Professional Documents
Culture Documents
BatteryTesting Guide
BatteryTesting Guide
www.megger.com 3
Stationary battery testing
The stationary backup batteries are the life line in any safety
system, a life line that simply cannot fail. In order to ensure safe
operation it is recommended to implement a sound and solid
battery maintenance program.
Each of the various standards (IEEE 450, IEEE 1188, IEEE 1106) have
their own best practices for battery maintenance, which we have
summarized into the following:
� Perform a capacity test if the Impedance value has changed VLA batteries are typically large batteries with low impedance. You
significantly. need adequate current to test these large low impedance batteries.
Small hand-held testers do not have the current. The BITE2 tests
� Follow a given practice (preferably from the IEEE standard) with a full 10 A of current. More than enough to get reliable
for all temperature, voltage, gravity measurements etc. and
repeatable measurements on large flooded cells.
fill in a report. This will be a great help for trending and
fault tracing. VRLA batteries typically fail in an open state due to dry-out. This
1 = 1 + 1 1 = 1 + 1
Why perform impedance testing? R T
R R 1 2
R1
R R T 2
Batteries can fail between discharge tests. This quick easy test will
increase reliability for your critical loads.
Not only will this inform you about chemical changes in your
batteries but it will also test your inter-cell connections, the battery
charge balance as well as the state of health of the charger.
www.megger.com
www.megger.com 5 5
Why backup batteries are needed
Batteries are used to ensure that critical electrical equipment is A battery is two dissimilar metallic materials in an electrolyte. In
always on. There are so many places where batteries are used – it fact, you can put a penny and a nickel in half of a grapefruit and
is nearly impossible to list them all. Some of the applications for you now have a battery. Obviously, an industrial battery is more
batteries include: sophisticated than a grapefruit battery. Nonetheless, a battery, to
work the way it is supposed to work must be maintained properly.
� Electric generating stations and substations for protection
A good battery maintenance program may prevent, or at least,
and control of switches and relays
reduce the costs and damage to critical equipment due to an AC
� Telephone systems to support phone service, especially mains outage.
emergency services
Even though there are many applications for batteries, standby
� Industrial applications for protection and control batteries are installed for only two reasons:
� Back up of computers, especially financial data and
information � To protect and support critical equipment during an AC
outage
� “Less critical” business information systems
� To protect revenue streams due to the loss of service
Without battery back-up hospitals would have to close their doors
until power is restored. But even so, there are patients on life The following discussion about failure modes focuses on the
support systems that require absolute 100% electric power. For mechanisms and types of failure and how it is possible to find
those patients, as it was once said, “failure is not an option.” weak cells. Below is a section containing a more detailed discussion
about testing methods and their pros and cons.
Just look around to see how much electricity we use and then to
see how important batteries have become in our everyday lives. Why batteries fail
The many blackouts of 2003 around the world show how critical
In order for us to understand why batteries fail, unfortunately a little
electrical systems have become to sustain our basic needs. Batteries
bit of chemistry is needed. There are two main battery chemistries
are used extensively and without them many of the services that
used today – lead-acid and nickel-cadmium. Other chemistries are
we take for granted would fail and cause innumerable problems.
coming, like lithium, which is prevalent in portable battery systems,
Why test battery systems but not stationary, yet.
There are three main reasons to test battery systems: Volta invented the primary (non-rechargeable) battery in 1800.
Planté invented the lead-acid battery in 1859 and in 1881 Faure
� To insure the supported equipment is adequately first pasted lead-acid plates. With refinements over the decades,
backed-up it has become a critically important back-up power source. The
� To prevent unexpected failures by tracking the battery’s refinements include improved alloys, grid designs, jar and cover
health materials and improved jar-to-cover and post seals. Arguably,
the most revolutionary development was the valve-regulated
� To forewarn/predict death development. Many similar improvements in nickel-cadmium
And, there are three basic questions that battery users ask: chemistry have been developed over the years.
6 title
6 Battery Testing Guide www.megger.com
Battery types
There are several main types of battery technologies with subtypes: and allows them to migrate so that they react back to form water.
This is why VRLA never needs water added compared to flooded
� Lead-acid (wet, vented) lead-acid batteries.
