Professional Documents
Culture Documents
A Simple Model For Transformer Inrush Current Calculation and Harmonic Analysis
A Simple Model For Transformer Inrush Current Calculation and Harmonic Analysis
Abstract
Measurements of transformer inrush current offer important data for power system operation and protec-
tion. Since inrush current is the result of a system transient, it is difficult to observe this phenomenon and
analyze its effect instantaneously. This paper proposes a simple model to represent and simulate the
magnetizing inrush current of transformers using real-time measurements. The proposed method formulates
a simplified model to represent the inrush current under different loading conditions. The simulation data
are also used for harmonic analysis. The relationship of the harmonics to all parameters is discussed. The
proposed simulation results are compared with the experimental results with very good agreement. The
results establish a guideline for elimination of harmonics due to inrush current, and offer an important
reference for system design considerations.
(6)
1
+ ob sin(wt + a) for I, >, 0
(i2)k =a @$!!_L2Q!!$ (9)
2[
= -[L + s,( -& - M
where
+ ob sin(ot + a) for I, < 0 (13)
(A&)k =; (An,), where
1
Based on the flowchart of Fig. 3, a ~eal-time An experiment was carried o u t w h e n the rema-
p r o g r a m was implemented on a PC-AT c o m p u t e r nent flux linkage ~r was 0 Wb turns. The experi-
to calculate the magnetizing inrush c u r r e n t of mental d a t a and the simulation d a t a for p e a k
single-phase transformers. In this experimental values within 10 cycles are compared in Table 1.
system, N sets of ,~1 and im data were computed There is good a g r e e m e n t b e t w e e n the c u r r e n t s
from the im--~l hysteresis curve of the trans- from experiments ( E + ) and from simulations
former [3], and were used as input d a t a for the (S*). The difference in each cycle is less t h a n 5%.
next calculations. Other data were as follows: Comparing the results u n d e r different rema-
nent flux linkages, ~r = 0, 0.1951 (0.42max), • • •,
Primary V, = 130 V Ii(rating) = 5A --0.3902 Wb turns, the v a r i a t i o n in inrush cur-
winding rent is sensitive to the r e m a n e n t flux. For large
Secondary V2 = 130 V /2(rating) = 23 A
positive values of the r e m a n e n t flux, the rema-
winding
nent flux is added to the main flux. Therefore,
Third V3 = 7600 V I3(rating) = 0.395 A
core s a t u r a t i o n becomes more severe and results
winding
in a larger inrush current, and vice versa within
(not used)
certain limits. Comparing the simulation results
The resistive part of the load impedance, Z2, under ~ r = 0 W b t u r n s and switch-on angle
was set at a very high value to consider it as an = 0 °, 3 0 ° , . . . , 150 °, the inrush c u r r e n t is found
open circuit; it was fixed at 26 ~ for all loading to decrease as the switch-on angle increases.
tests. The p o w e r factors for all the different load- However, w h e n ~ > 90 °, the negative inrush cur-
ing conditions were controlled by changing the rent increases. F o r large values of ~, b u t less
series inductor or the parallel capacitor. t h a n 90 °, flux s a t u r a t i o n in the core is n o t signifi-
cant, and the inrush c u r r e n t decreases.
