Professional Documents
Culture Documents
ONGC Report
ONGC Report
(2021-22)
Mentored by,
Mrs. Garima Verma
SE (M)
Electrical Maintenance
Tel Bhavan, ONGC Dehradun
2
ACKNOWLEDGEMENT
The project is done as summer training with the objective of familiarisation with
the industry during summer vacations. We have taken a lot of effort into this
project/training. We acquire this opportunity with much pleasure to acknowledge
the invaluable assistance of Oil and Natural Gas Corporation Limited and all the
people who have helped us through the course of our journey in the successful
completion of this training.
We would like to express our deepest appreciation to all those who provided us
the possibility to complete this report. A special gratitude we give to our project
mentor, Mrs. Garima Verma, SE(M), ONGC Ltd., whose contribution in
stimulating suggestions and encouragement, helped us to coordinate our project
especially in writing this report.
We would like to thank our mentor for organizing virtual visits to different ONGC
venues. Our deepest thanks to Mr. Vachaspati Sharma for conducting our online
visit to ONGC Hospital and clearing all our doubts regarding components and
their process of working.
The completion of this project could not have been possible without the
participation and assistance of a lot of individuals contributing to this project so
last but not least, we would like to thank everyone who is involved in the project
directly or indirectly.
3
TABLE OF CONTENTS
Sl.
Contents Page No.
No.
13 Conclusion 100
14 Bibliography 101
4
EXECUTIVE SUMMARY
DG Sets: -
Diesel generating sets are used in places without connection to a power grid, or
as an emergency power supply if the grid fails, as well as for more complex
applications such as peak-lopping, grid support, and export to the power grid.
Set sizes range from 8 to 30 kW (also 8 to 30 KVA single phase) for homes, small
shops, and offices with the larger industrial generators from 8 KW (11 KVA) up
to 2,000 kW (2,500 KVA three-phase) used for large office complexes, factories,
and other industrial facilities. A 2,000 KW set can be housed in a 40 ft. (12 m)
ISO container with a fuel tank, controls, power distribution equipment, and all
other equipment needed to operate as a standalone power station or as a standby
5
backup to grid power. These units, referred to as power modules, are gensets on
large triple axle trailers weighing 85,000 pounds (38,555 kg) or more. A
combination of these modules is used for small power stations and these may use
from one to 20 units per power section and these sections can be combined to
involve hundreds of power modules. In these larger sizes, the power module
(engine and generator) are brought to the site on trailers separately and are
connected with large cables and a control cable to form a complete synchronized
power plant. Several options also exist to tailor specific needs, including control
panels for auto start and mains paralleling, acoustic canopies for fixed or mobile
applications, ventilation equipment, fuel supply systems, exhaust systems, etc.
Diesel generators are not only for emergency power, but may also have a
secondary function of feeding power to utility grids either during peak periods,
or periods when there is a shortage of large power generators. In the UK, this
program is run by the national grid and is called STOR.
Ships often also employ diesel generators, sometimes not only to provide
auxiliary power for lights, fans, winches, etc. but also indirectly for main
propulsion. With electric propulsion the generators can be placed in a convenient
position, to allow more cargo to be carried. Electric drives for ships were
developed before World War I. Electric drives were specified in many warships
built during World War II because manufacturing capacity for large reduction
gears was in short supply, compared to capacity for manufacture of electrical
equipment. Such a diesel-electric arrangement is also used in some very large
land vehicles such as railroad locomotives.
6
HVAC Systems: -
HVAC (heating, ventilating, and air conditioning) is the technology of indoor and
vehicular environmental comfort. Its goal is to provide thermal comfort and
acceptable indoor air quality. HVAC system design is a sub-discipline of
mechanical engineering, based on the principles of thermodynamics, fluid
mechanics, and heat transfer. HVAC is important in the design of medium to large
industrial and office buildings such as skyscrapers and in marine environments
such as aquariums, where safe and healthy building conditions are regulated
concerning temperature and humidity, using fresh air from outdoors.
The filtered and cleaned air then is used in heating, ventilation, and air
conditioning. Air cleaning and filtration should be taken into account when
protecting our building environments. Today’s Air-Conditioning (AC)
technology is so prevalent that it is considered a necessity for the majority of
residential and commercial buildings throughout the world. During the 100-plus
years of development, Air-Conditioners have been optimized for cost and
thermodynamic efficiency, both of which are nearing their practical limits. In
modern buildings, the design, installation, and control systems of these functions
7
are integrated into one or more HVAC systems. For very small buildings,
contractors normally estimate the capacity, engineer, and select HVAC systems
and equipment.
For larger buildings, building service designers, mechanical engineers, or
building services engineers analyse, design, and specify the HVAC systems.
Speciality mechanical contractors then fabricate and commission the systems.
Building permits and code-compliance inspections of the installations are
normally required for all sizes of buildings.
The report also includes the study of different types of refrigerants and their effect
on the cooling load, efficiency, and environment. It consists of a detailed study
of equipment like the Air handling unit, Fan coil unit, and Cooling Towers, their
operations, and maintenance. In the end, the project involves the subjective
analysis of HVAC systems and comes up with the probable solution for the
problems faced in the operation of HVAC systems.
8
INTRODUCTION TO ONGC
Oil and Natural Gas Corporation (ONGC) is a Public Sector Undertaking (PSU)
of the Government of India, under the administrative control of the Ministry of
Petroleum and Natural Gas, registered in New Delhi. It is India's largest oil and
gas exploration and production company. The headquarters is located in
Dehradun, India. It is India's largest oil and gas exploration and production
company. It produces around 70% of India's crude oil (equivalent to around 57%
of the country's total demand) and around 84% of its natural gas. In November
2010, the Government of India conferred the Maharatna status to ONGC.
On 19 May 2014, its market capitalization hit the highest of INR 3.56 trillion. On
July 10th, the market capitalization hit INR 1.48 trillion. In a government survey
for FY 2019-20, it was ranked as the largest profit-making PSU in India. ONGC
has been ranked 190th in the Fortune Global 500 list of the world's biggest
corporations for the year 2020. It is ranked 11th among the Top 250 Global
Energy Companies by Platts on September 25th,2017.
ONGC was founded on 14 August 1956 by the Government of India, which
currently holds a 69.23% equity stake. It is involved in exploring for and
exploiting hydrocarbons in 26 sedimentary basins of India and owns and operates
over 11,000 kilometres of pipelines in the country. ONGC has discovered 7 of
the 8 commercially producing Indian Basins, in the last 50 years, adding over
7.15 billion tons of In-place Oil & Gas volume of hydrocarbons in Indian basins.
Against a global decline of production from matured fields, ONGC has
maintained production from its brownfields like Mumbai High, with the help of
aggressive investments in various IOR (Improved Oil Recovery) and EOR
(Enhanced Oil Recovery) schemes.
9
ONGC Group of Companies comprises of Oil and Natural Gas Corporation
Limited (ONGC - The Parent Company); ONGC Videsh Limited (OVL - a
wholly-owned subsidiary of ONGC); ONGC Nile Ganga BV (ONG BV - a
wholly-owned subsidiary of OVL) and Mangalore Refinery and Petrochemicals
Limited (MRPL - a subsidiary of ONGC).
ONGC Videsh Limited (OVL) is the overseas arm of ONGC, engaged in
Exploration & Production Activities. It trans-national operates E&P Business in
15 countries, making ONGC the biggest Indian Multinational Corporation. In
recent years, it has laid footholds in hydrocarbon acreage in various countries
including Ivory Coast and Australia. ONGC Nile Ganga BV is a wholly-owned
subsidiary of OVL and has equity in the producing field in Sudan.
ONGC has many matured fields with a current recovery factor of 25-33%. Its
Reserve Replacement Ratio for between 2005 and 2014, has been more than one.
During FY 2012-13, ONGC had to share the highest ever under-recovery of INR
494.2 million (an increase of INR 49.6 million over the previous financial year)
towards the under-recoveries of Oil Marketing Companies (IOC, BPCL, and
HPCL).
History: -
a) 1947-1960: -
During pre-independence, the Assam Oil Company in the North-Eastern and
Attock Oil Company in the North-Western part of undivided India were the only
oil companies producing oil in the country. The major part of Indian sedimentary
basins was deemed to be unfit for the development of oil and gas resources.
After independence, the Government
realized the importance of oil and gas for
rapid industrial development and its strategic
role in defence. Consequently, while framing
the Industrial Policy Statement of 1948, the
development of the hydrocarbon industry in
the country was considered to be of utmost
necessity.
10
Until 1955, private oil companies mainly explored the hydrocarbon resources of
India. The Assam Oil Company was producing oil at Digboi, Assam (discovered
in 1889), and the Oil India Ltd. (a 50% joint venture between the Government of
India and Burma Oil Company) was engaged in developing two fields
Naharkatiya and Moran in Assam. In West Bengal, the Indo-Stanvac Petroleum
project (a joint venture between the Government of India and Standard Vacuum
Oil Company of the USA) was engaged in exploration work. The vast
sedimentary tract in other parts of India and adjoining offshore remained largely
unexplored.
In 1955, the Government of India decided to develop the oil and natural gas
resources in the various regions of the country as part of Public Sector
development. With this objective, an Oil and Natural Gas Directorate was set up
in 1955 under the then Ministry of Natural Resources and Scientific Research.
The department was constituted with a nucleus of geoscientists from the
Geological Survey of India. A delegation under the leadership of Mr. K.D.
Malviya, the then Minister of Natural Resources, visited several countries to
study the oil industry and to facilitate the training of Indian professionals for
exploring potential oil and gas reserves. Foreign experts from the USA, West
Germany, Romania, and the erstwhile USSR visited India and helped the
government with their expertise. Finally, the visiting Soviet experts drew up a
detailed plan for geological and geophysical surveys and drilling operations to be
carried out in the 2nd Five Year Plan (1956-57 to 1960-61).
In April 1956, the Government of India adopted the Industrial Policy Resolution,
which placed the mineral oil industry amongst the Schedule 'A' industries, the
future development of which was to be the sole and exclusive responsibility of
the state.
Soon, after the formation of the Oil and Natural Gas Directorate, it became
apparent that it would not be possible for the Directorate with limited financial
and administrative powers to function efficiently. So in August 1956, the
Directorate was raised to the status of a commission with enhanced powers,
although it continued to be under the government. In October 1959, the
Commission was converted into a statutory body by an act of Parliament, which
enhanced the powers of the commission further. The main functions of the Oil
and Natural Gas Commission subject to the provisions of the Act were "to plan,
promote, organize and implement programs for the development of Petroleum
Resources and the production and sale of petroleum and petroleum products
produced by it, and to perform such other functions as the Central Government
may, from time to time, assign to it".
