Belimo Room-And-Zone-Control CR24 Application Brochure En-Gb
Belimo Room-And-Zone-Control CR24 Application Brochure En-Gb
Layout
System - Application - Number ->
Key
System - Application - Number -> System Application
5.04 Trk
Overview IRC applications
The application library consists of various singles room applications based on the proofed Belimo actuators for motorized air and water
applications and the new CR24 single room controller range. The applications are subdivided according to its system type.
The library is being update regularly, please check for the lasted issue: on the INTRANET or under www.belimo.ch
The detailed function description and technical data of the CR24 controller can be found in the CR24 Product-Information: www.belimo.ch
Water applications
Application Description CR24 Type
Heat-/Chilled Ceiling-Systems
Application Description CR24 Type
5.04 Trk
Overview IRC applications
5.04 Trk
Air-System, pressure depending
AC 24 V
0...10V
external remote
~ _
NTC-sensor setpoint shift
EHO St-By
ao1 U5 1 U5 2
3 4 5
ai/di1 di2 ai2
1 2 6 7 8 CR24-B1
1 2 3y 5 Supply air Pressure depending damper application. The room temperature aims as
~ U5
* Optional
Note Hints
The pin numbering corresponds to the Belimo Mode setting damper: 2...10 V
actuator connections.
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. time switch
di2 – Stand by, e.g. motion detector
1 P-Band: normal - breit 1 2
Setpoint W H range:
Operations - MMI
Subject of changes
15...36 °C
CR24-A1 without user interface Mode: AUTO
CR24-B1 with user interface Mode: AUTO-ECO-MAX
AC 24 V
0...10V
external remote setpoint
~ _
NTC - sensor shift
Change-Over
Change-
EHO
Over
ao1 U5 1 U5 2
3 4 5
ai/di1 di2 ai2
1 2 6 7 8 CR24-B1
Inputs
- ai/di1 EHO / ext. Sensor *
- di2 Change/Over 2
- ai2 Remote setpoint shift * 0
tR
Outputs [°C]
W htg W clg
- ao1 Change/over actuator 2…10V
* Optional
Note Hint
The pin numbering corresponds to the Belimo Mode setting actuator: 2...10 V
actuator connections.
Bedienung
Setpoint W H range:
Subject to changes
5.04 Trk
VAV-System, pressure independent
AC 24 V
0...10V
external remote
~ _
NTC- sensor setpoint shift
EHO St-By
ao1 U5 1 U5 2
3 4 5
ai/di1 di2 ai2
1 2 6 7 8 CR24-B1
The room temperature aims as the demand related control value of the
1 2 3y 5
~
2)
U5
1)
VAV 1 connected VAV units. The variable volumetric flow range V’min...V’max
equals to:
1 2 3y 5
~ U5 VAV 2 1) Master-Slave
or - V’min - to the hygienic air change
2) parallel
- V’max - to the maximum cooling demand.
Mode setting VAV-controller: 2...10V
Functional diagram
Y XP clg
[V] Volumetric flow
In- & Output assignment V'max
10
ao1
Inputs
- ai/di1 EHO / ext. Sensor *
- di2 Stand by *
- ai2 Remote setpoint shift *
2 V'min
Outputs EHO
0 Closed
- ao1 VAV system output (0)2…10V tR
[°C]
W htg Wclg
* Optional
Note
Hints
The pin numbering corresponds to the Belimo
Application requires VAV - controller mode setting: 2...10 V
actuator connections.
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. timeswitch
di2 – Stand by, e.g. motion detector
1 P-Band: normal - wide 1 2
Setpoint W H range:
Operations - MMI
15...36 °C
CR24-A1 without user interface Mode: AUTO
Subject to changes
0...10V
AC 24 V External setpoint shift
~ temperatur sensor _
Boost
3 4 12 5
ao3 ao2 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B3
The room temperature aims as the demand related control value of the
connected VAV units. The variable volumetric flow range V’min...V’max
1 2 3y 5 equals to: hygienic air change … maximum cooling demand.
~ U5 VAV 1
2) 1)
1 2 3y 5 Room preconditioning can be triggered via Boost input di3, e.g. via external
~ U5 VAV 2 1) Master-Slave
or timer, building management system.
2) parallel
Function ‚Boost Temperature controlled’
Mode setting VAV-controller: 2...10V
- ON: di3 active -> VAV output ao1 10 V (V’max)
- OFF: di3 inactive or -> Auto operation
In- & Output assignment
comfort setpoint reached -> Auto operation
Inputs
- ai/di1 EHO / ext. Sensor *
Functional diagram
- di2 Stand by *
Y XP clg
- di3 Boost Volumetric flow
[V]
- ai2 Remote setpoint shift *
10 V'max
Boost ao1
Outputs 'Temperatur
controlled'
- ao1 VAV system output (0)2…10V
* Optional 2 V'min
EHO
0 Closed
tR
[°C]
W htg Wclg
Note
The pin numbering corresponds to the Belimo
actuator connections. Hints
Application requires VAV - controller mode setting: 2...10 V
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. timeswitch
di2 – Stand by, e.g. motion detector
1 P-Band: normal - wide
1 2 3 4 5 6
Operations - MMI
Setpoint W H range:
Subject to changes
AC 24 V external remote
0...10V
~ NTC- sensor setpoint shift _
hot
cold
3 4 5
ao1 U5 1 U5 2
ai/di1 di2 ai2
1 2 6 7 8 CR24-B1
The cold and the hot air supplied by the dual duct system get mixed
by the two volume controller according to the required room
1 2 3y 5 demand.
~ U5 VAV - cold air mixing controller
htg clg
Note V'max
The pin numbering corresponds to the Belimo actuator
hot air
connections
cold air
V'min
t room
W kü
P-band cooling
Refer to the CR24 Product-Information for technical data and detailed information. Hints
Application requires VAV - controller mode setting: 2...10 V
Setpoint W H range:
Operations - MMI
Subject to changes
15...36 °C
CR24-A1 without user interface Mode: AUTO
CR24-B1 with user interface Mode: AUTO-ECO-MAX
0...10V
AC 24 V external remote
~ NTC - sensor setpoint shift _
+
M
EHO St-By Boost
Boost
ao3 ao2 ao1 U5 1 U5 2
3 4 12 5
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B3
1 2 3y The room temperature aims as the demand related control value of the
heating 0...10V
~
connected VAV units. The variable volumetric air flow range V’min...V’max
equals to: - V’min - to the hygienic air change
1 2 3y 5
~
2)
U5
1)
VAV 1 - V’max - to the maximum cooling demand.
The reheater gets controlled via the connected 0…10 V valve at heating
1 2 3y 5
~ U5 VAV 2 1) Master-Slave request. To ensure the required airflow over the reheater the volumetric air
or
2) parallel flow gets controlled V’min.... 80% V’max during that condition.
Hint: Mode setting VAV controller: 2...10V
Option:
Digital input di3 driven by a Boost signal allows the preconditioning of the
In- & Output assignment room. Two Boost modes can be used:
- Boost – ‘Temperature controlled’: quick-heating and/or, -cooling
Inputs - Boost – V’max: room flush, support smoke extraction
- ai/di1 EHO / ext. Sensor *
- di2 Stand by *
Functional diagram
- di3 Boost *
- ai2 Remote setpoint shift *
Y XP htg XP clg
[V] Volumetric air flow
Outputs
V'max
VAV system output (0)2…10V 10 x x
- ao1 ao2 ao1
- ao3 Heating output 3-point V'maxhtg Boost
'Temperature controlled'
Boost 'V'max'
* Optional
2 V'min
EHO
0 closed
tR
[°C]
Note W htg W clg
The pin numbering corresponds to the Belimo
actuator connections.