� Flooded (wet): lead-calcium, lead-antimony A battery has alternating positive and negative plates separated
� Valve Regulated Lead-acid, VRLA (sealed): by micro-porous rubber in flooded lead-acid, absorbed glass matte
lead-calcium, lead-antimony-selenium in VRLA, gelled acid in VRLA gel batteries or plastic sheeting in
NiCd. All of the like-polarity plates are welded together and to the
� Absorbed Glass Matte (AGM) appropriate post. In the case of VRLA cells, some compression of
the plate-matte-plate sandwich is exerted to maintain good contact
� Gel
between them. There is also a self-resealing, pressure relief valve
� Flat plate (PRV) to vent gases when over-pressurization occurs.
� Tubular plate
Nickel-Cadmium Overview
� Nickel-cadmium
Nickel-Cadmium chemistry is similar in some respects to lead-acid
� Flooded in that there are two dissimilar metals in an electrolyte. The basic
� Sealed reaction in a potassium hydroxide (alkaline) electrolyte is:
� Flat plate However, in NiCd batteries the potassium hydroxide (KOH) does
not enter the reaction like sulphuric acid does in lead-acid batteries.
Lead-acid overview The construction is similar to lead-acid in that there are alternating
positive and negative plates submerged in an electrolyte. Rarely
The basic lead-acid chemical reaction in a sulphuric acid electrolyte,
seen, but available, are sealed NiCd batteries.
where the sulphate of the acid is part of the reaction, is:
www.megger.com 7
Battery construction and nomenclature
Now that we know everything there is to know about battery To prevent plates from touching each other and shorting the
chemistry, except for Tafel curves, ion diffusion, Randles equivalent battery, there is a separator between each of the plates. Figure 1 is
cells, etc., let’s move on to battery construction. A battery must a diagram of a four-post battery from the top looking through the
have several components to work properly: a jar to hold everything cover. It does not show the separators.
and a cover, electrolyte (sulphuric acid or potassium hydroxide
solution), negative and positive plates, top connections welding all Configurations
like-polarity plates together and then posts that are also connected
Batteries come in various configurations themselves. Add to that
to the top connections of the like-polarity plates.
the many ways that they can be arranged, the number of possible
All batteries have one more negative plate than positive plate. configurations is endless. Of course, voltage plays the biggest part
That is because the positive plate is the working plate and if there in a battery configuration. Batteries have multiple posts for higher
isn’t a negative plate on the outside of the last positive plate, the current draws. The more current needed from a battery, the bigger
whole outer side of last positive plate will not have anything with the connections must be. That includes posts, intercell connectors
which to react and create electricity. Hence, there is always an odd and buss bars and cables.
number of plates in a battery, e.g., a 100A33 battery is comprised
of 33 plates with 16 positive plates and 17 negative plates. In this Single post batteries
example, each positive plate is rated at 100 Ah. Multiply 16 by 100
Smaller battery systems are usually the simplest battery systems and
and the capacity at the 8-hour rate is found, namely, 1600 Ah.
are the easiest to maintain. They usually have single post batteries
Europe uses a little different calculation than the US standards.
connected with solid intercell connectors. Frequently, they are
In batteries that have higher capacities, there are frequently four quite accessible but because they are small and can be installed in a
or six posts. This is to avoid overheating of the current-carrying cubby hole occasionally, they may be quite inaccessible for testing
components of the battery during high current draws or lengthy and maintenance.
discharges. A lead-acid battery is a series of plates connected to
top lead connected to posts. If the top lead, posts and intercell Multiple post batteries
connectors are not sufficiently large enough to safely carry the Batteries with multiple posts per polarity start to become interesting
electrons, then overheating may occur (i2R heating) and damage quickly. They are usually larger and frequently are more critical.
the battery or in the worst cases, damage installed electronics due
to smoke or fire.
Lead-acid (flooded) failure modes Corrosion of the top lead, which is the connection between the
plates and the posts is hard to detect even with a visual inspection
� Positive grid corrosion since it occurs near the top of the battery and is hidden by the
cover. The battery will surely fail due to the high current draw
� Sediment (shedding) build-up when the AC mains drop off. The heat build-up when discharging
will most likely melt then crack open and then the entire string
� Top lead corrosion drops off-line, resulting in a catastrophic failure.
