Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Electric Power Systems Research, 24 (1992) 153-163 153

A simple model for transformer inrush current calculation and


harmonic analysis

C. L. Cheng, a C. E. Lin, b C. L. Huang b and J. C. Yeh b


aDepartment of Electrical Engineering, Yunlin Polytechnic Institute, Yunlin (Taiwan)
bDepartment of Electrical Engineering, Cheng Kung University, Tainan (Taiwan)

(Received March 12, 1992)

Abstract

Measurements of transformer inrush current offer important data for power system operation and protec-
tion. Since inrush current is the result of a system transient, it is difficult to observe this phenomenon and
analyze its effect instantaneously. This paper proposes a simple model to represent and simulate the
magnetizing inrush current of transformers using real-time measurements. The proposed method formulates
a simplified model to represent the inrush current under different loading conditions. The simulation data
are also used for harmonic analysis. The relationship of the harmonics to all parameters is discussed. The
proposed simulation results are compared with the experimental results with very good agreement. The
results establish a guideline for elimination of harmonics due to inrush current, and offer an important
reference for system design considerations.

Keywords: inrush current, harmonic analysis, numerical simulation, real-time measurements.

1. I n t r o d u c t i o n harmonics in the applications was not a major


concern. Owing to the serious effects of harmon-
This paper presents a simple model for inrush ics on power system operation in the last decade,
current representation and its application to har- the influence of harmonics is now an important
monic analysis for single-phase transformers. issue. Solid-state power electronics devices are
The magnetizing transformer inrush current has known to be strong sources of harmonics under
a close relationship with the nonlinearity and steady-state conditions. However, during switch-
hysteresis of the iron core. This results in analyt- ing and fault transients, harmonics generated
ical complexity. Several methods [1-7] have been from power transformers are also annoying, caus-
used to derive the analytical solution or the nu- ing false tripping of protection relays. Over-
merical simulation by applying various tech- voltages [3, 8, 9] resulting from inrush currents
niques. The main drawback of these methods was also cause serious damage to power devices.
their mathematical complexity and the difficulty The proposed method provides an improved
of obtaining parameters. In addition, these meth- model to express the inrush current from a finite
ods could not cover all loading conditions accu- difference form using digital data acquisition [10-
rately. They were only suitable for some par- 12]. The inrush current data obtained are used for
ticular conditions of power system operation. harmonic analysis. The fast Fourier transform
In power system operation, transformers are (FFT) is used to analyze the frequency spectrum
switched on and off quite frequently under nor- and harmonic content of the inrush current. Since
mal conditions. Inrush currents resulting from the proposed technique is simple and straightfor-
transformer switching, therefore, cause more se- ward, simulations can be carried out repeatedly
rious problems than the energizing currents of under different setting conditions. The analysis
transformers. An accurate method to predict the can therefore look into more details for each
magnetizing inrush currents is useful for system particular condition of the studied problems.
operation and protection. Considering the transient inrush current, the
When the above-mentioned methods were used relationship representing both the im-~b (magne-
to investigate inrush currents in transformers, tizing c u r r e n t - m u t u a l flux) hysteresis loop [10]

0378-7796/92/$5.00 © 1992 Elsevier Sequoia. All rights reserved


154

and the saturation characteristics [11] has a


strong influence on the simulation accuracy. il • I ] • i2
When they are used in combination with circuit I o
loop equations, a numerical simulation method
must be applied. The numerical simulation tech-
nique presented in this paper uses a new method
1
+
v2 R2I
L2

to include both the i m - ¢ hysteresis loop and the


saturation characteristics [10, 11]. This expres-
- -
° -]j , r
~
x,.. . . . . . . . . j
I
sion satisfies the above conditions, and is very
simple to use for the proposed applications.
The proposed numerical model is described in
this paper. Experiments as well as simulations
~i ~ • I I • i2
are carried out to examine this method. Different
test parameters such as switch-on angle, load
power factor and remanent flux are taken into
consideration. The experimental and simulation
results are compared. Very good agreement can
be achieved.

,b) l ........ "l


2. T h e p r o p o s e d m e t h o d Fig. 1. A c t u a l t r a n s f o r m e r l o a d i n g : ( a ) i n d u c t i v e l o a d ; (b) c a p a c -
itive load.

The transformer is a major piece of equipment


in a power system. Its duty relating to electro- inductance, equal to the primary winding leak-
magnetic conversion connects higher levels of age inductance if the source impedance is ne-
power delivery to lower utility levels. Flux link- glected, Ema x the maximum voltage of e(t), u~ the
age of the primary and secondary windings in the frequency (in rad/s), of the exciting voltage, and
iron core is designed to carry out the energy the switch-on angle (in rad) of the voltage
conversion. However, considering practical waveform.
conditions, flux leakage of transformer windings
plays a significant part in such a conversion. 2.1. No load, resistive load or inductive load
Therefore, flux leakage and hysteresis loops, Under no load, resistive load and inductive
in terms of i m and q~, should also be included in load, since they have similar characteristics, the
the representative circuit modeling. Here, only system can be discussed in general. We assume
the effect of eddy currents in the iron core is that the impedance of the secondary winding can
neglected. be neglected in comparison with the load
In general, the transformer secondary may be impedance when the transformer secondary is
unloaded (open circuit) or loaded with different connected to a resistive load or an inductive load
power factors. A power transformer is assumed as shown in Fig. l(a). The differential equation of
to be connected to an infinite bus. By Kirchhoff's the secondary circuit is written as
voltage law, the differential equation of the pri-
mary circuit in Fig. 1 can be written as d~2 = R2 i2 + L2 di2 (3)
dt dt
dih di,
e(t) = - ~ [ + R~i, + L, ~[ (1) where ~2 is the instantaneous mutual flux linkage
(in Wb turns) in the secondary winding, i~ the
and instantaneous secondary current, R2 the sec-
ondary circuit series resistance, and L2 the sec-
e(t) =/{:max sin(~ot + a) (2) ondary circuit series inductance.
where e(t) is the instantaneous exciting voltage, t When the resistance part increases, the load of
the time measured at switch-on, )v~ the instanta- the transformer secondary circuit drops until it
neous mutual flux linkage (in Wb turns) in the is open-circuited.
primary winding, i 1 the instantaneous primary
current, R~ the primary circuit resistance, equal 2.2. Capacitive load
to the primary winding resistance if the source For capacitive load, a resistor in parallel with
impedance is neglected, L, the primary circuit a capacitor is assumed, as shown in Fig. l(b). The
155

differential equation of the secondary circuit can


be written as
1 dl,
i,, =-- (4)
R, dt
and
d2il,
i,, = C, -
dt’
Then,
. .
La = l2R + bC

(6)

where i2Ris the instantaneous value of the resis-


tive current, i,, the instantaneous value of the
capacitive current, R, the parallel load resis-
tance, and C, the parallel load capacitance.
Fig. 2. Simple hysteresis curve.
2.3. Numerical method
Equations (1) and (2) can be written in finite
difference form as follows: After (i2)k is calculated from eqns. (9) or (lo),
the new (i,)k and (Ail)k can be obtained by the
sin(wtk + a) (7)
ek = &,a,
following equations:
(Ah )k (Ai, )k
=ek - R,(i,)k -L, 7 h)k = (dk + (i2)k v2/vl (11)
At
where t, = k At, k represents the sampling steps (h)k = (h)k - (&)k-l (12)

in the simulation, where (i,)k is the magnetizing current with re-


(A&), = (A,)k+, - @I),
spect to (3Ll)k.When the hysteresis loop and the
saturation curve of the studied transformer are
(&)k = (idk - (h)k-l
established by the developed method [lo-121, the
Similarly, i, of eqns. (3) and (6) for different simulation results can be applied to find (i&
load characteristics can be written in finite with respect to (A,),. The mathematical expres-
difference form as follows. sion for the i,-I, hysteresis curve [lo] in Fig. 2 is
(a) For no load, resistive load or inductive
load, i, = i,, + s,(& - A,,)

1
+ ob sin(wt + a) for I, >, 0
(i2)k =a @$!!_L2Q!!$ (9)
2[
= -[L + s,( -& - M
where
+ ob sin(ot + a) for I, < 0 (13)
(A&)k =; (An,), where
1

V, and V, are the primary and secondary rating 1l(n-1) <(&IGI


voltages, respectively,
i, is the instantaneous magnetizing current, I,
(Ai2)k = (i2)k - (i2)k - 1 the instantaneous mutual flux linkage (in Wb
turns), s the slope of the corresponding line sec-
(b) For capacitive load,
tions, ob the maximum distance between the mid-
point locus and the periphery of the hysteresis
(10)
loop, and n = 1,2,3,4. The dynamic hysteresis
where A2 represents the second-order difference, loop’ represented by eqn. (13) in the iron core is
composed of two symmetrical parts. For the first
(A&),lAt -(A&&-l/At part, the normal magnetizing curve, marked by
At ‘aoc’ in Fig. 2, is the locus of the midpoints of the
156

hysteresis loop. This can be o b t a i n e d by the mea-


sured hysteresis data. Usually, for modern trans-
formers, a normal magnetizing curve can be . Read Emax, a, Ir, RI, LI,
a p p r o x i m a t e d by four line sections. The second R2, L 2, C2, El, 62, M, At
part, the loss part, m a r k e d by distances such as (il)0=0o (i2)0=0, (A~I)0=0,
'ef' in Fig. 2, represents loss in the hysteresis (Ail)0=0, k=0
loop. It is also termed the 'consuming function'
b e c a u s e it c o n t r i b u t e s the proper shape and area Calculate e k using Eq. 7 I
n=0, q=0
of the hysteresis loop. The distance 'ef' changes
periodically by a half-wave symmetry. The pe-
riphery of the hysteresis loop is o b t a i n e d by
adding or s u b t r a c t i n g the c o n s u m i n g function to I

Calculate (im) k using Eq. I3 I


the normal magnetizing curve. The a c c u r a c y of I

the above m a t h e m a t i c a l model can be improved . q ~ . q ......