11
b) 1960-1990: -
Since its inception, ONGC has been instrumental in transforming the country's
limited upstream sector into a large viable playing field. In the inland areas,
ONGC not only found new resources in Assam but also established a new oil
province in the Cambay basin (Gujarat), while adding new petroliferous areas in
the Assam-Arakan Fold Belt and East coast basins (both inland and offshore).
ONGC went offshore in the early ‘70s and discovered a giant oil field in the form
of Bombay High, now known as Mumbai High. This discovery, along with
subsequent discoveries of huge oil and gas fields in Western offshore changed
the oil scenario of the country. Subsequently, over 5 billion tons of hydrocarbons,
which were present in the country, were discovered. The most important
contribution of ONGC, however, is its self-reliance and development of core
competence in E&P activities at a globally competitive level.
c) 1990-Present: -
After the conversion of business of the
erstwhile Oil & Natural Gas Commission to
that of Oil & Natural Gas Corporation
Limited in 1993, the Government
disinvested 2 percent of its shares through
competitive bidding. Subsequently, ONGC
expanded its equity by another 2 percent by
offering shares to its employees.
In March 1999, ONGC, Indian Oil Corporation (IOC) - a downstream giant and
Gas Authority of India Limited (GAIL) - the only gas marketing company, agreed
to have a cross-holding in each other's stock. This paved the way for long-term
strategic alliances both for the domestic and overseas business opportunities in
the energy value chain, amongst themselves. Consequent to this the Government
sold off 10 percent of its shareholding in ONGC to IOC and 2.5 percent to GAIL.
With this, the Government holding in ONGC came down to 84.11 percent.
In the year 2002-03, after taking over MRPL from the A V Birla Group, ONGC
diversified into the downstream sector. ONGC has also entered the global field
through its subsidiary, ONGC Videsh Ltd. (OVL). ONGC has made major
investments in Vietnam, Sakhalin, Columbia, Venezuela, Sudan, etc., and earned
its first hydrocarbon overseas revenue from its investment in Vietnam.
12
Oil and Natural Gas Corporation Limited Dehradun: -
The headquarters of the Oil and Natural Gas Corporation Limited at Dehradun
(ONGC) was set up in Tel Bhawan (Patiala House), Dehradun in 1956. ONGC is
the foremost exploration and production company in India. It is responsible for
most of the exploration effort, established reserves, and oil and gas production in
India. ONGC possesses the fiscal, technical and managerial strength to rank as a
world-class oil and gas company.
Oil and Natural Gas Corporation Limited (ONGC) at Dehradun constitutes part
of a company with a global vision and
noble mission. Having a workforce of
over 41,000 dedicated to constant
technological innovation and up-
gradation, it employs experts in its
business. Apart from an excellent
atmosphere for growth, the company
offers a remuneration package at par
with the best in the Indian
industry.
13
Strengths: -
a. O.N.G.C LTD is perceived to be the leader in the oil production industry.
b. O.N.G.C has a very efficient and professional management team.
c. O.N.G.C being an international company has sufficient resources and
capital to invest.
d. Overseas acquisition in the oil field has increased to seventeen countries
and leads to increased production on a sharing basis.
e. Energy utilization of buried coal resources (700 -1700M), estimated 63BT
– Equivalent to 15000 BCM.
Weakness: -
a. O.N.G.C facing difficulties to produce oil from ageing reservoirs.
b. Security of personnel & property especially crude oil continues to be a
cause of concern in certain areas.
c. In some exploration, Campaign Company involves high technology, High
investment, and high risks.
Threats: -
a. Non-availability of deep drilling RIGS in international markets.
b. Depleting reservoirs all over the world.
c. Policies all over the world demand a decrease in oil production due to
increased concern for global warming and greenhouse gases.
Profile: -
a. Forbes has ranked ONGC, 3rd largest in India and 220 worldwide.
b. It is ranked 160th in Forbes Global 500 list of the World's biggest
companies for 2019.ONGC ranks 377 in the Forbes Global list of 750 World
Best Employers compiled in partnership with Statista, the market research
firm.
c. ONGC has been ranked 39th among the world's 105 largest listed
companies in 'transparency in corporate reporting' by Transparency
International making it the most transparent company in India.
14
ONGC: India's Most Valuable Public Sector Enterprise: -
a. The Company won Petrified Oil & Gas Industry Awards 2011 in three
categories- "Environmental Sustainability: Company of the Year", "Human
Resource Management: Company of the Year" and "Innovator of the Year:
Team (Won by IOGPT)".
b. It was bestowed with the "Most Attractive Employer" Award in Randstad
Awards 2011.
c. Won "Golden Peacock Award for Sustainability" for the year 2011.
d. Awarded with the Gold Trophy of SCOPE Meritorious Award for
"Environmental Excellence & Sustainable Development" for the Year 2010-
11 by former President Smt. Pratibha Devi Singh Patil.
e. Anointed "Outstanding PSU of the Year" at AIMA Managing India
Awards 2012.
f. Awarded the Best Overall Performance PCRA Award in the Upstream
Sector (Oil & Gas) for the 3rd consecutive year.
g. Awarded the "ICSI National Award for Excellence in Corporate
Governance for 2011"- Certificate of Recognition.
h. Awarded NIPM National Award for Best HR Practices – 2011.
i. Adjudged amongst 20 Top Companies for Leaders 2011 in Aon Hewitt
Awards.
j. "Best Enterprise Award" for the organization in the Maharatna and
Navratna Category at the 22nd National Meet of Women in Public Sector
(WIPS).
k. It was bestowed with Safety Innovation Award 2011 in the Oil & Gas
sector for innovative safety measures.
15
Listing and Shareholding: -
The equity shares of ONGC
are listed on the Bombay
Stock Exchange where it is a
constituent of the BSE
SENSEX index the National
Stock Exchange of India
where it is a constituent of the
S&P CNX Nifty. As of 31
March 2021, the Government
of India held around 60%
equity shares in ONGC. Over
480,000 individual
shareholders hold approx.
2.45% of its shares.
16
AN INTRODUCTION TO ENGINES
An engine is a device that converts one form of energy into another useful form
of energy. If we talk in the language of thermodynamics and engineering, a heat
engine is a system that converts heat to mechanical energy, which can then be
used to do mechanical work. It does this by bringing a working substance from a
higher state temperature to a lower state temperature. A heat source generates
thermal energy that brings the working substance to a high-temperature state. The
working substance generates work in the working body of the engine while
transferring heat to the colder sink until it reaches a low-temperature state. During
this process, some of the thermal energy is converted into work by exploiting the
properties of the working substance. The working substance can be any system
with a non-zero heat capacity, but it usually is a gas or liquid. During this process,
some heat is normally lost to the surroundings and is not converted to work. Also,
some energy is unusable because of friction and drag.
17
Heat Engines Thermal Efficiency: -
The efficiency of a heat engine relates to how much useful work is obtained as
the output for a given amount of heat energy input.
QH = W + QC
where,
W = ∮ PdV is the work done by the engine,
QH=Th ∆Sh is the heat energy taken from the high-temperature system,
and
QC=Tc ∆Sc is the heat energy delivered to the cold temperature system.
In other words, a heat engine absorbs heat energy from the high-temperature heat
source, converting part of it to useful work and delivering the rest to the cold
temperature heat sink.
Mathematically,
W
Efficiency, 𝜂=
QH
The typical range of efficiencies of various heat engines proposed or used today
are as follows:
a. 3% (97 percent waste heat using low-quality heat) for the ocean thermal
energy conversion (OTEC) ocean power proposal
b. 25% for most automotive gasoline engines.
c. 49% for a supercritical coal-fired power station.
d. 60% for a combined cycle gas turbine.
18
Types of Engines: -
Based on the location of the combustion chamber, the engines are classified as
follows:
a. Internal combustion engines (I.C. Engines).
b. External combustion engines (E.C. Engines).
External heat engines are steam engines, an external combustion engine would
use a flame to heat water into steam, then using the steam to turn a turbine.
Example: Power Plants, Stirling engines.
19
Examples of Heat Engines: -
Everyday examples of heat engines include the thermal power station, internal
combustion engine, firearms, fireworks, refrigerators, and heat pumps.
e. In Phase change cycles, the working fluids are gases and liquids. The
engine converts the working fluid from a gas to a liquid, from liquid to gas, or
both, generating work from the fluid expansion or compression.
20
Liquid to solid cycle (Frost heaving — water changing from ice to liquid
and back again can lift the rock to 60 cm.)
Solid to gas cycle (firearms — solid propellants combust to hot gases.)
f. In Gas cycles and engines, the working fluid is always a gas (i.e., there is
no phase change):
21
INTERNAL COMBUSTION ENGINES
a. Cylinder Block: -
22
b. Cylinder Head: -
The cylinder head is bolted to the
cylinder Block through studs.
The water jackets are provided for
cooling water circulation.
The materials used for the cylinder
head are cast iron, aluminium alloy,
etc.
This is also generally made of single
cast iron.
c. Liner: -
The liner is a sleeve that is fitted into the
cylinder bore. It provides a wear-resisting
surface for the cylinder bores. Liners are
classified into wet and dry liners.
Wet Liner: These liners are
surrounded or wetted by cooling
water. It provides a wear-resisting
surface for the piston to reciprocate.
Also, it acts as a seal for the water
jacket.
d. Crankcase: -
It may be cast integral with the cylinder block.
Sometimes, it is cast separately and then attached
to the block. The materials used for a crankcase are
cast iron, aluminium alloys, or alloy steels.
23
e. Oil pan or oil sump: -
The oil sump is the bottom part of the engine. It
contains lubricating oil. A drain plug is provided to
the oil sump to drain out the oil. It is made of a
pressed sheet.
f. Piston: -
The piston serves the following purposes:
It acts as a movable gas-tight seal to keep the
gases inside the cylinder.
It transmits the force of the explosion in the
cylinder to the crankshaft through the
connecting rod.
Some of the materials used for piston are cast
iron, aluminium alloy, chrome-nickel alloy,
nickel-iron alloy, and cast steel.
The materials used for the piston should be wear-
resistant. Normally piston rings are made of alloy
steel iron-containing silicon, manganese alloy steel,
etc.
g. Piston rings: -
Piston rings are inserted in the grooves provided in the piston. Two types of piston
rings are used in the piston: compression rings and oil rings or oil control rings.
