DIESEL GENERATOR SET

Genset Model: J5G22P


400V/230V 3Phase 4W

RPM1500 50Hz

R atin g R an g e
Stan d b y (M EC C ):
Prime: 1612.
KW65 kW
Prim e(M EC C ): 11.5 kw
11.5kw
20 KVA
Stan d b y (Levo y So m er):
Standby: 1817.
KW6 kw
17.6kw
Prim e(Levo y So m er): 2216KVA
kw

16kw

STANDARD FEATURES AND CHARACTERISTICS

ASSEMBLY

※ The engine and alternator are coupled together by means of a SAE flange. A full torsional analysis will be carried
Out to ensure vibration to be reduced to the minimum.
※ Anti-vibration pads are affixed between both engine and alternator; and the base frame. This will ensure better
vibration isolation of the rotating assemblies and enabling the machine to be placed on uneven terrain without
any detrimental effects.
※ For improved durability and corrosion resistance, all metallic fabrication surfaces of the canopy will have to be
treated for coating by grit blast cleaning. They are then covered by special three layers painting system which will
provide an excellent corrosion resistant surface.

CONTROL SYSTEM AND PROTECTION

※ Controllers are available for all types of applications. Using functional grouping, the control systems can be
specified into key start controller model, automatic start control model and PCRC three remote control systems.
See controller features inside.

WARRANTY

※ Jensonn provides warranty obligation for all its products. All products are out through rigorous testing proc
edures to ensure optimal performance. Load tests are all ran with various load factors and protective devic
es and control functions are all stimulated and checked before being despatched.
※ Engine and Alternator are all on standard principle warranty of 12 months or 18 months from shipment, wh
ichever comes first.
※ All engines, alternator and components are all backed by international warranty from respective suppliers to
allow
hassle free support.
Prime power (P)
These ratings are applicable for supplying continuous electrical power (at variable load). There is no limitation to
the annual hours of operation and this model can supply 10% over-load power for 1 hour in12 hours.
Standby power(S)
Standby power is defined as the maximum power available, under the agreed operating conditions, for which the
generating set is capable of delivering for up to 500h of operation per year.
DIESEL ENGINE

·Engine Model Perkins 404A-22

ENGINE SPECIFICATIONS FUEL CONSUMPTION


Manufacturer Perkins Fuel injection pump model Cassette
Number of cylinders 4 type Indirect injection
Air intake way Naturally aspirated
Bore (mm) 84 Max. fuel input resistance of transfer
Stroke (mm) 100 pump(mmHg) NA
Displacement, total (L) 2.216 Max. Overflow fuel resistance at
Speed-droop TBD overflow pipe of injector (mmHg) NA
Compression ratio 23.3:1 Total fuel overflow amount (L/h) 63
Engine weight, dry (kg) 242
CONSUMPTION
TECHNICAL DATA
Standby power (L/h) 6.1
Engine speed (rpm) 1500 100% prime power (L/h) 5.3
Base Output Power (kW) 18.7 75% prime power (L/h) 4.0
Standby Power (kW) 20.6 50% prime power (L/h) 2.9
Torque (Nm) NA 25% prime power (L/h) NA
Low idle (rpm ) NA Continuous power (L/h) NA
Piston speed (m/s) 5
Engine coolant flow (L/sec) 0.67 COOLING SYSTEM
Air intake flow (L/sec) 24.2
Exhaust flow (L/sec) 65.7 Coolant capacity (L) 7
Exhaust temperature (℃) 505 Max. Coolant cycling resistance exterior engine
(kPa) NA
EXHAUST SYSTEM Thermostat adjusting temperature (range) (℃) 82-95
Min. opening pressure of radiator cap (kPa) NA
Max. back pressure(kpa) 10.2 Max. Coolant temperature permitted _
Diameter of exhaust pipe recommended (mm) 42mm Standby Power/Base output Power (%) ( ℃) NA