Xl)k= [ (Xl)}+ q=q+l


by increasing n, the n u m b e r of line sections. (il)q-]/2 Calculate (il)q , (i2)kq.
Using eqns. (8)-(12) as one iteration routine, a Ail)q=[(Ail)q + (Ail)q using Eqs. 8-!2
new (il)k is o b t a i n e d for the sample k. If the
difference b e t w e e n (il)~ from eqn. (11) and the
starting v a l u e in eqn. (8) is larger t h a n a spe-
cified tolerance, the average of these two values
, ~ yes
is used as (i~)k for the next iteration routine,
Write tk, (il)q , (i2)q
starting from eqn. (8) again. A similar process is k=k+l
used for (Ai~)k. This r o u t i n e from eqn. (8) to eqn.
(12) is r e p e a t e d until both specified error values
are achieved. Then, one simulated sample of the
inrush c u r r e n t i~ at t = k At, t h a t is, (i~)k, is ob-
Fig. 3. F l o w c h a r t for s i m u l a t i o n . ~:t a n d ~ : ~ = t o l e r a n c e s ,
tained from the iteration process as s h o w n in
M = m a x i m u m n u m b e r of s i m u l a t i o n s a m p l e s , n = n u m b e r of
Fig. 3. The values of (A~1)t~ and (i2)h can easily be s a m p l e d p o i n t s in t h e h y s t e r e s i s loop, q = i t e r a t i o n n u m b e r .
c a l c u l a t e d from eqns. (8) and (9) or from eqns. (8)
and (10) in the last i t e r a t i o n of k.
W h e n t = (k + 1) At, ( ~ ) ~ ~ can be c a l c u l a t e d rent harmonic analysis are chosen to c o u n t cycle
by the following equations: by cycle over the first few cycles. The time re-
quired to distinguish a fault c u r r e n t from the
(;q),~., = (2,)k + (A~,)k (14)
inrush c u r r e n t is a d o m i n a n t factor in c o m p u t e r
Applying eqn. (13), (im)k+ 1 can be calculated. For relaying techniques. Of course, the least required
k = k + 1, c a l c u l a t e time is desirable. Since the inrush c u r r e n t is
decaying, the energy of each cycle is decreasing.
(il),.~ , = (im)k-~ + (i2),~ V 2 / V I The s p e c t r u m v a r i a t i o n b e t w e e n the first few
and cycles and the next few cycles c a n n o t be clearly
identified. Each cycle from the first few cycles of
(Ai,)k+l = ( i , ) , ~ . 1 - - (i~),~ the inrush c u r r e n t is t a k e n into a c c o u n t corre-
and s u b s t i t u t e them into eqn. (8) t o g e t h e r with spondingly in the analysis. This ensures an obvi-
ek.~ from eqn. (7) to get ous spectrum v a r i a t i o n from cycle to cycle.
The F F T is used to analyze the frequency con-
(A,;o,)k ~, (Ai,)h+, (15) tents of the simulated inrush current. The varia-
At = ej~_l - Rl(il)k+l - L 1 At
tions of the harmonics and their phases with
By the same p r o c e d u r e for the following itera- respect to time, the switch-on angle and various
tions, (il)h for all k can be o b t a i n e d to get a loading conditions are obtained.
simulation result for the magnetizing inrush cur-
rent. The overall simulation p r o c e d u r e is s h o w n
in Fig. 3. 3. Example

2.4. H a r m o n i c a n a l y s i s A 3 kVA, 130 V/130 V/7600 V single-phase trans-


The o b t a i n e d inrush c u r r e n t data are used for former was used for on-site m e a s u r e m e n t s of in-
the h a r m o n i c analysis. M e t h o d s of inrush cur- rush c u r r e n t in our laboratory.
157

Based on the flowchart of Fig. 3, a ~eal-time An experiment was carried o u t w h e n the rema-
p r o g r a m was implemented on a PC-AT c o m p u t e r nent flux linkage ~r was 0 Wb turns. The experi-
to calculate the magnetizing inrush c u r r e n t of mental d a t a and the simulation d a t a for p e a k
single-phase transformers. In this experimental values within 10 cycles are compared in Table 1.
system, N sets of ,~1 and im data were computed There is good a g r e e m e n t b e t w e e n the c u r r e n t s
from the im--~l hysteresis curve of the trans- from experiments ( E + ) and from simulations
former [3], and were used as input d a t a for the (S*). The difference in each cycle is less t h a n 5%.
next calculations. Other data were as follows: Comparing the results u n d e r different rema-
nent flux linkages, ~r = 0, 0.1951 (0.42max), • • •,
Primary V, = 130 V Ii(rating) = 5A --0.3902 Wb turns, the v a r i a t i o n in inrush cur-
winding rent is sensitive to the r e m a n e n t flux. For large
Secondary V2 = 130 V /2(rating) = 23 A
positive values of the r e m a n e n t flux, the rema-
winding
nent flux is added to the main flux. Therefore,
Third V3 = 7600 V I3(rating) = 0.395 A
core s a t u r a t i o n becomes more severe and results
winding
in a larger inrush current, and vice versa within
(not used)
certain limits. Comparing the simulation results
The resistive part of the load impedance, Z2, under ~ r = 0 W b t u r n s and switch-on angle
was set at a very high value to consider it as an = 0 °, 3 0 ° , . . . , 150 °, the inrush c u r r e n t is found
open circuit; it was fixed at 26 ~ for all loading to decrease as the switch-on angle increases.
tests. The p o w e r factors for all the different load- However, w h e n ~ > 90 °, the negative inrush cur-
ing conditions were controlled by changing the rent increases. F o r large values of ~, b u t less
series inductor or the parallel capacitor. t h a n 90 °, flux s a t u r a t i o n in the core is n o t signifi-
cant, and the inrush c u r r e n t decreases.
W h e n the inrush c u r r e n t is simulated, the
4. M a i n r e s u l t s s p e c t r u m analysis can be o b t a i n e d using the F F T
algorithm. Table 2 shows the harmonic c o n t e n t s
4.1. No-load condition c o n t a i n e d in the first cycle of the inrush current.
W h e n a t r a n s f o r m e r is energized, its s e c o n d a r y The analysis is carried o u t independently, one
is open-circuited, and the initial magnetizing in- cycle after another, as previously described. It is
rush c u r r e n t has a close relationship with the found t h a t the harmonic c o n t e n t s are rich in the
r e m a n e n t flux ~br. The r e m a n e n t flux linkage ~r, DC component, the second and the third har-
corresponding to ~br, will be used as a p a r a m e t e r monic. A comparison of the results for r e m a n e n t
in a later discussion. flux linkages ~r=0.3902 and 0.1951Wb t u r n s

TABLE 1. C o m p a r i s o n of i n r u s h c u r r e n t s (A) for v a r i o u s r e m a n e n t flux and switch-on angle conditions

,~r Cycle 1 2 3 4 5 6 7 8 9 10
(A)

0° 0 S* 40.0 8.9 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
E+ 40.3 9.2 6.0 4.8 4.3 4.0 3.9 3.7 3.6 3.6
0° 0.1951 S* 55.3 9.1 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
0.3902 S* 65.4 9.1 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6
-0.1951 S* 21.0 8.0 5.5 4.5 4.1 3.9 3.7 3.7 3.6 3.6
-0.3902 S* 6.7 5.0 4.4 4.0 3.8 3.7 3.6 3.6 3.6 3.6

30 ° 0 S* 35.3 8.9 5.7 4.6 4.2 3.9 3.8 3.7 3.6 3.6
E+ 35.8 9.1 5.9 4.7 4.3 3.9 3.8 3.8 3.7 3.6
60 ° 0 S* 18.8 7.8 5.4 4.5 4.1 3.8 3.7 3.6 3.6 3.6
E+ 19.2 8.0 5.5 4.7 4.2 3.9 3.8 3.7 3.6 3.6
90 ° 0 S* 4.0 3.8 3.7 3.6 3.6 3.6 3.6 3.6 3.6 3.6
E+ 4.2 3.9 3.8 3.7 3.6 3.6 3.6 3.6 3.6 3.6
120 ° 0 S* -14.7 -7.1 -5.2 -4.4 -4.1 -3.8 -3.7 -3.6 -3.6 -3.6
150 ° S* -33.0 -8.8 -5.7 -4.6 -4.2 -3.9 -3.8 -3.7 -3.6 -3.6

S* = s i m u l a t i o n results; E + = e x p e r i m e n t a l results.
158

T A B L E 2. H a r m o n i c a n a l y s i s u n d e r n o - l o a d , v a r i o u s r e m a n e n t flux a n d s w i t c h - o n a n g l e c o n d i t i o n s ( a l l h a r m o n i c s a r e s h o w n a s a
p e r c e n t a g e of t h e f u n d a m e n t a l c u r r e n t for t h e f i r s t c y c l e )

Magnetizing inrush current (%)

0:' 0~ 0 .... 0" 0~ 30:' 60: 90 120' 150


~r 0 0.1951 0.3902 -0.1951 -0.3902 0 0 0 0 0

DC 55.6 58.0 61.6 52.0 30.3 54.1 49.7 6.2 51.6 55.2
2nd 63.0 58.3 50.1 62.7 39.7 62.9 60.2 7.5 66.1 66.7
3rd 34.3 27.5 19.1 37.2 35.4 34.8 37.0 39.1 38.3 36.4
4th 15.3 12.8 9.7 15.7 9.4 16.4 15.8 ] .6 15.7 16.7
5th 7.4 6.3 5.6 8.1 7.6 7.3 6.9 7.5 6.1 8.1
6th 4.3 3.7 2.6 2.3 0.7 4.0 2.9 0.4 2.3 3.9
7th 1.8 2.3 1.5 2.0 0.9 2.2 1.2 0.3 0.'7 2.2
8th 1.2 1.2 1.2 1.1 1.2 ] .0 0.7 0.3 0.2 1.0
9th 0.8 0.8 0.4 0.2 1.7 0.3 0.5 0.3 0.1 0.7

with those for zero r e m a n e n t flux linkage condi- 180

tions has been made. The larger positive rema- |th Condition:
n e n t flux linkages result in smaller h a r m o n i c u =0"
contents, except for the DC component. Compar- 9O r=0 Wb.turns.
ing the results u n d e r the r e m a n e n t flux linkage tn
~r = 0 Wb turns, with v a r y i n g switch-on angles
e%
= 0 °, 30 °, 60 ° a n d 90 °, the h a r m o n i c c o n t e n t s are J 0 [ I I I I
5 7 9
found to decrease as the switch-on angle ~ in- o~
creases, except for the 3rd harmonic. CycleNumber
F i g u r e 4 shows the percentage of h a r m o n i c
c o n t e n t s up to the fifth h a r m o n i c over ten cycles.
O4-90
It can be seen t h a t the second h a r m o n i c term is
larger t h a n the DC c o m p o n e n t in the first cycle,
-180
but decays more r a p i d l y t h a n the latter. F i g u r e 5
shows the phase shifts of the h a r m o n i c c o n t e n t s Fig. 5. P h a s e s h i f t s of h a r m o n i c c o n t e n t s a s a f u n c t i o n o f t i m e
for a = 0 ~' a n d "it = 0 W b t u r n s .
up to the fifth h a r m o n i c over ten cycles. The
phase shift v a r i a t i o n of the even h a r m o n i c s is
seen to converge to 0 °, but t h a t of the odd har- monics stays between - 1 4 0 ° and - 1 8 0 ~ u n d e r
steady-state conditions.

