FAT ACCEPTANCE TEST REPORT

P CUSTOMER : POWERTECH ENGINEERS PVT. LTD.


PROJECT : 132/33kV GRID SUB-STATION
END USER : BIHAR STATE POWER TRANSMISSION COMPANY LTD., (BSPTCL)
P.O.NO. : PO/PTE/SEL/BSPTCL/71-PR/05/14-15

EQUIPMENT DETAILS:
Description: -33KV LINE CONTROL & RELAY PANEL (SIMPLEX TYPE)
(250V DC)

Panel S.No. : SEL/33L/2015/08-024

A. This is to certify that the equipment manufactured is in accordance with the relevant clause indicated
in IS: -8623-(1993)
B. The Following Routine Tests has been carried out:

S.No TEST PERFORMED Method Observation


1 Visual Checks Visual Ok
Layout & Mounting as per General
2
Arranged Drawing Visual Ok
Dimensional Checks
3
Visual Ok
Insulation Resistance Test:
4
IR TESTER MOTWANE Value as per
A DC SOURCE
make (500V) standard
I Positive & Earth __DO__ >250kΩ >1MΩ
ii Negative & Earth __DO__ >250kΩ >1MΩ
IR TESTER MOTWANE Value as per
B AC SOURCE
make (500V) standard
I Phase & Earth __DO__ >250kΩ >1MΩ
ii Neutral & Earth __DO__ >250kΩ >1MΩ

WITNESSED BY: TESTED BY:

Page 1 of 2
FAT ACCEPTANCE TEST REPORT

S.No. Type of Equipment TEST PERFORMED Observation


I 351A1(SEL) Analog, Binary inputs and outputs channels tested and OK
(Numerical Over found satisfactory
current Protection
Relay)
ii MKG (SALZER) DC Fail Accept Relay checked and found satisfactory OK
iii VAJHM13 Master Trip relay (86A) checked and found satisfactory OK
iv VAX31 Trip Circuit supervision checked and found satisfactory OK
V Digital Meters Ammeter, Voltmeter, Frequency Meter, MW meter, MVAR OK
meter as per scheme checked and found Ok.
vi Tri vector Meter 4 wire 3 elements TVM checked with secondary injection OK
testing kit. And found the analog values correctly.

vii Control switch Voltmeter Selector Switch, and Breaker Selector OK


switches position checked and found satisfactory
viii Annunciator 12 Window annunciator, Electronic Buzzer, Hooter, OK
and Bell checked and found satisfactory
iX Indicating lamps As per Scheme checked and found satisfactory OK
X Semaphore Isolator, Breaker and Earth Switch Semaphores were OK
checked and found working satisfactory.
Xi Push Button As per Scheme checked and found satisfactory OK
Xii TTB Injected Current & Voltage Checked circuit and found OK
satisfactory
Xiii VA11 DC supervision relay checked and found satisfactory OK
xiv MCB, Fuses and TB As per Scheme checked and found satisfactory OK
Details

WITNESSED BY: TESTED BY: