Professional Documents
Culture Documents
Full Keropok M&e
Full Keropok M&e
2 2.0 Introduction 2
2.1 Objectives 2
2.2 Building background and location 2
6 6.0 Reference 31
7 7.0 Appendix 32
1.0 Group Members
1
2.0 Introduction
2.1 Objectives
The objectives of this project are:
1. To conduct an educational visit virtually via google meet and google maps to
an identified building as a case study project.
2. To illustrate, explain and justify the mechanical and electrical system in the
building through report and schematic drawings with specified standard and
requirements.
1. Act as a hub for intercity travels across the west coast of Malaysia.
2. Provides a safe structure for passengers to arrive and depart from the train
3. One of the operation centres for the KTM west coast line.
The Segamat Railway Station is located in the town of Segamat as seen in Figure 2.1
2
3.0 Selection Of M&E Systems in Buildings
Ventilation is important to allow for the exchange of air from the outside and circulation
air within building. The process of changing air in any space to provide high indoor air quality.
For example, to control temperature, replenish oxygen, remove pollutants generated by
breathing, remove odours, smoke, heat and dust. Poor indoor air quality causes 50% of all
illnesses and can lead to a host of health problems for people of all ages. Nowadays, mechanical
ventilation can make it safe to seal unwanted air leaks and install as much insulation as needed.
Ventilation in modern buildings that are in enclosed space and without natural ventilation
requires additional equipment to create air movement. Full mechanical control of air
conditioning and ventilation system are in used. All systems are designed to give comfort to
the users and to keep it more comfortable inside the building than the outside.
i. Split/Window units.
ii. Package units.
iii. Centralised air-conditioning systems.
The split unit consist of the indoor unit and outdoor unit. The indoor unit is installed
inside the area to be cooled and it can be ceiling or wall suspended and comprises the
evaporator or cooling coil and the cooling fan while the outdoor unit is installed outside and
comprises the compressor and condenser. Next, the package units are for higher capacity air-
conditioning loads in the range of 3 to 15 tonnes. It comprises of the filtering, dehumidifying
and cooling as well as air handling components with air-cooled condensers and water-cooled.
Lastly, the centralised system can be direct expansion system or indirect chilled water system
(M F Othman, 2013). This subtopic of mechanical ventilation system focused on an actual
building installed with air-cooled split unit and ceiling cassette air conditioner type are used.
3
3.1.2 Main component of the System
The air-conditioner used in the Segamat Station layout is ceiling cassette split type air
conditioner with wired remote control consists of indoor unit and outdoor unit. The indoor unit
is called air-cooled split unit (ACSU) and the outdoor unit is air-cooled condensing unit
(ACCU).
The indoor component is much lighter and quieter and can be placed depending in the
design. On the indoor component there is always a coarse air filter to protect the coils from
large particles and often there are also fine filters and air purification equipment built in to
remove fine dust, odours and chemical pollutants. It also has evaporator and blower or cooling
fan (International, 2017).
4
Removable face grille Evaporator Blower/Cooling fan
and filter
Outdoor components are usually noisier than indoor component. The main components
found at Segamat Station are compressor and condenser unit. It is wall mounted and are placed
outside of the building. It is also connected with the indoor component by the copper pipe.
Based on the Segamat Station schematic drawings of the systems in the building, how
the system work is explained. Figure 3.5 below shows the Air-Cooled Split Unit Refrigerant
Schematic on how the air conditioning system working in the building.
5
Figure 3.4: Legend drawing.
Grilles
As a cover to allow air to pass in and
out through it.
Filter
To remove solid contaminants such
as smoke, pollen, dust to ensure
better air quality for the occupants.
Figure 3.7: Ceiling Cassette.
6
Usually placed on the return air of
the air conditioning system. The air
that contained the contaminants are
trapped here and clean air is then
discharged into the space together
with the cool air.
Expansion valve, blower and evaporator
Refrigerant passes through the
expansion valve and valve relieves
pressure from the liquid refrigerant
which rapidly cools it. The liquid
refrigerant is quite cold and allows
it to absorb heat from the air.