Compression rings: Compression rings
provide an effective seal for the high-pressure
gases inside the cylinder. They prevent the
leakage of high-pressure gases from the
combustion chamber into the crankcase. Each
piston is provided with at least two
compression rings.
Oil rings: Oil rings wipe off the excess oil
from the cylinder walls. It also returns excess
oil to the oil sump, through the slots provided
in the rings.
24
h. Cam Shaft: -
i. Crank Shaft: -
j. Connecting Rod: -
It connects the piston and crankshaft.
It transmits the force of the explosion during
power stroke to the crankshaft.
The connecting rod has bearings at both ends.
The small end of the connecting rod has a
solid or split eye and contains a bush.
This end is connected to the piston employing
a gudgeon pin. The other end is called the big
end of the connecting rod.
The connecting rods must withstand heavy thrusts. Hence it must have
strength and rigidity. They are usually drop-forged I sections.
The materials used are plain carbon steel, aluminium alloys, nickel alloy
steels, etc.
25
Classification of IC Engines: -
d. Ignition Method:
Spark Ignition (SI)
Compression-Ignition(CI)
e. Cooling System:
Air-cooled Engines
Water Cooled Engines
f. Valves Location:
L head (Side valve) engine
T Head (Side valve) engine
I head (overhead valve) engine
F head (overhead inlet and side exhaust) engine
26
Chart: Classification of internal combustion engines
27
Nomenclature: -
a. Cylinder Bore(d): -
The nominal inner diameter of the working cylinder is called the cylinder bore
and is designated by the letter d and is usually expressed in millimetres (mm).
b. Piston Area(A): -
The area of a circle of diameter equal to the cylinder bore is called the piston area
and is designated by the letter A and is usually expressed in square centimetre
(cm2).
c. Stroke(L): -
The nominal distance through which a working piston moves between two
successive reversals of its direction of motion is called the stroke and is
designated by the letter L and is expressed usually in millimetres (mm).
e. Dead Centre: -
The position of the working piston and the moving parts which are mechanically
connected to it, at the moment when the direction of the piston motion is reversed
at either end of the stroke is called the dead centre.
There are two dead centres in the engine as
indicated in Fig. They are:
28
SPARK IGNITION ENGINE
SI engine stands for the spark-ignition engine. Spark ignition engine means any
engine in which fuel is ignited by a spark plug or by a predefined ignition source.
Many of us have the misconception that only petrol engines are SI engines but
actually, petrol engines are a type of SI engine. There are many other SI engines
like gas engines, Hydrogen engines, LPG engines, etc.
a. Principle: -
We know that stroke is defined as the maximum movement of the piston in any
direction inside the engine cylinder. For example, if a piston moves from bottom
dead centre to top dead centre is known as a stroke. If it returns to the bottom
dead centre, it is known as 2 strokes. Similarly, if it again moves towards TDC
and comes back BDC, it completes four strokes. This is the basic principle of a
four-stroke engine. An engine that completes four strokes into one power stroke
or to complete one cycle is called a four-stroke engine. The crankshaft completes
one revolution in two strokes. So it rotates two revolutions in four-stroke engines.
29
b. Working: -
30
c. Application: -
d. Advantages: -
e. Disadvantages: -
Two-Stroke SI Engine: -
a. Principle: -
31
b. Working: -
c. Application: -
These engines are used in small vehicles like mopeds, scooters, etc.
Small gasoline engines are used for lawnmowers.
These are used for ship propulsions.
It is also used for small electric generator sets, pumping sets, and
outboard motorboats.
32
d. Advantages: -
Lower cost.
High power compared to four-stroke engines.
Easy maintenance due to absence of valve mechanism and lubrication
system.
Compact compared to four-stroke engines.
Produce uniform torque on crankshaft.
More power to weight ratio.
e. Disadvantages: -
33
COMPRESSION IGNITION ENGINE
The diesel engine, named after Rudolf Diesel, is an internal combustion engine
in which ignition of the fuel is caused by the elevated temperature of the air in
the cylinder due to the mechanical compression; thus, the diesel engine is a so-
called compression-ignition engine (CI engine). This contrasts with engines using
spark plug-ignition of the air-fuel mixture, such as a petrol engine (gasoline
engine) or a gas engine (using a gaseous fuel like natural gas or liquefied
petroleum gas).
Diesel engines work by compressing only the air. This increases the air
temperature inside the cylinder to such a high degree that atomized diesel fuel
injected into the combustion chamber ignites spontaneously. With the fuel being
injected into the air just before combustion, the dispersion of the fuel is uneven;
this is called a heterogeneous air-fuel mixture. The torque a diesel engine
produces is controlled by manipulating the air-fuel ratio (λ); instead of throttling
the intake air, the diesel engine relies on altering the amount of fuel that is
injected, and the air-fuel ratio is usually high.
34
ascends. The compression ratio usually
varies from 14:1 to 22:1. The pressure at
the end of the compression stroke
ranges from 30 to 45 kg/cm2. As the air
is progressively compressed in the
cylinder, its temperature increases, until
when near the end of the compression
stroke, it becomes sufficiently high
(650-80O oC) to instantly ignite any fuel
that is injected into the cylinder. When
the piston is near the top of its
compression stroke, a liquid
hydrocarbon fuel, such as diesel oil, is
sprayed into the combustion chamber under high pressure (140-160 kg/cm2),
higher than that existing in the cylinder itself. This fuel then ignites, being burnt
with the oxygen of the highly compressed air.
During the fuel injection period, the piston reaches the end of its compression
stroke and commences to return on its third consecutive stroke, viz., power stroke.
During this stroke the hot products of combustion consisting chiefly of carbon
dioxide, together with the nitrogen left from the compressed air expand, thus
forcing the piston downward. This is only the working stroke of the cylinder.
During the power stroke, the pressure falls from its maximum combustion value
(47-55 kg/cm2), which is usually higher than the greater value of the compression
pressure (45 kg/cm2), to about 3.5-5 kg/cm2 near the end of the stroke. The
exhaust valve then opens, usually a little earlier than when the piston reaches its
lowest point of travel. The exhaust gases are swept out on the following upward
stroke of the piston. The exhaust valve remains open throughout the whole stroke
and closes at the top of the stroke.
The reciprocating motion of the piston is converted into the rotary motion of the
crankshaft by means of a connecting rod and crankshaft. The crankshaft rotates
in the main bearings, which are set in the crankcase. The flywheel is fitted on the
crankshaft to smoothen out the uneven torque that is generated in the
reciprocating engine.
35
Two-Stroke CI Engine: -
The air thus flows into the cylinder, where the piston compresses it as it ascends,
till the piston is nearly at the top of its stroke. The compression pressure is
increased sufficiently high to raise the temperature of the air above the self-
ignition point of the fuel used. The fuel is injected into the cylinder head just
before the completion of the compression stroke and only for a short period. The
burnt gases expand during the next downward stroke of the piston. These gases
escape into the exhaust pipe to the atmosphere through the piston uncovering the
exhaust port.
36
RECIPROCATING ENGINE
a. Applications: -
37
b. Technology Description: -
The main difference between the two cycles is the method of igniting the fuel.
Spark ignition engines (Otto cycle) use a spark plug to ignite a pre-mixed air-fuel
mixture introduced into the cylinder. Compression ignition engines (Diesel-
cycle) compress the air introduced into the cylinder to high pressure, raising its
temperature to the auto-ignition temperature of the fuel that is injected at high
pressure.
38
temperature of the compressed air in the cylinder. In spark-ignition
engines, the compressed air-fuel mixture is ignited by an ignition source at
or near TDC.
Power stroke: Acceleration of the piston by the expansion of the hot, high-
pressure combustion gases.
Exhaust stroke: The movement of an engine piston (as of a 4-stroke-cycle
engine) that forces the used gas or vapour out through the exhaust ports
c. Performance Characteristics: -
The five systems range from 100 kW to 9.3 MW, which covers most CHP
installations that use reciprocating engines. Electric efficiencies generally
increase with size, and the electric efficiencies for the five systems range from
approximately 30% (System #1) to 42% (System #5). Overall CHP efficiencies
are near 80%, ranging from approximately 77% (System #5) to 83% (System #1).
As electrical efficiency increases, the quantity of thermal energy available to
produce useful heat decreases per unit of power output, and the power to heat
ratio generally increases. A changing ratio of power to heat impacts project
economics and may affect the decisions that customers make in terms of CHP
acceptance, sizing, and the desirability of selling power. For the representative
system, the power to heat ratio ranges from 0.56 to 1.20. In power generation and
CHP applications, reciprocating engines generally drive synchronous generators
at a constant speed to produce steady alternating current (AC) power. As load is
reduced, the heat rate of spark ignition engines increases and efficiency decreases.
While gas engines compare favourably to gas turbines which typically experience
efficiency decreases of 15 to 25 percent at half load conditions, multiple engines
may be preferable to a single large unit to avoid efficiency penalties.
The costs are average values based on data collected from multiple
manufacturers. Installed costs can vary significantly depending on the scope of
the plant equipment, geographical area, competitive market conditions, special
site requirements, emissions control hardware, and prevailing labour rates.
Capital costs for generator set packages include all expenses for a complete CHP
system, including heat recovery hardware and emission control equipment. The
CHP systems shown in Table 3 are assumed to produce hot water, although
reciprocating engines are also capable of producing low-pressure steam. With
construction and installation included, installed costs range from $2,900 to $1,430
per kW. As indicated, capital costs decline on a per kW basis as size increases.
39
Non-fuel operation and maintenance (O&M) costs are also shown in Table 3. As
indicated, these costs range from 2.4 to 0.9 ¢/kWh. Like capital costs, O&M costs
decline as capacity increases. Maintenance costs vary with type, speed, size, and
number of cylinders of an engine. These costs typically include:
Maintenance labour.
Engine parts and materials (e.g., oil filters, air filters, spark plugs, gaskets,
valves, piston rings, electronic components, etc.) and consumables, such as
oil.
Minor and major overhauls Maintenance can either be done by in-house
personnel or contracted out to manufacturers, distributors, or dealers under
service contracts.
e. Emissions: -
40
FUEL AIR CYCLE
The theoretical cycle based on the actual properties of the cylinder contents is
called the fuel-air cycle. The fuel-air cycle takes into consideration the following:
The actual composition of the cylinder contents.
The variation in the specific heat of the gases in the cylinder.