4.2. Resistive load condition


IOO
Ist W h e n a t r a n s f o r m e r is reclosed so t h a t its
secondary is connected to a resistive load, the
1 Condition: initial magnetizing i n r u s h c u r r e n t is closely re-
80- ~ ,', - 0 " ,
.\ Xr-0 Wb.turns. lated to the value of the resistance.
,~ 2nd Experiments a n d simulations were carried out
w h e n the t r a n s f o r m e r secondary was c o n n e c t e d
to different resistive loads. The comparison be-
~"" 60-40.I20.d...DC~ tween the experimental d a t a a n d the d a t a from
the s i m u l a t i o n for peak values over 10 cycles is
shown in Table 3. Good a g r e e m e n t resulted, with
a difference of less t h a n 5%. Comparing the re-
sults u n d e r the resistive loads R2 of 26 and 43.3
with the open-circuit results, it is found t h a t the
0 | I , , , I v a r i a t i o n of the i n r u s h c u r r e n t is sensitive to
3 ; "} 9
Cycle Number load changes. For larger secondary currents, the
Fig. 4. P e r c e n t a g e h a r m o n i c c o n t e n t s u p t o t h e fifth h a r m o n i c a s main flux i n t e r a c t s with the reverse l i n k a g e flux,
a f u n c t i o n of t i m e for c~ = 0 ~' a n d 2.. = 0 W b t u r n s . and vanishes. Therefore, u n d e r h e a v y loading
159

T A B L E 3. C o m p a r i s o n of i n r u s h c u r r e n t s (A) for ~r = 0 Wb t u r n s , for v a r i o u s load, p o w e r f a c t o r a n d s w i t c h - o n a n g l e c o n d i t i o n s

Z2 ~ pf Cycle 1 2 3 4 5 6 7 8 9 10
(fl) (A)

0° S* 40.0 8.9 5.8 4.7 4.2 3.9 3.8 3.7 3.6 3.6

43.3 0° 1.0 S* 35.4 9.4 6.2 5.2 4.7 4.5 4.5 4.5 4.5 4.5
E+ 35.1 10.0 6.4 5.2 4.7 4.4 4.4 4.4 4.4 4.4

26 0° 1.0 S* 32.6 10.0 7.2 6.9 6.9 6.9 6.9 6.9 6.9 6.9
E+ 32.8 10.6 7.3 7.1 7.0 6.9 6.9 6.9 6.9 6.9

26 0° 0.9 S* 34.4 12.5 9.3 8.3 7.8 7.5 7.4 7.3 7.3 7.3
E+ 33.2 13.0 9.7 8.6 7.8 7.5 7.4 7.3 7.3 7.3

26 0° 0.8 S* 35.2 13.6 10.2 9.1 8.5 8.1 7.9 7.8 7.7 7.7
E+ 34.1 14.3 10.7 9.4 8.8 8.5 8.1 7.8 7.7 7.7

26 0° 0.7 S* 35.7 14.4 10.9 9.7 9.1 8.7 8.5 8.3 8.2 8.2
0.6 S* 36.2 15.4 11.8 10.5 9.8 9.4 9.2 9.0 8.9 8.9

26 0° -0.9 S* 33.0 6.9 6.8 6.8 6.8 6.8 6.8 6.8 6.8 6.7
E+ 32.2 7.1 7.0 6.9 6.9 6.9 6.9 6.9 6.9 6.9

26 0° -0.8 S* 33.3 6.8 6.8 6.7 6.7 6.7 6.7 6.7 6.7 6.7
E+ 33.9 7.1 7.0 7.0 7.0 6.9 6.9 6.9 6.9 6.9

26 0° -0.7 S* 33.8 6.8 6.7 6.7 6.7 6.6 6.6 6.6 6.6 6.6
-0.6 S* 34.4 6.8 6.7 6.6 6.5 6.5 6.5 6.5 6.5 6.5

26 30 ° 1.0 S* 27.5 9.8 7.1 6.9 6.9 6.9 6.9 6.9 6.9 6.9
60 ° S* 14.0 8.1 6.9 6.9 6.9 6.9 6.9 6.9 6.8 6.8
90 ° S* 7.5 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8 6.8
120 ° S* -11.2 -7.5 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9
150 ° S* -25.6 -9.6 -7.1 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9 -6.9

26 30 ° 0.8 S* 30.5 13.3 10.1 9.0 8.5 8.1 7.9 7.8 7.7 7.7
60 ° S* 17.1 11.2 9.5 8.7 8.3 8.0 7.9 7.8 7.7 7.7
90 ° S* 7.1 7.8 7.7 7.7 "7.7 7.6 7.6 7.6 7.6 7.6
120 ° S* -14.4 -10.5 -9.2 -8.6 -8.2 -8.0 -7.8 -7.7 -7.7 -7.7
150 ° S* -28.6 -13.1 -10.0 -9.0 -8.5 -8.1 -7.9 -7.8 -7.7 -7.7