As the refrigerant flows, the blower
fan draws hot room air over the
evaporator coil. Refrigerant absorbs
heat from passing air and it warms
up and evaporates.
When the warm household water
vapour hits the cold evaporator
coils, the water vapour condenses
into liquid form and drips down into
the condensate pan which drains the
water away outdoors (Experts,
2020).
Copper pipe
Copper pipe runs between the
cassette air conditioner unit and the
outdoor condenser.
Refrigerant gas runs through these
pipes and transfers the heat from
inside the room to outside.
7
It also pumps any excess
condensation in the room away
making an air conditioning unit a
dehumidifier at the same time
(Refrigeration, 2011).
Condenser unit
After refrigerant absorbs heat from
home’s air, it travels outside via
copper pipe to the condenser unit.
The low-pressure, warm refrigerant
gas enters the compressor.
The compressor pressurizes the
refrigerant turning it into a hot,
Based on the site project layouts, all mechanical ventilation system installation shall
comply with Uniform Building by Laws (UBBL) 1984.
8
2. Any application for the waiver of the relevant by-laws shall only be considered if in
addition to the permanent air-conditioning system there is provided alternative
approved means of ventilating the air-conditioned enclosure, such that within half an
hour of the air-conditioning system failing, not less than the stipulated volume of fresh
air specified hereinafter shall be introduced into the enclosure during the period when
the air-conditioning system is not functioning.
3. The provisions of the Third Schedule to these By-laws shall apply to buildings which
are mechanically ventilated or air-conditioned.
4. Where permanent mechanical ventilation in respect of lavatories, water closets,
bathrooms or corridors is provided for and maintained in accordance with the
requirements of the Third Schedule to these By-laws, the provisions of these By-laws
relating to natural ventilation and natural lighting shall not apply to such lavatories,
water-closets, bathrooms or corridors.
9
suppression system is used in conjunction with fire detection system to increase public safety.
This system is governed by the codes under the National Fire Protection Association (NFPA).
Main components of the fire detection system found in the layout of Segamat Statiton
are as follows:
Call button
Alarm bell Break glass
Figure 3.10: Manually fire detection system
10
Dry powder portable fire Fixed CO2 system Hydrant system- hose reel
extinguisher
Figure 3.12: Fire suppression system
11
ii. Automatic fire detection system (based on layout)
Smoke Detector/ Heat Detector
When fire occurrence happened, fire will be
detected by heat detector or smoke detector
installed in building. If the alarm is triggered,
sounders will operate to warn people in the
building that there may be a fire and to evacuate.
Then will be detected on control panel, and
automatically connected to fire department.
12
disables the fire ability to spread. (Wartsila,
2020)
Based on site project layouts, all fire protection services installation shall comply with
Uniform Building by Laws (UBBL) and the rules and regulations of Jabatan Bomba dan
Penyelamat Malaysia (JBPM). All firefighting installation and appliances shall conform to the
latest local authority requirements and current edition of the following standards:
13
All the valves and fitting shall be in accordance with the relevant British Standard (BS) and
shall be approved by the relevant authorities. All pipework, conduit and trunking shall be
painted in different colours to match the building and subject to engineer’s approval.
In modern building, movement system is important system to carry user from place to another
place. There are three type of building transportation system:
Each type has its own function and uses. For example, elevator need in high risk building to
keep users easy to move from lower to upper floor. For moving walkways, usually in wide area
of building such as international airport. It became easier to senior citizen and disabled person
to walk away to other places. For escalator, usually in hypermarket, subway station and
shopping mall. Escalator is used as an alternative to the mundane staircase.
i. Elevator (Lift)
In large buildings, an electronic control system that directs the cars to the correct floors
using a so-called "elevator algorithm" (a sophisticated kind of mathematical logic) to
ensure large numbers of people are moved up and down in the quickest, most efficient way
(particularly important in huge, busy skyscrapers at rush hour). Intelligent systems are
programmed to carry many more people upward than downward at the beginning of the
day and the reverse at the end of the day.
Elevator, also called lift, car that moves in a vertical shaft to carry passengers or freight
between the levels of a multi-story building. Most modern elevators are propelled by
electric motors, with the aid of a counterweight, through a system of cables and sheaves
(pulleys). By opening the way to higher buildings, the elevator played a decisive role in
creating the characteristic urban geography of many modern cities.
Lift performance depends on its acceleration, retardation, car speed, speed of door
operation and stability of speed and performance with variations of carload.
14
ii. Escalator
The benefits of escalators are many. They have the capacity to move large numbers of people,
and they can be placed in the same physical space as stairs would be. They have no waiting
interval, except during very heavy traffic; they can be used to guide people towards main exits
or special exhibits; and they may be weather proofed for outdoor use.
15
3.3.3 Working Principle of the System
Building Transportation System
i. Elevator (Lift)
16
In this drawing, lift shaft from plan
view for actual dimension of lift core.
17
The drawing shows the connection and
functional of lift and escalator supervisory
panel. Supervisory panel works to control
all the movement of elevator and
escalator.
ii. Escalator
All information on side view plan of
escalator:
Upper and lower electric motor
must connect to 13A socket
outlet to supply source.
Detailing for Finish Floor Level
(FFL) at upper and lower
landing.
Detailing UPVC pipe opening for
cable entry, roller step, chain step
Figure 3.25: Side View
and turnaround step.
18
Plan view
The movement of the escalator and
dimension of the escalator steps,
handrail, and landing plate.
19
3.3.4 Specification of the System
Based on site project layouts, all fire protection services installation shall comply with
Jabatan Keselamatan dan Kesihatan Pekerjaan Malaysia (JKKP) and the rules and regulations
of Jabatan Bomba dan Penyelamat Malaysia (JBPM). All building transportation system item
shall conform to the latest local authority standard, requirements and current edition of the
following standards:
i. Lift and Escalator Regulation – BS 2655 under Factory and Machineries Act 1967.
ii. Jabatan Keselamatan dan Kesihatan Pekerjaan Malaysia (JKKP) advice and approval.
All the specification and installation of the lift and escalator must accordance to British and
Malaysia standard (BS, MS). All the dimension and location must follow on drawing and
subject to engineer approval. Civil and Structure engineer must make sure lift core and position
of elevator and escalator in a correct specification and equipment based on structure and
detailing drawing.
Figure 4.2: Layout Schematic Drawings (Active fire protection system part 1)
Figure 4.3: Layout Schematic Drawings (Active fire protection system part 2)
21
Figure 4.4: Layout Schematic Drawings (Active fire protection system part 3)
22
4.2 Drawing by Using Google Sketch Up
4.2.1 Mechanical ventilation system
23
Figure 4.9: 3D Drawings (Active fire protection system part 2)
24
4.2.3 Building transportation system
25
5.0 Relevant Standard and Requirements for the Selected M&E System in Building
5.1 Mechanical ventilation system
26
xi. Minimum insulation thickness for wall concealed
refrigerant copper pipe and condensate drainpipe shall
be 10mm unless specified otherwise.
xii. Minimum density of the closed cell elastomer thermal
insulation for refrigerant copper pipe and condensate
drainpipe shall be 65 kg/m3.
27
ii. All piping material used shall be of carbon steel as ASTM A-53,
A-106 or ANSI B-36-10.
iii. All fittings used shall be heavy duty to ANSI Standard.
iv. CO2 system with more than 3 cylinders shall be provided with a
pilot cylinder (nitrogen) to activate the discharge from each
cylinder.
v. Limit switch shall be installed at the pilot cylinder to provide a
signal back to the control panel to indicate CO2 gas has been
discharged (under manual mood).
vi. The discharge nozzles shall be installed orifice of suitable size
proposed.
vii. All openings shall be provided with fire curtains which operates
automatically prior to any gas discharge.
viii. All CO2 cylinders before installation shall be weighted and
witnessed by consultant or client. Fire contractor is required to
provide a weighting equipment to site for this purpose.
28
5.3 Building Transportation System
Table 5.3: Item, standard and requirements
Item Standard and Requirements
Elevator (Lift) i. All lift shall comply to latest MS EN81-1 and local authorities’
requirements of the difference rules, regulation or codes differ.
