Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , OPTIMIZATION AND SIGNAL P ROCESSING

Optimal Placement of Distributed Generation in


Electric Distribution Networks
Dr. Mounir Bouzguenda1, Abdullah Samadi2, S. RajaMohamed3
1,2,3
College of Engineering, King Faisal University
Hofuf-31982, Al-Hasa, Saudi Arabia
1
email: mbuzganda@kfu.edu.sa

Abstract—This paper proposes a simple numerical mechanism [1]. Based on existing of conventional sources
method to determine the optimal location of a power grid, smart grid is a new type of power grid, which
distributed generation (DG) within the distribution highly integrates with renewable energy and modern
network. The main objective of this work is to find the advanced information technologies, communication and
optimal number, the type, the size and the bus location control techniques with power grids. Currently, the power
of DG that would enhance the voltage levels and grids are facing the challenges of interconnected (DG)
reduce the power losses of the distribution network. distributed generation with in it due to their old structure
Initially, load flow, using Newton Raphson Method, and also it affects the utilization of renewable sources for
was carried out without DG to identify the weak the last few years. The model of smart grid has been put
busses on the distribution network, then, the load flow advancing for the power system in the future [2].
simulation was carried out with the DG units being
connected on the identified weak busses to evaluated Distributed Generation
the impact of the DG units on the voltage profile and The contribution of distributed generators (DGs) in electric
power losses. The test case IEEE 30 bus system is power systems has been drastically increasing in the last
modeled using standard load flow software. few years. The growing concern about environmental
Simulation results with the DG units show pollution and more green energy utilization has also made
improvement in terms of voltage profile enhancement DG to be an appropriate auxiliary of the conventional
and power losses reduction. fossil fuel power plants. The design of the power system
with DG and reliability improvement requires considering
Test results indicate that the load flow studies yield important factors, such as, the number, size and type of the
positive impact on the 30-bus distribution systems. The DG units. In addition, the optimal location of these units in
maximum power losses reduction was as high as distribution system has been the subject of many studies.
15.30% and the bus voltage improvement reached 8.72 On the other hand, the connection of the DG units at the
% for optimally placed single DG and 13.89% for 4 inappropriate places on distribution system can increase
DG units. system power losses and drop the voltage level below the
accepted voltage level at certain busses. As a result, the
Keywords— Distributed generation, Power losses optimal placement of DG is extremely essential in order to
reduction, Voltage profile enhancement, Load flow. reduce the overall power system power losses and
therefore improve voltage profile [3].
I.INTRODUCTION
Smart Grids Load Flow Analysis with DG
Currently, all the countries actively involved to reduce Many research activities have proposed various optimal
CO2 (Carbon dioxide) emission objectives, the solution placement methods. These activities range from analytical
for save the environment from CO2 pollution problem to to optimization approaches that have successfully allocated
turn to new energies with more sustainable and renewable. and sized DG units [4-5]. Author in [6] particle swarm
However, the integrating renewable energy sources to the optimization (PSO) algorithm for prime placement of
existing electrical power grid structure has more multi-DG is proposed and tested in IEEE 30 and IEEE 33
challenges that are technical. To increase the efficiency of bus system, the simulation results presented that the
the existing power grid and utilize the renewable energy proposed method effectively reduces the total real power
exactly, new power grid structure that is called ‘smart loss, and improving voltage profile limit. In addition, the
grid’ developed and used to meet the present enormous proposed methodology is compared with other standard
electricity demands of the electricity consumers as utilize optimization algorithm. This method is fast, efficient and
the renewable energy in most proficient way. Smart grid perfect in identifying the optimal number size, type, and
is the most significant and sustainable concepts currently places of DG. Author in [7] proposed hybridized PSO
to provide reliable, secured, clean and high quality known method has been to determine the finest size and
electricity supply to the consumer using advanced control location the DG units based on the power losses drop. The

978-1-5090-4778-9/17/$31.00 ©2017 IEEE


2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , OPTIMIZATION AND SIGNAL P ROCESSING

success of this method is tested on the IEEE 69 bus desired voltage profile is obtained. The system real power
system. The results concluded that proposed method is losses-Plosses, with n busses and M branches, as a function
simple and requires less computational time for finding the of DG size and system bus voltages is defined as follows:
optimum size and location of DG compared to EP and M
PSO algorithms. Author in [8], the DG optimal placement Plosses ¦P line( i , j ) (1)
DG is an integer problem and can be formulated using line( i , j ) 1
metaheuristic methods. Other work used Genetic
Algorithm (GA) to solve the DG placement and size and Pline(i , j ) Pi  Pj (2)
implemented on the IEEE 123 bus test system. Results
demonstration that the total losses were significantly
reduced by allocating the optimum size of DG in the Pi = PDGi - PDi Vi ¦ V >g k ik cos( T i  T k ) + b ik sin( T i  T k )@
optimum placement. In addition, the voltage profile of the (3)
network was within the specified standard range and in
¦ V >g sin( Ti  Tk ) + bik cos( Ti  Tk )@
general, voltage profile is enhanced.
Qi = QDGi - QDi Vi k ik

