Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

PROJECT: M&E SYSTEMS OF

SEGAMAT RAILWAY STATION

COURSE CODE BFC 32602


COURSE NAME MECHANICAL AND ELECTRICAL SYSTEM
FACULTY FACULTY KEJURUTERAAN AWAM DAN ALAM BINA
GROUP 4
GROUP 1. ANIS SAKINAH BINTI AHMAD UMAR
MEMBERS
(DF180085)
2. MUHAMAD SYAMIL BIN SABRI
(DF180149)
3. MUHAMMAD AIMAN BIN MOHAMMAD ANUAR
(DF180198)
4. MUHAMMAD EZZUL EHSAN BIN NAWAWI
(DF180196)
5. NAJMA AMIRA BINTI MARZUKI
(DF180157)
SECTION 5
LECTURER TS. SYED BURHANUDDIN HILMI BIN SYED MOHAMAD

DUE DATE 18 JUNE 2020


No. Item Page
1 1.0 Group members 1

2 2.0 Introduction 2
2.1 Objectives 2
2.2 Building background and location 2

3 3.0 Selection Of M&E Systems in Buildings 3


3.1 Mechanical Ventilation System 3-9
3.2 Active Fire Protection System 9-14
3.3 Building Transportation System 14-20

4 4.0 Layout Schematic Drawings 20


4.1 Drawing by Using AutoCAD 20
4.1.1 Mechanical ventilation system 20
4.1.2 Active fire protection system 21-22
4.1.3 Building transportation system 22
4.2 Drawing by Using Google Sketch Up 23
4.2.1 Mechanical ventilation system 23
4.2.2 Active fire protection system 23-24
4.2.3 Building transportation system 25
5 5.0 Relevant Standard and Requirements for the Selected M&E System 26
in Building
5.1 Mechanical ventilation system 26-27
5.2 Active fire protection system 27-28
5.3 Building transportation system 28-30

6 6.0 Reference 31

7 7.0 Appendix 32
1.0 Group Members

ANIS SAKINAH BINTI AHMAD UMAR


DF180085

MUHAMAD SYAMIL BIN SABRI


DF180149

MUHAMMAD AIMAN BIN MOHAMAD ANUAR


DF180198

MUHAMMAD EZZUL EHSAN BIN NAWAWI


DF180196

NAJMA AMIRA BINTU MARZUKI


DF180157

1
2.0 Introduction

2.1 Objectives
The objectives of this project are:
1. To conduct an educational visit virtually via google meet and google maps to
an identified building as a case study project.
2. To illustrate, explain and justify the mechanical and electrical system in the
building through report and schematic drawings with specified standard and
requirements.

2.2 Building Background and Location


The building chosen for this project is the Segamat Railway Station. The building is a
Malaysian train station located at and named after the town of Segamat in Johor. The
station serves as a KTM intercity train services for the KTM west Coast Line.

The functions of this building are:

1. Act as a hub for intercity travels across the west coast of Malaysia.
2. Provides a safe structure for passengers to arrive and depart from the train
3. One of the operation centres for the KTM west coast line.

The Segamat Railway Station is located in the town of Segamat as seen in Figure 2.1

Figure 2.1: satellite view of Segamat Railway Station on google maps

2
3.0 Selection Of M&E Systems in Buildings

3.1 Mechanical Ventilation System

Ventilation is important to allow for the exchange of air from the outside and circulation
air within building. The process of changing air in any space to provide high indoor air quality.
For example, to control temperature, replenish oxygen, remove pollutants generated by
breathing, remove odours, smoke, heat and dust. Poor indoor air quality causes 50% of all
illnesses and can lead to a host of health problems for people of all ages. Nowadays, mechanical
ventilation can make it safe to seal unwanted air leaks and install as much insulation as needed.
Ventilation in modern buildings that are in enclosed space and without natural ventilation
requires additional equipment to create air movement. Full mechanical control of air
conditioning and ventilation system are in used. All systems are designed to give comfort to
the users and to keep it more comfortable inside the building than the outside.

3.1.1 Background of System

The air-conditioning system can be classified into the following categories:

i. Split/Window units.
ii. Package units.
iii. Centralised air-conditioning systems.