The dissociation effect.
The variation in the number of moles present in the cylinder as the pressure
and temperature change.
No chemical changes in either fuel or air before combustion.
Combustion takes place instantaneously at the top dead center.
All processes are adiabatic.
The fuel is mixed well with air.
41
value of specific heats is used (2’) as shown in the figure. When taking variable
specific heat, the end of combustion will be (3’) instead of 3. The expansion
process would be 3’4’ when assumed isentropic, but expand variable-specifically
specific heats into accounts is above 3’4’ and represented by3’4’. Thus it is seen
that the effect of variation of specific heats is to deliver less work. The final cycle
is (123'4’).
42
ACTUAL CYCLE
h. Pumping loss: -
These are the losses occurring on account of power that is lost during the suction
and exhaust operation of the engine.
44
DEVELOPMENT AND USAGE OF IC ENGINE
OHV Engine: -
It is also called the Pushrod engine. In
an OHV (Over Head Valve) engine,
the camshaft is placed inside the block
and the valves are operated through
lifters, pushrods, and rocker arms.
This mechanism is called a valve
train. An OHV design has been
successfully used for many years.
Most early American cars had OHV
engines and they are still used in
trucks and sports cars.
On the downside, it's difficult to
precisely control the valve timing at
high rpm due to higher inertia caused
by larger amounts of valve train
components (lifter-pushrod-rocker
arm). Also, it's very difficult to install
more than 2 valves per cylinder.
45
DOHC Engine: -
DOHC means Double Overhead Cam,
or sometimes it could be called "Twin
Cam'' or "Double Cam''. The majority
of modern cars have a DOHC engine.
MPFI Engine: -
There are different types of gasoline injection systems in S I Engines, and one of
them is a Multi-Point Fuel Injection System or MPFI System.
46
a. Components: A mechanical solenoid injector, Electronic Control Unit
(ECU), Electronic sensors, Air filters, etc.
b. Working:
In the MPFI system, using the fuel pump which is driven by the electric
motor is used to spray fuel into the engine intake manifold.
This technique helps to provide an accurate air-fuel ratio at all operating
conditions.
The suction pressure of the engine is used to spray the fuel into the
cylinders (In carburetors, the vacuum is used to provide the fuel).
As shown in the figure, you can see that a single injector is placed on the
intake port of the different cylinders.
The process of fuel injection occurs simultaneously in each injector once
in every rotation.
Using the electrical fuel pump, fuel from the fuel tank supplies to each fuel
injector equally.
c. Advantages:
The power generated by the engine is more than the carburetion system.
Due to the accurate mixture of air-fuel supplied to each cylinder, the
difference between power generated at each cylinder is negligible.
Engine vibrations from MPFI equipped engines are very less, hence the life
of MPFI system-equipped engines is high.
This system is very responsive in case of sudden acceleration or
deceleration.
Lower fuel consumption leads to better mileage.
The volumetric efficiency of MPFI is high.
47
engine. Power for the supercharger
can be provided mechanically by a
belt, gear, shaft, or a chain
connected to the crankshaft.
When power is provided by a
turbine powered by exhaust gas, a
supercharger is known as a
turbosupercharger – typically
referred to simply as a
turbocharger or just turbo.
Common usage restricts the term
supercharger to mechanically
driven units. Turbochargers are a
type of forced induction system.
They compress the air flowing into
the engine.
To achieve this boost, the turbocharger uses the exhaust flow from the engine to
spin a turbine, which in turn spins an air pump. The turbine in the turbocharger
spins at speeds of up to 150,000 rotations per minute (rpm), which's about 30
times faster than most car engines can go. And since it is hooked up to the exhaust,
the temperatures in the turbine are also very high.
CRDI Engine: -
The common rail direct injection configuration for diesel engines is a great
example of modern diesel technology. Common rail direct injection uses a high-
pressure rail to deliver diesel fuel to each solenoid valve. Unlike conventional
direct fuel injection systems used in older diesel cars which use a low-pressure
pump nozzle to deliver diesel fuel. This traditional technology was inefficient and
48
wasted a lot of fuel. On diesel
engines, it features a high-pressure
(over 1,000 bar or 15,000 psi) fuel
rail feeding individual solenoid
valves, as opposed to low-pressure
fuel pump feeding unit injectors.
Third-generation common rail diesel
controls now feature piezoelectric
injectors for increased precision,
with fuel pressures up to 2,000 bar or
29,000 psi. In gasoline engines, it is
used in gasoline direct injection
engine technology.
a. Working:
The fuel in an electronically controlled engine is stored at variable pressure
in a cylinder or ‘rail’ connected to the engine’s fuel injectors via individual
pipes, making it a ‘common rail’ to all the injectors.
The pressure is controlled by a fuel pump but it is the fuel injectors,
working in parallel with the fuel pump, that controls the timing of the fuel
injection and the amount of fuel injected. In contrast, earlier mechanical
systems rely on the fuel pump for pressure, timing and quantity.
A further advantage of the CRDI system is that it injects the fuel directly
into the combustion chamber. The indirect injection (IDI) system in older
engines injected fuel into a pre-combustion chamber, which fed the main
combustion chamber.
b. Advantages:
CRDi diesel engines were developed out of necessity. A common problem
that plagued older diesel engines was black soot-like smoke and horrible
emissions. The CRDi diesel engine produces significantly less smoke and
tolerable emissions.
Utilising a common rail for fuel delivery, CRDi engines are not gas
guzzlers anymore. They provide great mileage which is how they outrank
petrol engines in terms of fuel economy.
Owing to a lot fewer moving parts and advancements in diesel engine
technology. CRDi engines are quieter.
CRDi engines are powerful, very powerful. A CRDi diesel engine produces
up to 25% more torque compared to a petrol engine displacing the same
amount of fuel.
49
I-VTEC Engine: -
I-VTEC stands for Intelligent
Variable Valve Timing and Lift
Electronic Control, a system
created by Honda to improve the
fuel consumption of Honda
vehicles. The VTEC system uses
two camshaft profiles and
hydraulically selects between the
two. This technology was invented
by Ikuo Kakitani, a Honda
engineer.
Honda i-VTEC permits the engine to effectively have multiple camshafts. The
difference with this technology is that the engine’s computer can activate
alternate lobes on the camshaft and change the cam timing as the engine moves
into different RPM ranges.
50
By generating two sparks at either end of the combustion chamber,
(approximately 90 to the valve axis) the Air-Fuel mixture gets ignited such that
there are 2 flame fronts created and therefore a reduction in flame travel of the
order of 40% is achieved.
A fast rate of combustion is achieved leading to a fast rate of pressure rise. The
obvious outcome of this is more torque, better fuel efficiency, and lower
emissions.
b. DTS-SI: -
The Digital Twin Spark - ignition or
DTS- i is the mother technology for the
latest Digital Twin Spark – Swirl
induction or DTS-Si technology. Thanks
to DTS- I, a fast rate of combustion and
therefore the resulting fast rate of
pressure rise is when we increase the
RPM harnessed by optimally positioning
this pressure to deliver maximum
possible work and obtain more torque,
better fuel efficiency, and lower
emissions.
When burning lean Air-Fuel mixtures, the two plugs provide rapid combustion,
but at light loads, the opportunity exists to improve the combustion further.
Combustion efficiency in lean Air-Fuel mixture conditions can be further
improved by generating high turbulence in the combustion chamber.
The result is lower efficiency. When high turbulence is generated and combustion
takes place, the surface of the ballooning flame front fragments itself, with
projection-like fingers, which increases its surface area, thereby improving
combustion further.
51
GDI (Gasoline Direct Injection): -
a. Advantages:
8-22% higher fuel economy.
More torque and horsepower allowing smaller engines.
Can inject fuel anytime during the 4-stroke cycle of events.
Cylinder scavenging is greatly enhanced.
Compression ratios can be higher.
Leaner fuel mixtures during cold engine operation.
Adjustable fuel modes to target emission problems.
Lower CO2 emission levels.
Reduced engine pumping losses.
Cylinder charge cooling.
Much smaller droplets spray of fuel.
Reduced cylinder wall temperatures (A/C theory- high-pressure liquid
changing to a low-pressure gas).
Spark knock is much more controlled.
52
b. Working:
c. Disadvantages:
53
DG SETS AT ONGC HOSPITAL
54
Oil Temperature Switch (maintained at 90℃-110℃): If the oil temperature
increases due to any reasons leading to heat up the engine resulting into the
decrease in the efficiency. Therefore, the temperature should be maintained
to get the higher efficiency.
Water Temperature: It is used to cool down the engine. Coolant used in
generator is mixed with the water in the certain ratio depending upon the
manufacturer.
Over-current: In the case of increased load, the amount of current exceeds the
actual value, which may lead to failure of the Engine. In that case, the engine
is stopped immediately.
In ONGC Hospital there are 4 substation panels present. Two panels are
Transformer incomer-1 and Transformer incomer-2 for the power supply coming
from the state. These panels distribute the supply to both the transformer for use
of hospital.
When DG works, Transformers are in the state of switch off mode as it charges
the different panel with the capacitor bank of 500KVR.
The Running DG is loaded with 400KVA, 50Hz frequency, 595KPa Oil Pressure,
17℃ Coolant Temperature worked for 224 hr.
55
INTRODUCTION TO HVAC SYSTEMS
History: -
The oldest form of HVAC is the Korean Ondol method. Dating back to the iron
age, it involved an outside furnace, underfloor pipes, and stone that would retain
heat well for long periods of time that releases slowly. During the Han Dynasty
around 206 B.C. in China, early cooling systems were invented. The windmill fan
was first created for the military and was later used for thresh grain.
Another design for ancient homes was the self-raining pavilion. It worked only for
homes built next to a river, but it combined a windmill and water wheel pump water
to the roof of a building where it then dripped down to form rain curtains that
provided a cooling effect.
In the 1600s, Louis Savot invented the circulating fireplace in France. It allowed
cold room air to enter at the bottom of the fireplace, be warmed and enter the room
through openings above the mantle. In England, a duct from the outside was added
to provide air for combustion.
In the 1840s, Dr. John Gorrie of Florida believed that hot weather contributed to
illness and cooling was essential to prevent the spread of malaria and other diseases.
Cooling methods at that time were difficult and expensive, requiring ice from
frozen lakes so he experimented with artificial cooling, eventually designing a
compressor powered by steam or horses that could create ice. He received a patent
for the same in 1851.
