN~6 UFN
VOLTAGE VALUE

24
BTG - ELECTRICAL

DETAILS OF NGT CABINET :-

QUANTITY
TYPE & SPECIFICATION UNIT
UNIT # 1 UNIT # 2 UNIT # 3 TOTAL

SINGLE PHASE ISOLATOR: 22KV /


400A NGT: 22/0.22KV, 50KVA

RESISTANCE: 0.4Ω, 50KW CT OF SET 1 1 1 3


NGT SECONDARY WIRING: 500/5A,
5P20

CT OF NGT PRIMARY WIRING: 5/5A,


0.5

25
BTG - ELECTRICAL

DETAILS OF PT / LA CABINET :-

QUANTITY
TYPE & SPECIFICATION UNIT
UNIT # 1 UNIT # 2 UNIT # 3 TOTAL

RN4 - 22, 0.5A Y5W1 - 24 / 61.6 SET 1 1 1 3

22/√3, 0.11/√3, 0.11/√3, 0.11/3 KV


0.2/3P/3P, 60VA SEMI-INSULATING

22/√3, 0.11/√3, 0.11/√3, 0.11/3 KV


0.2/3P/3P, 60VA SEMI-INSULATING

22/√3, 0.11/√3, 0.11/3, 0.11/3 KV


0.2/3P/3P, 60VA FULL-INSULATING

26
BTG - ELECTRICAL

DETAILS OF GENERATOR PROTECTION:-

SR.NO. GENERATOR PROTECTION PROTECTION CODE

1 GENERATOR DIFFERENTIAL PROTECTION 87G

2 VOLTAGE RESTRAINED OVER CURRENT PROTECTION 51VG)

3 GENERATOR BACK-UP IMPEDANCE 21G

4 STATOR EARTH FAULT 95% & 100% PROTECTION 64G1, 64G2


64G1 (ZERO SEQUENCE
A) GENERATOR STATOR 95% EARTHING PROTECTION
VOLTAGE THEORY)
64G2 (THIRD-HARMONIC
B) GENERATOR STATOR 100% EARTHING PROTECTION
THEORY)
5 STATOR INTER-TURN FAULT PROTECTION 95G

ASYMMETRIC NEGATIVE PHASE SEQUENCE OVER CURRENT


6 46G
PROTECTION

7 SYMMETRICAL THERMAL OVERLOAD PROTECTION 49G)

8 OVER/UNDER VOLTAGE PROTECTION 59/27G

9 OVER/UNDER FREQUENCY PROTECTION 81G

10 LOSS OF EXCITATION PROTECTION 40G

27
BTG - ELECTRICAL

DETAILS OF GENERATOR PROTECTION:-

SR.NO GENERATOR PROTECTION PROTECTION CODE

11 REVERSE POWER PROTECTION 32G

12 LOW FORWARD POWER PROTECTION 37G

13 GENERATOR OUT OF STEP PROTECTION 78G

14 OVER EXCITATION PROTECTION 61G

15 GENERATOR BACK-ENERGIZATION PROTECTION 51BEG

16 GENERATOR ROTOR EARTH FAULT PROTECTION 64F1、64F2

17 STARTUP/SHUTDOWN PROTECTION 59G

18 GENERATOR COOLING WATER-LOSS PROTECTION 30G

19 HEAT ENGINEERING PROTECTION (30T)

20 ET INSTANTANEOUS OVERCURRENT PROTECTION 50SET

28
BTG - ELECTRICAL

DETAILS OF GENERATOR PROTECTION:-

SR.NO GENERATOR PROTECTION PROTECTION CODE

21 ET OVERCURRENT PROTECTION 51ET

22 ET EXCITATION WINDING THERMAL OVERLOAD PROTECTION 49ET

23 ET WINDING TEMPERATURE PROTECTION ET26W

24 CT, VT SUPERVISION PROTECTION 97,60

25 UNIT EMERGENCE TRIPPING INTERFACE

26 EXCITATION SYSTEM FAULT TRIPPING INTERFACE

27 400KV BREAKER OUR OF ORDER TRIPPING INTERFACE

29
BTG - ELECTRICAL
SLD FOR GENERATOR AND GEN. PROTECTION & METERING:-

TO GT & UT

22 KV

IPBD TA8:25000 / 5A GPP - A


IPBD
5P40 60VA
TA9:400 / 5A
5P20 60VA GPP - A
TA7:25000 / 5A
5P40 60VA GPP - B
TA10:400 / 5A
5P20 60VA GPP - B
TA6:25000 / 5A
0.2 100VA GTP & AVR
TA11:400 / 5A GTP
0.5 30VA DC ENB TA5:25000 / 5A
0.2 100VA AVR
PT / LA
CABINET +
ET AVR GEN
1060V -
TA4:25000 / 5A
TA12:7500 / 5A GEMP
GPP - B 0.2S 100VA
GPP – A, GEMP

5P20 60VA
GPP – B - GFR
GPP - A

GPP - A TA3:25000 / 5A
TA13:7500 / 5A GPP - B
5P40 60VA
5P20 60VA
CABLE

SPARE
TA2:25000 / 5A
TA14:7500 / 5A GPP - A
5P40 60VA
0.5 30VA
GPP – B, AC ENB TA1:25000 / 5A
5P40 60VA TO GEN. & UT PROT. PANEL USING
GTP & AVR
FOR OVERALL DIFFERENTIAL
PROTECTION
GTP
TO GEN. GPP – A
N.G.T. GPP – A, GPP – B - GFR
SHAFT GPP – B
415 V MCC
TA0: 5 / 5A GFR
0.5 30VA 30
EARTHING
BTG - ELECTRICAL

31
VOTE OF THANKS