This paper presents the impacts of connected DG into (4)


distribution networks and investigates the optimal
locations and sizes of DGs using a simple numerical Where,
method. In Section II, a brief discussion of distributed x i is the location of DG unit (i=1, 2, 3…, n)
generation issues is presented. Section III discusses the x n is the total number of bus bars in the distribution
proposed numerical method used for a minimization of network.
power losses and improvement of voltage profile. Test x M is the number of branches in the power system
case system modelling and simulation on the IEEE 30 Bus x Pi and Qi are net real and reactive power injection in
system are reported in Section IV of the paper. Results and bus i, respectively.
discussions are included in Section V. Finally, Section VI x Vi and δi are the voltage magnitude and voltage angle
outlines the conclusion and recommendations. at bus i, respectively.
x PDGi and QDGi are the real and reactive power
II.DISTRIBUTED GENERATION generations of DG at bus i.
x PDi and QDi are the real and reactive power demand at
The distributed generation (DG) has different names for bus I, respectively.
x QDG is zero
different countries and for different regulatory agencies.
For instance, IEA-the International Energy Agency
defines distributed generation as a generating plant Therefore, the aim is to minimize Ploss subject to the
serving a utility or providing auxiliary support to a following constraints:
distribution network, connected to the grid at distribution- Vi min d Vi d Vi max (5)
level voltages. Moreover, CIGRE defines DG as a
generating plant that has the following characteristics:
Pline(i , j ) d Pline(i , j ) max (6)
x It is neither centrally planned and nor centrally
dispatched at the present stage. Properly setting the values of Vi,min and Vi,max would result
x It is normally connected and worked with distribution in a better system voltage profile [10]-[11].
network.
x The size is small and ranges from 50 MW to less than IV.METHODOLOGY
100 MW. Other organizations such as the Electric
Power Research Institute defines distributed The methodology consists of four main steps. The first
generation as generation size from a few kilowatts up step is to perform the load flow analysis on the network
to 50 MW. without distributed generation. The power losses and bus
voltages values are used as a reference. The second step is
The standard definition of the DG system is "Distributed to identify busses and feeders with significant losses and
Generation is an electric power source tied directly to the voltage violation. A voltage violation occurs when the bus
distribution network or on the consumer of the meter" [9]. voltage is not within the 5 percent margin. The third step is
to run the load analysis with the distributed generation
III.PROBLEM FORMAULTION connected to the identified busses either one bus at a time
or multiple busses at a time. The obtained results are
In this work, the number, location and size of DG units are compared with the reference case. The case that has
selected based on the minimum system power loss and highest power losses reduction and lowest voltage
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , OPTIMIZATION AND SIGNAL P ROCESSING

deviation violation is considered as the optimal case. The Table I. IEEE 30 Bus Description
voltage deviation 'V is expressed as: Item Details
N Busses 30
¦ 1  v
2
'V i (7) Lines 40
i 1 Generators Feeders 6
Where N is the number of busses in the system and i is the PV System Candidate
bus number. 2, 3, 4, 5, 6, 7, 8, 28
Busses
Transformers 4
The fourth step is to run the technical feasibility of the Slack Bus 1
distributed generation system in terms of land availability, PV Buses 2, 13, 22, 23, 27
prices and access. This step is beyond the scope of the 3,4,5,7,8,10,12,14,15,16,17,
paper and can be considered in a subsequent study. Further PQ Buses
18,19,20,21,24,26,29,30
improvement is the sensitivity analysis regarding DG
power factor, real and reactive power demands.
VI.RESULTS AND DISCUSSION
V.MODELLING AND SIMULATION The proposed methodology was investigated using the
IEEE 30 Bus system without distributed generation with
The IEEE 30-bus system as shown in Fig.1, standard the aim of finding critical busses. This will be referred to
data’s listed in Table I is selected to evaluate to the as a reference case. The reference case results without
placement and sizing methodology using a 20 MW solar distributed generation indicate that busses 4, 5, 6, 7 and
power plan within the distribution network and the impact 28, listed in Table II have a voltage below 0.95 p.u. All
on the power losses and bus voltages. The line other busses are within the accepted voltage range. While
characteristics of the IEEE 30 bus systems are found in Table 3 lists the power generation level for busses 1, 2,
Appendix A.During load flow analysis, the IEEE 30-bus 13, 22, 23 and 27. The total real power and reactive power
system power demand is 283.8 MW and 126.2 MVAR losses are estimated at 21.99 MW, 59.84 MVA,
with a power factor of 86 % and a total generation of respectively.
304.79 MW and 186.04 MVAR, with a power factor of
91%. A voltage violation occurs if the voltage at the bus is Table II. Busses Under Voltage Violation For The
below 0.95 p.u. or above 1.05 p.u. The cumulative Reference Case
distributed generation of 20 MW with a unity power
Per unit Load
factor is assumed throughout the study. Bus Load MW
voltage MVAR
5 0.913 94.200 19.000
6 0.943 0.000 0.000
7 0.924 22.800 10.900
8 0.929 30.000 30.000
28 0.945 0.000 0.000