The split unit consist of the indoor unit and outdoor unit. The indoor unit is installed
inside the area to be cooled and it can be ceiling or wall suspended and comprises the
evaporator or cooling coil and the cooling fan while the outdoor unit is installed outside and
comprises the compressor and condenser. Next, the package units are for higher capacity air-
conditioning loads in the range of 3 to 15 tonnes. It comprises of the filtering, dehumidifying
and cooling as well as air handling components with air-cooled condensers and water-cooled.
Lastly, the centralised system can be direct expansion system or indirect chilled water system
(M F Othman, 2013). This subtopic of mechanical ventilation system focused on an actual
building installed with air-cooled split unit and ceiling cassette air conditioner type are used.

3
3.1.2 Main component of the System

The air-conditioner used in the Segamat Station layout is ceiling cassette split type air
conditioner with wired remote control consists of indoor unit and outdoor unit. The indoor unit
is called air-cooled split unit (ACSU) and the outdoor unit is air-cooled condensing unit
(ACCU).

Figure 3.1: Ceiling cassette split type with remote control.

The indoor component is much lighter and quieter and can be placed depending in the
design. On the indoor component there is always a coarse air filter to protect the coils from
large particles and often there are also fine filters and air purification equipment built in to
remove fine dust, odours and chemical pollutants. It also has evaporator and blower or cooling
fan (International, 2017).

4
Removable face grille Evaporator Blower/Cooling fan
and filter

Figure 3.2: Indoor component.

Outdoor components are usually noisier than indoor component. The main components
found at Segamat Station are compressor and condenser unit. It is wall mounted and are placed
outside of the building. It is also connected with the indoor component by the copper pipe.

Compressor Condenser unit

Figure 3.3: Outdoor component.

3.1.3 Working Principle of the System

Based on the Segamat Station schematic drawings of the systems in the building, how
the system work is explained. Figure 3.5 below shows the Air-Cooled Split Unit Refrigerant
Schematic on how the air conditioning system working in the building.

5
Figure 3.4: Legend drawing.

Figure 3.5: Typical air-cooled split unit refrigerant schematic.

Figure 3.6: Air cooled split unit at Segamat Station Surau.

Grilles
 As a cover to allow air to pass in and
out through it.
Filter
 To remove solid contaminants such
as smoke, pollen, dust to ensure
better air quality for the occupants.
Figure 3.7: Ceiling Cassette.

6
 Usually placed on the return air of
the air conditioning system. The air
that contained the contaminants are
trapped here and clean air is then
discharged into the space together
with the cool air.
Expansion valve, blower and evaporator
 Refrigerant passes through the
expansion valve and valve relieves
pressure from the liquid refrigerant
which rapidly cools it. The liquid
refrigerant is quite cold and allows
it to absorb heat from the air.
 As the refrigerant flows, the blower
fan draws hot room air over the
evaporator coil. Refrigerant absorbs
heat from passing air and it warms
up and evaporates.
 When the warm household water
vapour hits the cold evaporator
coils, the water vapour condenses
into liquid form and drips down into
the condensate pan which drains the
water away outdoors (Experts,
2020).
Copper pipe
 Copper pipe runs between the
cassette air conditioner unit and the
outdoor condenser.
 Refrigerant gas runs through these
pipes and transfers the heat from
inside the room to outside.

Figure 3.8: Copper pipe.

7
 It also pumps any excess
condensation in the room away
making an air conditioning unit a
dehumidifier at the same time
(Refrigeration, 2011).
Condenser unit
 After refrigerant absorbs heat from
home’s air, it travels outside via
copper pipe to the condenser unit.
 The low-pressure, warm refrigerant
gas enters the compressor.
 The compressor pressurizes the
refrigerant turning it into a hot,

Figure 3.9: Condensor unit. high-pressure gas.


 The gas leaves compressor and
flows into condenser coils where
the refrigerant releases much of the
heat that was absorbed from the
home.
 The fan on top of the outdoor unit
blows air over the condenser coils
so the refrigerant inside loses heat
(Experts, 2020).

3.1.4 Specification of the System

Based on the site project layouts, all mechanical ventilation system installation shall
comply with Uniform Building by Laws (UBBL) 1984.

