Guide Specifications

Airfinity™ XL
Models IH / IC
Large Packaged Rooftop Units
120 to 230 kW

July 2018 RT-PRG011A-GB


TRANE Airfinity™ XL Large Packaged Rooftops

General

General configuration
Units shall be dedicated down flow or horizontal airflow, with the possibility to convert
the airflow configuration on-site with minimal modifications to the unit. Unit shall be
able to operate between 46°C and -18°C, in cooling mode. All units shall be factory
assembled wired, fully charged with refrigerant and run-tested before leaving the
factory. Internal wiring is colored and numbered for simplified identification.

All units shall be equipped with dual refrigeration circuits and alternate defrost for
reversible models.

The following auxiliary heat options shall be provided:


 Hot water coil
 Hot Gas burner
 Electrical heater

Performance
Units shall be certified and registered on the Eurovent certification under the RT
programme (http://www.eurovent-certification.com). Units net EER shall be a class A
or B in cooling mode. Reversible units net COP shall be a class A or B in heating
mode.

All units shall comply with the ErP regulation No 2016/2281.

Casing
Unit casing shall be constructed of zinc coated, heavy-gauge, galvanized steel, with
an exception of the panel doors, which shall be built in aluminum. All exterior
components shall be mounted in a weather resistant steel cabinet and painted with a
polyester white RAL 9002 powder paint. Where top cover seams exist, they shall be
double hemmed and gasket sealed to prevent water leakage. Cabinet construction
shall allow access for all maintenance on two sides of the unit. Service panels shall
have double hinged doors which can be opened from the left or the right hand side.
When closed, doors shall provide a water and air tight seal.

The indoor air section shall be fully insulated with a double wall panel and glass wool
with 50mm thickness and density according to norm DIN EN 1602. Insulation shall be
self-maintaining.

Filters
Units shall be provided with double filtration with easy rail access. G4 filters shall be
provided as standard, with the option to upgrade to one of the following filter grade
combinations:
 G4+F7
 F5+F7
 G4+F9

Compressors

RT-PRG010-E4 Page 2 of 7
TRANE Airfinity™ XL Large Packaged Rooftops

All units shall be equipped with scroll type compressors with intermediate discharge
valves (IDV) located close to the discharge of the compressor. The IDVs shall reduce
excessive compression of refrigerant under part-load conditions while maintaining the
same refrigeration capacity. Compressors shall be connected in tandem.

Compressors shall be direct-drive, hermetic with self-lubrication. Internal temperature


and current sensitive motor overloads shall be included for maximum protection.
Each compressor shall be protected by an external discharge temperature
thermostat, winding temperature thermostat and reverse rotation/phase loss
protection.

Each compressor shall be provided with a direct on line starter, factory mounted,
wired and tested. Soft Starter shall be an available as an option.
Outdoor fans
Rooftop unit shall be equipped with axial condenser fan and motors with permanently
lubricated ball bearings. Fans motors shall be class F, powered through an IP54
terminal box. The fan motors shall be permanently lubricated and shall have built-in
thermal overload protection. EC fans shall be provided as an option.

Indoor fans
Supply fans shall use EC plug fan technology with variable flow control. Impeller shall
be made of sheet aluminum, while support plates and brackets shall be constructed
in galvanized steel. All motors shall be equipped with a thermal overload protector
internally connected.

Hot water coil


This option shall be factory mounted and placed in the heating section. It shall be
shipped with one 3-way valve, 0 to 100% modulating built-in control and protection
against freeze. When integrated into a reversible unit, the option to select the hot
water coil as the primary source of heat shall be provided.

Electric heaters
This option shall be factory mounted and placed in the heating section. Electric
heater elements shall connected for 380 and 415 volt. Staging shall be achieved
through the unit controller. Each heater package shall have automatically reset high
limit control operating through heating element contactors. All heaters shall be
individually fused from factory, where required.

Roof Curb – Downflow configuration


The roof curb shall be designed to match with the downflow configuration unit and
provide support and watertight installation when installed according to supplier
recommendations. The roof curb design shall allow rectangular supply/return
ductwork to be connected directly to the curb.

Transportation and handling


Wooden blocks shall be provided with the unit to avoid damaging of the unit base
during crane lifting.

RT-PRG010-E4 Page 3 of 7
TRANE Airfinity™ XL Large Packaged Rooftops

RT-PRG010-E4 Page 4 of 7
TRANE Airfinity™ XL Large Packaged Rooftops

Refrigeration circuit

General - Refrigerant circuits


Units shall operate with R410A HFC-based refrigerant with a GWP of 2088. Each
refrigerant circuit shall have independent electronic expansion devices, service
pressure ports and refrigerant line filter driers factory-installed as standard. An area
shall be provided for replacement suction line driers. Refrigeration circuits shall be
protected against refrigerant leaks. Service valves shall be provided as standard and
located on the low pressure side of the refrigeration piping.