W h e n the inrush c u r r e n t is simulated, the
4. M a i n r e s u l t s s p e c t r u m analysis can be o b t a i n e d using the F F T
algorithm. Table 2 shows the harmonic c o n t e n t s
4.1. No-load condition c o n t a i n e d in the first cycle of the inrush current.
W h e n a t r a n s f o r m e r is energized, its s e c o n d a r y The analysis is carried o u t independently, one
is open-circuited, and the initial magnetizing in- cycle after another, as previously described. It is
rush c u r r e n t has a close relationship with the found t h a t the harmonic c o n t e n t s are rich in the
r e m a n e n t flux ~br. The r e m a n e n t flux linkage ~r, DC component, the second and the third har-
corresponding to ~br, will be used as a p a r a m e t e r monic. A comparison of the results for r e m a n e n t
in a later discussion. flux linkages ~r=0.3902 and 0.1951Wb t u r n s
,~r Cycle 1 2 3 4 5 6 7 8 9 10
(A)
0° 0 S* 40.0 8.9 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
E+ 40.3 9.2 6.0 4.8 4.3 4.0 3.9 3.7 3.6 3.6
0° 0.1951 S* 55.3 9.1 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
0.3902 S* 65.4 9.1 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
-0.1951 S* 21.0 8.0 5.5 4.5 4.1 3.9 3.7 3.7 3.6 3.6
-0.3902 S* 6.7 5.0 4.4 4.0 3.8 3.7 3.6 3.6 3.6 3.6
30 ° 0 S* 35.3 8.9 5.7 4.6 4.2 3.9 3.8 3.7 3.6 3.6
E+ 35.8 9.1 5.9 4.7 4.3 3.9 3.8 3.8 3.7 3.6
60 ° 0 S* 18.8 7.8 5.4 4.5 4.1 3.8 3.7 3.6 3.6 3.6
E+ 19.2 8.0 5.5 4.7 4.2 3.9 3.8 3.7 3.6 3.6
90 ° 0 S* 4.0 3.8 3.7 3.6 3.6 3.6 3.6 3.6 3.6 3.6
E+ 4.2 3.9 3.8 3.7 3.6 3.6 3.6 3.6 3.6 3.6
120 ° 0 S* -14.7 -7.1 -5.2 -4.4 -4.1 -3.8 -3.7 -3.6 -3.6 -3.6
150 ° S* -33.0 -8.8 -5.7 -4.6 -4.2 -3.9 -3.8 -3.7 -3.6 -3.6
S* = s i m u l a t i o n results; E + = e x p e r i m e n t a l results.
158
T A B L E 2. H a r m o n i c a n a l y s i s u n d e r n o - l o a d , v a r i o u s r e m a n e n t flux a n d s w i t c h - o n a n g l e c o n d i t i o n s ( a l l h a r m o n i c s a r e s h o w n a s a
p e r c e n t a g e of t h e f u n d a m e n t a l c u r r e n t for t h e f i r s t c y c l e )
DC 55.6 58.0 61.6 52.0 30.3 54.1 49.7 6.2 51.6 55.2
2nd 63.0 58.3 50.1 62.7 39.7 62.9 60.2 7.5 66.1 66.7
3rd 34.3 27.5 19.1 37.2 35.4 34.8 37.0 39.1 38.3 36.4
4th 15.3 12.8 9.7 15.7 9.4 16.4 15.8 ] .6 15.7 16.7
5th 7.4 6.3 5.6 8.1 7.6 7.3 6.9 7.5 6.1 8.1
6th 4.3 3.7 2.6 2.3 0.7 4.0 2.9 0.4 2.3 3.9
7th 1.8 2.3 1.5 2.0 0.9 2.2 1.2 0.3 0.'7 2.2
8th 1.2 1.2 1.2 1.1 1.2 ] .0 0.7 0.3 0.2 1.0
9th 0.8 0.8 0.4 0.2 1.7 0.3 0.5 0.3 0.1 0.7
tions has been made. The larger positive rema- |th Condition:
n e n t flux linkages result in smaller h a r m o n i c u =0"
contents, except for the DC component. Compar- 9O r=0 Wb.turns.
ing the results u n d e r the r e m a n e n t flux linkage tn
~r = 0 Wb turns, with v a r y i n g switch-on angles
e%
= 0 °, 30 °, 60 ° a n d 90 °, the h a r m o n i c c o n t e n t s are J 0 [ I I I I
5 7 9
found to decrease as the switch-on angle ~ in- o~
creases, except for the 3rd harmonic. CycleNumber
F i g u r e 4 shows the percentage of h a r m o n i c
c o n t e n t s up to the fifth h a r m o n i c over ten cycles.
O4-90
It can be seen t h a t the second h a r m o n i c term is
larger t h a n the DC c o m p o n e n t in the first cycle,
-180
but decays more r a p i d l y t h a n the latter. F i g u r e 5
shows the phase shifts of the h a r m o n i c c o n t e n t s Fig. 5. P h a s e s h i f t s of h a r m o n i c c o n t e n t s a s a f u n c t i o n o f t i m e
for a = 0 ~' a n d "it = 0 W b t u r n s .
up to the fifth h a r m o n i c over ten cycles. The
phase shift v a r i a t i o n of the even h a r m o n i c s is
seen to converge to 0 °, but t h a t of the odd har- monics stays between - 1 4 0 ° and - 1 8 0 ~ u n d e r
steady-state conditions.