UBBL 1984 – Mechanical Ventilation and Air Conditioning

1. Where permanent mechanical ventilation or air-conditioning is intended, the relevant


building by-laws relating to natural ventilation, natural lighting and heights of rooms
may be waived at the discretion of the local authority.

8
2. Any application for the waiver of the relevant by-laws shall only be considered if in
addition to the permanent air-conditioning system there is provided alternative
approved means of ventilating the air-conditioned enclosure, such that within half an
hour of the air-conditioning system failing, not less than the stipulated volume of fresh
air specified hereinafter shall be introduced into the enclosure during the period when
the air-conditioning system is not functioning.
3. The provisions of the Third Schedule to these By-laws shall apply to buildings which
are mechanically ventilated or air-conditioned.
4. Where permanent mechanical ventilation in respect of lavatories, water closets,
bathrooms or corridors is provided for and maintained in accordance with the
requirements of the Third Schedule to these By-laws, the provisions of these By-laws
relating to natural ventilation and natural lighting shall not apply to such lavatories,
water-closets, bathrooms or corridors.

3.2 Active Fire Protection System


Fire protection systems are very important systems that must be included in buildings.
Active fire protection (AFP) is characterized by items or system, which require a certain
amount of motion and response in order to work, contrary to passive fire protection. AFP
consists of fire detection and fire suppression. Fire protection systems are designed to provide
warning of the outbreak of fire and allow appropriate firefighting action to be taken before the
situation gets out of control. All systems are designed primarily to protect life and property.
Therefore, fire protection system must be specially designed to meet the requirements as
different buildings present a different set of problems that trigger the risk of fire and fire spread.

3.2.1 Background of System

Fire detection system is designed to identify unwanted presence of fire by monitoring


environmental changes associated with combustion. There are two types of fire detection
systems which are manually fire detection system and automatic fire detection system. Fire
detection system is designed to identify unwanted presence of fire by monitoring
environmental changes associated with combustion. Two types of fire detection systems
included are manually fire detection system and automatic fire detection system. While fire

9
suppression system is used in conjunction with fire detection system to increase public safety.
This system is governed by the codes under the National Fire Protection Association (NFPA).

3.2.2 Main Component of the System

Fire Detection System

Main components of the fire detection system found in the layout of Segamat Statiton
are as follows:

i. Manually fire detection system


Manual fire alarm activation requires human intervention, as distinct from automatic
fire alarm activation such as that provided through the use of heat detectors and smoke
detectors. It consists of alarm bell, break glass and call button.

Call button
Alarm bell Break glass
Figure 3.10: Manually fire detection system

ii. Automatic fire detection system


Consists of smoke detector, heat detector and fire control panel.

Smoke detector Heat detector Fire control panel


Figure 3.11: Automatic fire detection system

Fire Suppression System


The main component of the fire suppression system found in the layout of Segamat
Station are fire extinguisher and hydrants. Fire extinguisher system includes portable fire
extinguisher and automatic fire extinguisher. Portable fire extinguisher includes dry powder
and CO2 extinguisher and automatic fire extinguisher found is the gas extinguishing system or
fixed carbon dioxide (CO2) system. While for hydrants system, hose reel system is used in this
site project.

10
Dry powder portable fire Fixed CO2 system Hydrant system- hose reel
extinguisher
Figure 3.12: Fire suppression system

3.2.3 Working Principle of the System


Fire Detection System
i. Manually fire detection system (based on layout)

When fire occurrence happened, fire will be detected


by the fire detection device, manually break the glass
for call button. If the alarm is triggered, sounders will
operate to warn people in the building that there may
be a fire and to evacuate. Fire department will be
called manually.

Figure 3.13: Manually fire detection system

11
ii. Automatic fire detection system (based on layout)
Smoke Detector/ Heat Detector
 When fire occurrence happened, fire will be
detected by heat detector or smoke detector
installed in building. If the alarm is triggered,
sounders will operate to warn people in the
building that there may be a fire and to evacuate.
Then will be detected on control panel, and
automatically connected to fire department.