S * = simulation results; E + = experimental results.

conditions, t h a t is, with small resistive loads tions of R2 = 26 ~, pf = 1.0, a n d ~ = 0 °, 30 °, 60 ° and


across the t r a n s f o r m e r secondary, the peak in- 90 °, it can be seen t h a t the h a r m o n i c s decrease as
rush c u r r e n t is smaller, a n d vice versa w i t h i n the switch-on angle a increases.
c e r t a i n limits. Comparing the results u n d e r Figure 6 shows the percentages of h a r m o n i c
R2=26ft a n d switch-on angle ~ = 0 °,30 ° , c o n t e n t s up to the fifth h a r m o n i c over ten cycles
. . . . 150 °, it is found t h a t the i n r u s h c u r r e n t de- u n d e r R2 = 26 ~. The second h a r m o n i c is larger
creases as the switch-on angle ~ increases. How- t h a n the DC component in the first cycle, but
ever, w h e n ~ > 90 °, the n e g a t i v e i n r u s h c u r r e n t decays more rapidly t h a n the latter. Figure 7
increases. For large values of a, but less t h a n 90 °, shows the phase shifts of the h a r m o n i c c o n t e n t s
flux s a t u r a t i o n in the core is less severe, so the up to the fifth h a r m o n i c over ten cycles u n d e r
i n r u s h c u r r e n t decreases. R2 = 26 ~. The phase shift v a r i a t i o n of the even
Table 4 shows the h a r m o n i c c o n t e n t s c o n t a i n e d h a r m o n i c s converges t o w a r d s 0 °, but t h a t of the
in the first cycle of the i n r u s h current. The har- odd h a r m o n i c s stays between - 1 4 0 ° a n d - 1 8 0 °
monic c o n t e n t s are rich in the DC component, the u n d e r steady-state conditions.
second and the t h i r d harmonics. Comparing the
results u n d e r different resistive loads R2 = 26 a n d 4.3. Inductive load condition
43.3 ~ with the open-circuit results, it is found W h e n a t r a n s f o r m e r is reclosed u n d e r the condi-
t h a t the h e a v i e r load results in smaller h a r m o n i c tion t h a t its secondary is connected to an in-
components. Comparing the results u n d e r condi- ductive load, the initial m a g n e t i z i n g c u r r e n t is
160

i00

80 Condition:
=0 ° ,
=0 Wb. turns,
R2=26 Ohms.
60
oo
g H
,--4

S C
H
40
cg ~
i
2O
eg c~
m o
©
0.
3 5 7 9

Cycle Number
o

© Cg ~ ~ Fig. 6. P e r c e n t a g e h a r m o n i c c o n t e n t s up to t h e fifth h a r m o n i c a s
a f u n c t i o n o f t i m e for x = 0 , ) , = 0 W b t u r n s , a n d R 2 = 2 6 ~.

cq ~ ~

180,

cq ~ ~ Condition:
|th
a =0 ° ,

oo 90
lr=O Wb.turns,
cq co ~ ~n
R2=26 Ohms.

,J
DC
? cg 0 I I I I I I I I I
5 7 9
to
Cycle Number
~D
c
m -90

oo

ea
-180

© Fig. 7. P h a s e s h i f t s o f h a r m o n i c c o n t e n t s as a f u n c t i o n o f t i m e
for ~ = 0 ' , 2 r = 0 W b t u r n s a n d R 2 = 26t1.
©

~D c more severe and has a close relationship to the


0
power factor of the load.
>
Experiments were carried out under different
cq ~ ~
inductive loads. The comparison between the ex-
perimental data and the data from the simulation
~0 c, oo
for peak values within 10 cycles is shown in
<D
u Table 3. There is good agreement between the
r~
~o two sets of data. Comparing the results under
=q ~ <D
Z2=26~ and p f = 1 , 0 . 9 . . . . . 0.6 lagging, the
variation of the inrush current is sensitve to the
Cq ~ ~ changing power factor. For a large power factor,
the main flux interacts with the real part of the
reverse linkage flux, and vanishes. Therefore,
under larger power factor conditions, the peak
inrush current is smaller, and vice versa within
certain limits. Comparing the results under
Z2 = 26 ~1 for pf = 0.8, and ~ = 0 °, 30 °, . . . . 150 °, it
is found that the inrush current decreases as
the switch-on angle a increases. However, when
161