56
Types of HVAC Systems
The major classification of HVAC systems is central system and decentralized or
local system. Types of a system depend on addressing the primary equipment
location to be centralized as conditioning entire building as a whole unit or
decentralized as separately conditioning a specific zone as part of a building.
Therefore, the air and water distribution system should be designed based on
system classification and the location of primary equipment.
The major classification of HVAC systems is central system and decentralized or
local system. Types of a system depend on addressing the primary equipment
location to be centralized as conditioning entire building as a whole unit or
decentralized as separately conditioning a specific zone as part of a building.
Therefore, the air and water distribution system should be designed based on
system classification and the location of primary equipment.
a) Central HVAC Systems: -
A central HVAC system may serve one or more thermal zones, and its major
equipment is located outside of the served zone(s) in a suitable central location
whether inside, on top, or adjacent to the building. Central systems must
condition zones with their equivalent thermal load. Central HVAC systems will
have as several control points such as thermostats for each zone.
The thermal energy transfer medium can be air or water or both, which
represent as all-air systems, air-water systems, all-water systems. Also, central
systems include water-source heat pumps and heating and cooling panels. All
of these subsystems are discussed below. Central HVAC system has combined
devices in an air handling unit, as shown in Figure, which contains supply and
return air fans, humidifier, reheat coil, cooling coil, preheat coil, mixing box,
filter, and outdoor air.
57
b) Local HVAC Systems: -
Some buildings can have multiple zones or have a large, single zone, which
needs central HVAC systems to serve and provide the thermal needs. However,
other building may have a single zone which needs equipment located inside
the zone itself, such as small houses and residential apartments. This type of
system is considered as local HVAC systems since each equipment serving its
zone without crossing boundaries to other adjacent zones (e.g., using an air
conditioner to cool down a bedroom, or using an electrical heater for the living
room). Therefore, a single zone requires only one-point control point connected
to a thermostat to activate the local HVAC system. Some buildings have
multiple local HVAC systems as proper equipment serving specific single
zones and controlled by the one-point control of the desired zone. However,
these local systems are not connected and integrated to central systems, but still
part of a large full-building HVAC systems.
Purpose: -
The main purpose of commercial HVAC (heating, ventilating, and air
conditioning) is to achieve the environmental requirements of the comfort of
occupants and a process, simultaneously providing conditioned air to environment
of application. "Conditioned" air means that air is clean and odor-free, and the
temperature, humidity, and movement of the air are within certain comfort ranges.
Well-designed efficient systems do this with minimal non-renewable energy and
air, and water pollutant emissions.
58
Many factors affect the way people respond to their work environment. Air quality
is one of these factors. The American Society of Heating, Refrigerating and Air-
Conditioning Engineers (ASHRAE) has established standards which outline air
quality for indoor comfort conditions. Generally, these indoor comfort conditions,
sometimes called the "comfort zone," are between 20⁰C to 24⁰C for winter and 23⁰C
to 27⁰ C during the summer. Both these temperature ranges are for room air at
approximately 50% relative humidity and moving at velocity of 9 meter per minute
or slower. Factor other than temperature like humidity, odor and composition of
specific substance also effect the performance of HVAC.
The objective of successful HVAC is to control the temperature of air inside the
designated “Air Conditioned” space along with control of moisture, filtration of air
and containment of air borne particles, supply of outside fresh air for control of
oxygen and carbon dioxide levels in the air-conditioned space, and finally control
of the movement of air or draught. Air conditioning has changed over the years
from just cooling of a space to the effective control of all the above-mentioned
parameters.
The requirements and objective of HVAC systems had suffered constant evolution
from the day of evolution to present. The outbreak of SARS-CoV-2 has associated
disinfection as another specification to modern HVAC systems. This could be
achieved by application of UV Lamp into the system.
Even the best HVAC equipment and systems cannot compensate for a faulty rig
design. Problems of this type, causes inherently high cooling and heating needs and
consume unnecessary resources and should be corrected if possible. The most
important factors in these designs are careful control of solar gain, while taking
advantage of passive heating, day lighting, natural ventilation and cooling. The
critical factors in mechanical systems' energy consumption - and capital cost - are
reducing the cooling and heating loads they must handle.
Terminology: -
a) Absorption chiller
Absorption chillers differ from mechanical vapor compression chillers in the fact
that they utilize a heat source (thermal or/and chemical process) to produce the
refrigeration effect necessary to provide chilled water. There is no mechanical
compression of the refrigerant taking place within the machine as it occurs within
more traditional vapor compression type chillers.
59
Following are the type of Absorption Chiller:
1. Water Cooled
2. Air Cooled
60
f) Air treatment
Process comprising of sequential action to modify the state of the air with respect
to various properties such as temperature, moisture content, dust content, bacterial
count, gas and vapor contents.
g) Barrier, radiant
A thin, reflective foil sheet that exhibits low radiant energy transmission and
under certain conditions can block radiant heat transfer; installed in attics to
reduce heat flow through a roof assembly into the living space. This is used to
improve upon efficiency by reducing the losses.
h) Barrier, vapor
A moisture-impervious layer applied to the surfaces enclosing a humid space to
prevent moisture travel to a point where it may condense due to lower
temperature.
i) Boundary conditions
Values of physical parameters (e.g. temperature, heat flux, mass flux, velocity,
etc.) that are specified at the boundaries of a solution domain and are required for
solving the discretized equations in a CFD (computational fluid dynamics)
solution or any other physical problem.
k) Chilled beam
A cooled element or cooling coil situated in, above or under a ceiling which cools
convectively using natural or induced air flows. The cooling medium is usually
water.
61
l) Chimney effect
The tendency of heated air or gas to rise in a duct or other vertical passage, such
as in a chimney, small enclosure, or building staircase, due to its lower density
compared to the surrounding air or gas.
m) Cogeneration
Simultaneous production of two or more forms of useable energy from a single
fuel source, e.g., heat energy and electrical or mechanical power, in the same
facility. Because a typical cogeneration facility uses thermal energy which is
generally wasted in a traditional power plant, the process can be 50 to 70 percent
more efficient. Fuels used in cogeneration facilities may take the form of natural
gas, biomass, oil or coal. Cogeneration systems are designed to simultaneously
produce electric power and thermal heat for industrial processes or the heating
and cooling of buildings. Cogeneration plants can be any size, from 10 kilowatts
to 1,000 megawatts or more.
n) Commissioning
The testing of HVAC systems prior to building occupancy to check whether the
systems meet the operational needs of the building within the capabilities of the
system design. Start-up of a building that includes testing and adjusting HVAC,
electrical, plumbing, and other systems to assure proper functioning and
adherence to design criteria. Commissioning also includes the instruction of
building representatives in the use of the building systems.
Operating Principles: -
HVAC systems works on the principles of thermodynamics, fluid mechanics and
heat transfer. All three principles utilized at different steps of the whole process
in the HVAC system. The Thermodynamics concept comes in effect to maintain
the indoor air quality of the premises. The fluid flow mechanics comes in effect to
maintain the temperature by passing the coolants in the coils of the air conditioning
system. The third portion of the principle is the heat transfer segment of the main
principle, where desired heat supply to the air supplied in the room.
62
Air conditioning theory
There are two laws that are significant to understand the basic refrigeration cycle
and air conditioning.
1. First Law of Thermodynamics explains that energy cannot be created nor
destroyed, but can be changed from one form to another.
2. Second Law of Thermodynamics can help us better understand how the
basic refrigeration cycle works. Once of these laws state that heat always flows
from a material at a high temperature to a material at a low temperature.
As mentioned earlier, air conditioning (the refrigeration cycle) is a process that
simply removes heat from an area that is not wanted and transfers that heat to an
area that makes no difference. The air conditioner itself does not create heat, it
just transfers heat. For heat to transfer, there has to be a temperature and pressure
difference. In the refrigeration process there are two sections which produce a
pressure difference: a high-pressure, high temperature section (condenser) and a
low-pressure, low temperature section (evaporator).
The refrigeration system removes heat from an area that is low-pressure, low
temperature (evaporator) into an area of high-pressure, high temperature
(condenser). For example, if cold refrigerant (5° C) flows through the evaporator
and the air surrounding evaporator is 25° C, the cold 5° C refrigerant will absorb
the heat from the 25° C space. By absorbing the heat from the warm space, it also
cools the space. It then transfers that heats to condenser (high side) through
compressor.
A hot refrigerant from the compressor flows to a cooler location the condenser
medium (air surround condenser) for example, the refrigerant will give up the
vapor heat that it absorbs from the indoor evaporator and becomes cool again and
turns back to liquid. This is what the second thermodynamics’ law stated.
The main objective of the HVAC system is to supply fresh and filtered air in the
production area where proper air control is the desired condition. It controls the
temperature, air quality and moisture of the subjected room.
63
Figure: Diagram of Air-Conditioning
There are three modes of heat transfer: - conduction, convection, and radiation
or any combination of the three methods. Heat transfer is the movement of heat
from solid, liquid or gas materials to other solid, liquid and gas materials.
According to the second law of thermodynamics, heat always flows from a
material at a high temperature to a material at a low temperature. For heat to
transfer, there has to be a temperature difference between the two materials. Heat
transfer by conduction is when as heat transfer takes place if there is a temperature
gradient in a solid or stationary fluid medium. That is molecule to molecule heat
transfer.
Radiation is the transfer of heat in an invisible ray, for example, sun ray. We
cannot see it, but we can feel the sun ray on our skin. Convection is the transfer
of heat from one place to a different location by circulating it with movement of
fluid (force movement) or natural movement.
Air conditioner refrigerant is a chemical substance that air conditioner units use;
these refrigerants absorb heat from low-pressure, low temperature evaporator and
condensing at a higher pressure, high temperature condenser. These refrigerants
64
could be R-22, R-410a or R-134a. It depends on what kind of refrigerant the air
conditioner units are designed for.
Refrigerant can change state from vapor (by absorbing heat) to liquid (by
condensing that heat). In residential, the Freon is R-22 and R410a.
65
Two forms of heat: -
Sensible Heat when change in temperature can be measured by a thermometer or
when we put our hand on an object we’ll feel heat. That is sensible heat.
Latent Heat absorbed or rejected when a refrigerant is changing state from liquid
to gas, or vice versa; however, the temperature remains the same. Heat is known
to add to refrigerant but does not register in a thermometer, it just changed the
refrigerant state (gas to liquid, or vice versa).
Required Properties of Ideal Refrigerant: -
1) The refrigerant should have low boiling point and low freezing point.
2) It must have low specific heat and high latent heat. Because high specific
heat decreases the refrigerating effect per kg of refrigerant and high latent
heat at low temperature increases the refrigerating effect per kg of
refrigerant.
3) The pressures required to be maintained in the evaporator and condenser
should be low enough to reduce the material cost and must be positive to
avoid leakage of air into the system.
4) It must have high critical pressure and temperature to avoid large power
requirements.
5) It should have low specific volume to reduce the size of the compressor.
6) It must have high thermal conductivity to reduce the area of heat transfer
in evaporator and condenser.
7) It should be non-flammable, non-explosive, non-toxic and non-corrosive.
8) It should not have any bad effects on the stored material or food, when
any leak develops in the system.
9) It must have high miscibility with lubricating oil and it should not have
reacting properly with lubricating oil in the temperature range of the system.
10) It should give high COP in the working temperature range. This is
necessary to reduce the running cost of the system.
11) It must be readily available and it must be cheap also.
Important Refrigerants: Properties at −15° C
(1) Ammonia (NH3) (R-717)
Latent heat = 1312.75 kJ/kg Specific volume = 0.509 m3 /kg
66
(2) Dichloro–Difluoro methane (or Freon–12) (R-12) [C Cl2 F2]
Latent heat = 162 kJ/Kg Specific volume = 0.093 m3 /kg
(3) Difluoro monochloro methane (or Freon-22) (R-22) [C H Cl F2]
Latent heat = 131 kJ/Kg Specific Volume = 0.15 m3 /kg.
(4) 1,1,1,2-Tetrafluoroethane (R-134a) [C F3 C H2 F ]
Latent heat = 216.97 kJ/Kg Specific volume = 0.1247 m3 /kg
Refrigeration Cycle: -
The refrigeration cycle, also called a heat pump cycle, is a means of routing heat
away from the area you want to cool. This is accomplished by manipulating the
pressure of the working refrigerant (air, water, synthetic refrigerants, etc.) through
a cycle of compression and expansion.
The four fundamental elements of a basic cycle are as follows:
● The compressor
● The condenser
● The expansion device
● The evaporator
67
In the refrigeration cycle, heat is transported from a colder location to a hotter
area. As heat would naturally flow in the opposite direction, work is required to
achieve this. A refrigerator is an example of such a system, as it transports the
heat out of the interior and into its environment (i.e., the room). The refrigerant is
used as the medium which absorbs and removes heat from the space to be cooled
and subsequently rejects that heat elsewhere.
Circulating refrigerant vapor enters the compressor and is compressed to a higher
pressure, resulting in a higher temperature as well. The hot, compressed
refrigerant vapor is now at a temperature and pressure at which it can be
condensed and is routed through a condenser. Here it is cooled by air flowing
across the condenser coils and condensed into a liquid. Thus, the circulating
refrigerant moves heat from the system and the heat is carried away by the air.
The condensed and pressurized liquid refrigerant is next routed through an
expansion valve where it undergoes an abrupt reduction in pressure. That pressure
reduction results in flash evaporation of a part of the liquid refrigerant, lowering
its temperature. The cold refrigerant is then routed through the evaporator. A fan
blows the warm air (which is to be cooled) across the evaporator, causing the
liquid part of the cold refrigerant mixture to evaporate as well, further lowering
the temperature. The warm air is therefore cooled.
To complete the refrigeration cycle, the refrigerant vapor is routed back into the
compressor.
By placing the condenser inside a compartment, and the evaporator in the ambient
environment (such as outside), or by merely running an air conditioner's
refrigerant in the opposite direction, the overall effect is the opposite, and the
compartment is heated instead of cooled.
The first heat exchange that occurs in this basic refrigeration cycle is the
evaporator. The air conditioner evaporator is located between points 6 and 1, in the
basic refrigeration cycle diagram. The evaporator is a heat exchange that is
responsible for absorbing heat from whatever place (medium) that needs to be
cooled; for our discussion it’s indoor.
Since the evaporator is at a low temperature than the air surrounding it, it will
absorb the surrounding heat until the refrigerant liquid inside the evaporator coils
starts boiling as result of absorbing that heat. As the evaporator refrigerant has
boiled completely to vapor it’s now saturated vapor at point 7. Some compressors
cannot pump liquid; if it does pump liquid, it will damage it. This is why we need
the entire liquid refrigerant to boil at point 7.
After, the entire liquid refrigerant turns to vapor and passes point 7. Superheat
occurs. Superheat is between point 7 and 1. Superheat is life insurance for the
compressor. It makes sure the compressor does not pull in liquid refrigerant from
the evaporator.
The air conditioner compressors located between points 1 and 2 has two important
lines: a suction line (low side pressure and back pressure) and discharge line (high
side pressure, head pressure). The suction line is the line that pulls the low-pressure
and temperature from the evaporator and the discharge line is the line that
compresses and pushes that superheat vapor to the condenser. It creates a pressure
difference in the air conditioning system by pulling in low pressure, low
temperature vapor from the evaporator suction line and increasing it to high
pressure, high temperature superheat. This pressure difference what makes the
refrigerate flow in a refrigeration cycle.
69
The air conditioner condenser located between points 2 and 5 is a heat exchange;
it rejects both sensible (measurable) and latent (hidden) heat absorbed by the indoor
evaporator plus heat of compression from the compressor. There are three
important states that take place in the condenser heat rejection.
The first state points 2 and 3 it de-superheat or simply rejects hot superheat vapor
(it removes sensible heat). At points 3 and 4 this the state where it rejects so many
saturated vapors heat, it starts changing phase from vapor to liquid; as the
refrigerant reaches point 4 it is 100 percent saturated liquid refrigerant. From points
4 and 5 it removes sensible heat from the saturated liquid refrigerant. This is where
we could use a thermometer and tell how much heat it has removed; as more heat
is removed it’s now in the sub cooled region.
The expansion device (metering Device) is normally installed in the liquid line
between condenser and evaporator (points 5 and 7). We cannot see it, since the
device is within a compartment. In a regular split central air conditioners system,
it’s located indoors with or near the evaporator coils.
The general principle behind any metering device is it acts as a restriction. It
reduces high-pressure, high temperature refrigerant from the condenser liquid line
to low-pressure, low temperature refrigerant for the evaporator.
Applications: -
70
A. Hospitals
Hospitals require efficient heating, ventilation, and air conditioning (HVAC)
systems to maintain good indoor air quality (IAQ). Hospital ventilation must be
effective for controlling airborne transmission and preventing outbreaks of
infectious diseases. The medical equipment in hospitals and healthcare facilities
are sensitive to temperature levels and require perfect air control to function
accurately.
B. Laboratories
Laboratory ventilation, a part of the HVAC system, is the supply of fresh/clean
air to displace contaminated air and dilute it to safe levels. Air is continuously
exchanged between buildings and their surroundings. The rate at which air is
exchanged is an important property for the purposes of ventilation design and heat
loss calculations and is expressed in ‘air changes per hour’ (ach). Different
laboratory areas and rooms in the building will need a different number of air
changes. Rooms containing fume cupboards and higher containment need a
greater number of air changes than a general laboratory.
71
C. Commercial buildings
HVAC systems are designed to maintain stable temperatures, protect indoor air
quality, and assure appropriate humidity levels. Although air conditioning is
sometimes provided via a refrigerant-based system, for commercial applications,
evaporative cooling is often the preferred option. Evaporative cooling uses
chillers, refrigeration units specifically designed to remove heat from water. This
chilled water is then circulated throughout the system and run through air-handlers
located near the rooms being cooled. The water may be chilled using air-cooled
chillers located outside the building or water-cooled chillers located inside.
Generally speaking, chillers are quieter, more energy efficient and longer lasting
than refrigerant-based systems.
D. Nuclear facilities
HVAC plays an essential role in ensuring the safety and smooth operation of
nuclear power plants. As in most commercial applications, HVAC in a nuclear
power plant is used to maintain ambient conditions within acceptable limits of
temperature and humidity, and control contamination. In addition, these systems
help protect staff and equipment from specific risks inside the buildings, such as
explosions or fire. Perhaps most importantly, these systems monitor the release of
air from the controlled areas and contain any radioactivity that might be released
in the event of a malfunction, failure, or accident.
72
Figure: Nuclear Facility
Load Calculations: -
The load calculation is how HVAC professionals determine the correct size
for your home’s HVAC equipment, whether you’re building a new home or
installing new HVAC equipment. Load calculation takes into account many
factors and comes up with numbers that represent your home’s total heating
and cooling requirements.
Load calculation used to depend only on square footage, but the formula has
become more complicated and accurate in recent years.
HVAC contractors use factors such as square footage, home sealing,
insulation and household activity to complete a load calculation. Today’s
calculations can be completed efficiently with computer programs although
some contractors may prefer entering information on a worksheet and
completing calculations manually. Early days in the industry involved
simple determinations based primarily on square footage. However, more
advanced insulating options, multi-pane windows, efficient home sealing
and other structural factors make it possible for two homes of similar size to
have dramatically different heating and cooling needs.
Cooling load is considered to be the amount of cooling necessary to maintain
a structure at 26 C during the summer months. Heating load is considered to
73
be the amount of heating needed to maintain a structure at 18 C degrees
during the winter.
The amounts determined by use of formulas or programs allow a contractor to
select comfort control equipment that will work optimally in your residence.
Sizing of a system is the capacity of a system to heat or cool a structure.
Heat load calculation method
A building or room gains heat from many sources. Inside occupants, computers,
copiers, machinery, and lighting all produce heat. Warm air from outside enters
through open doors and windows, or as ‘leakage’ though the structure. However,
the biggest source of heat is solar radiation from the sun, beating down on the roof
and walls, and pouring through the windows, heating internal surfaces. The sum of
all these heat sources is known as the heat gain (or heat load) of the building, and
is expressed either in BTU (British Thermal Units) or Kw (Kilowatts).
For an air conditioner to cool a room or building its output must be greater than the
heat gain. It is important before purchasing an air conditioner that a heat load
calculation is performed to ensure it is big enough for the intended application.
There are several different methods of calculating the heat load for a given area:
Quick calculation for offices
For offices with average insulation and lighting, 2/3 occupants and 3/4 personal
computers and a photocopier, the following calculations will suffice:
Heat load (BTU) = Length (ft.) x Width (ft.) x Height (ft.) x 4
Heat load (BTU) = Length (m) x Width (m) x Height (m) x 141
For every additional occupant add 500 BTU. If there are any additional significant
sources of heat, for instance floor to ceiling south facing windows, or equipment
that produces lots of heat, the above method will underestimate the heat load. In
which case the following method should be used instead.