Fire Control Panel


Figure 3.14: Smoke detector marked S
 The control panel is the "brain" of the fire
detection and alarm system. It is responsible for
monitoring the various alarm "input" devices
such as manual and automatic detection
components, and then activating alarm "output"
devices such as horns, bells, warning lights,
emergency telephone diallers and building
Figure 3.15: Fire control panel controls. (Artim, 2019)

Fire Suppression System (based on layout)


Portable Fire Extinguisher
 Portable extinguishers are intended as a first line
defence to cope with fires of limited size.
 Dry powder extinguishers are similar to dry
chemical except that they extinguish the fire by
separating the fuel from the oxygen element or
by removing the heat element of the fire triangle.
 CO2 extinguishers contain carbon dioxide in
Figure 3.16: Dry powder and CO2 liquid form, it is released into the air neutralising
extinguisher the oxygen that the fire is feeding on then later

12
disables the fire ability to spread. (Wartsila,
2020)

Fixed CO2 System


 A fixed installation designed to displace the
oxygen in the protected space and extinguish the
fire. Usually used to fight fires in engine room
and consists of a series of large CO2 cylinders.
Figure 3.17: Fixed CO2 system
CO2 is supplied from the cylinder manifold to
suitable points with diffusing nozzles. The
discharge valve is located in a locked cabinet.
Opening the cabinet activates an alarm to give
personnel time for evacuation. (Wartsila, 2020)

Hose Reel System


 Fire hose reel system consists of pumps, pipes,
water supply and hose reels located strategically
Figure 3.18: Hose reel system in a building to ensure proper coverage of water
to combat a fire. This system is manually
operated and activated by opening a valve
enabling the water to flow into the hose. (Jensens,
2019)

3.2.4 Specification of the System

Based on site project layouts, all fire protection services installation shall comply with
Uniform Building by Laws (UBBL) and the rules and regulations of Jabatan Bomba dan
Penyelamat Malaysia (JBPM). All firefighting installation and appliances shall conform to the
latest local authority requirements and current edition of the following standards:

i. Hydraulic hose reel – MS 1489 Part 1:1999, MS 1447, MS 1488


ii. Fire extinguisher – MS 1539 Part 1
iii. Fire alarm and detection system - MS 1745
iv. Clean agent system - NFPA 2001
v. Fixed CO2 system – MS 1590 and NFPA 12

13
All the valves and fitting shall be in accordance with the relevant British Standard (BS) and
shall be approved by the relevant authorities. All pipework, conduit and trunking shall be
painted in different colours to match the building and subject to engineer’s approval.

3.3 Building Transportation System

In modern building, movement system is important system to carry user from place to another
place. There are three type of building transportation system:

 Vertical transportation system (elevator/ lift)


 Horizontal transportation system (moving walkways)
 Inclined transportation systems (escalators).

Each type has its own function and uses. For example, elevator need in high risk building to
keep users easy to move from lower to upper floor. For moving walkways, usually in wide area
of building such as international airport. It became easier to senior citizen and disabled person
to walk away to other places. For escalator, usually in hypermarket, subway station and
shopping mall. Escalator is used as an alternative to the mundane staircase.

3.3.1 Building Transportation Example

i. Elevator (Lift)

In large buildings, an electronic control system that directs the cars to the correct floors
using a so-called "elevator algorithm" (a sophisticated kind of mathematical logic) to
ensure large numbers of people are moved up and down in the quickest, most efficient way
(particularly important in huge, busy skyscrapers at rush hour). Intelligent systems are
programmed to carry many more people upward than downward at the beginning of the
day and the reverse at the end of the day.

Elevator, also called lift, car that moves in a vertical shaft to carry passengers or freight
between the levels of a multi-story building. Most modern elevators are propelled by
electric motors, with the aid of a counterweight, through a system of cables and sheaves
(pulleys). By opening the way to higher buildings, the elevator played a decisive role in
creating the characteristic urban geography of many modern cities.

Lift performance depends on its acceleration, retardation, car speed, speed of door
operation and stability of speed and performance with variations of carload.