� Plate sulphation Plate sulphation is an electrical path problem. A thorough visual
inspection can sometimes find traces of plate sulphation. Sulphation
� Hard shorts (paste lumps)
is the process of converting active plate material to inactive white
lead sulphate. Sulphation is due to low charger voltage settings
Each battery type has many failure modes, some of which are
or incomplete recharge after an outage. Sulphates form when
more prevalent than others. In flooded lead-acid batteries, the
the voltage is not set high enough. Sulphation will lead to higher
predominant failure modes are listed above. Some of them
impedance and a lower capacity.
manifest themselves with use such as sediment build-up due
to excessive cycling. Others occur naturally such as positive grid Lead-acid (VRLA) failure modes
growth (oxidation). It is just a matter of time before the battery
fails. Maintenance and environmental conditions can increase or � Dry-out (Loss-of-Compression)
decrease the risks of premature battery failure.
� Plate Sulphation (see above)
Positive grid corrosion is the expected failure mode of flooded
� Soft and Hard Shorts
lead-acid batteries. The grids are lead alloys (lead-calcium, lead-
antimony, lead-antimony-selenium) that convert to lead oxide over � Post leakage
time. Since the lead oxide is a bigger crystal than lead metal alloy,
� Thermal run-away
the plate grows. The growth rate has been well characterized and is
taken into account when designing batteries. In many battery data � Positive grid corrosion (see above)
sheets, there is a specification for clearance at the bottom of the jar Dry-out is a phenomenon that occurs due to excessive heat (lack
to allow for plate growth in accordance with its rated lifetime, for of proper ventilation), over charging, which can cause elevated
example, 20 years. internal temperatures, high ambient (room) temperatures, etc. At
elevated internal temperatures, the sealed cells will vent through
At the designed end-of-life, the plates will have grown sufficiently to the PRV. When sufficient electrolyte is vented, the glass matte no
pop the tops off of the batteries. But excessive cycling, temperature longer is in contact with the plates, thus increasing the internal
and over-charging can also increase the speed of positive grid impedance and reducing battery capacity. In some cases, the PRV
corrosion. Impedance will increase over time corresponding to the can be removed and distilled water added (but only in worst case
increase in electrical resistance of the grids to carry the current. scenarios and by an authorized service company since removing
Impedance will also increase as capacity decreases as depicted in the PRV may void the warranty). This failure mode is easily detected
the graph in figure 2. by impedance and is one of the more common failure modes of
VRLA batteries.
Sediment build-up (shedding) is a function of the amount of cycling
a battery endures. This is more often seen in UPS batteries but can Soft (a.k.a. dendritic shorts) and Hard shorts occur for a number of
reasons. Hard shorts are typically caused by paste lumps pushing
be seen elsewhere. Shedding is the sloughing off of active material
through the matte and shorting out to the adjacent (opposite
from the plates, converting to white lead sulphate. Sediment build-
polarity) plate. Soft shorts, on the other hand, are caused by deep
up is the second reason battery manufacturers have space at the
discharges. When the specific gravity of the acid gets too low, the
bottom of the jars to allow for a certain amount of sediment before lead will dissolve into it. Since the liquid (and the dissolved lead)
it builds-up to the point of shorting across the bottom of the plates are immobilized by the glass matte, when the battery is recharged,
rendering the battery useless. The float voltage will drop and the the lead comes out of solution forming threads of thin lead metal,
amount of the voltage drop depends upon how hard the short is. known as dendrites inside the matte. In some cases, the lead
Shedding, in reasonable amounts, is normal. dendrites short through the matte to the other plate. The float
voltage may drop slightly but impedance can find this failure mode
Some battery designs have wrapped plates such that the sediment easily but is a decrease in impedance, not the typical increase as in
is held against the plate and is not allowed to drop to the bottom. dry-out. See figure 2, Abnormal Cell.
Therefore, sediment does not build-up in wrapped plate designs.
The most common application of wrapped plates is UPS batteries. Thermal run-away occurs when a battery’s internal components
melt-down in a self-sustaining reaction.
www.megger.com 9
Failure modes
Normally, this phenomenon can be predicted by as much as four Gradual loss of capacity occurs from the normal aging process. It is
months or in as little as two weeks. The impedance will increase irreversible but is not catastrophic, not unlike grid growth in lead-
in advance of thermal run-away as does float current. Thermal acid.
run-away is relatively easy to avoid, simply by using temperature-
compensated chargers and properly ventilating the battery room/ Carbonation is gradual and is reversible. Carbonation is caused by
cabinet. Temperature-compensated chargers reduce the charge the absorption of carbon dioxide from the air into the potassium
current as the temperature increases. Remember that heating is hydroxide electrolyte which is why it is a gradual process. Without
a function of the square of the current. Even though thermal run- proper maintenance, carbonation can cause the load to not be
away may be avoided by temperature-compensation chargers, the supported, which can be catastrophic to supported equipment. It
underlying cause is still present. can be reversed by exchanging the electrolyte.