A more accurate heat load calculation for any type of room or building
The heat gain of a room or building depends on:
a) The size of the area being cooled
b) The size and position of windows, and whether they have shading
c) The number of occupants
d) Heat generated by equipment and machinery
e) Heat generated by lighting
74
By calculating the heat gain from each individual item and adding them together,
an accurate heat load figure can be determined.
Step One: -
Calculate the area in square feet of the space to be cooled, and multiply by 31.25
Area BTU = length (ft.) x width (ft.) x 31.25
Step Two: -
Calculate the heat gain through the windows. If the windows don’t have shading
multiply the result by 1.4
North window BTU = Area of North facing windows (m. sq.) x 164
If no shading,
North window BTU = North window BTU x 1.4
South window BTU = Area of South facing windows (m. sq.) x 868
If no shading,
South window BTU = South window BTU x 1.4
Add the results together.
Total window BTU = North window + South window
Step Three: -
Calculate the heat generated by occupants, allow 600 BTU per person.
Occupant BTU = number of people x 600
Step Four: -
Calculate the heat generated by each item of machinery - copiers, computers, ovens
etc. Find the power in watts for each item, add them together and multiply by 3.4
Equipment BTU = total equipment watts x 3.4
75
Step Five: -
Calculate the heat generated by lighting. Find the total wattage for all lighting and
multiply by 4.25
Step Six: -
Add the above together to find the total heat load.
Total heat load BTU = Area BTU + Total Window BTU + Occupant BTU +
Equipment BTU + Lighting BTU
Step Seven: -
Divide the heat load by the cooling capacity of the air conditioning unit in BTU, to
determine how many air conditioners are needed.
Number of a/c units required = Total heat load BTU / Cooling capacity
BTU
Maintenance: -
A regular maintenance plan keeps your HVAC system running smoothly, lowers
your utility bills, and offers greater protection for your family.
If an HVAC system has a problem, it not only may result in costly repairs, but it
could also endanger your family. In the event of a short circuit, there’s always the
possibility of a fire. While you want to ensure you have a quality HVAC technician
looking over your system each summer and winter, there are some things you can
do yourself to help keep your HVAC equipment operating efficiently and running
smoothly throughout the year.
76
1. Change your filters: You should change your filters every 30 to 90 days. A
clean filter greatly enhances the efficiency of your HVAC unit. Dirty filters
mean your equipment has to work much harder to keep your home at the
temperature you desire.
2. Clear Debris Around Outside Units: Remove the build-up of leaves and
overgrown vegetation so they do not interfere with the airflow of your
outdoor unit. You can trim any bushes or trees also, so your unit has plenty
of clearance, about 2 feet, on all sides. Keep a close eye if you have bushes
or trees that give off excessive pollen, such as Cottonwood trees in particular.
They are notorious for clogging up condensing units.
3. Check Refrigerant Lines Monthly: Refrigerant lines that come from your
HVAC unit into your home are what ensure you have the heating or the
cooling you need. If those lines get worn, develop leaks or become detached,
you won’t get the comfortable temperatures you and your family want.
5. Check Your Evaporator Coil’s Drain Pipe and Drain pan: Check your
HVAC system’s drainpipe and clear any blockages of the algae/mold that
sometimes builds up there. A wet-dry vacuum can suction out any plugged-
up areas, and bleach can help clean it too. Often customers learn of it when
water comes pouring through their ceiling unless a protective float switch or
“ceiling saver” is installed, which switches off the air conditioning to prevent
damaging leaks.
77
monoxide detector and your fire alarm are the same unit, so you only need
to replace one set of batteries every six months.
8. Make sure Unit is leveled: Over time, the concrete slab that your outdoor
unit is on can shift. If your outdoor compressor is not level, this can disrupt
refrigerant and oil flow through the system. This could lead to some costly
repairs if not leveled out at some point. If the unit is not level, you can
possibly correct this by using a few rot-resistant shims. If this doesn’t work,
it’ll be best to call your HVAC technician.
9. Inspection of fan blades: The motor and blades on the fan should be
checked to make sure they are not damaged.
10. Blower maintenance (AC system): Adjusting the blower components can
help maintain proper airflow. The blower assembly should be cleaned during
routine maintenance.
11. Examine heating elements (AC system): For safe operation, gas or oil
connections should be clean and unblemished, and there should be no leaks.
New Technologies: -
While the initial development in HVAC technology focused on mechanical
advancements and increased efficiency, the current focus has also majorly grown
towards sustainability, comfort, and energy-saving. This is extremely important
considering the current impact on our climate and the rise in demand for efficient
heating and cooling systems.
Engineers and scientists are looking for new and different ways to enhance the
HVAC landscape. Many answers lie in improved technologies, renewable energy
sources, or even a complete reimagining of how an HVAC system should work.
78
Latest advancements in technology that are taking the present-day HVAC system
towards a brighter future:
79
4. Solar HVAC: Thermally driven air conditioning is a new HVAC technology
picking up on the need for sustainable systems. It provides an energy-
efficient cooling method and can be used as an alternative to traditional air
conditioners. Instead of electricity, this system utilizes solar energy for
cooling, and if unavailable, then natural gas kicks in. This eliminates
electricity costs. While this HVAC technology is not extremely widespread,
it is an excellent glimpse into an eco-friendly future. Thermally driven air
conditioning systems remove heat with evaporation at low pressure. They
are highly effective and efficient; however, a high temperature (around
350F) is required to generate electricity from the solar panels.
5. Dual Fuel Heat Pump: This is an excellent system for homes in areas where
the electricity rates are not too high, and during winter, the temperature does
not fall below freezing point. This advanced HVAC technology utilizes a gas
furnace and a heat pump to provide efficient, cost-effective heating and
cooling. If the outdoor temperature is above 35 degrees, the heat pump
utilizes electricity to pull in heat from the outside air. This is extremely cheap
compared to firing up the furnace. Although, once temperatures are below
35, gas is used to create heat for higher efficiency. When the weather is cool,
such as in spring, the dual fuel heat pump comes in handy to distribute air.
Even during summer, the heat pump circulates the refrigerant through the
furnace’s air conditioning coil to blow cool air. This system has a high
upfront cost, but this can be recovered through energy savings over the next
few years.
80
6. Zoned HVAC: An HVAC zoning system divides a house into different
areas, each of which can be individually controlled by a separate thermostat.
Different temperature settings may be required in different parts of a home,
and by utilizing zoning, you can achieve the best temperature for each area.
This is especially important to decrease usage in empty rooms. Zones can be
applied to central air conditioning systems, VRF systems, or ductless
systems. Zones can easily be installed in existing systems also by utilizing a
zone control panel.
81
Figure: Air-Conditioners
From manual buttons, dialers, remote controls to controlling your HVAC system
via voice commands, technology has come a long way. HVAC is bound to embrace
new technologies. The smart home trend is here to stay. AI in the form of machine
learning is going to thrive. Fully automated, super-efficient, self-learning, and
sustainable HVAC systems are the future.
82
SPECIFICATIONS OF ONGC HVAC
1. REFRIGERATION CYCLE
2. CHILLING WATER CYCLE
3. CONDENSED WATER CYCLE
REFRIGERATION CYCLE: -
83
Figure: Compressor
Figure: Condenser
84
CHILLING WATER CYCLE: -
85
Air Handling Unit- Regulate room temperature
Chiller Flow Switch- To control flow of chilled water
Fan/Blower- To flow air through tubes of chilled water
Screw Compressor- Coolant used HCF R134A
86
Types of Central AC System
DX (Direct expansion system) system: -
The DX Air Conditioner system uses a refrigerant vapor expansion and
compression cycle to cool air coming in through a supply plenum and returns
it to the area that needs cooling through the return. The unit effectively
circulates refrigerant through a series of condensers and evaporators, which
warm air moves through and is cooled down before being pushed through the
return.
This has an advantage of having the entire cooling system self-contained in
one unit. This allows for the installation on top of or alongside a building
without too large of a footprint, and are generally less expensive to install.
Air Cooled Chiller system: -
Chiller units also use a vapor expansion/compression cycle for liquid
refrigerant, much like the DX units. The refrigerant is continuously
transformed from a liquid, to a vapor, and back again. This process cools down
the refrigerant which is passed through an evaporator. Warm water coming
through a 2-5-inch radius supply hose is passed over the evaporator and cooled
off to the desired temperature. Typically, the cooled water is used for existing
air handler systems.
Oil separator: -
The function of an oil separator is to separate oil from the hot gas in the
discharge line and return it to the compressor crankcase or to the oil reservoir in
systems with multiple compressors.
87
Compressors Used in ONGC: -
The compressor used are screw (3) and scroll type (2)
Screw compressor –
Refrigerant of screw compressor R134a is a HFC, used in automotive air
conditioning and as a replacement for R12 and R22 in medium and high
temperature refrigeration applications, such as commercial and domestic
refrigeration and chillers. R-134a is an HFC refrigerant, which requires
polyolester (POE) lubricant to be used in the compressor.
Scroll compressor-
Refrigerant of scroll compressor is R-407C which is a non-azeotropic
mixed refrigerant composed of the three ingredients R-32, R-125, and R-
134a, and was developed as a substitute refrigerant for R-22, used in
applications such as air conditioning equipment and chiller equipment for
medium temperature ranges. It possesses outstanding properties as a
refrigerant for air conditioners, chillers, vending machines, and other
equipment.
88
Figure: Scroll Compressor
Figure: Y Strainer
89
Air Handling Unit (AHU)-
Figure: AHU
Power supply to our ONGC Systems by government is about 11000 KV, which in
case of emergency is supported by the generators.
90
ONLINE VISITS
ONGC HOSPITAL
ONGC hospital is situated in Krishna Nagar, Dehradun Uttarakhand. It is also
known as Satya Pal Wahi Hospital as a tribute to Sri Satya Pal Wahi ji. Satya Pal
Wahi was an Indian corporate executive, army officer, technocrat, writer and a
former chairman of public sector enterprises such as Oil and Natural Gas
Commission (ONGC) and Cement Corporation of India (CCI). The Government
of India awarded him the third highest civilian honour of the Padma Bhushan, in
1988, for his contributions to society. This hospital was inaugurated by Sri Dinesh
Kumar on the ONGC Day, 14th August 2017.
