répartie
current value of the 1st peak as a function Isc : assumed symmetrical short-circuit assymetric factor
of rms Isc kA (rms value) k
4,5 ≤ I ≤ 6 1,5
6 < I ≤ 10 1,7
10 < I ≤ 20 2,0
20 < I ≤ 50 2,1
50 < I 2,2
Ipeak (kA) For example: for a circuit with a assumed short-circuit current of 50 kA rms, the first
250
peak reaches 105 kA (50 kA x 2.1): see figure opposite.
200
150 v the short-term short-circuit current, lcw, of the BBT, must be greater than the
current flowing through the installation for the duration of the short-circuit Isc
105 kA (duration T - total breaking time - including the time delay if any -).
100
For example: a KTA16 BBT has an lcw characteristic of 60 kA for T = 1 second, i.e. a
50 thermal stress withstand expressed in A2s equal to 3.6x109 A2s.
E 38885E
rms Isc
0
4,5 6 10 20 50 100 If one of these relationships is not verified, a suitable higher rating must be chosen
for the BBT.
transient and steady states of a short-term short-circuit
13