The most stringent requirements shall prevail.
ii. All lift cars, hall doors including frames shall be fire resistance
to the authorities’ approval.
iii. Suitable approved jointing box shall be provided between lift
control panel and lift car for power, signal and control cables.
iv. Fire Emergency Return (FER) : when the fire alarm panel give
fire signal, all calls are cancelled and all cars are immediately
called to main lift lobby and park there with door open.
v. Provide 3ways intercom communication between lift car, lift
control panel and lift supervisory panel.
vi. The floor levelling accuracy between lift cars and lobby
finished floor level shall be to in 5mm average in horizontal
tolerance.
vii. All outgoing power, signal and control cables for fire lift shall
be of fire rated with BOMBA approved or endorsement.
viii. Ventilation fans shall provide in each lift car and the internal
noise level shall not exceed NC 40.
ix. Features for handicapped or disable people shall be provided in
accordance with the latest edition of MS 1184
Stainless steel handrails on three sides.
Lowered auxiliary panel.
Braille identification on auxiliary panel.
Different audible tones for up and down at lift lobbies.
Audible tone for each floor sounding in lift car.
Alternatively, voice announcement system in lift car in lieu.
x. Tenderer to confirm all proposed motors efficiency (lift and
escalator) comply to recommendations stipulated in MS 1525.
29
xi. Surge protection shall be provided for lift and escalator control,
supervisory panel and intercom system.
xii. All lift car’s comfort riding shall be 15 MG peak to peak for
x/y/z axis respectively.
xiii. Lift pits and lift motor room must comply with latest JKKP
requirement.
xiv. Rated voltage for all lift’s equipment shall be 400v.
xv. Lift loading factor should capability to load 80% (max) of the
rated lift car capacity.
xvi. All passenger lift car internal floor to suspended ceiling height
shall be min 2600mm.
30
6.0 References
Artim, N. (2019). 3.2 An Introduction to Fire Detection, Alarm, and Automatic Fire Sprinklers.
Retrieved from Northeast Document Conservation Center:
https://www.nedcc.org/free-resources/preservation-leaflets/3.-emergency-
management/3.2-an-introduction-to-fire-detection,-alarm,-and-automatic-fire-
sprinklers
Barcy, G. C. (2003). Elevator Traffic handbook. spon press.
Experts, A. (2020). What Are Evaporator and Condenser Coils and How Do They Help Cool
Your Home? Retrieved from https://yourairexperts.com/article/what-are-evaporator-
and-condenser-coils-and-how-do-they-help-cool-your-home
Greeno, R. (1997). Building Services, tecnology and design. Essex: longman.
Hall, F. &. (2005). building survices Handbook. Oxford: Elsevier.
International, A. (2017). Ceiling Cassette Split Type Air Conditioner.
Jensens, P. D. (2019). Fire Hose Reel System. Retrieved from Grundfos:
https://www.grundfos.com/service-support/encyclopedia-search/fire-hose-reel-
systems.html
M F Othman, H. A. (2013). Performance evaluation of an actual building air-conditioning
system .
Malaysia, L. o. (1967). Factory and Machineries Act 1967. Malaysia government .
Refrigeration, L. A. (2011). Ceiling Cassette Systems . Retrieved from
http://www.lionaircon.com.au/ceiling_cassette_systems.html#:~:text=Ceiling%20Cas
sette%20Systems,and%20a%20condenser%20placed%20outside.
strakosch, G. R. (1998). Vertical Transportation Handbook. wilcy.
Wartsila. (2020). Carbon Dioxide Flooding System. Retrieved from Wartsila Encyclopedia of
Marine Technology: https://www.wartsila.com/encyclopedia/term/carbon-dioxide-
(co2)-flooding-system
31
7.0 Appendix
ATTACHMENT
32
ATTACHMENT
33
ATTACHMENT
34
ATTACHMENT
35
ATTACHMENT
36
ATTACHMENT
37
ATTACHMENT
38
ATTACHMENT
39
ATTACHMENT
40