14
ii. Escalator

Escalator or moving staircase used as transportation between floors or levels in subways,


buildings, and other mass pedestrian areas. Modern escalators are usually inclined at 30°,
limited in rise to about 60 feet (18 m), with floor-to-floor rise of about 12 feet (3.5 m). They
are electrically powered, driven by chain and sprocket, and held in the proper plane by two
tracks. As the treads approach the landing, they pass through a comb device; a deflection switch
is actuated to cut off power if an object becomes jammed between the tread and the comb.

The benefits of escalators are many. They have the capacity to move large numbers of people,
and they can be placed in the same physical space as stairs would be. They have no waiting
interval, except during very heavy traffic; they can be used to guide people towards main exits
or special exhibits; and they may be weather proofed for outdoor use.

Elevators (Lift) Escalator

Figure 3.19: Building transportation example

15
3.3.3 Working Principle of the System
Building Transportation System
i. Elevator (Lift)

In lift shaft drawing shows all detailing


component of moving mechanism
elevator.

 Wall mounted exhaust fan c/w


automatic shuttle and timer to
lift manufacturer
recommendation.
 Length travel of elevator.
 Hoist taxy hoof / beam min
withstand able load and lift
counterweight.
 Detailing for lighting inside
elevator (flug light, switch,
Figure 3.20: Typical Lift Shaft.
and socket outlet.

Sectional and front view shows all


detailing:

 Position and dimension of call


button, door lift, hall lantern
and entrance frame by refer and
approval by architect.
 Detailing of narrow door jamb
Figure 3.21: Sectional and Front view of lift entrance. and car sill at entrance.

16
In this drawing, lift shaft from plan
view for actual dimension of lift core.

A little space must avoid from anything


which is between lift car and lift core.
The space is provided to maintenance
worker for service purpose.

Also installing 3 phase isolator and


control panel of elevator at lift core.

Figure 3.22: Detailing for Lift Shaft.


Schematic diagram shows the
movement of electric current coming
from power supply transfer to isolator.

From isolator, electric transfer to


escalator controller at the side of
escalator.

Escalator receive around 16 KW of


electric supply.
Lift controller control and distribute
electric to lift pit & shaft fluorescent
Figure 3.23: Schematic diagram for electric power
lighting, power point inside lift car, lift
supply (Lift)
shaft exhaust air fan.

17
The drawing shows the connection and
functional of lift and escalator supervisory
panel. Supervisory panel works to control
all the movement of elevator and
escalator.

The process begins with sensing cables


from lift shaft trigger to supervisory panel.
Also, intercom cables from motor room
less trigger to supervisory panel.

For escalator, supervisory panel control all


movement from controller escalator
Figure 3.24: Schematic diagram of elevator monitoring
connected with sensing cables in trunking/
system.
G.I conduit.

Signal cables to system and signal cabling


for ‘Fire Mode’ is controlled by control
circuit.

ii. Escalator
All information on side view plan of
escalator:
 Upper and lower electric motor
must connect to 13A socket
outlet to supply source.
 Detailing for Finish Floor Level
(FFL) at upper and lower
landing.
 Detailing UPVC pipe opening for
cable entry, roller step, chain step
Figure 3.25: Side View
and turnaround step.

18
Plan view
The movement of the escalator and
dimension of the escalator steps,
handrail, and landing plate.

Figure 3.26: Plan view


All information on side view plan of
escalator:

 Upper, middle, lower emergency


stop button & key on off switch
position.
 Both side upper and lower safety
railing.
 FFL platform level at upper and
ground level.
 All dimension of Pit, comb plate
and balustrade of escalator.

Figure 3.27: Front view

Schematic diagram shows the movement


of electric current coming from power
supply transfer to isolator.

From isolator, electric transfer to


escalator controller at the side of
escalator.

Escalator receive around 15 KW of


Figure 3.28: Schematic Diagram for electric power
electric supply.
supply.

19
3.3.4 Specification of the System

Based on site project layouts, all fire protection services installation shall comply with
Jabatan Keselamatan dan Kesihatan Pekerjaan Malaysia (JKKP) and the rules and regulations
of Jabatan Bomba dan Penyelamat Malaysia (JBPM). All building transportation system item
shall conform to the latest local authority standard, requirements and current edition of the
following standards:

i. Lift and Escalator Regulation – BS 2655 under Factory and Machineries Act 1967.
ii. Jabatan Keselamatan dan Kesihatan Pekerjaan Malaysia (JKKP) advice and approval.

