TEST RESULT OF CONCRETE CUBE

NAME OF WORK:-CONSTRUCTION OF 10+2 LEVEL SCHOOL BUILDING (G+2) AT UPGRADED SENIOR SECONDARY SCHOOL
BILASPUR,BLOCK:- MAIRWA,DIST:-SIWAN GROUP NO:-SSS-1439
NAME OF AGENCY:-SHASHI KUMAR SINGH AGREEMENT NO:-11 F2 OF 2021-22 REFERENCE:-Lt No:- BSEIDC/GS/A.E/-27A-12/21 ,Dated…
27.12.2021 OF A.E BSEIDC LTD, DIST:-SIWAN

Obtained Average Required of


Date of NATURE OF Test at Area of Maximum Compressive Compressive Compressive
Sl. No. Conecreeti WORK
Mix Desing Date of Test
Days Cube in Load kg. Strength in kg. Strength in kg. Strength in kg. Remarks
ng Cm2
cm2 cm2 cm2
1 2 4 5 7 10 12 13 14 15 17
05.12.2021 M25 03.01.2022 28 225 65500 291.11
2nd FLOOR
1 " SLAB " " - 225 65750 292.22 290.74 -
CASTING
" " " - 225 65000 288.89
05.12.2021 M25 03.01.2022 28 225 64750 287.78 TEST IS
2nd FLOOR
2 " SLAB " " - 225 66500 295.56 291.11 - CONDUCTED
CASTING AS PER
" " " - 225 65250 290.00 SAMPLE
RESIEVED AT
05.12.2021 M25 03.01.2022 28 225 65000 288.89 LAB.VIDE
2nd FLOOR
3 " SLAB " " - 225 65500 291.11 292.59 - ABOVE
CASTING REFERENCE
" " " - 225 67000 297.78
05.12.2021 2nd FLOOR M25 03.01.2022 28 225 67000 297.78
4 " SLAB " " - 225 62500 277.78 291.85 -
CASTING
" " " - 225 67500 300.00

A.D, R.C.D., Quality Control, Siwan Letter No.___________Date______________


SAMPLE IS SUPLIED BY J.E OF ABOVE MENSIONED WORK SITE

A.R.O. A.D
Quality Control Quality Control
Road Division, Siwan Road Division, Siwan
TEST RESULT OF CONCRETE CUBE
NAME OF WORK:-CONSTRUCTION OF 10+2 LEVEL SCHOOL BUILDING (G+2) AT UPGRADED SENIOR SECONDARY SCHOOL
BILASPUR,BLOCK:- MAIRWA,DIST:-SIWAN GROUP NO:-SSS-1439
NAME OF AGENCY:-SHASHI KUMAR AGREEMENT NO:-11 F2 OF 2021-22 REFERENCE:-Lt No:- BSEIDC/GS/A.E/-01A-01/22
SINGH ,Dated…01.01.2022 OF A.E BSEIDC LTD, DIST:-SIWAN

Obtained Average Required of


Sl. Date of NATURE OF Area of Maximu Compressive Compressive Compressiv
No Conecreeti WORK
Mix Desing Date of Test Test at Days Cube in m Load Strength in kg. Strength in kg. e Strength Remarks
. ng Cm2 kg.
cm2 cm2 in kg. cm2

1 2 4 5 7 10 12 13 14 15 17

27.12.2021 M25 02.01.2022 7 225 42500 188.89


TEST IS
CONDUCTED
AS PER
1 " SLAB " " - 225 43500 193.33 189.63 - SAMPLE
CASTING RESIEVED AT
LAB.VIDE
ABOVE
REFERENCE
" " " - 225 42000 186.67

A.D, R.C.D., Quality Control, Siwan Letter No.___________Date______________


SAMPLE IS SUPLIED BY J.E OF ABOVE MENSIONED WORK SITE

A.R.O. A.D
Quality Control Quality Control
Road Division, Siwan Road Division, Siwan
25+3.3 28.3X10.1972
288.58KG/CM2
TEST RESULT OF CONCRETE CUBE
NAME OF WORK:-CONSTRUCTION OF 10+2 LEVEL SCHOOL BUILDING (G+2) AT UPGRADED SENIOR
BILASPUR,BLOCK:- MAIRWA,DIST:-SIWAN GROUP NO:-SSS-1439
NAME OF AGENCY:-SHASHI KUMAR AGREEMENT NO:-11 F2 OF 2021-22 REFERENCE:-Lt No:- BSE
SINGH 23.12.20212 OF A.E BSEI

Obtained
Sl. Date of NATURE OF Area of Maximu Compressive
No Conecreeti WORK
Mix Desing Date of Test Test at Days Cube in m Load Strength in kg.
. ng Cm2 kg.
cm2

1 2 4 5 7 10 12 13

18.12.2021 M25 24.12.2021 7 225 43000 191.11

PARAPET
1 " STIFENER " " - 225 42750 190.00
CASTING

" " B - 225 42500 188.89

A.D, R.C.D., Quality Control, Siwan Letter No._____


SAMPLE IS SUPLIED BY J.E OF ABOVE MENSIONED WORK SITE

A.R.O.
Quality Control
Road Division, Siwan
UBE
UPGRADED SENIOR SECONDARY SCHOOL

ERENCE:-Lt No:- BSEIDC/GS/A.E/-…....... ,Dated…


2.20212 OF A.E BSEIDC LTD, DIST:-SIWAN

Average Required of
Compressive Compressiv
Strength in kg. e Strength Remarks
cm2 in kg. cm2
25+3.3 28.3X10.1972
14 15 17 288.58KG/CM2

TEST IS
CONDUCTED
AS PER
190.00 - SAMPLE
RESIEVED AT
LAB.VIDE
ABOVE
REFERENCE

iwan Letter No.___________Date______________

A.D
Quality Control
Road Division, Siwan