Heat exchangers
The outdoor heat exchanger shall operate on 100% outdoor air. The coil will be
constructed with 5/16" copper tubes mechanically bonded to plate aluminum plate
fins.

The indoor heat exchanger coils shall be 3/8"internally finned copper tubes
mechanically bonded to high performance aluminum plate fins. Indoor coils shall be
protected with an anti-frost control protection.

Sloped condensate drain pans are standard and provided in full aluminum, and shall
be completely removable for trouble-free maintenance.

Coils will be factory leak tested at 50 bars. If the unit will be installed on corrosive
environment, an option shall be provided for aluminum fins pre-coated with gold
epoxy, with minimum thickness of 8µm, in order to withstand 1000 hours of salt spray
test according ISO 9227.

Electrical panel
Unit shall be provided with an IP54 power panel, with a single point connection with
disconnect switch. The disconnect switch shall be mechanically interlocked to
disconnect line power from power panel, accessible from the outside the unit. All
components and control cables shall be numbered in accordance with CEI 60750.

Fresh air management

Free cooling
The economizer shall be factory installed and provided as a standard for fresh air
management and free cooling applications. The assembly includes: fully modulating
0-100 percent motor and dampers, regulated by an independent ModBus controller
device, minimum position setting, preset linkage, wiring harness, and differential
enthalpy control.

Building pressurization control: Barometric relief damper


The unit shall be provided with a barometric relief damper. The barometric relief
damper shall deliver space pressure equalization and be gravity closing to prohibit
entrance of outside air during the equipment "off" cycle.

RT-PRG010-E4 Page 5 of 7
TRANE Airfinity™ XL Large Packaged Rooftops

Building pressurization control: Power exhaust fan


Power exhaust fan shall be of EC type. It shall be available as a factory installed
option on all unit sizes. It shall assist the barometric relief damper in maintaining
building pressurization.

CO2 sensor
This accessory shall measure CO2 concentration inside the building in order to
increase or decrease the fresh air amount introduced into the building via the rooftop
unit. It shall be compatible with the fresh air and free cooling functions.

Energy recovery (ERM)


The unit shall be equipped with a heat recovery module. The module shall be
provided in one single package which is easy to install without the requirement for an
additional roofcurb. The module shall include:
 Rotary enthalpy wheel, certified by Eurovent
 Exhaust fan of EC plug fan type
 Micro-inverter for freeze protection
 Temperature and humidity sensors
 G4 filters on fresh air
 G4 filters on exhaust air

When free cooling is needed, energy recovery shall be bypassed to avoid heat
exchange on the fresh flow entering the building. Fresh air and exhaust air flow shall
be filtered using G4 filters before entering the heat exchanger in order to prevent
exchanger clogging.

Controls

Controls - General
Units shall be completely factory wired with necessary controls and terminal block for
power wiring. Units shall provide an external location for mounting a fused disconnect
device. The unit controller shall be provided for all 24 volt control functions.

The resident control algorithms shall make all heating, cooling and/or ventilating
decisions in response to electronic signals from sensors measuring indoor and
outdoor temperatures. The control algorithm maintains accurate temperature control,
minimizes drift from set point and provides better building comfort. The unit controller
shall provide anti-short cycle timing and time delay between compressors to provide
a higher level of machine protection.

Heat pump units shall manage alternate defrost cycles based on demand defrost
logic.

Unit shall be powered by 400V/3/50Hz supply (without neutral) on a single point of


power connection.

Through-the-base electrical provision

RT-PRG010-E4 Page 6 of 7
TRANE Airfinity™ XL Large Packaged Rooftops

An electrical service entrance shall be standard which allows access to route all high
and low voltage electrical wiring inside the curb, through the bottom (vertically) and
through the side (horizontally) of the outdoor section of the unit and into the control
box area.

Disconnect switch:
A factory installed disconnect switch with an external handle shall be mounted inside
the unit control box.

Dirty filter detection


This option allows for individual dirty filter indication. In case of dirty filter, a warning
shall be available on the Service Terminal or Building Automation System.

Smoke detector
This option shall trip off in case of presence of smoke in the supply side of the unit
and shall close the return air damper, if any, and stop the unit.

Phase monitoring relay


The phase monitoring relay shall detect phase loss, phase reversal and phase
imbalance from main power supply. In case of fault, the unit shall stop.

Fire thermostats
Manually resettable high temperature thermostats shall provide input to the unit
controls to shut down the system if the temperature measured is 57°C at the return or
115°C at the discharge.

Thermostats and zone sensors


The thermostats and zone sensors shall be provided to interface with the CH536 unit
controller and shall be available in either manual or automatic programmable mode
with system malfunction lights or remote sensor options.

Communication interfaces

The following protocols shall be available to interface with the Building Automation
System: Modbus RTU, Bacnet MS/TP, Lon FTT-10A.

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and
sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems,
comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2018 Trane All rights reserved