Floating effects are the gradual loss of capacity due to long periods
Nickel-Cadmium failure modes on float without being cycled. This can also cause a catastrophic
NiCd batteries seem to be more robust than lead-acid. They are failure of the supported load. However, through routine
more expensive to purchase but the cost of ownership is similar maintenance, this can be avoided. Floating effects are reversible by
to lead-acid, especially if maintenance costs are used in the cost deep-cycling the battery once or twice.
equation. Also, the risks of catastrophic failure are considerabllower
NiCd batteries, with their thicker plates, are not well-suited for
than for VRLAs.
cycling applications. Shorter duration batteries generally have
The failure modes of NiCd are much more limited than lead-acid. thinner plates to discharge faster due to a higher surface area.
Some of the more important modes are: Thinner plates means more plates for a given jar size and capacity,
and more surface area. Thicker plates (in the same jar size) have
� Gradual loss of capacity less surface area.
� Floating effects
� Cycling
www.megger.com 11
Maintenance philosophies
Capacity
Corrosion at Terminals
DC Float Current
Cycling of Ni / Cd batteries
Spectrum Analyzer
www.megger.com 13
Practical battery testing
Common test times are 5 or 8 hours and common end of discharge 11. Maintain the discharge until the battery terminal
voltage for a lead acid cell is 1.75 or 1.80 V. It is recommended voltage has decreased to the specified end of
to use the same testing time during the battery’s lifetime. This will
discharge voltage (for instance 1.75 x number of
improve accuracy when trending how battery’s capacity changes.
cells)
If the battery reaches the end of discharge voltage at the same time
as the specified test time the battery’s actual capacity is 100% of 12. Record the voltage of every cell and the battery
the rated capacity. If it reaches the end of discharge at 80% (8 h) terminal voltage at the end of the test. The
or before of the specified 10 h it is shall be replaced. See figure 3. cell voltages at the end of the test have special
Procedure for capacity test of vented lead acid importance since weak cells are indicated here.
battery 13. Calculate the actual battery capacity
1. Verify that the battery has had an equalizing It is important to measure the individual cell voltages. This has to
charge if specified by the manufacturer be made a couple of times during the test. Most important is to
measure the cells at the end of the discharge test in order to find
2. Check all battery connections and ensure all the weak cells.
resistance readings are correct
It is also very important that the time OR the current during a
3. Record specific gravity of every cell discharge test is adjusted for the temperature of the battery. A
cold battery will give less Ah than a warm. Temperature correction
4. Record the float voltage of every cell factors and methods are described in the IEEE standards.
Figure 3 If the battery reaches the end of discharge at 80% Figure 4 Replacement of battery is recommend-
(8 h) or before of the specified 10 h it is shall be replaced. ed when the capacity is 80% of rated.
Batteries can also be tested at a shorter time than their in a battery that are additive (subtractive). Other AC currents are
duty cycle, for instance at 1 hour. Then the current rate has present from the charger system. The test is performed by applying
to be increased. Advantage is that less capacity is drained an AC test signal to the terminal plates. Then measure both the total
from the battery (valid for lead-acid) and it requires less time AC current in the string and the voltage drop of each unit in the
to recharge it. Also less man-hour is needed for the test. string by measuring each cell and intercell connector consecutively
Contact your battery manufacturer for more information. until the entire string is measured. The impedance is calculated,
At higher rates it is more important to supervise the battery’s displayed and stored. As the cells age, the internal impedance
temperature. increases as depicted in figure 2. By measuring impedance, the
condition of each cell in the string can be measured and trended
Between load tests, impedance measurement is an excellent
to determine when to replace a cell or the string which helps in
tool for assessing the condition of batteries. Furthermore, it is
planning for budgetary needs.
recommended that an impedance test be performed just prior
to any load test to improve the correlation between capacity and The impedance test is a true four-wire, Kelvin-type measurement
impedance. that provides excellent reliability and highly reproducible data on
which to base sound decisions with regard to battery maintenance
Impedance test and replacement. Impedance is able to find weak cells so that
proactive maintenance can be performed. After all, the battery is a
Impedance, an internal ohmic test, is resistance in AC terms. With
cost but it is supporting a critical load or revenue stream. If a single
regard to DC battery systems, impedance indicates the condition
cell goes open.
