Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

U1 (typical U2 to U6)

Circuit Breaker
Ckt. # Qty. Load Description VA V A Size of Wire Size of Conduit
AT AF p
1 7 Lighting Outlet 700 230 3.04 15 50 2 2-3.5sq.mm. THHN+2.0sq.mm. TW 20mm. Dia. PVC
2 6 Convenience Outlet 1080 230 4.70 20 50 2 2-3.5sq.mm. THHN+3.5sq.mm. TW 20mm. Dia. PVC
3 1 Refrigerator outlet 1000 230 4.35 20 50 2 2-3.5sq.mm. THHN+3.5sq.mm. TW 20mm. Dia. PVC
4 1 ACU ( 1.5Hp) 2300 230 10 30 50 2 2-5.5sq.mm. THHN+3.5sq.mm. TW 20mm. Dia. PVC
5 1 Spare 1500 230 6.52 30 50 2 20mm. Dia. PVC
total: 6580 28.61
Size of wire Size of Circuit Breaker
Iw=It-0.25*LML lcb= It+(1.5*LML)
Iw= 31 lcb= 43.61
at85%DF= 26.44 at85%D 37.07
use: 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe use: 40AT/100AF,2P, bolt on type
Main Distribution Panel

Connected Loads Circuit Breaker


Ckt# QTY. Load Description VA V Size of Wire Size of Conduit
AN BN CN AT AF P
1 1 U1 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
2 1 U2 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
3 1 U3 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
4 1 U4 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
5 1 U5 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
6 1 U6 6580 230 28.61 40 100 2 2-8.0+1-5.5sq.mm. THHN in 20mm dia. Pipe 20mm dia. Pipe
7 5 LO 500 230 2.17 15 50 2 2-3.5sq.mm. THHN+2.0sq.mm. TW 20mm dia. PVC
total loads: 39980 59.39 57.22 57.22

It=LCL+(.25*LML)
It= 61.89 AMPS

Size of Wire Size of Circuit Breaker


Iw= It+(.25*LML) lcb= It+(1.5*LML)
Iw = 64.39 A lcb= 76.89 A
at85%DF= 55 at85%DF= 65

Use: 4-30sq.mm. THHN + 1-8 sq.mm. THHN in 40mm dia. PVC Use: 100AT/100AF, 3P

You might also like