Table III.Real and Reactive Power Generation Without


Distributed Generation
Bus 1 2 13 22 23 27 Total
Real
Power 264.79 40.00 0.00 0.00 0.00 0.00 304.79
(MW)
Reactive
Power 89.37 25.68 4.55 45.05 0.00 21.39 186.04
(MVAR)

To assess the impact of distributed generation on the


system power losses and voltage profile, 10 cases were
considered. The details of these cases are shown in Table
4. For Case 9, two solar PV units each rated 10 MW are
connected into the system. While, in Case 10, four DG
units; each rated 5 MW; are connected at 4 different
Fig. 1. IEEE 30-bus power system [11] busses. The solar panels and balance of systems
characteristics are not within the scope of the present
paper.
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , OPTIMIZATION AND SIGNAL P ROCESSING

Table IV. Selected Dg Placement Locations On the other hand, the voltage levels in the busses listed
Case Location Description in Table II and shown in Fig.3, has improved by almost 1
Case 1 Bus 2 percent for busses 5, 7 and 8 and by less than 0.5% for
Case 2 Bus 3 busses 3, 6 and 28.
Case 3 Bus 4
Case 4 Bus 5
One unit rated 20 MW Voltage Deviation at busses 2-8 and at bus 28
Case 5 Bus 6 0.100

Case 6 Bus 7 0.090


Ref Case 1 Case 2
Case 7 Bus 8 Case 3 Case 4 Case 5
Case 8 Bus 28 0.080 Case 6
Case 9
Case 7
Case 10
Case 8

Bus 5 and 0.070


Case 9 One 10 MW unit at each bus
Bus 7 0.060
Busses 5
Case 10 One 5 MW unit at each bus
through 8 0.050

0.040

The power generation and power losses are listed in Table 0.030
V. As shown in Table V, Case 4, Case 5 and Case 9 have
the lowest power generation and the lowest power losses; 0.020

with Case 1 has the highest power generation and losses 0.010

of 303.74 MW and 19.92 MW, respectively. It is worth 0.000

mentioning that placing the distributed generation in bus 5 3 4 5 6 7 8 28

or bus 6 (Case 4 and Case 5) yielded the same values. Fig 3. Impact of distributed generation on the voltage
Fig.2 shows actual power losses of all cases including the levels for busses 3 through 8 and 28.
reference case and the relative power losses reduction
with the respect to the reference case, shown in solid
orange. VII. CONCLUSION
In this paper, the authors presented a simple numerical
method to find the optimal location or locations of a
distributed solar photovoltaic power generation within a
standard distribution network. The Newton Raphson
based load flow method was without and with distribution
and proved effective for a system with a limited number
of busses. The ideal bus for placing distributed generation
were either bus 5 or bus 6, for which the impact on the
power losses and bus voltage improvement were identical.
Overall, test results indicated the positive impact of the 20
MW solar PV system on the 30-bus distribution systems
with power losses reduction as high as 15.30%

Further studies deem necessary such as sensitivity


Fig 2. Impact of distributed generation on power losses
analysis while considering the DG power factor and size.
for the different connection scenarios
Other studies would include the annual energy losses
reduction, energy losses savings and DG financial
Table V. Power Generation and Power Losses for
benefits, solar PV in this case including solar panel types,
all Cases with Distributed Generation
balance of system and maintenance requirements.
Reactive Power
Real Power (MW)
Case (MVAR)
Generation Losses Generation Losses REFERENCES
Case 4 301.58 17.78 174.96 48.77
Case 5 301.58 17.78 174.96 48.77 [1]. U.S. Department of Energy. The Smart Grid: An
Case 9 301.66 17.85 175.36 49.16 Introduction. United States of America. 2008
Case 6 301.80 18.02 176.02 49.82 [2]. Hasmi, M. Hanninen, S. and Maki, K., Survey of Smart
Case 10 301.87 18.08 176.00 49.80 Grid Concepts, Architectures, and Technological
Case 7 302.10 18.31 176.62 50.43 Demonstrations Worldwide. IEEE, 2011.
Case 8 302.15 18.36 176.71 50.52 [3]. Celli G., Ghiani E., Mocci S. and Pilo F., “A
Case 3 302.66 18.87 178.72 52.52 multiobjective evolutionary algorithm for the sizing and
Case 2 303.19 19.40 180.17 53.98 siting of distributed generation,” IEEE Transactions on
Case 1 303.74 19.92 182.68 56.48 Power Systems, 2005, vol. 20, no. 2, pp 750-757.
2017 IEEE INTERNATIONAL CONFERENCE ON INTELLIGENT T ECHNIQUES IN CONTROL , OPTIMIZATION AND SIGNAL P ROCESSING