Z2 ~ pf Cycle 1 2 3 4 5 6 7 8 9 10
(fl) (A)
0° S* 40.0 8.9 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
43.3 0° 1.0 S* 35.4 9.4 6.2 5.2 4.7 4.5 4.5 4.5 4.5 4.5
E+ 35.1 10.0 6.4 5.2 4.7 4.4 4.4 4.4 4.4 4.4
26 0° 1.0 S* 32.6 10.0 7.2 6.9 6.9 6.9 6.9 6.9 6.9 6.9
E+ 32.8 10.6 7.3 7.1 7.0 6.9 6.9 6.9 6.9 6.9
26 0° 0.9 S* 34.4 12.5 9.3 8.3 7.8 7.5 7.4 7.3 7.3 7.3
E+ 33.2 13.0 9.7 8.6 7.8 7.5 7.4 7.3 7.3 7.3
26 0° 0.8 S* 35.2 13.6 10.2 9.1 8.5 8.1 7.9 7.8 7.7 7.7
E+ 34.1 14.3 10.7 9.4 8.8 8.5 8.1 7.8 7.7 7.7
26 0° 0.7 S* 35.7 14.4 10.9 9.7 9.1 8.7 8.5 8.3 8.2 8.2
0.6 S* 36.2 15.4 11.8 10.5 9.8 9.4 9.2 9.0 8.9 8.9
26 0° -0.9 S* 33.0 6.9 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.7
E+ 32.2 7.1 7.0 6.9 6.9 6.9 6.9 6.9 6.9 6.9
26 0° -0.8 S* 33.3 6.8 6.8 6.7 6.7 6.7 6.7 6.7 6.7 6.7
E+ 33.9 7.1 7.0 7.0 7.0 6.9 6.9 6.9 6.9 6.9
26 0° -0.7 S* 33.8 6.8 6.7 6.7 6.7 6.6 6.6 6.6 6.6 6.6
-0.6 S* 34.4 6.8 6.7 6.6 6.5 6.5 6.5 6.5 6.5 6.5
26 30 ° 1.0 S* 27.5 9.8 7.1 6.9 6.9 6.9 6.9 6.9 6.9 6.9
60 ° S* 14.0 8.1 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.8
90 ° S* 7.5 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8 6.8
120 ° S* -11.2 -7.5 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9
150 ° S* -25.6 -9.6 -7.1 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9
26 30 ° 0.8 S* 30.5 13.3 10.1 9.0 8.5 8.1 7.9 7.8 7.7 7.7
60 ° S* 17.1 11.2 9.5 8.7 8.3 8.0 7.9 7.8 7.7 7.7
90 ° S* 7.1 7.8 7.7 7.7 "7.7 7.6 7.6 7.6 7.6 7.6
120 ° S* -14.4 -10.5 -9.2 -8.6 -8.2 -8.0 -7.8 -7.7 -7.7 -7.7
150 ° S* -28.6 -13.1 -10.0 -9.0 -8.5 -8.1 -7.9 -7.8 -7.7 -7.7
i00
80 Condition:
=0 ° ,
=0 Wb. turns,
R2=26 Ohms.
60
oo
g H
,--4
S C
H
40
cg ~
i
2O
eg c~
m o
©
0.
3 5 7 9
Cycle Number
o
© Cg ~ ~ Fig. 6. P e r c e n t a g e h a r m o n i c c o n t e n t s up to t h e fifth h a r m o n i c a s
a f u n c t i o n o f t i m e for x = 0 , ) , = 0 W b t u r n s , a n d R 2 = 2 6 ~.
cq ~ ~
180,
cq ~ ~ Condition:
|th
a =0 ° ,
oo 90
lr=O Wb.turns,
cq co ~ ~n
R2=26 Ohms.
,J
DC
? cg 0 I I I I I I I I I
5 7 9
to
Cycle Number
~D
c
m -90
oo
ea
-180
© Fig. 7. P h a s e s h i f t s o f h a r m o n i c c o n t e n t s as a f u n c t i o n o f t i m e
for ~ = 0 ' , 2 r = 0 W b t u r n s a n d R 2 = 26t1.