of batteries. Since it tests the condition of the entire electrical path
of a battery from terminal plate to terminal plate, impedance can
find weaknesses in cells and intercell connectors easily and reliably.
www.megger.com 15
Practical battery testing
Specific gravity traditionally has not provided much value in There are two types of DC current on a battery: recharge
determining impending battery failure. In fact, it changes very little current which is the current applied to recharge a battery after a
after the initial 3 to 6 months of a battery’s life. This initial change discharge and float current which is the current used to maintain
is due to the completion of the formation process, which converts a battery in a fully charged state. If there is a difference between
inactive paste material into active material by reacting with the the charger setting and the battery’s voltage, that difference will
sulphuric acid. A low specific gravity may mean that the charger cause a current to flow. When the battery is fully charged [1], the
voltage is set too low causing plate sulphation to occur. only current flowing is the float current which counteracts the
self-discharge of the battery (<1% per week). Since the voltage
In a lead-acid battery the sulphate is a closed system in that the differential between the charger and the battery is small, the float
sulphate must be either on the plates or in the acid. If the battery current is small. When there is a large voltage difference such as
is fully charged then the sulphate must be in the acid. If the battery after a discharge the current is high and is limited by the charger
is discharged, the sulphate is on the plates. The end result is until the voltage difference becomes less. When the current is on
that specific gravity is a mirror image of voltage and thus state- the plateau in the graph below, this is called current limit. When
of-charge. Specific gravity readings should be taken when things the voltage differential becomes less, the charge current is reduced
are amiss in the battery to obtain as much information about the as depicted on the downward sloping charge current line on the
battery as possible. graph shown in figure 8. The charge voltage is the voltage of the
battery, not the charger setting which is why it is increasing.
Different battery applications and geographies have varying specific
gravities to accommodate rates, temperature, etc. Following is a Float current will vary with battery size. The larger the battery is,
table that describes some applications and their specific gravities. the more float current it will take to keep it fully charged. Float
current can increase for a couple of reasons: ground faults on
Specific gravities and their applications floating battery systems and internal battery faults. Ground faults
Specific gravity Percent acid Application are discussed later. As a battery’s internal impedance increases, it
1.170 25 Tropical stationary takes more current to pass through that higher impedance. The
1.215 30 Standard stationary increase in float current can be an indicator of battery faults. In lieu
1.250 35 UPS/high rate of measuring float current, many of the same conditions are found
1.280 38 Automotive with impedance.
1.300 40 VRLA stationary
1.320 42 Motive power In VRLA batteries, float current[2,3] seems to be an indicator of
1.400 50 Torpedo battery problems, namely thermal runaway. Thermal runaway is the
Float current result of a battery problem, not the cause. Some of the causes that
can lead to thermal runaway are shorted cells, ground faults, dry-
Another leg of the Ohm’s Law triangle is current. The charger out, excessive charging and insufficient heat removal. This process
voltage is used to keep a battery charged but voltage is really the takes anywhere from two weeks to four months to occur once the
vehicle to get current into the battery (or out of it during discharge). float current starts its increase. By measuring float current, it may
It is current that converts the lead sulphate back to active material be possible to avoid catastrophic failure of the battery and damage
on the grids. to connected and nearby equipment. Impedance will find many of
these same errors.
Ripple current
Batteries, as DC devices, prefer to have only DC imposed on them.
The charger’s job is to convert AC into DC but no charger is 100%
efficient. Frequently, filters are added to chargers to remove the
AC current from the DC output. The AC current on the DC is called
ripple current. Battery manufacturers have stated that more than
about 5 A rms of ripple for every 100 Ah of battery capacity can
lead to premature failure due to internal heating. Ripple voltage
is not a concern since it is the heating effect of the ripple current
Figure 8 Constant-voltage Constant-current charge that damages batteries. The 5% ripple current figure is a rough
characteristics estimate and depends also on the ambient temperature. Ripple
current can increase slowly as the electronic components in the
[1] Cole, Bruce, et al., Operational Characteristics of VRLA Batteries Configured in Parallel Strings, GNB Technologies
[2] Brown, AJ, An Innovative Digital Flat Current Measurement Technique - Part Two, Proceedings of BattConn® 2000
[3] Boisvert, Eric, Using Float Charging Current Measurements to Prevent Thermal Runaway on VRLA Batteries, Multitel
[4] Ruhlmann, T., Monitoring of Valve Regulated Lead Acid Batteries, Proceedings of BattConn® 2000
www.megger.com 17
Practical battery testing
they may all age the same but most likely there will be some
cells which begin to fail early. In either case new or old we are
looking for the differences. Below in the table are strap resistance
measurements of a 60 cell string. It is easy enough to look through
the data and see a few numbers which do not seem correct, but
when you look at the graph of the same data it is a lot clearer what
needs to be looked at and what does not.