Hints
- Application requires VAV - controller mode setting: 2...10 V
- Heating output ao2: 0...10 V
Refer to the CR24 Product-Information for technical data and detailed
information.
external remote
0...10V
AC 24 V
~ NTC - sensor setpoint shift
_
+
M
EHO St-By Air flush
Air
3 4 12 5 flush
ao1 U5 1 U5 2
ao3
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B2
1 2 3 The room temperature aims as the demand related control value of the
heating 3-point
connected VAV units. The variable volumetric air flow range V’min...V’max
equals to: - V’min - to the hygienic air change
1 2 3y 5
~
2)
U5
1)
VAV 1 - V’max - to the maximum cooling demand.
A reheater gets activated via the connected 3-point valve at heating
1 2 3y 5
~ U5 VAV 2 1) Master-Slave request. To ensure the required airflow over the reheater the volumetric air
or
2) parallel flow gets controlled V’min.... 80% V’max during that condition.
Hint: Mode setting VAV-controller: 2...10V
Option:
The VAV-application can be forced to the ‘V’max’ step by the use of the
In- & Output assignment digital input di3. Typical use air flush via an independent air quality control
loop, support of smoke extraction, etc. The heating output does not get
Inputs influenced during that condtion.
- ai/di1 EHO / ext. Sensor *
- di2 Stand by *
Functional diagram
- di3 Air flush *
- ai2 Remote setpoint shift *
Y XP htg XP clg
[V] Volumetric air flow
Outputs
V'max
- ao1 VAV system output (0)2…10V 10
ao3 air ao1
- ao3 Heating output 3-point V'max htg flush
* Optional
2 V'min
EHO
0 closed
tR
[°C]
Note W htg W clg
The pin numbering corresponds to the Belimo
actuator connections.
Hints
- Application requires VAV - controller mode setting: 2...10 V
- Heating output ao3: 3-point actuator, optimized for 150 s running time
Refer to the CR24 Product-Information for technical data and detailed
information.
di3 – Air flush, e.g. air quality control, ext. time switch
2 V'max htg Off - 80% 2
1 2
Setpoint W H range:
ai2 – external setpoint shift, e.g. So/Wi-compensation
0...10V
AC 24 V supply air temp. remote
°C
~ NTC5K setpoint shift
_
3 4 12 5
ao3 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8
CR24-B2E
VAV 1
- V’max - to the maximum cooling demand.
~ y U5
a) b)
(optional) VAV 2
1 2 3 5
At heating conditions the reheater gets controlled via the ON/OFF
~ y U5 a) parallel connection
b) Master-Slave connection Triac-output. The volumetric flow gets increased 35 ... 80% V’max to
ensure the thermal transfer.
Boost
Outputs 10 do3 V'max
II
- ao1 VAV system output (0)2…10V 8,4
ao1
* Optional I
2 V'min
Note EHO
0
The pin numbering corresponds to the Belimo actuator tR [°C]
connections.
WH WC
Refer to the CR24 Product Information and the data sheet CR24-B2E for technical data Hints
and detailed information.. - Application requires VAV - controller mode setting: 2...10 V
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. time switch
di2 – Stand by, e.g. motion detector
1 Steps: 1 or 2 - binary 1 2
0...10V
AC 24 V supply air temp. remote
~ NTC5K setpoint shift
_ °C
3 4 12 5
ao3 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8
CR24-B2E
Electrical The room temperature aims as the demand related control value of
II re-heater the connected VAV units. The variable volumetric air flow range
V’min...V’max:
1 2 3 5
- V’min - to the hygienic air change
Note:
~ y U5 VAV 1
a) b) - V’max - to the maximum cooling demand.
(optional) VAV 2
Step II
Step I
1 2
~
3
y
5
U5 a) parallel connection At heating conditions the 2-step re-heater gets controlled via the two
b) Master-Slave connection
ON/OFF Triac-outputs in a binary mode which gives an almost
modulating control mode. The volumetric flow gets increased 35 ...