AIR INTAKE SYSTEM ELECTRIC SYSTEM


Max. air intake resistance
Starter(V) 12
Dirty filter (kpa) 6.4 Battery charging system(A) 15
Normal air cleaner and clean filter (kpa) 3 Max. starting circuit resistance( Ω) NA
Heavy duty cleaner and clean filter (kpa) NA Min. battery capacity_ -12℃ (CCA) 540
Diameter of intake pipe recommended (mm) NA
NOTE:
LUBRICATION SYSTEM All data is based on:
1. Engine operating with fuel system, water pump, lubricating oil
Normal oil pressure range pump, air cleaner and exhaust silencer; not included are battery
Low idle (kPa) NA charging alternator, fan, and optional driven components.
Rated speed (kPa) NA 2. Engine operating with fuel corresponding to grade No. 2-D per
Max. oil temperature permitted in oil pan( ℃) 125 ASTM D975.
Oil pan capacity (Max/Min) (L) 10.6-8.9 3. ISO 3046, Part 1, Standard Reference Conditions of:
Lubrication system Min. capacity (L) NA Barometric Pressure: 100 kPa (29.53 in Hg)
Usage inclining degree permitted 35° Air Temperature : 25℃ (77℉ )
Altitude: 110 m (361 ft)
Relative Humidity: 30%
Air Intake Restriction: 254 mm H2O (10 in H2 O)
Exhaust Restriction: 51 mm Hg (2 in Hg)
N/A: Not Available
TBD: To Be Determined
CP: Continuous power
FSP: Fuel stop power

Altitude: Derating is at 2.0% per 300m for elevation above 1000m. For attitude more than 2450m, please contact us or our
dealer for assistance.
Temperature: Derating is at 6.0% per 11 degree for temperature above 40 degree.
ALTERNATOR

Alternators meet the requirement of BS EN 60034


STAMFORD and the relevant section of other international
Alternator Model PI144D standards such as BS5000, VDE 0530, NEMA MG1-32,
IEC34, CSAC22.2-100, As1359, and other standards
Frequency and Speed 50Hz/1500rpm
and certifications can be considered on request.
Voltage (V) 400/230
Prime capacity (KVA) 20 The 2/3 pitch design avoids excessive neutral currents.
With the 2/3 pitch and carefully selected pole and
Prime power (KW) 16
tooth designs, ensures very low waveform distortion.
Power efficiency (%) 85.1
Brushless alternator with brushless pilot exciter for
Input power(KW) 18.8
excellent load response.
Voltage regulation ±1.0%
0.8 The insulation system is class H, easy paralleling
Rated power factor
with mains or other generators, standard 2/3 pitch
Stator winding 2/3 stator windings avoid excessive neutral currents.
Maximum overspeed 2250min-1
Backed by worldwide service network.
Sustained short circuit 99
Cooling Air (m3/sec) 0.1

Dimensions and Weights


SOUNDPROOF STYLE

Overall Size, L×W×H,mm 2050×870×1110


Net Weight (radiator model), kg 732kg

NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor
for more detailed information.
®

DSE4610/20 ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
AUTO START AND AUTO MAINS FAILURE BS EN 61000-6-2
EMC Generic Immunity Standard for
CONTROL MODULES the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
The DSE4610 Auto Start Control Monitoring engine speed, oil Through USB Communication both including Electrical Business Equipment
Module and the DSE4620 Auto pressure, coolant temperature, modules can be easily configured TEMPERATURE
Mains (Utility) Failure Control frequency, voltage, current, power using the DSE Configuration Suite BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
Module are suitable for a wide and fuel level, the modules will give PC Software or can be fully BS EN 60068-2-2
variety of single gen-set comprehensive engine and configured through the module's Bb/Be Dry Heat +70 oC
applications. alternator protection. This will be front panel editor.
VIBRATION
indicated on the largest back-lit BS EN 60068-2-6
Whilst maintaining functions LCD icon display in its class via an All DSE products are supported by Ten sweeps in each of three
major axes
included within higher end array of warning, electrical trip and the DSE global technical support 5 Hz to 8 Hz @ +/-7.5 mm,
controllers, such as generator or shutdown alarms. team which gives our customers 8 Hz to 500 Hz @ 2 gn
load power monitoring, the and end users access to 24 hour
HUMIDITY
DSE46xx range of especially Alternator sensing, engine support system help and advice. BS EN 60068-2-30
compact controllers provide the for diesel, gas and petrol engines Db Damp Heat Cyclic 20/55 oC
@ 95% RH 48 Hours
user with the ultimate size to all in one variant. With a number of BS EN 60068-2-78
feature ratio. flexible inputs, outputs and Cab Damp Heat Static 40 oC
protections, the modules can be @ 93% RH 48 Hours
easily adapted to suit a wide range SHOCK
of applications including lighting BS EN 60068-2-27
Three shocks in each of three major axes
towers with the added option for 15 gn in 11 mS
staged loading outputs.
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 4 3