Among the finest Hospitals in the city, Satya Pal Wahi Hospital in Krishna Nagar,
Dehradun is known for offering excellent patient care. The clinic is located
centrally in Krishna Nagar, a prominent locality in the city. There is no dearth of
public modes of transport to reach the clinic from all major areas of the city. Satya
Pal Wahi Hospital in Krishna Nagar, Dehradun has a well-equipped clinic with
all the modern
equipment. The
clinic has separate
waiting and
consultation areas
which allow enough
space for patients to
wait conveniently at
the clinic. Being a
specialized
Hospitals, the doctor
offers a number of
medical services.
91
HVAC SYSTEM AT ONGC HOSPITAL
HVAC stands for Heating, ventilation and air conditioning system. Any machine
which fulfils the below four factors can be categorized as air conditioning system.
a. Temperature control
b. Air circulation
c. Air purification
d. Humidity control
In HVAC system, 1 TR (Ton of refrigeration) can remove 12,000 Btu (British
thermal units in FPS system) or 3,000 kilo Calorie (in MKS system) of heat each
hour. Ton is a unit of heat and one ton refers to the amount of heat required to
completely melt a ton of ice. Melting this amount of ice requires 2, 86,000 Btu.
24 hours is used as standard time period for air conditioners by HVAC technician.
Under standardized conditions, melting of a ton of ice in 24 hours requires 11,917
Btu/hour or approximately 12,000 Btu/hr.
Earlier, refrigerants used were CFC and dichlorodifluoromethane but these
refrigerants pose severe threat to ozone layer. So now-a-days refrigerant being
used is HFC (hydrofluorocarbon or freons). It does not damage the ozone layer.
HVAC system at ONGC Hospital employs Central air conditioning with chilled
water system. It comprises of 4 basic cycle.
1. Refrigeration cycle
2. Condenser-water cycle
3. Chilled water cycle
4. Air circulation cycle
92
Figure: Central air conditioning with chilled water system
b. Shell and tube type condenser: Water flows through the tube and vapor
refrigerant surrounds it in the shell. Due to the differences in temperature
of the refrigerant and the water (temperature of water being lower than that
of refrigerant), exchange of heat takes place which leads to condensation
of the vapor refrigerant. Thus, the fluid leaving the condenser is liquid
refrigerant which subsequently enters the expansion valve.
93
c. Thermostatic expansion valve: As the liquid refrigerant passes through
the expansion valve, throttling occurs due to which there is decrease in
pressure of the refrigerant.
d. Shell and tube type chiller or evaporator: Low temperature and low-
pressure refrigerant enters in tube side of the chiller and in shell side water
is present. Chiller remains insulated. Temperature of the liquid refrigerant
is less than the temperature of the water. Due to the exchange of heat
between two fluids, water cools (chilled water) and the liquid refrigerant
vaporizes. This cooled/chilled water flows through pipes in a building and
passes through cooling coils of AHU (air handling unit). The vapour
refrigerant enters the compressor through the suction lines and the
refrigeration cycle continues.
2. Condenser-water cycle:
It has three basic parts, Condenser water pump, Condenser, Cooling tower.
Condenser water pump sucks the cold water from the sump of cooling tower. This
cold water is made to pass through Y-strainer (to capture the dust particles) and
is then supplied to the tube of the shell and tube type condenser. This cold water
after gaining heat from the vapor refrigerant present in the shell side of condenser
becomes warm and it is subsequently forced back to the cooling tower where it
gets cooled down. Cooling towers are usually installed on open space like terrace
where there is free flow of air. Cooling towers cools the warm water discharged
from the condenser and feed the cooled water back to the condenser. A fan is
mounted at the top of the cooling tower. Warm water is sprinkled with the help
of nozzle in cooling tower and due to contact with the circulating air, water cools.
Cold water collects in the sump of cooling tower which is subsequently circulated
to the condenser tube with the help of condenser water pump.
94
The cold water from the shell side of the shell and tube type chiller is circulated
to cooling coils of AHU at different location using chilled water pump. A blower,
run by motor, is used to suck the return air of AHU room. Return air is made to
pass through the filter of AHU to remove the dust particles. Temperature of return
air being higher than the water present in the cooling coil, return air cools and is
circulated forward. The temperature of the water in cooling coil rises. This water
is circulated back to the chiller where it is cooled down.
When water in the chiller cools, its volume decreases. To overcome this decrease
in volume, extra volume of water is supplied from the expansion tank. When plant
is closed, the temperature of water in chiller increases due to which its volume
increases. This extra volume of water transfers to the expansion tank through the
pipeline.
4. Air Circulation cycle: Various parts involved in the air circulation cycle are
a. AHU
b. Supply air duct
c. Supply air diffuser
d. Air conditioning room
e. Return air diffuser
f. Return air duct
g. Fresh air duct
h. AHU room
The blower run by the motor causes the movement of filtered cold air to the air
conditioning room through the supply air duct. Supply air diffuser spreads the
cold air in the air conditioning room. Cold air absorbs the heat from the air
conditioning room due to which its temperature rises. This air is collected by the
return air diffuser and is forwarded to the AHU room through the return air duct.
The air reaching the AHU room has less percentage of oxygen and high
percentage of carbon dioxide. In order to maintain the level of oxygen, a fresh air
duct is present in the AHU room which introduces the fresh air from outside.
Mixture of return air and fresh air enters back into the AHU and the cycle
continues.
95
Specification of various components and miscellaneous points
Three screw compressor each of capacity 160 TR. Out of the three screw
compressors, one is kept standby and the other two remains in running
condition. So, there is a load of 320 TR.
The refrigerant used in case of screw compressor is R134A.
Four condenser pumps are installed. Out of which one is kept standby and
other three remains in running condition.
Since three chillers are present, so three cooling towers each having a
capacity of 200 TR is installed.
Three secondary chilled water pumps are used to pump the chilled water
to AHU at different location in the ONGC hospital.
One primary pump performs the function of handling warm water coming
from different location to circulate it in chiller.
In package unit, 6 scroll compressor each of capacity 10 ton are installed.
Here, two chilled water pumps are installed out of which one is kept
standby.
In case of scroll compressor, the refrigerant used is R407 and the
refrigerant discharging from scroll compressor into the condenser gets
condensed with the help of atmospheric air (using fan).
A centralized control panel is present in the plant to control the AHU at
different location wherever air-conditioning is required.
Operation panel of AHU has 2 modes i.e. auto mode and manual mode.
At critical places in ONGC hospital like ICU, OT etc. HEPA filters (very
fine filter) are used for the purification of air.
An upcoming technology, which employs the usage of UV lamps in AHU
to sterilize the air, is very soon going to be installed in the ONGC hospital.
96
SUBIR RAHA OIL MUSEUM
SROM has been housed in The ‘PATIALA HOUSE’, the most significant
heritage building of Tel Bhawan Complex of ONGC, Dehradun, India. The
‘Patiala House’ was the first property in Dehradun which ONGC had
acquired on 2 April 1957 after beginning its operations to find oil fields in
India. Later, the Building became the Headquarter of ONGC and the
complex was renamed as ‘Tel Bhawan’ which means, the Oil Mansion.
This is also the Building where Keshav Dev Malaviya – known as “Tel
Purush, a great Indian visionary in oil field, held office as the First
Chairman of ONGC.”. Thus, the Patiala House became the Hub of activity
for 60 odd Oilmen in search of oil in India and hence, it is pride of ONGC.
97
Once activities initiated for setting up of oil museum, the Patiala House,
was decided to be architecturally conserved and renovated as the Oil
Museum to become a repository of ONGC’s heritage. Later, ONGC Oil
Museum was inaugurated by Dr. A.P.J. Abdul Kalam, the then President
of India, launching the Golden Jubilee Year of ONGC in 14th August,
2005. In a befitting tribute to the visionary leader, the ONGC Golden
Jubilee Museum was rechristened as ‘Subir Raha Oil Museum’ in March,
2010 in the memory of its chairman who in true sense envisioned the
concept of oil museum for ONGC during his tenure.
98
Interesting communication strategies are deployed in the museum to
explain entire gamut of oil through informative Posters, Models, and
Interactive Displays. There is quiz section too which makes the learning
experience fun. There are also Interesting out-door displays including
working Models of real Sucker rod pumps transported from Assam and
installed for live demonstration, a working model of Christmas tree which
attracts the viewers, a model of Coiled Tubing Unit (CTU) also known as
doctor for sick wells and a bit garden where different types of drill bits are
displayed. Two Marine and Fresh Water aquaria attract children and adults
alike for its exquisite beauty.
There are “Coffee Table Book”, “Upstream and Downstream Books” &
Technical Memoirs which relive the historic moments of ONGC, spread
across a more than half century from the days of its humble beginning the
need arises to in 1956 to India’s top E & P Company.
Though at present Oil museum is closed for visitors for Covid safety,
however ONGC museum is outreaching through online presentation in a
lucid manner to far flung places for virtual visits to the students who
otherwise could not have visited museum.
At present museum Mr Ashish Garg Chief General Manager has taken over
charge as Head Museum of Subir Raha ONGC Oil Museum in Tel Bhawan
Dehradun.
Thus, The Oil Museum is a gift from ONGC to the Indian Oil Industry, the
State of Uttarakhand and the people of India. It’s a Pride of ONGC. It’s a
Pride of Uttarakhand.
99
CONCLUSION
The online summer training at ONGC, Dehradun has been a very good learning
experience. The knowledge of any theoretical subject is not enough for any
engineering student, one has to have the practical knowledge to remove the gap
between the expected and the actual performance. This particular training helped
a lot to develop various technical, industrial as well as communication skills. It
also gave a deep insight to actual equipment, the process, various operational
phases and safety aspects.
We started to study through some books, internet and materials shared by our
mentor from the basics. We have now learnt to admire these IC Engine and
HVAC System. Their elegant working, beautiful craftsmanship has us spell
bound. We have enjoyed to study during period of one month. In this project the
basic as well as advanced concept regarding IC engine as well as HVAC system
have been discussed to make us aware of all the old as well as new technology.
In this project, classification of heat engine, IC engine and different components
used in HVAC System has been discussed and about its part and application as
well.
Apart from that, the online tours to S P Wahi ONGC HOSPITAL, DEHRADUN
and a virtual visit to Subir Raha Tel Museum were a great value addition and also
initiated a spark for Industry Visit. With this we really would like to thank each
and every person I have interacted during the training and who have helped so
deep in clearing all the problems that we faced.
100
BIBLIOGRAPHY
101