All the specification and installation of the lift and escalator must accordance to British and
Malaysia standard (BS, MS). All the dimension and location must follow on drawing and
subject to engineer approval. Civil and Structure engineer must make sure lift core and position
of elevator and escalator in a correct specification and equipment based on structure and
detailing drawing.

4.0 Layout Schematic Drawings


4.1 Drawing by Using AutoCAD
4.1.1 Mechanical ventilation system

Figure 4.1: Layout Schematic Drawings (Mechanical ventilation system)


20
4.1.2 Active fire protection system

Figure 4.2: Layout Schematic Drawings (Active fire protection system part 1)

Figure 4.3: Layout Schematic Drawings (Active fire protection system part 2)

21
Figure 4.4: Layout Schematic Drawings (Active fire protection system part 3)

4.1.3 Building transportation system

Figure 4.5: Layout Schematic Drawings (Building transportation system)

22
4.2 Drawing by Using Google Sketch Up
4.2.1 Mechanical ventilation system

Figure 4.6: 3D Drawings (Mechanical ventilation system part 1)

Figure 4.7: 3D Drawings (Mechanical ventilation system part 2)

4.2.2 Active fire protection system

Figure 4.8: 3D Drawings (Active fire protection system part 1)

23
Figure 4.9: 3D Drawings (Active fire protection system part 2)

Figure 4.10: 3D Drawings (Active fire protection system part 3)

Figure 4.11: 3D Drawings (Active fire protection system part 4)

24
4.2.3 Building transportation system

Figure 4.12: 3D Drawings (Building transportation system part 1)

Figure 4.13: 3D Drawings (Building transportation system part 2)

Figure 4.14: 3D Drawings (Building transportation system part 3)

25
5.0 Relevant Standard and Requirements for the Selected M&E System in Building
5.1 Mechanical ventilation system

Table 5.1: Systems, standard and requirements of air-conditioning.

System Standard and Requirements


Air-conditioning and i. All air-Cond and mechanical ventilation control panels
mechanical ventilation shall be provided with a 24volt fire relay to facilitate the
tripping of the fan motor in the event of fire alarm. All
wiring to the fire alarm panel shall be under fire
protection scope of work.
ii. All fans shall be complete with fan enclosure, weather
louvres with minimum free area of 48% shall be
provided when fan is mounted on external wall.
iii. All fresh air grilles shall be completed with volume
control damper and weather type.
iv. All refrigerant and drainpipes exposed or running at low
level shall be covered with galvanized trunking (painted)
to engineer’s approval.
v. All fans shall be provided with anti-vibration equipment
not limited to inertial block, neoprene pad, spring
isolator etc. At no extra cost to reduce the transmission
of noise and vibration from the fan.
vi. All air-conditioning condensate pipe shall be provided
with insulation as per engineer’s specification
vii. For split type air-conditioning units, compressor shall be
inverter type and suitable for operation with R410A.
viii. All external facing louvres shall be fitted with insect
netting.
ix. Refrigerant copper pipe shall comply to ASTM B88
Type K or L.
x. Minimum insulation thickness for concealed refrigerant
copper pipe and condensate drainpipe shall be 10mm
unless specified otherwise.

26
xi. Minimum insulation thickness for wall concealed
refrigerant copper pipe and condensate drainpipe shall
be 10mm unless specified otherwise.
xii. Minimum density of the closed cell elastomer thermal
insulation for refrigerant copper pipe and condensate
drainpipe shall be 65 kg/m3.

5.2 Active Fire Protection System


Table 5.2: System, standard and requirements of active fire protection system
System Standard and Requirements
Fire Detection System i. All works shall be carried out to relevant standard and include
(manually or automatic all test and components required statutory authorities having
fire detection system) jurisdiction over this work.
ii. Cause and effect fire alarm programmable of all devices shall be
submitted to consultant before installation of devices at site.
iii. All fire alarm equipment and accessories which are exposed to
weather or installed in wet area shall be weatherproof
construction complying to IP54.
Fire Suppression System Portable Fire Extinguisher
i. All portable fire extinguisher shall be installed in accordance with
the Malaysia Fire Code, Malaysia UBBL, MS 1539 and JBPM
requirements.
ii. Dry powder, carbon dioxide or gas type fire extinguisher will be
provided accordance to the application and function of the
protected areas. All fire extinguishers will be texted and certified
by local authorities.
iii. Portable fire extinguishers at public area shall be housed within
mild steel cabinet with epoxy coated red colour.