80% V’max to ensure the thermal transfer.
In- & Output assignment
Options:
Inputs By the use of an external sensor mounted in the supply duct the air
- ai/di1 supply air limitation * / EHO * injection temperature can be limited to a maximum of about 50°C.
- di2 Stand by *
- di3 Boost * Functional diagram
- ai2 Remote setpoint shift *
Y [V]
Outputs
Boost
- ao1 VAV system output (0)2…10V 10
do3 I/II
V'max
V'maxH ao1
- do3/1 Heating output I 24 VAC ON/OFF 8,4
- do3/2 Heating output II 24 VAC ON/OFF III
* Optional
II
2 V'min
Note I EHO
0
The pin numbering corresponds to the Belimo actuator tR [°C]
connections.
WH WC
Refer to the CR24 Product-Information and the data sheet CR24-B2E for technical data Hints
and detailed information.. - Application requires VAV - controller mode setting: 2...10 V
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. time switch
di2 – Stand by, e.g. motion detector
1 Steps: 1 or 2 - binary 1 2
0...10V
AC 24 V remote
~ setpoint shift
_
Boost
3 4 12 5
ao1 U5 1 U5 2
ao3
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8
CR24-B2E
Radiator valve The room temperature aims as the demand related control value of
24VAC ON/OFF the connected VAV units. The variable volumetric air flow range
V’min...V’max:
1 2
~
3
y
5
U5 VAV 1 - V’min - to the hygienic air change
a) b) - V’max - to the maximum cooling demand.
(optional) VAV 2
1 2
~
3
y
5
U5 a) parallel connection At heating conditions the ON/OFF radiator valve gets controlled via
b) Master-Slave connection
the CR24 Triac-output.
* Optional 2 V'min
EHO
0
tR [°C]
WH WC
Note
The pin numbering corresponds to the Belimo actuator
connections. Hints
- Application requires VAV - controller mode setting: 2...10 V
Refer to the CR24 Product-Information and the data sheet CR24-B2E for technical data
and detailed information.
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. time switch
di2 – Stand by, e.g. motion detector
1 Steps: 1 or 2 - binary 1 2
0...10V
AC 24 V external setpoint shift
~ NTC - sensor _
3 4 12 5
ao3 ao2 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B3
1 2
~
3
y cooling 0...10V a) The room temperature aims as the demand related control value of the
connected VAV units and chilled ceiling. The variable volumetric air flow
1 2 3y 5 range V’min...V’max equals to: hygienic air change … maximum cooling
~ U5 VAV 1
2) 1) demand.
1 2 3 5
~ y U5 VAV 2 1) Master-Slave
or
2) parallel
Option – unit sequencing:
a)
Mode setting VAV controller: 2...10V The two cooling units can also be used in control sequencing:
a) control signal input needs to be adjusted in case of unit sequencing Unit 1 - Chilled ceiling: 0 … 5 V (MFT-actuator)
Unit 2 - VAV: 5 …10 V (MFT-controller. E.g. NMV-D2M)
Dew point
Function Dew point control: cooling
undershot
Functional diagram
Y XP clg Option
In- & Output assignment [V] Volumetric flow unit sequencing
10 V'max V'max
Inputs
- ai/di1 EHO / ext. Sensor * VAV ao1
* Optional
Note
The pin numbering corresponds to the Belimo Hints
actuator connections. - Application requires VAV - controller mode setting: 2...10 V
- Cooling output 0 … 10 V
By the use of the control sequencing option the control input of the MFT-actuators
Refer to the CR24 Product-Information for technical data and detailed need to be adjusted (PC-Tool or MFT-Handy)
information.