Cell’s % change
Cell’s % change
Cell’s % change
Cell’s % change
from last test
overall
overall
Figure 11 Impedance percent deviation from average
Lead-acid, Flooded 5 2 15 2 20
Lead-acid, VRLA,
10 3 30 3 50
AGM
Lead-acid, VRLA,
10 3 30 3 50
Gel
NiCd, Flooded 15 10 50 10 100
NiCd, Sealed 15 5 35 5 80
All of the data presented thus far has been presented using a
standard Excel spreadsheet. Spreadsheets are very useful and have
been around almost as long as computers. There are software
packages presently available such as PowerDB that automatically
chart and trend the data for you. The important step is to use
graphics to help in the analysis of data that is newly measured and
possibly with data still contained in a paper or electronic file.
www.megger.com 19
Locating ground faults on DC systems
without sectionalizing
Overview A better test method
The main objective of a battery system is to provide standby and Developments have led to a better test method; injecting a
emergency power to operate industrial, consumer, commercial low-frequency AC signal and using that AC signal to locate the
or protective devices. Some of these devices include emergency ground in the DC system. This method can be performed without
lighting units, uninterruptible power supplies, continuous process sectionalizing the DC system and it reduces the fault locating time
systems, operating controls, switchgear components and protective from days to hours. Furthermore, it allows for system protection to
relays. be present at all times.
In emergency situations, it is essential that these devices be in The AC injection method measures single or multiple ground faults
proper operating condition. Failure of a DC system or the battery by first injecting a low-frequency, 20 Hz AC signal between the
can result in operational failure of the devices connected to that station ground and the battery system. Second, the resulting current
system. System failure can lead to loss of revenue, damage to is then measured by using a clamp-on sensing current transformer.
equipment and/or injured personnel. From this, the resistance value can be calculated using the in-phase
component of the circulating current, thus rejecting the effect of
It is a common situation for a floating DC system to develop grounds capacitive loads. Therefore, if the signal is injected at the battery
within it. When a battery system is partially or completely grounded, terminal and the clamp-on CT is connected to the outgoing lead,
a short circuit is formed across the battery and consequently may the instrument will measure the total ground resistance present
cause the protective device to fail to operate when needed. on the battery system. If the CT is clamped on a feeder, then the
instrument will measure the ground resistance on that feeder.
Current test methods Faults can be traced easily regardless of the number of distribution
Traditionally utilities and industrial complexes have gone to great panels or circuits because the “tracer” is merely following the
lengths to find ground faults within their battery systems. However, strength of the AC signal. System integrity is maintained because it
locating these battery grounds proves to be a very elusive and time- is an on-line AC test and is designed to prevent system trips.
consuming process. The current ground-fault location method
After injection of a low-frequency AC waveform, a resistive fault
involves sectionalizing, or interruption, of DC branches to isolate
on a branch of the battery system will be indicated by a low-
the ground fault. Sectionalizing disables the system protection and
resistance value. For example, if the total resistance of a battery
has been known to cause inadvertent line and generator tripping.
system showed 10 kΩ, this would indicate a resistive fault on the
For this reason, many utilities have banned sectionalizing. Until
battery system. The resistive fault can be located by clamping on
more recently, though, this had been the only method available to
each individual circuit until a resistive value of 10 kΩ is found.
locate ground faults.