> 90 °, the negative inrush c u r r e n t increases. 100-


For larger values of the switch-on angle ~, b u t
less t h a n 90 ° , flux s a t u r a t i o n in the core is less Condition:
severe, so the inrush c u r r e n t decreases. J0*,
Ar=0 Wb.turns,
U n d e r this test condition the harmonic con-
pf=0.8 lagging,
tents up to the ninth, c o n t a i n e d in the first cycle 60 Z2=26 Ohms.
of the inrush current, are shown in Table 4. The
harmonic contents are also rich in the DC com-
H 40 2nd
ponent, the second and the third harmonics.
Comparing the results u n d e r p f = 1, 0 . 9 , . . . , 0.6
lagging with those u n d e r lower p o w e r factor con-
ditions, the low order harmonic contents
(DC, 2nd, 4th) are smaller, b u t the high order
harmonic c o n t e n t s (8th, 9th) are larger. Compar- 0'~'-~ i i , , I
3 5 9
ing the results u n d e r conditions of pf = 0.8 and Cycle Number
= 0 °, 30 °, 60 °, and 90 °, the low order harmonic
c o n t e n t s (DC, 2nd, 3rd) decrease as the switch-on Fig. 8. P e r c e n t a g e h a r m o n i c c o n t e n t s u p t o t h e fifth h a r m o n i c a s
a f u n c t i o n o f t i m e for a = 0 °, ~r = 0 W b t u r n s , p f = 0.8 l a g g i n g ,
angle increases.
a n d Z 2 = 26 ~.
Figure 8 shows the percentages of harmonic
contents up to the fifth harmonic over ten cycles
under Z2 = 26 ~ and pf = 0.8 lagging. The second 180
Condition:
harmonic is seen to be larger t h a n the DC compo- 4th a -0",
nent in the first cycle, b u t decays more rapidly ~rffi0 Wb.turns,
t h a n the latter. Figure 9 shows the phase shifts of 90 pf-0.8 lagging,
the harmonic c o n t e n t s up to the fifth harmonic G,I Z2ffi26 Ohms.
over ten cycles u n d e r Z2 = 26 f~ and pf = 0.8 lag-
ging. The phase shift v a r i a t i o n of the even har- ~ o
DC
1 I I I I I I I I
monics is t o w a r d 0 °, b u t t h a t of the odd h 3 5 7 9
h a r m o n i c s is b e t w e e n - 1 4 0 ° and - 1 8 0 ° under Cycle Number
steady-state conditions.
~ -90 -

4.4. Capacitive load condition


U n d e r capacitiv e load conditions, the inrush
c u r r e n t also has a close relationship with the -180

load p o w e r factors. Fig. 9. P h a s e s h i f t s o f h a r m o n i c c o n t e n t s a s a f u n c t i o n o f t i m e


The experiments were carried o u t u n d e r differ- for a = 0 °, ~ = 0 W b t u r n s , p f = 0.8 l a g g i n g , a n d Z 2 = 26 ~l.

ent capacitive loads. The comparison b e t w e e n


the experimental data and the data from the Figure 10 shows the p e r c e n t a g e s of harmonic
simulation for peak values within 10 cycles is contents up to the fifth harmonic over ten cycles
listed in Table 3. The results are in good agree- u n d e r Z2 = 26 ~ and p f = - 0 . 8 leading. The sec-
ment. Comparing the results for p f = 1 , - 0 . 9 , ond harmonic is larger t h a n the DC c o m p o n e n t
. . . . - 0 . 6 , the v a r i a t i o n of the inrush c u r r e n t is in the first cycle, b u t decays more rapidly t h a n
sensitive to changes in the p o w e r factor. For the latter. Figure 11 shows the phase shifts of the
larger p o w e r factors, the main flux interacts with harmonic c o n t e n t s up to the fifth harmonic over
the real part of the reverse linkage flux, and ten cycles u n d e r Z2 = 26 ~ and pf = - 0 . 8 leading.
vanishes. Therefore, u n d e r larger p o w e r factor The phase shift v a r i a t i o n of the even harmonics
conditions, the peak inrush c u r r e n t is smaller, tends t o w a r d 0 °, b u t t h a t of the odd h a r m o n i c s is
and vice versa within certain limits. b e t w e e n - 1 4 0 ° and - 1 8 0 ° u n d e r steady-state
Table 4 lists the harmonic c o n t e n t s up to the conditions.
ninth, c o n t a i n e d in the first cycle of the inrush
current. The harmonic c o n t e n t s are rich in the
DC component, the second and the third harmon- 5. D i s c u s s i o n
ics. Comparing the results for p f = 1 , - 0 . 9 , . . . ,
- 0 . 6 , the harmonic c o n t e n t s increase as the H a r m o n i c analysis, applying the F F T using the
power factor decreases. proposed simulation technique, is investigated.
162

contents, except for the 3rd harmonic, decrease.


lOOklst The larger the r e m a n e n t flux, the longer the phase
[\ Condition: shift v a r i a t i o n of the f u n d a m e n t a l c o m p o n e n t
8OT\'' a =o., remains.
\ r=O b'<urn . (2) Resistive loads. The heavier the load, the
I \ leadi. , more the harmonic contents decrease. The larger
z =26 ohms. the switch-on angle, the more the harmonic con-
tents decrease. The heavier the load, the longer
the phase shift v a r i a t i o n of the f u n d a m e n t a l com-
p o n e n t remains.
(3) Inductive loads. The higher the p o w e r fac-
tor, the more the low order h a r m o n i c contents
increase, b u t the high order harmonic contents
decrease. The larger the switch-on angle, the
1 3 5 7 9
more the low order harmonic contents decrease.
Cycle Number
The higher the power factor, the longer the
Fig. 10. Percentage harmonic contents up to the fifth harmonic phase shift v a r i a t i o n of the f u n d a m e n t a l compo-
a s a f u n c t i o n o f t i m e f o r = = i f , i,. = 0 W b t u r n s , p f = 0.8 l e a d i n g ,
nent remains.
a n d Zz = 26 g/.
(4) Capacitive loads. The higher the p o w e r £hc-
tor, the more the h a r m o n i c c o n t e n t s decrease. The
180 • larger the switch-on angle, the more the harmonic
Condition:
,th
=0",
c o n t e n t s decrease. The higher the p o w e r factor,
=0 Wb.turns, the s h o r t e r the time the phase shift v a r i a t i o n of
r
90 pfz0.8 leading the f u n d a m e n t a l c o m p o n e n t is observed.
~n
o Z2=26 Ohms.
Cl

