Professional Documents
Culture Documents
Vsaos: Vaxvxsx Cos, 10
Vsaos: Vaxvxsx Cos, 10
vaxVxsxcos, x 10 Mw
where Vs is expressed in kV, and 1, in A]
(transmission efficiency)
PRx 100 = 80
x 100 =93.72%
Ps 85.359
Example 3.14: A three phase, 33 kV overhead power line has effective resistance and reactance.
nce of
72 and 20 2 per phase, respectively. The three phase load at the receiving end is 30 MW, operatin
with 0.8 power factor (lagging). Find the voltage at the sending end. What will be the kVAR ratingof t
compensating equipment inserted at the receiving end so as to maintain a voltage of 33 kV at each endo
Find also the maximum load that can be transmitted.
Power 30 x 10
- 2 - cos' 0.8
3xV x cos v3 x 33 x
10 x08
= 5242-36.86° A.
33 x 10
3+
V= V+Z= +5242-36.86° x 21.18/70.7°
D -
Vsaos (@- ) cos -
Here. 1zl=21.182, 6 =70.7°. |Vs=33 kV (L-L) =|V»|l. with receiving end voltage maintained at the
end voltage.
evel of sending
We have
1
21.18
20.85-48.52 = -27.67 MVAR
where =|V
But Q, (reactive power demand at load bus)
= PR tan o= Pz tan (cos 0.8)
22.5 MW
need to supply the samne
total inductive load of (27.67 +22.5) MVAR, we
Hence to compensate the must be capacitive.
bus and this reactive power injection
amount of reactive power at the
load
5) =
0.91
S =
70.7° -23.92°
. =46.77°.
3
1)S2i n (70.7° - 46.77) (33)2 sin 70.7
21.18
=
20.85 -48.52 =
-27.67 MVAR
where Vs=VR
But Q, (reactive power demand at load bus)
=
PR tan do =
PR tan
(cos 0.8)
22.5 MW
Hence to compensate the total inductive load of
(27.67+22.5) MVAR, we need to supply the same
amount of reactive power at the load bus and this reactive
power injection must be capacitive.
Qc(capacitive) =27.67 +22.5
= 50.17 MVAR
for transfer of maximum power
We know, 0=6.
X= 400 x 2xTx50x1x103
= 125.6 Q (for entire line)
128 POWER SYSTEM ANALYSIS OPERATION AND CONTROL
Z= (14+j125.6) 2
= 126.3783.6° Q
A= 1+2
=1+x1.256x 103290°x126.37283.6
= 1+0.0792173.6
= 1+(-0.078 +j0.008)
= 0.922 +j0.008
= 0.92220.490
B Z= 126.37 283.6°2.
We know that
P cos(B-9-1cos
PAB |B| (-a)
Here
=
|V =275 kV
B= 126.372 A=6.922
B 83.6
a = 0.49°
PR 0 (since line is at no load)
(275)2 0.922
0
0=
126.37
(83.6-)126.37
598.44 cos (83.6)-66.19
(2.751? cos (83.6°-0.49)
Or,
66.19
cos (83.6-8)
598.44
or, 83.6-8 83.64
or, S = 0.04°
ee p = 2
7
7 5 2
= 46.89 MVAR
Thius, to have Vs r at light or no load condition, we need to compensate the capacitive QR whose
the rating of the inductive compensator should be 46.89 MVAR so as to
waue is just obtained. Hence,
end at nominal value.
keep the bus voltage at the receiving
Determine
3.16:
Example 3.16:
Example The shunt admittance of a 200 km transmission line is Y= j7 x 10- U/km.
of a shunt reactor that will compensate for 60% of the total shunt admitance.
the ABCD constants
Total Y= j7x 10° x 200
Solution:
= j1400 x 10 5
60% compensation means
840 x 10-° U
O
Flg. E3.8
m (say).
OPERATION AND CONTROL
ANAL YSIS
SYSTEM
POWER
130
Write,
we can
At load bus,
Vs1Vl sin osa
Pp-Ps Xse
S stands for sending
end and "*°
for receiving end. Also, |Xe=l.
where suffix
mPp. Xs (vVe-F
Rearranging, we get a quadratic equation in |V
/2
or,
i--
ql/2
the negative root of V; is neglected)
Example 3.18: 3 phase power is transferred through a 300 km power line having surge
350 2. If the power angle be 36° and wavelength of the voltage wave be 4x 10 m, find he
40
impedance loading (P,) for this line. Assume the sending end and the receiving voltages
(LL) at SIL. Also, find the line loadability in terms of SIL.
Solution: We know from text that for a power line,
SIL Zo
P 400X4O0.457.14 MW
Here,
350
in terms of SIL is represented as
laadability
Line
P sin o
SIL sin 6
0=BD=xD
36° 360
P= SIL xSin x 300
Here sin 27 4000
= 270
0.588
P 457.14x x = 592.067 MW
Ol, 0.454
Jence the ine loadability is 592.067 MW while the SIL value is 457.14 MW.
having reactancé
interconnector of
Example 3.19: Figure E3.9 represents power flow through an
stations. If the voltage profile in thee
5/ph (resistance is negligible) linking two generating
the power angle and the station power
interconnector is 33 kV (L-L) throughout the line, estimate
factors.