Fixed CO2 System


i. The CO2 extinguisher system shall be installed as MS 1590:2003
and JBPM’s requirement.

27
ii. All piping material used shall be of carbon steel as ASTM A-53,
A-106 or ANSI B-36-10.
iii. All fittings used shall be heavy duty to ANSI Standard.
iv. CO2 system with more than 3 cylinders shall be provided with a
pilot cylinder (nitrogen) to activate the discharge from each
cylinder.
v. Limit switch shall be installed at the pilot cylinder to provide a
signal back to the control panel to indicate CO2 gas has been
discharged (under manual mood).
vi. The discharge nozzles shall be installed orifice of suitable size
proposed.
vii. All openings shall be provided with fire curtains which operates
automatically prior to any gas discharge.
viii. All CO2 cylinders before installation shall be weighted and
witnessed by consultant or client. Fire contractor is required to
provide a weighting equipment to site for this purpose.

Hose Reel System


i. The hose reel system shall be designed, installed and tested
accordance with the Malaysia Fire Code, Malaysia UBBL, MS
1489, MS 1210 and JBPM requirement.
ii. Hose reel cabinet shall be mild steel with epoxy coated red colour.
iii. Hose reel shall have a length of 30m tubing. Hose reel shall be
certified by local authorities.
iv. All hose reel shall be come with isolation valve and material used
shall comply with authority requirement.
v. Contractor shall label the hose reel enclosure in accordance with
Malaysia Fire Code and Malaysia UBBL.
vi. Automatic air vent shall be provided at each high point of water
pipeline.

28
5.3 Building Transportation System
Table 5.3: Item, standard and requirements
Item Standard and Requirements
Elevator (Lift) i. All lift shall comply to latest MS EN81-1 and local authorities’
requirements of the difference rules, regulation or codes differ.
The most stringent requirements shall prevail.
ii. All lift cars, hall doors including frames shall be fire resistance
to the authorities’ approval.
iii. Suitable approved jointing box shall be provided between lift
control panel and lift car for power, signal and control cables.
iv. Fire Emergency Return (FER) : when the fire alarm panel give
fire signal, all calls are cancelled and all cars are immediately
called to main lift lobby and park there with door open.
v. Provide 3ways intercom communication between lift car, lift
control panel and lift supervisory panel.
vi. The floor levelling accuracy between lift cars and lobby
finished floor level shall be to in 5mm average in horizontal
tolerance.
vii. All outgoing power, signal and control cables for fire lift shall
be of fire rated with BOMBA approved or endorsement.
viii. Ventilation fans shall provide in each lift car and the internal
noise level shall not exceed NC 40.
ix. Features for handicapped or disable people shall be provided in
accordance with the latest edition of MS 1184
 Stainless steel handrails on three sides.
 Lowered auxiliary panel.
 Braille identification on auxiliary panel.
 Different audible tones for up and down at lift lobbies.
 Audible tone for each floor sounding in lift car.
 Alternatively, voice announcement system in lift car in lieu.
x. Tenderer to confirm all proposed motors efficiency (lift and
escalator) comply to recommendations stipulated in MS 1525.

29
xi. Surge protection shall be provided for lift and escalator control,
supervisory panel and intercom system.
xii. All lift car’s comfort riding shall be 15 MG peak to peak for
x/y/z axis respectively.
xiii. Lift pits and lift motor room must comply with latest JKKP
requirement.
xiv. Rated voltage for all lift’s equipment shall be 400v.
xv. Lift loading factor should capability to load 80% (max) of the
rated lift car capacity.
xvi. All passenger lift car internal floor to suspended ceiling height
shall be min 2600mm.

