System At T2-II
19256-P1-IC-DAT-0002 Rev 1
Contents
This document is issued in accordance with an agreement between Penspen Limited and the Client, which sets out the entire rights, obligations and liabilities of the parties with
respect to the content and use of this document.
Any other party relying in any way on any aspect of this document does so at its own risk. Penspen makes no warranty or representation, express or implied, to any party other
than its client under the Agreement and only then as stated therein, with respect to the accuracy, completeness, or usefulness of any information contained in this document.
Penspen assumes no liabilities with respect to any other party's use of, or damages suffered as a result of, any use of or reliance on, any information, conclusions or
recommendations contained in or imputed from the document.
37 CABLE TWIST(IEC 794/1-E7) 10 CYCLES 180 DEG TWISTING, 2.0 METRE SAMPLE *
38 WATER PENETRATION(IEC 794/1-F5B) 3 METRE SAMPLE , 1METRE WATER PRESSURE,24 HRS *
39 MINIMUM BENDING RADIUS 20 TIMES OF OD (#)
40 DELIVERY LENGTH (MIN. / MAX.) #
41 CHROMATIC DISPERSION #
MFR. OPTICAL PROPERTIES
42 NUMERICAL APERTURE
43 MINIMUM NORMALISED BANDWIDTH @ 1310nm #
44 MINIMUM NORMALISED BANDWIDTH @ 1550nm #
45 ATTENUATION @1310nm <=0.36 DB/KM
46 ATTENUATION @1550nm <=0.25 DB/KM.
47 DIFFERENCE IN ATTENUATION COEFFICIENT
48 MANUFACTURER #
49 MODEL NO. #
NOTES:
1. # - TO BE FURNISHED BY THE VENDOR ALONG WITH HIS OFFER
2. *- ALL THE REQUIRED TESTS SHALL BE CARRIED OUT ACCORDING TO THE PERTINENT
STANDARD AND THE VENDOR MUST PROVIDE NECESSARY DOCUMENTATION.
3. QUANTITY SHALL BE FINALISED BY CONTRACTOR BASED ON THE LAYOUT DRAWINGS AND FIBRE OPTIC
CABLE ROUTING DRAWINGS DEVELOPED BY CONTRACTOR DURING DETAIL ENGINEERING.
4. ADDITIONAL QTY (AS REQUIRED) FOR REMOTE STANDS RTU SHALL BE IN CONTRACTORS SCOPE.
5. ALL FO CABLES THOUGH SUITABLE FOR DIRECT BURIAL SHALL BE INSTALLED IN UPVC DUCTS/CONDUITS .