It is easy to see that this method can be adapted in a straight
forward manner to locate multiple faults by using the theory of
parallel paths. For example, if the total system resistance indicates
1 kΩ and an individual branch indicates 10 kΩ resistive fault, the
user would know that the system has a second fault because the
total system resistance and the branch resistance do not match. By
using the AC injection method, ground faults on ungrounded DC
systems is easy, straight-forward and safe.
www.megger.com 21
Megger products overview
Megger offers solutions to ensure system performance with BITE3
� Determines the condition
its comprehensive line of Battery Test Equipment, Low Resistance
of lead-acid batteries
Ohmmeters and Micro-ohmmeters, Insulation Testers, and
Multimeters. � On-line testing with Pass/
Warning/Fail calculations
An overview of the various products available is described
below. For more information on these and many other Megger � Measures impedance,
products, visit our web site www.megger.com for the most intercell connection
up-to-date news, product and service information. resistance, cell voltage
Taking the battery off-line for testing is time consuming and adds BITE2 and BITE2P
risk to the process. This process is unnecessary with the on-line
testing capabilities of the Megger family of battery test products.
The highly repeatable instruments help reduce downtime.
� On-line testing
www.megger.com 23
Capacity testing
� Unit adjusts to include load currents in the test parameters � Automates battery voltage measurement during
capacity tests
� User adjustable alarm and shutdown points to avoid excessive
discharge � Up to 2x120 units can be used (Daisy-chain)
Batteries in power plants and transformer substations must provide The Megger BVM is a battery voltage measurement device that
the equipment they serve with standby power in the event of a is used for the capacity testing of large, industrial battery banks
power failure. Unfortunately, however, the capacity of such commonly found in electrical power substations, telecom facilities
batteries can drop significantly for a number of reasons before their and computer data center UPS systems. When used in conjunction
calculated life expectancy is reached. This is why it is so important with a TORKEL unit and PowerDB and TORKEL Win, the BVM
to check batteries at regular intervals, and the only reliable way of enables the TORKEL to perform a completely automated battery
measuring battery capacity is to conduct a discharge test. bank capacity test according to IEC test methods. The test also
meets NERC/FERC requirements. The BVM is designed in modular
The TORKEL instruments are used for discharge testing. Tests form where one BVM device is used for each battery or “jar” in the
can be conducted at constant current, constant power, constant string to be tested. One BVM for each battery connects to the next
resistance or in accordance with a pre-selected load profile. For in a “daisy-chain” fashion, thereby providing easy and economical
extra discharge capacity there are auxiliary load units available. expandability to meet the testing requirements for small-to-large
battery bank systems.
TORKEL 860 is designed for users who travel from place to place
to maintain battery systems having different voltages. It features Setup is fast and easy using the BVM. Each BVM is identical and
excellent discharging capacity plus a broad voltage range and can be connected in any battery test position, thus providing
outstanding portability. The TORKEL 860 is used for systems maximum flexibility and interchangeability of the BVMs. Up to
ranging from 12 to 480 V. 120 BVMs can be daisy chained in a single battery bank under
test. The BVM “Auto Discovery” feature enables the host device
to automatically determine the number of batteries under test and
provide sequential identification of each BVM in the test string.
TORKEL 900
www.megger.com 25
Ground fault tracing equipment
Battery Ground-fault Locator (BGL) Digital Low Resistance Ohmmeters (DLRO®) and
Microhmmeters (MOM)
Many times batteries fail not because of weak cells but due to weak
intercell connections. Torquing is a mechanical method to ensure
that the electrical path resistances is very low. But it does not truly
indicate the quality of the electrical path resistance. The only true
method is to measure each intercell connection resistance.
Megger has several DLROs and MOMs that are appropriate for
intercell connection resistance. The portability of the instruments
allows effortless mobility around battery strings.
� Ground faults in ungrounded DC battery systems The instruments are built into strong, lightweight cases that are
are easily located
equally at home in the field or in the laboratory.
� Features an automatic bridge
DLRO200 and DLRO600
� Battery operated
� Simplifies fault tracing by identifying fault characteristic � Small and weighs less than
(resistive and capacitive) magnitudes 15kg (33 lbs)
The DLRO10 and DLRO10X are fully automatic instruments, � Resolution 1µΩ on 200 mΩ range
selecting the most suitable test current, up to 10 A DC to measure
resistance from 0.1 µΩ to 2000 Ω on one of seven ranges. � Standard inaccuracy of ±1%
For users who desire more control over the measurement process, � MOMWin™ software
DLRO10X uses a menu system to allow manual selection of the test � AC output
current. DLRO10X also adds real-time download of results and on-
board storage for later download to a PC. In addition to high current capacity, MOM690™ features
microprocessor-based measurement, storage and reporting. The
built-in software enables you to carry out an individual test or an
� True DC ripple free current entire series of tests and store the results.
