Electrical Specifications:: Riser Diagram

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

2 - 30 sq. mm THW WIRE IN 32 mm DIA.

RSC PIPE
SERVICE ENTRANCE

M A ( 200 A, 2P, 240 V )

150 A, 2P, 240 V, ACB


AS MAIN DISCONNECT

C1 15A 15A C2

C3 15A 15A C4

C5 15A 15A C6

C7 15A 15A C8

C9 15A 15A C10

C11 15A 20A C12

C13 20A 30A C14

C15 30A 20A C16

C17 20A 30A C18

C19 30A 30A C20

C21 20A 20A C22

C23 SPARE SPARE C24

GROUND

36 RISER DIAGRAM
E-2

ELECTRICAL SPECIFICATIONS :
ALL ELECTRICAL WORKS AND INSTALLATION SHALL BE DONE IN ACCORDANCE
1. WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE
EXISTING ORDINANCES, RULES AND REGULATIONS OF THE LOCAL
ELECTRICAL COOPERATIVE.

2.
ALL ELECTRICAL WORKS SHALL BE DONE STRICTLY UNDER THE DIRECT

SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.


3. MINIMUM SIZE OF THE CONDUCTOR USED SHALL BE THW WIRE NO. 3.5 SQUARE mm.
4.
MOUNTING HEIGHTS:
CONVENIENCE OUTLET 0.34 M. ABOVE FINISH FLOOR LINE
WALLSWITCHES 1.37 M. ABOVE FINISH FLOOR LINE

1.829 M. FROM THE TOP OF PANEL TO FIN. FLOOR LINE


ARCHITECT PROJECT TITLE OWNER SHEET CONTENT CAD DESIGNER SHEET NO.

THE COPYRIGHT OF THIS DRAWING REMAINS THE PROPERTY OF ARKI - GENESIS GROUP WHOSE PERMISION MUST BE OBTAINED BEFORE ANY USE OF IT CAN BE MADE

01 10
THE COPYRIGHT OF THIS DRAWING REMAINS THE PROPERTY OF ARKI - GENESIS GROUP WHOSE PERMISION MUST BE OBTAINED BEFORE ANY USE OF IT CAN BE MADE

AS SHOWN
PRC NO. : PTR NO. : A-01