V,40°
- V,20° 2 T V46
10 MW
(R+jX) 30 MW load
50 MW load
(0.8 p.f. lag) (0.75 p.f. lag)
Fig. E3.99
Solution: At bus-1,
Load P + j0 = 50 +j50 tan (cos- 0.8)
= (50+j37.5) MVA
At bus-2,
Load= P, +j0, = 30 +j30 tan (cos 0.75)
Also, Vs=VR=33kV(L-L)
and
Ps=PR= 10 MW (given)
Also,
Ps=PR x sin 6
132 POWER SYsTEM ANALYSIS OPERATION AND
CONTROL
33 x 33
Here 10= sin
2.63.
Hence, the operating power angle is 2.63°, i.e. Vz£6 =33 kV22.63° while V28 = V.
V, V
V, to send real power from bus-2 to bus -I).
Next, we compute the reactive power.
- V_cs
-cos8
when =e=|Vl
cos 2.63
Here ,-
8.07 MVAR
-8.07=37.5 8.07 = 29.43 MVAR
Q,
-
1
cos (p.f. at station-1) =cos| tan
P
-1 29.43
Cos tan 50
= 0.862 (lag)
Q, (reactive power at station-2)
26.46 +8.07 =34.53 MVAR
1, +Os =
Find an expression for driving point impedance (Z) voltage gain and current ga |
of secondary constants of the line. What is the
expression for transmission efficiency
STEADY STATE PERFORMANCE AND OPERATION
OF TRANSMISSION LINES 133
ution:
We know that the sending end voltage (V,) and current (I,) can be represented in terms of
eceiving end voltage (V) and current (1,) using the following relations:
he
:a+jß=
Z
impedance (Z1) becomes Z the surge impedance of the line.
Thus, the driving point
from the first equation (equation (i)),
Next, we find
have
and from the second equation,
we
-OD
e
Also,
2aD
= Sy2e
d21-2aD
S12 can be calculated
as,
efficiency
Since transmission
1s real,
-h12aD in p.u.
P G=0, 2,=
a n d r=
javle.]
line is
lossless,
i.c. R =0,
The reader may 'note here that ifthe
Z(B- a) = (82.74 -0.522) = 82.220
MVAR
-38.38 MVAR
MW
82.22
Radius
(475.79 MVA) (509.69 MVA)
Fig. E3.10
By measurement, we find from Fig. E3.10 that MVAR (Q.) is 38.38 MVAR. Thus, the shunt reactor
should be rated as 38.38 MVAR to maintain 220 kV at the receiving side of the line.
Example 3.22: A 3 phase, 50 Hz, 400 kV power transmission line has a series reactance of 81.6 ohm
with negligible series resistance and shunt susceptance of 6.29 x 10 290° mho. The line length is
200 km.
) Determine the reactance and rating of an inductance shunt reactor to be connected at the
receiving end if the receiving end voltage is to be maintained at 400 kV or no load
(ii) If the line delivers 650 MVA at 0.8 p.f. lag at the receiving end, compute the capacitance and
MVAR of the shunt capacitor connected at the receiving end to maintain 400 kV load bus
voltage.
Solution: () Let us assume that the receiving end bus is unloaded. From equation Vs= V cosh yD +
sinh yD, we get for I =0
and 0.000629
20 10'F
C 2Tx 50
= x
0.26
360 2
20x 107
Load bus
(receiving end)
Is
Fig. E3.11
Here, the receiving end current is given by
By
jXsh
substituting the value of Ip in the
expression of Vs we get
VsVCos (BD) +j2, sin BD xR
jX sh
cosh (iBD) =cosh (0 + jßD)
cosh 0.cos
(BD) +j sinh 0.s1n (BD)
cos(BD)
Or,
cos (BD) +20 sin (BD) }
Xsh VR
STEADY STATE PERFORMANCE AND OPERATION OF TRANSMISSION LINES 137
Simplification yields
sin (BD)
sh Vs
Vcos (BD)
VR
. represents the value of required inductive reactance to compensate for the voltage rise at no load for
the line.
In this problem
360 x sin (0.22)
1-cos(0.227)
-3158.18 /ph
rating 2sh is obtained as
Shunt reactor
RMV
sh
AR/ph.
Sincewe require V=|s
Osh (237.11)=17.8
3158.18
MVAR/ph.
(i) Real power delivered at the receiving end is 650 x 0.8 = 520 MW.
bus
P sin 6,, [suffix 1 stands for sending end and suffix 2 stands for receiving end]
X12
PaX12 520x81.6 -0.2652
Here, sin Vs|V 400x400
2 = 15.38°.
sin (ß- a)
360 j0.225
j81.02 Q=81.02L90°N
and
A = cosh yD = 0.974 20°.
CONTROL
OPERATION AND
SYSTEM ANALYSIS
138 POWER
Thus, in order to maintain the rated voltage at the receiving end, Og= 6.805 MVAR/ph is to bedmdrawn
reactive power status at the load bus is diagrammal
alongwith the reactive load demand. The
represented in Fig. E3.12.
R.E.
From
S.E. +130 MVAR/ph
-6.805
MVAR/ph Load
Fig. E3.12
We now can write
or,
-6.805 +Q= 130
O= 130 +6.805
The compensating shunt capacitor should
have 136.805MVAR/ph
of
=
rating
voltage at the specified load level. 136.805 MVAR/ph to keep load bu
Also,
xea 237.113
Oc 136.805410.95 Q
or,
C 410.95
C2x50 x
7.75 uFlph.
410.95
.A 3 phase, 50
Receiving end Hz, 20 km long
EXERCISES
Load delivered voltage
at
33 kV transmission line has the
Impedance
Findout the
receiving end 20 MW at
per phase following data:
per km 0.8
sending end (0.8+ p.f. lagging
Ans. voltage, linej0.5)current
Q