©
I I I I I I
6. Conclusions
5 7 9
Cycle Number This paper d e m o n s t r a t e s an a c c u r a t e model £br
predicting the magnetizing inrush c u r r e n t in sin-
~ -90
gle-phase transformers. Conditions under investi-
gation are related to transformer loading,
switch-on angles, and r e m a n e n t flux. The results
-180 of the simulation by the proposed method are
Fig. 11. P h a s e s h i f t s o f h a r m o n i c c o n t e n t s a s a f u n c t i o n o f t i m e compared with the experimental results by on-
f o r ~ = O , )~,.= 0 W b t u r n s , p f = 0.8 l e a d i n g , a n d Z 2 = 26 ft. line measurements. These two sets of results
agree very well.
The h a r m o n i c c h a r a c t e r i s t i c s in the inrush cur- From the analysis and results, harmonics due
r e n t are analyzed and studied in detail. U n d e r to inrush c u r r e n t s can be simulated accurately.
no-load and v a r i o u s loading conditions, the vari- Each c o m p o n e n t t h a t causes effects on protec-
ations of the h a r m o n i c c o n t e n t s and their phase tive relays can also be simulated. This is valu-
shifts with r e s p e c t to time are described in vari- able for applications such as t r a n s f o r m e r
ous diagrams and tables. protective relaying. Also, the main h a r m o n i c s
From the results obtained, it is found t h a t the can be eliminated by changing loading condi-
h a r m o n i c c o n t e n t s are rich in the DC compo- tions, switch-on angles and power factors. Over-
nent, the second and the third harmonics. U n d e r voltage resulting from h a r m o n i c r e s o n a n c e can
no load, resistive, inductive and capacitive load, be avoided in practical system operation.
the second h a r m o n i c is always larger t h a n the In addition to this study, investigations on in-
DC c o m p o n e n t in the first cycle, b u t decays more rush currents and harmonics in three-phase trans-
rapidly t h a n the latter. F u r t h e r conclusions are formers are being carried o u t in our laboratory.
summarized as follows.
(1) No-load condition. The larger the r e m a n e n t
flux, the g r e a t e r the h a r m o n i c contents, except for Acknowledgement
the DC component, which decreases. The larger
the switch-on angle, the more the h a r m o n i c This w o r k is s u p p o r t e d by the N a t i o n a l Science
163
Council under research projects NSC78-0404- magnetising inrush current in transformers, Electr. Power
E006-04 and NSC80-0404-E006-04. Syst. Res., 2 (1979) 179-182.
7 S. Akpinar, M. Coulson, R. R. S. Simpson and R. D. Slater,
Calculation of transient current in transformers, Proc. Inst.
Electr. Eng., Part C, 129 (1982) 30 34.
References 8 J. P. Bowles, Overvoltages in HV DC transmission systems
caused by transformer magnetizing inrush currents, IEEE
1 L. A. Finzi and W. H. Mutschler, The inrush of magnetizing Trans., PAS-99 (1974) 487-493.
current in single-phase transformers, Trans. AIEE, 70 (1951) 9 D. Povh and W. Schultz, Analysis of overvoltages caused by
1436-1438. transformer magnetizing inrush current, I E E E Trans., P A S -
2 J. E. Holcomb, Distribution transformer magnetizing inrush 97 (1978) 1355-1365.
current, Trans. AIEE, Part 3, 57 (1961) 697 702. 10 C. E. Lin, J. B. Wei, C. L. Huang and C. J. Huang, A new
3 R. Yacamini and A. Abu Nasser, Transformer inrush current method for representation of hysteresis loops, I E E E Trans.,
and their associated overvoltages in HVDC schemes, Proc. PWRD-4 (1989) 413 420.
Inst. Electr. Eng., Part C, 133 (1986) 353-358. 11 C. E. Lin, J. B. Wei, C. L. Huang and C. J. Huang, A new
4 R. Yacamini and A. Abu Nasser, The calculation of inrush model for transformer saturation characteristics by includ-
current in three-phase transformers, Proc. Inst. Electr. Eng., ing hysteresis loops, IEEE Trans., MAG-25 (1989) 2706-
Part B, 133 (1986) 31-40. 2712.
5 R. Yacamini and A. Abu Nasser, Numerical calculation of 12 C. E. Lin, C. L. Cheng and C. L. Huang, Hysteresis character-
inrush current in single-phase transformers, Proc. Inst. istic analysis of transformers under non-sinusoidal excita-
Electr. Eng., Part B, 128 (1981) 327-334. tions using real time measurements, I E E E Trans., P W R D - 6
6 M. Basu and K. P. Basu, Computerised evaluation of the (1991) 873-879.