USB CONFIGURABLE DC OUTPUT ANALOGUE SENDERS DC POWER


PORT INPUTS (2 for DSE4610) SUPPLY

DSE4610/20
7

OTHER

MAINS (UTILITY) DC OUTPUT GENERATOR / DC OUTPUT GENERATOR CHARGE FUEL AND MAGNETIC PICK-UP
SENSING 1 OF 4 4620 LOAD CURRENT 1 OF 4 4620 SENSING ALTERNATOR CRANK OUTPUTS
(DSE4620) 1 OF 2 4610 1 OF 2 4610

VOLTS VOLTS
D+ +
+ + W/L

1ph 1 1ph 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N

ISSUE 1
®

DSE4610/20 SPECIFICATION

DC SUPPLY
AUTO START AND AUTO MAINS FAILURE CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CONTROL MODULES CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

DSE4620 MAXIMUM OPERATING CURRENT


85 mA at 12 V, 96 mA at 24 V

MAXIMUM STANDBY CURRENT


51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT


DSE4610 35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT


<10 uA at 12 V, <10 uA at 24 V

MAINS (UTILITY) DSE4620 ONLY


VOLTAGE RANGE
15 V to 415 V AC (L-N) 719 V ph - ph

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage

AUXILIARY OUTPUTS C & D


2 A DC at supply voltage
KEY BENEFITS KEY FEATURES • Alternator & MPU speed
• Ultimate size to feature ratio • Largest back-lit icon display in sensing in one variant AUXILIARY OUTPUTS E & F DSE4620
2 A DC at supply voltage
• Automatically transfers between its class • 3 engine maintainance alarms
mains (utility) and generator • Fully configurable via the fascia • Engine speed protection GENERATOR
(DSE4620 only) or PC using USB • Engine hours counter VOLTAGE RANGE
15 V to 415 V AC (L-N) 719 V ph - ph
• Hours counter provides accurate communication • Engine pre-heat
information for monitoring and • Extremely efficient power save • Engine run-time scheduler FREQUENCY RANGE
maintenance periods mode • Battery voltage monitoring 3.5 Hz to 75 Hz
• User-friendly set-up and button • 3 phase generator sensing • Start on low battery voltage MAGNETIC PICK UP
layout for ease of use • 3 phase mains (utility) sensing • Configurable remote start input VOLTAGE RANGE
• Multiple parameters are (DSE4620 only) • 1 alternative configuration +/- 0.5 V to 70 V
monitored simultaneously which • Generator/load power • Comprehensive warning, FREQUENCY RANGE
are clearly displayed on the monitoring (kW, kV A, kV Ar, pf) electrical trip or shutdown 10,000 Hz (max)
largest back-lit icon display in • Generator/load current protection upon fault condition
DIMENSIONS
its class monitoring and protection • LCD alarm indication OVERALL
• The module can be configured • Fuel and crank outputs • Event log (15) 140 mm x 113 mm x 43 mm
to suit a wide range of • Compatible with 600 V ph - ph 5.5’’ x 4.4” x 1.7”
applications nominal systems PANEL CUT-OUT
• Uses DSE Configuration Suite • 4 configurable DC outputs 118 mm x 92 mm
PC Software for simplified • Magnetic pickup speed sensing 4.6’’ x 3.6”
configuration • 3 configurable analogue/digital MAXIMUM PANEL THICKNESS
• Licence-free PC software inputs 8 mm
• IP65 rating (with optional • 4 configurable digital inputs 0.3”
gasket) offers increased • Configurable staged loading STORAGE TEMPERATURE RANGE
resistance to water ingress outputs -40°C TO +85°C

OPERATING TEMPERATURE RANGE


RELATED MATERIALS -30°C TO +70°C
TITLE PART NO’S
DSE4610/20 Installation Instructions 053-156 OPTIONAL PARTS
DSE4610/20 Operator Manual 057-200
DSE4610/20 Configuration Suite PC Manual 057-201 PART PART NUMBER
IP65 Gasket 020-282