I I I I I I
6. Conclusions
5 7 9
Cycle Number This paper d e m o n s t r a t e s an a c c u r a t e model £br
predicting the magnetizing inrush c u r r e n t in sin-
~ -90
gle-phase transformers. Conditions under investi-
gation are related to transformer loading,
switch-on angles, and r e m a n e n t flux. The results
-180 of the simulation by the proposed method are
Fig. 11. P h a s e s h i f t s o f h a r m o n i c c o n t e n t s a s a f u n c t i o n o f t i m e compared with the experimental results by on-
f o r ~ = O , )~,.= 0 W b t u r n s , p f = 0.8 l e a d i n g , a n d Z 2 = 26 ft. line measurements. These two sets of results
agree very well.
The h a r m o n i c c h a r a c t e r i s t i c s in the inrush cur- From the analysis and results, harmonics due
r e n t are analyzed and studied in detail. U n d e r to inrush c u r r e n t s can be simulated accurately.
no-load and v a r i o u s loading conditions, the vari- Each c o m p o n e n t t h a t causes effects on protec-
ations of the h a r m o n i c c o n t e n t s and their phase tive relays can also be simulated. This is valu-
shifts with r e s p e c t to time are described in vari- able for applications such as t r a n s f o r m e r
ous diagrams and tables. protective relaying. Also, the main h a r m o n i c s
From the results obtained, it is found t h a t the can be eliminated by changing loading condi-
h a r m o n i c c o n t e n t s are rich in the DC compo- tions, switch-on angles and power factors. Over-
nent, the second and the third harmonics. U n d e r voltage resulting from h a r m o n i c r e s o n a n c e can
no load, resistive, inductive and capacitive load, be avoided in practical system operation.
the second h a r m o n i c is always larger t h a n the In addition to this study, investigations on in-
DC c o m p o n e n t in the first cycle, b u t decays more rush currents and harmonics in three-phase trans-
rapidly t h a n the latter. F u r t h e r conclusions are formers are being carried o u t in our laboratory.
summarized as follows.
(1) No-load condition. The larger the r e m a n e n t
flux, the g r e a t e r the h a r m o n i c contents, except for Acknowledgement
the DC component, which decreases. The larger
the switch-on angle, the more the h a r m o n i c This w o r k is s u p p o r t e d by the N a t i o n a l Science
163

Council under research projects NSC78-0404- magnetising inrush current in transformers, Electr. Power
E006-04 and NSC80-0404-E006-04. Syst. Res., 2 (1979) 179-182.
7 S. Akpinar, M. Coulson, R. R. S. Simpson and R. D. Slater,
Calculation of transient current in transformers, Proc. Inst.
Electr. Eng., Part C, 129 (1982) 30 34.
References 8 J. P. Bowles, Overvoltages in HV DC transmission systems
caused by transformer magnetizing inrush currents, IEEE
1 L. A. Finzi and W. H. Mutschler, The inrush of magnetizing Trans., PAS-99 (1974) 487-493.
current in single-phase transformers, Trans. AIEE, 70 (1951) 9 D. Povh and W. Schultz, Analysis of overvoltages caused by
1436-1438. transformer magnetizing inrush current, I E E E Trans., P A S -
2 J. E. Holcomb, Distribution transformer magnetizing inrush 97 (1978) 1355-1365.
current, Trans. AIEE, Part 3, 57 (1961) 697 702. 10 C. E. Lin, J. B. Wei, C. L. Huang and C. J. Huang, A new
3 R. Yacamini and A. Abu Nasser, Transformer inrush current method for representation of hysteresis loops, I E E E Trans.,
and their associated overvoltages in HVDC schemes, Proc. PWRD-4 (1989) 413 420.
Inst. Electr. Eng., Part C, 133 (1986) 353-358. 11 C. E. Lin, J. B. Wei, C. L. Huang and C. J. Huang, A new
4 R. Yacamini and A. Abu Nasser, The calculation of inrush model for transformer saturation characteristics by includ-
current in three-phase transformers, Proc. Inst. Electr. Eng., ing hysteresis loops, IEEE Trans., MAG-25 (1989) 2706-
Part B, 133 (1986) 31-40. 2712.
5 R. Yacamini and A. Abu Nasser, Numerical calculation of 12 C. E. Lin, C. L. Cheng and C. L. Huang, Hysteresis character-
inrush current in single-phase transformers, Proc. Inst. istic analysis of transformers under non-sinusoidal excita-
Electr. Eng., Part B, 128 (1981) 327-334. tions using real time measurements, I E E E Trans., P W R D - 6
6 M. Basu and K. P. Basu, Computerised evaluation of the (1991) 873-879.

You might also like