[4]. John E. Candelo, Helman Hernández Riaño,’’Location Line Line Impedance (p.u.) Half line
and Size of Distributed Generation to Reduce Power Charging
Losses using a Bat-inspired Algorithm’’ VII Simposio Susceptance
From To Resistance Reactance
Internacional sobre la calidad de la energía eléctrica
(p.u.)
SICEL 2013.
[5]. N.Acharya, P. Mahat, N. Mithulananthan, “An 2 6 0.0581 0.1763 0.0187
Analytical approach for DG allocation in Primary 4 6 0.0119 0.0414 0.0045
Distribution Network,” Electrical Power and Energy 5 7 0.046 0.116 0.0102
Systems, Elsevier, Vol. 28, pp. 669-678, 2006. 6 7 0.0267 0.052 0.0085
[6]. K. Varesi, “Optimal Allocation of DG Units for Power
Loss Reduction and Voltage Profile Improvement of
6 8 0.012 0.042 0.0045
Distribution Networks using PSO Algorithm, World 6 9 0.0 0.208 0.0
Academy of Science, Engineering and Technology Vol:5 6 10 0.0 0.556 0.0
2011-12-26. 9 11 0.0 0.208 0.0
[7]. Haruna Musa, Sanusi Sani Adamu,’’Optimal Allocation 9 10 0.0 0.11 0.0
and Sizing of Distributed Generation for Power Loss
Reduction using Modified PSO for Radial Distribution 4 12 0.0 0.256 0.0
Systems’’, Journal of Energy Technologies and Policy, 12 13 0.0 0.14 0.0
Vol.3, No.3, 2013. 12 14 0.1231 0.2559 0.0
[8]. Mohd RuddinAb Ghani, Ihsan Jabbar Hasan, Chin Kim 12 15 0.0662 0.1304 0.0
Gan, Z. Jano,’’ Losses Reduction and Voltage 12 16 0.0945 0.1987 0.0
Improvement with Optimum DG Allocation using GA,
MAGNT Research Report Vol.3 (6). PP: 16-23, 2015 14 15 0.221 0.1997 0.0
[9]. El-Khattam W. and Salama M.M.A., “Distributed 16 17 0.0824 0.1923 0.0
generation technologies, definitions and benefits”, 15 18 0.1073 0.2185 0.0
Electric Power System Research., 2004, 71, pp. 119–128. 18 19 0.0639 0.1292 0.0
[10]. [10] M. H. Aliabadi, B. Behbahani, A. Jalilvand,
19 20 0.034 0.068 0.0
“Combination of GA and OPF for Allocation and Active
and Reactive Power Optimization in Distributed 10 20 0.0936 0.209 0.0
Generation Units,” 2nd IEEE International Conference 10 17 0.0324 0.0845 0.0
on Power and Energy (PECon 08) Johor Baharu, 10 21 0.0348 0.0749 0.0
Malaysia, December 1-3, 2008. 10 22 0.0727 0.1499 0.0
[11]. [11] M. J. Jahromi, E. Farjah, M. Zolghadri, “Mitigating
21 22 0.0116 0.0236 0.0
Voltage Sag By Optimal Allocation Of Distributed
Generation Using Genetic Algorithm,” 9th International 15 23 0.1 0.202 0.0
Conference, Electrical Power Quality and Utilization, 22 24 0.115 0.179 0.0
Barcelona, 9-11 October, 2007. 23 24 0.132 0.27 0.0
24 25 0.1885 0.3292 0.0
APPENDIX A: IEEE 30 BUS LINE DATA 25 26 0.2544 0.38 0.0
25 27 0.1093 0.2087 0.0
Line Line Impedance (p.u.) Half line 28 27 0.0 0.396 0.0
Charging 27 29 0.2198 0.4153 0.0
From To Resistance Reactance Susceptance 27 30 0.3202 0.6027 0.0
(p.u.)
29 30 0.2399 0.4533 0.0
1 2 0.0192 0.0575 0.0264
8 28 0.0636 0.2 0.0214
1 3 0.0452 0.1852 0.0204
6 28 0.0169 0.0599 0.065
2 4 0.057 0.1737 0.0184
3 4 0.0132 0.0379 0.0042
2 5 0.0472 0.1983 0.0209

You might also like