General
General configuration
Units shall be dedicated down flow or horizontal airflow, with the possibility to convert
the airflow configuration on-site with minimal modifications to the unit. Unit shall be
able to operate between 46°C and -18°C, in cooling mode. All units shall be factory
assembled wired, fully charged with refrigerant and run-tested before leaving the
factory. Internal wiring is colored and numbered for simplified identification.
All units shall be equipped with dual refrigeration circuits and alternate defrost for
reversible models.
Performance
Units shall be certified and registered on the Eurovent certification under the RT
programme (http://www.eurovent-certification.com). Units net EER shall be a class A
or B in cooling mode. Reversible units net COP shall be a class A or B in heating
mode.
Casing
Unit casing shall be constructed of zinc coated, heavy-gauge, galvanized steel, with
an exception of the panel doors, which shall be built in aluminum. All exterior
components shall be mounted in a weather resistant steel cabinet and painted with a
polyester white RAL 9002 powder paint. Where top cover seams exist, they shall be
double hemmed and gasket sealed to prevent water leakage. Cabinet construction
shall allow access for all maintenance on two sides of the unit. Service panels shall
have double hinged doors which can be opened from the left or the right hand side.
When closed, doors shall provide a water and air tight seal.
The indoor air section shall be fully insulated with a double wall panel and glass wool
with 50mm thickness and density according to norm DIN EN 1602. Insulation shall be
self-maintaining.
Filters
Units shall be provided with double filtration with easy rail access. G4 filters shall be
provided as standard, with the option to upgrade to one of the following filter grade
combinations:
G4+F7
F5+F7
G4+F9
Compressors
RT-PRG010-E4 Page 2 of 7
TRANE Airfinity™ XL Large Packaged Rooftops
All units shall be equipped with scroll type compressors with intermediate discharge
valves (IDV) located close to the discharge of the compressor. The IDVs shall reduce
excessive compression of refrigerant under part-load conditions while maintaining the
same refrigeration capacity. Compressors shall be connected in tandem.
Each compressor shall be provided with a direct on line starter, factory mounted,
wired and tested. Soft Starter shall be an available as an option.
Outdoor fans
Rooftop unit shall be equipped with axial condenser fan and motors with permanently
lubricated ball bearings. Fans motors shall be class F, powered through an IP54
terminal box. The fan motors shall be permanently lubricated and shall have built-in
thermal overload protection. EC fans shall be provided as an option.
Indoor fans
Supply fans shall use EC plug fan technology with variable flow control. Impeller shall
be made of sheet aluminum, while support plates and brackets shall be constructed
in galvanized steel. All motors shall be equipped with a thermal overload protector
internally connected.
Electric heaters
This option shall be factory mounted and placed in the heating section. Electric
heater elements shall connected for 380 and 415 volt. Staging shall be achieved
through the unit controller. Each heater package shall have automatically reset high
limit control operating through heating element contactors. All heaters shall be
individually fused from factory, where required.
RT-PRG010-E4 Page 3 of 7
TRANE Airfinity™ XL Large Packaged Rooftops
RT-PRG010-E4 Page 4 of 7
TRANE Airfinity™ XL Large Packaged Rooftops
Refrigeration circuit
Heat exchangers
The outdoor heat exchanger shall operate on 100% outdoor air. The coil will be
constructed with 5/16" copper tubes mechanically bonded to plate aluminum plate
fins.
The indoor heat exchanger coils shall be 3/8"internally finned copper tubes
mechanically bonded to high performance aluminum plate fins. Indoor coils shall be
protected with an anti-frost control protection.
Sloped condensate drain pans are standard and provided in full aluminum, and shall
be completely removable for trouble-free maintenance.
Coils will be factory leak tested at 50 bars. If the unit will be installed on corrosive
environment, an option shall be provided for aluminum fins pre-coated with gold
epoxy, with minimum thickness of 8µm, in order to withstand 1000 hours of salt spray
test according ISO 9227.
Electrical panel
Unit shall be provided with an IP54 power panel, with a single point connection with
disconnect switch. The disconnect switch shall be mechanically interlocked to
disconnect line power from power panel, accessible from the outside the unit. All
components and control cables shall be numbered in accordance with CEI 60750.
Free cooling
The economizer shall be factory installed and provided as a standard for fresh air
management and free cooling applications. The assembly includes: fully modulating
0-100 percent motor and dampers, regulated by an independent ModBus controller
device, minimum position setting, preset linkage, wiring harness, and differential
enthalpy control.
RT-PRG010-E4 Page 5 of 7
TRANE Airfinity™ XL Large Packaged Rooftops
CO2 sensor
This accessory shall measure CO2 concentration inside the building in order to
increase or decrease the fresh air amount introduced into the building via the rooftop
unit. It shall be compatible with the fresh air and free cooling functions.
When free cooling is needed, energy recovery shall be bypassed to avoid heat
exchange on the fresh flow entering the building. Fresh air and exhaust air flow shall
be filtered using G4 filters before entering the heat exchanger in order to prevent
exchanger clogging.
Controls
Controls - General
Units shall be completely factory wired with necessary controls and terminal block for
power wiring. Units shall provide an external location for mounting a fused disconnect
device. The unit controller shall be provided for all 24 volt control functions.
The resident control algorithms shall make all heating, cooling and/or ventilating
decisions in response to electronic signals from sensors measuring indoor and
outdoor temperatures. The control algorithm maintains accurate temperature control,
minimizes drift from set point and provides better building comfort. The unit controller
shall provide anti-short cycle timing and time delay between compressors to provide
a higher level of machine protection.
Heat pump units shall manage alternate defrost cycles based on demand defrost
logic.
RT-PRG010-E4 Page 6 of 7
TRANE Airfinity™ XL Large Packaged Rooftops
An electrical service entrance shall be standard which allows access to route all high
and low voltage electrical wiring inside the curb, through the bottom (vertically) and
through the side (horizontally) of the outdoor section of the unit and into the control
box area.
Disconnect switch:
A factory installed disconnect switch with an external handle shall be mounted inside
the unit control box.
Smoke detector
This option shall trip off in case of presence of smoke in the supply side of the unit
and shall close the return air damper, if any, and stop the unit.
Fire thermostats
Manually resettable high temperature thermostats shall provide input to the unit
controls to shut down the system if the temperature measured is 57°C at the return or
115°C at the discharge.
Communication interfaces
The following protocols shall be available to interface with the Building Automation
System: Modbus RTU, Bacnet MS/TP, Lon FTT-10A.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and
sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems,
comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
RT-PRG010-E4 Page 7 of 7