Operations - MMI
Setpoint W H range:
Subject to changes
Water applications
Application Description CR24 Type
5.04 Trk
Water application
0...10V
AC 24 V External Setpoint shift
~ NTC sensor _
°C
+
EHO St-By
3 4 12 5 M
ao3 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B2
1 2 3
heating 3-point
Functional diagram
In- & Output assignment
Inputs Y XP htg
- ai/di1 EHO / ext. Sensor * [V]
- di2 St-By Standby * 10
- ai2 Remote setpoint shift * ao3
Outputs
- ao1 Heating valve 3-point
EHO
* Optional 0
tR
[°C]
W htg
Note
The pin numbering corresponds to the Belimo Hint
actuator connections. Heating output ao3: 3-point actuator, optimized for 150s running time
Operations - MMI
Setpoint W H range:
CR24-A2 without user interface Mode: AUTO
Subject to changes
0...10V
~ NTC - sensor _
Change-Over
°C
+
Change/
EHO
over
-
3 4 5 M
ao1 U5 1 U5 2
ai/di1 di2 ai2
1 2 6 7 8 CR24-B1
1 2 3y 5
~ U5 Change/over 2...10 V
Functional diagram
Y XP htg XP clg
In- & Output assignment [V]
10
Inputs heating C-O cooling
- ai/di1 EHO / ext. Sensor *
- di2 Change/over signal
- ai2 Remote setpoint shift *
2
Outputs
- ao1 Change/over actuator 2…10V 0
tR
[°C]
W htg W clg
* Optional
Note Hint
The pin numbering corresponds to the Belimo Actuator setting: 2...10 V
actuator connections.
DIP-Switch setting: di1 – EHO Energy hold off, e.g. window switch, ext. timeswitch
ai1 – external temperature sensing – exhaust duct
1 P-Band: normal - wide 1 2
Operations - MMI
Setpoint W H range:
CR24-A1 without user interface Mode: AUTO
Subject to changes
Heat-/Chilled Ceiling-Systems
Application Description CR24 Type
5.04 Trk
Heat-/Chilled ceiling system
0...10V
AC 24 V external remote
~ NTC sensor setpoint shift_
M
remote
setpoint shift
EHO St-By Dew point
limiter
3 4 12 5
ao3 ao2 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B3
below
Dew point
Functional diagram
In- & Output assignment
Inputs Y XP clg
- ai/di1 EHO / ext. Sensor * [V]
- di2 Stand by * 10
ao2
- di3 Dew point limiter
- ai2 Remote setpoint shift *
Outputs
- ao2 Cooling output 0...10V
dew point limiter
0
tR
* Optional [°C]
W htg
W clg
Note Hint
The pin numbering corresponds to the Belimo - Cooling output ao2: 0...10 V
actuator connections.
Operations - MMI
Setpoint W H range: CR24-A3 without user interface Mode: AUTO
CR24-B3 with user interface Mode: AUTO-ECO-MAX
15...36 °C
Subject to changes
0...10V
AC 24 V External Setpoint shift
~ NTC - sensor _
Change-over
3 4 12 5
ao3 ao2 ao1 U5 1 U5 2
ai/di1 di2 di3 ai2
1 2 9 10 11 6 7 8 CR24-B3
This water ceiling system can be used to cover heating and cooling
1 2 3
y
5
cooling / heating 0...10V
dem and due to the build-in Change/over function of the room tem perature
~ U5
controller controlling the common 0...10 V valve. Change/over gets
activated by an ext ernal command wired to digital input di3. The dew point
limiter cares for perspiration water free operation as it switches off the
Function input di3:
cooling cooling via a 2-point signal.
dew point or heating
undershot
* Optional
Dew point undershot
0
tR
[°C]
W htg W clg
Note
The pin numbering corresponds to the Belimo
actuator connections.
Hint
- Cooling output ao2: 0...10 V
Refer to the CR24 Product-Inform ation for technical data and detailed
inform ation.
Operations - MMI
Setpoint W H range: CR24-A3 without user interface Mode: AUTO
CR24-B3 with user interface Mode: AUTO-ECO-MAX
15...36 °C