� Inaccuracy ±0.3 μΩ With the optional MOMWin™ software you can also
export the test results to a PC for further analysis and reporting.
� Two displays LED and LCD
Ranges are set automatically, resistances are measured continually
for visibility
and test results can be automatically captured at a preset test
in all conditions
current.
� Low weight, 8.8 kg (19.4
lbs) and 13.8 kg (30.4 lbs)
www.megger.com 27
Insulation resistance test equipment
Batteries are supposed to be well insulated from adjacent MIT400/2 series insulation
equipment and metallic objects. The insulation provides several resistance testers
benefits: 1) keeps the charge in the battery rather than letting it
leak, 2) provides for normal float current, and 3) reduces energy � Choice of 4 models for commercial
losses. If a battery is leaking electrolyte, then there may be a path and plant applications: MIT Models
to ground. When a path exists, the current needed to keep the 400/2, 410/2, 420/2 and 430/2
battery fully charged increases. It also shortens the length of back-
� Choice of 2 models for telecom
up time of the battery depending upon the severity of the leak. An
applications:
insulation resistance test can identify whether there are leaks. The
MIT Models 480/2 and 481/2
insulation resistance is measured across one of the terminals of the
battery to some ground, presumably the battery rack or tray. It is a
very easy test to perform and provides for a lot of confidence in the
overall state of electrical insulation.
This test applies a DC voltage, say 500 Vdc, between the buss,
The series consists of six instruments
off-line and the rack. Then measures the DC leakage current to
calculate resistance in MΩ or GΩ. The higher the resistance is the MIT400/2 250 V, 500 V and 1000 V
better. This test is recommended at installation and whenever a MIT410 /2 50 V, 100 V, 250 V, 500 V and 1000 V plus
leak may be suspected (from tell-tale signs such as salt build-up.) PI, DAR and timed
MIT420/2 Same as Model 410/2 plus result storage
Megger offers the MIT400/2 Series insulation and continuity and download
testers designed for electrical testing by power utilities, industrials,
MIT430/2 Same as Model 420/2 plus Bluetooth®
telecommunication companies, commercial/ domestic electricians download
and anyone with unique test voltage requirements. The wide range
MIT480/2 50 V, 100 V, 250 V, 500 V
of features also makes the MIT400/2 Series ideal for maintenance
MIT481/2 50 V, 100 V, 250 V, 500 V, result storage and
technicians and engineers. Bluetooth®
These instruments are available from as low as 50 V to as high as
1 kV. For analytical applications, multiple test voltages are desired.
� Windows-based PC software available in three versions Test forms are designed for the majority of the electrical apparatus
on the market today. PowerDB currently supports the following
� Interfaces to instruments via either Serial RS232, Ethernet,
devices:
or USB flash drive (depending on instrument)
� Allows user to set up test routines in advance of testing � Batteries � Insulation fluids
� User can customize the User Interface (test form view) with � Circuit breakers � Motor control centers
the ONBOARD and Full versions
� Coordination data � Power Ffactor tests
� Disconnects � Relays
PowerDB is a powerful software package providing data
management for each of your acceptance and maintenance testing � Generators � Switchboards
jobs. Data can be imported from various sources, acquired directly
from test instruments, or entered manually. Test results for all � Ground fault tests � Transfer switches
electrical apparatus are synchronized to your company’s central � Ground Mat/Grid tests � Watthour meters
database. Result and summary reports can be easily generated.
� Instrument transformers � transducers
PowerDB Lite is free software allowing you to use standard
PowerDB test forms with Megger instruments. It provides a � Power transformers
simple and consistent user interface to many Megger instruments
including the Delta3000 power factor test set, 3-Phase TTR, earth
The software will perform extensive information processing
testers and 5 and 10kV insulation testers.
including equation calculations, temperature correction factors
PowerDB ONBOARD runs directly on the Megger test instrument, and charting. Data trending for predictive failure analysis is
and the forms are the instrument’s user interface. Test results are accomplished by charting historical results, stored in PowerDB or
transferred with a standard USB drive and can then be read into imported from other party’s proprietary database software, for any
PowerDB or PowerDB Lite. piece of equipment.
www.megger.com 29
Megger Limited
Archcliffe Road
Dover CT17 9EN
United Kingdom
www.megger.com
BatteryTesting Guide_EN_V02
The word ‘Megger’ is a registered trademark. Copyright © 2021