19256-P1-IC-DAT-0002 Rev 1
Contents

S.No. Description Page No.


1 DATA SHEET FOR FIBRE OPTIC CABLES 3

Copyright © 2019 Penspen International Limited all rights reserved.

This document is issued in accordance with an agreement between Penspen Limited and the Client, which sets out the entire rights, obligations and liabilities of the parties with
respect to the content and use of this document.
Any other party relying in any way on any aspect of this document does so at its own risk. Penspen makes no warranty or representation, express or implied, to any party other
than its client under the Agreement and only then as stated therein, with respect to the accuracy, completeness, or usefulness of any information contained in this document.
Penspen assumes no liabilities with respect to any other party's use of, or damages suffered as a result of, any use of or reliance on, any information, conclusions or
recommendations contained in or imputed from the document.

REVISION AND AUTHORISATION RECORD


Rev. Date Description By Chkd Appr.

1 18/9/2019 Re-Issued for Tender AF TT CJW


0 8/8/2019 Issued for Tender TT MK CJW

19256-P1-IC-DAT-0002 Rev 1 Page 2 of 3


DATA SHEET FOR FIBRE OPTIC CABLES
1 APPLICATION DIRECT BURIED OR INSTALLED ON CABLE TRAYS (Note-5)
GENERAL
2 APPLICABLE STANDARDS IEC 60793, IEC 60794,IEC-60332-1,TIA-455,TIA-598, ITU G652D
3 QUANTITY 20500{8000(RTU)+12500(AOF A&B)} METERS (APPROX) (Note-4)
4
5 MODE SINGLE MODE, ITU G652.D
6 MATERIAL ULTRA PURE FUSED SILICA GLASS
7 NO. OF FIBRES 24 NOS.
OPTICAL FIBRE

8 CORE DIAMETER 9.0 MICRONS


9 CORE CONCENTRICITY ERROR <1%
10 CORE NON CIRCULARITY <6%
11 CLADDING DIAMETER 125 MICRONS
12 CLADDING NON CIRCULARITY <2%
13
14 NUMBER OF TUBES 6 TUBES WITH 4 FIBRES EACH
15 MATERIAL PBTP (POLY BUTYLENE TEREPHTHALATE)
BUFFER TUBE
CONSTRUCTION

16 THICKNESS (MINIMUM) 0.4 MM


17 INNER DIAMETER
18 OUTER DIAMETER
19 BUFFER TUBE CONSTRUCTION TUBE WITH LOOSE FIBRES IN JELLY COMPOUND
20 FILLING COMPOUND MATERIAL SLIGHTLY THIXOTROPIC AND CHEMICALLY NEUTRAL
21 CENTRAL STRENGTH MEMBER MATERIAL RESIGN GLASS (#)
22 CENTRAL STRENGTH MEMBER OUTER DIA.
OTHER REQUIREMENTS

23 PRIMARY BEDDING/INNER SHEATH MATERIAL WEATHER RESISTANT POLYETHYLENE,UV STABILISED(1.5MM)#


24 ARAMID LAYER ARAMID YARN
25 SEC. BEDDING/ INTERMEDIATE SHEATH HDPE 1.0 MM THICK MIN(#)
26 ARMOUR CORRUGATED STEEL TAPE,0.15 MM THICK(IEC 60794-1-2)
27 OUTER SHEATH HDPE 1.5 MM THICK MIN(#)
28 OUTER SHEATH CONSTR. REQUIREMENT OVER ARMOUR
29 RIP CORD(PROPERLY WAXED) UNDER INNER SHEATH
30 FIBRE PROOF TEST >=0.69 Gpa
31 COLOUR CODING AS PER IEC-304/ TIA-598
COND.
ENVIR

32 TEMPERATURE RANGE -20°C TO +70°C


.

33 RELATIVE HUMIDITY 0 TO 100%


34 TENSILE LOAD (IEC 794/1-E1) DYNAMIC : 5000 N *
35 CRUSH RESISTANCE (IEC 794/1-E3) 5000 N/10 cm, 3 Cycles ,0.5 mm Hammer radius *
MECHANICAL

36 IMPACT RESISTANCE (IEC 794/1-E4) 10 Nm, 3 Cycles ,No Fibre break*


REQ.

37 CABLE TWIST(IEC 794/1-E7) 10 CYCLES 180 DEG TWISTING, 2.0 METRE SAMPLE *
38 WATER PENETRATION(IEC 794/1-F5B) 3 METRE SAMPLE , 1METRE WATER PRESSURE,24 HRS *
39 MINIMUM BENDING RADIUS 20 TIMES OF OD (#)
40 DELIVERY LENGTH (MIN. / MAX.) #
41 CHROMATIC DISPERSION #
MFR. OPTICAL PROPERTIES

42 NUMERICAL APERTURE
43 MINIMUM NORMALISED BANDWIDTH @ 1310nm #
44 MINIMUM NORMALISED BANDWIDTH @ 1550nm #
45 ATTENUATION @1310nm <=0.36 DB/KM
46 ATTENUATION @1550nm <=0.25 DB/KM.
47 DIFFERENCE IN ATTENUATION COEFFICIENT
48 MANUFACTURER #
49 MODEL NO. #
NOTES:
1. # - TO BE FURNISHED BY THE VENDOR ALONG WITH HIS OFFER
2. *- ALL THE REQUIRED TESTS SHALL BE CARRIED OUT ACCORDING TO THE PERTINENT
STANDARD AND THE VENDOR MUST PROVIDE NECESSARY DOCUMENTATION.
3. QUANTITY SHALL BE FINALISED BY CONTRACTOR BASED ON THE LAYOUT DRAWINGS AND FIBRE OPTIC
CABLE ROUTING DRAWINGS DEVELOPED BY CONTRACTOR DURING DETAIL ENGINEERING.
4. ADDITIONAL QTY (AS REQUIRED) FOR REMOTE STANDS RTU SHALL BE IN CONTRACTORS SCOPE.
5. ALL FO CABLES THOUGH SUITABLE FOR DIRECT BURIAL SHALL BE INSTALLED IN UPVC DUCTS/CONDUITS .