Escalator i. If there is discrepancy of requirement in tender drawing, tender


document or schedule of price the more stringent requirement
shall take precedent.
ii. All escalator shall comply to latest BS 5656, EN 115 and JKKP
requirements of the different rules, regulation or codes differ. The
most stringent requirements shall prevail.
iii. Contractor need to check and verify all the dimension and floor
finishes in the architectural drawing on site and report and
discrepancy to the engineer prior to construction.
iv. Wedge guard plate where the escalator intersect with ceiling or
others shall be provided by contractor.
v. All escalator provided shall be heavy duty type and suitable for
commercial or retail usage.
vi. Escalator rise shown is indicative only. Exact dimensions shall be
determined and verified at site by contractor to suit the required
floor level to achieve fit for purpose at no additional cost.

30
6.0 References

Artim, N. (2019). 3.2 An Introduction to Fire Detection, Alarm, and Automatic Fire Sprinklers.
Retrieved from Northeast Document Conservation Center:
https://www.nedcc.org/free-resources/preservation-leaflets/3.-emergency-
management/3.2-an-introduction-to-fire-detection,-alarm,-and-automatic-fire-
sprinklers
Barcy, G. C. (2003). Elevator Traffic handbook. spon press.
Experts, A. (2020). What Are Evaporator and Condenser Coils and How Do They Help Cool
Your Home? Retrieved from https://yourairexperts.com/article/what-are-evaporator-
and-condenser-coils-and-how-do-they-help-cool-your-home
Greeno, R. (1997). Building Services, tecnology and design. Essex: longman.
Hall, F. &. (2005). building survices Handbook. Oxford: Elsevier.
International, A. (2017). Ceiling Cassette Split Type Air Conditioner.
Jensens, P. D. (2019). Fire Hose Reel System. Retrieved from Grundfos:
https://www.grundfos.com/service-support/encyclopedia-search/fire-hose-reel-
systems.html
M F Othman, H. A. (2013). Performance evaluation of an actual building air-conditioning
system .
Malaysia, L. o. (1967). Factory and Machineries Act 1967. Malaysia government .
Refrigeration, L. A. (2011). Ceiling Cassette Systems . Retrieved from
http://www.lionaircon.com.au/ceiling_cassette_systems.html#:~:text=Ceiling%20Cas
sette%20Systems,and%20a%20condenser%20placed%20outside.
strakosch, G. R. (1998). Vertical Transportation Handbook. wilcy.
Wartsila. (2020). Carbon Dioxide Flooding System. Retrieved from Wartsila Encyclopedia of
Marine Technology: https://www.wartsila.com/encyclopedia/term/carbon-dioxide-
(co2)-flooding-system

31
7.0 Appendix
ATTACHMENT

Figure 7.1: Layout AutoCAD (Mechanical ventilation system part 1)

Figure 7.2: Layout AutoCAD (Mechanical ventilation system part 2)

32
ATTACHMENT

Figure 7.3: Layout AutoCAD (Mechanical ventilation system part 3)

Figure 7.4: Layout AutoCAD (Mechanical ventilation system part 4)

33
ATTACHMENT

Figure 7.5: Layout AutoCAD (Active fire protection system part 1)

Figure 7.6: Layout AutoCAD (Active fire protection system part 2)

34
ATTACHMENT

Figure 7.7: Layout AutoCAD (Active fire protection system part 3)

Figure 7.8: Layout AutoCAD (Active fire protection system part 4)

35
ATTACHMENT

Figure 7.9: Layout AutoCAD (Active fire protection system part 5)

Figure 7.10: Layout AutoCAD (Active fire protection system part 6)

36
ATTACHMENT

Figure 7.11: Layout AutoCAD (Active fire protection system part 7)

Figure 7.12: Layout AutoCAD (Active fire protection system part 8)

37
ATTACHMENT

Figure 7.13: Layout AutoCAD (Building transportation system part 1)

Figure 7.14: Layout AutoCAD (Building transportation system part 2)

38
ATTACHMENT

Figure 7.15: Layout AutoCAD (Building transportation system part 3)

Figure 7.16: View in 3-Dimensional (3D)

39
ATTACHMENT

Figure 7.17: Internal View in 3-Dimensional (3D)

Figure 7.18: Internal View in 3-Dimensional (3D)

40

You might also like